ELECTRICAL LOAD DESIGN ANALYSIS

CONDOTEL
UNIT A-101, UNIT A-102, UNIT A-302

A. Air-Conditioning Load

4 – 1HP ACU @ 1,210VA Rated Power = 4,840 VA

2 – 2HP ACU @ 2,120VA Rated Power = 4,240 VA

Total: Air conditioning Load = 9,080 VA

B. General Lighting and Convenience Outlet Load

418m2 x 24VA/m2 = 10,032 VA

Application of Demand Factor

First 3 kVA @ 100% DF = 3,000 VA

Remainder @ 35% DF = 2,461 VA

Total: General Lighting and Convenience Outlet Load = 5,461 VA

C. Other Loads

1 – Washing Machine = 1,500 VA

1 – Water Heater = 3,500 VA

= 5,000 VA

UNIT A-101 TOTAL NET LOAD

First 8kVA of Other load, GL and CO Load = 8,000 VA

Remainder @ 40% DF = 984.4 VA

ACU Load = 9,080 VA

PER UNIT TOTAL NET LOAD = 18,065 VA

CONDOTEL TOTAL NET LOAD FOR 3 UNITS = 54, 193 VA


HOUSE 38
Note: House 38 is locked during Survey

Used DWG No. 682824 as reference

A. Air-Conditioning Load

5 – ACU @ 2,500VA Rated Power = 12,500 VA

Total: Air conditioning Load = 12,500 VA

B. General Lighting and Convenience Outlet Load


Lighting Load = 5,220 VA
Convenience Outlet Load = 13,660 VA
= 18,880 VA

Application of Demand Factor

First 3 kVA @ 100% DF = 3,000 VA

Remainder @ 35% DF = 5,558 VA

Total: General Lighting and Convenience Outlet Load = 8,558 VA

D. Other Loads

1 – Range = 4,000 VA

1 – Water Heater = 3,500 VA

= 7,500 VA

House 38 TOTAL NET LOAD

First 8kVA of Other load, GL and CO Load = 8,000 VA

Remainder @ 40% DF = 3,223 VA

ACU Load = 12,500 VA

TOTAL NET LOAD = 40,264 VA


HOUSE 45
A. Air-Conditioning Load

3 – ACU @ 2,500VA Rated Power = 7,500 VA

Total: Air conditioning Load = 7,500 VA

B. General Lighting and Convenience Outlet Load


Lighting Load (4Ckt X 1500) = 6,000 VA
Convenience Outlet Load (4 Ckt X 2000) = 13,660 VA
= 19,660 VA

Application of Demand Factor

First 3 kVA @ 100% DF = 3,000 VA

Remainder @ 35% DF = 5,831 VA

Total: General Lighting and Convenience Outlet Load = 8,831 VA

C. Other Loads

1 – Range = 4,000 VA

1 – Water Heater = 3,500 VA

= 7,500 VA

House 45 TOTAL NET LOAD

First 8kVA of Other load, GL and CO Load = 8,000 VA

Remainder @ 40% DF = 3,332 VA

ACU Load = 7,500 VA

TOTAL NET LOAD = 18,832 VA