ITEM(1):Diesel Engine Driven Fire Pump QTY:1

PUMP:
Flow : 750 GPM
Head : 150 PSI
Type : Horizontal End-Suction
Manufacture : Waterfall Pumps Manufacturing
Model : WF-4X12 ESF
Speed : 3000 RPM
Listing : UL-Listed & FM Approved
Construction : Bronze Impeller, Ductile Iron casing
Accessories : Suction & Discharge Gauges, Fuel Tank, Batteries
with Cables, PRV, Waste Cone
ENGINE:
Type : Diesel Engine
Manufacture : Kirloskar
Model : KFP6R-UF26R2
Speed : 3000 RPM
Rating : 217.0 HP
Listing : UL Listed & FM Approved
CONTROLLER:
Type : Diesel Engine Controller
Manufacture : Firetrol
Listing : UL Listed & FM Approved
Supply : 220V/1Phase/50-60Hz
Enclosure : Nema 2

Phone:+971 4 26 333 25
Website: www.wfpumps.com
Email: info@wfpumps.com 2
Location: Dubai,UAE|P.O Box 446054
ITEM(2):Electric Motor Driven Jockey Pump QTY:1
PUMP:
Flow : 20 GPM
Head : 160 PSI
Type : Jockey Pump
Model : RV4-10
Speed : 3500 RPM
Construction : Stainless Steel/ Cast Iron
Accessories : Suction & Discharge Gauges
DRIVER:
Type : Electric Motor
Speed : 3500 RPM
Rating : 5.5 HP
Supply : 220-240V/3Phase/60Hz
Enclosure : TEFC
CONTROLLER:
Type : Jockey Pump Controller
Manufacture : Firetrol
Rating : 5.5 HP
Listing : UL Listed
Supply : 220-240V/3Phase/60Hz
Enclosure : Nema 2

Phone:+971 4 26 333 25
Website: www.wfpumps.com
Email: info@wfpumps.com 3
Location: Dubai,UAE|P.O Box 446054
Performance Curve WF-4X12 ESF

100 180 1000


WF-4X12 ESF
750 GPM
152.25 psi (107.1 m)
90 160 3000 RPM (1-Stage) 900
Max. 140% at Shut-off

80 800
140

70 700
TOTAL HEAD (meters of head)

120 Rated

60 600
150% Rated
100

NPSH (m)
ɳ(%)

BHP
50 500

80
40 400
Min. 65% at 150% Rated
60
30 300

40
20 200

10 20 100

0 0 0
0 200 400 600 800 1000 1200 1400
FLOW (GPM)
----

A B C D E F G H
ENGINE A B C D
KFP4R-UF16R1/R2 2245.0 2000.0 444.5 1391.5

-A-
8 KFP6R-UF26R1/R2 2502.3 2200.0 435.0 1484.0 8

7 7

123+2.5
6
-2.5
TOP VIEW 6

A+10
-10

-A-
-A-

5 5

Ø100MM DISCHARGE
Ø253.5MM O.D FLANGE
8-Ø22 BOLTS 672+5
-5 475
ASME B16.42
CLASS 300

4 4
D+10
-10

-A- 317+2.5
-2.5
-A-

Ø125.5MM SUCTION
Ø279MM O.D FLANGE
C+5
-5

8-Ø22 BOLTS
3 ASME B16.42 3
CLASS 300
380+5
-5
760+10
-10
B+10
-10

FRONT VIEW Note:All dimensions are in mm.


SIDE VIEW
WATERFALL
2 2
PUMPS
MANUFACTURING
DRAWING TITLE:

R3 12/14/2020 TOLERANCE AN MODIFICATION


G&A WF-4x12 ESF PUMP WITH
DIESEL ENGINE KIRLOSKAR
R2 05/27/2020 TEMPLATE CHANGE AND UPDATIONS PUMP MODEL: WF-4X12 ESF SCALE:
For Preliminary Use.
1 R1 08/06/2019 DATA UPDATIONS DRAWING No: M412ESFGA-D-KRL NTS 1
Not For Construction Unless Engineering Drawings PAGE SIZE:
R0 09/20/2018 FOR INITIAL SUBMISSION DRN BY: CHKD BY: APPD BY: DRN DATE: REVISION No:
Represent General Construction. A4
R3
REVISIONS DESCRIPTION
A.D L.S L.R 12/14/2020 PAGE:
REV No DATE
1 of 1
A B C D E F G H
www.wfpumps.com
www.wfpumps.com

END SUCTION FIRE PUMP


End Suction Fire Pumps are engineered to last with a precision-cast,
dynamically balanced and enclosed impeller that minimizes the vibration and
maximizes bearing life. Due to its back-pull-out design, the complete bearing
assembly including impeller and casing cover can be dismantled without
removing the volute casing from the pipe system. It can be driven by either
an electric motor or diesel engine with a full range of options and accessories
available to complete the NFPA-compliant fire pump. Heavy fabricated steel
base is available to mount the pump and driver along with flexible coupling
connects driver to pump. End Suction Fire Pumps are ideal when the source
of water is located above the ground as it provides a positive suction pressure
to the pump at any performance point.

PUMP PERFORMANCE
• Flow ranges from 50 GPM up to 1000 GPM
• Pressure ratings from 80 psi up to 309 psi

DESIGN FEATURES
• Underwriter Laboratories (UL) – 448
• Factory Mutual (FM) – 1319
• NFPA 20
www.wfpumps.com

CROSS SECTIONAL
1. PUMP CASING: Rugged heavy duty, integrally cast supports, volute type, centerline discharge and
self-venting. Back-pull-out design allows removal of bearing assembly and impeller without disturbing
the pipe connection. Provided with O-ring seals between pump casing and back cover to avoid any
leakage.
2. CASING WEAR RING: Standard enclosed impellers are designed with integral casing wear rings to
reduce end thrust.
3. IMPELLER: End suction type, enclosed, dynamically and hydraulically balanced prior to the assembly.
Impellers designed with back rings to minimize axial thrust. Impellers are firmly keyed and locked to an
accurately finished oversized shaft to absorb all shock loads.
4. BEARING HOUSING: Two anti-friction, grease lubricated stainless steel bearings selected to carry
design loads while offering higher life than specified by standards. Both the inboard and outboard
bearings are protected by lip seals to keep contaminants out of bearing.
5. LANTERN RING: Perforated hollow ring made of corrosion resistant material designed to allow flow of
cooling water uniformly around the shaft to provide lubrication and cooling.
6. GLAND PACKING: Packing rings selected to offer maximum tightness while allowing smooth and
friction free running of the shaft.
7. CASING COVER: Casing cover with integral stuffing box designed for maximum working pressure.
Stuffing box sized to house five rings of packing along with lantern ring.
8. SHAFT SLEEVE: Centrifugally cast renewable shaft sleeves protect the shaft from corrosion, packing
wear and are sealed to prevent leakage. Sleeves are accurately positioned and locked in place.
9. BEARING: Grease lubricated stainless steel radial and thrust bearings maintains impeller in their central
position. Bearings are selected to offer very high operating life.
10. SHAFT: Made of high strength alloy steel accurately machined and polished to a smooth surface. Sized
with a liberal safety factor to transmit full driver horsepower while offering minimum deflection in full
range operation.

1
7

5 9

8
4

6
10
KIRLOSKAR OIL ENGINES LIMITED
Engine Scope of Supply Basic Engine Model:
Kirloskar Oil Engines Limited KFP6R-UF26R2
Laxmanrao Kirloskar Road, Ref. No. : ESS - UF26R2 - 00
Khadki, Pune - 411003 (India)
Revision Date : 28.05.2018
Rev. Number : 00

KFP6R-UF26R2
OVERALL WIDTH - 932 MM
Equipment Standard Equipment Standard
Air Cleaner Direct Mounted, Disposable, Indoor Manual Start On Instrument Panel
Service with Drip shield Controls
Alternator 12V - DC, 35 AMPS, With Belt Guard Fuel Inj. System Direct Injection
Flywheel Housing S.A.E. #3 Governor & Speed Mechanical & Constant Speed

Flywheel Power S.A.E. 11.5" Fuel Stop Energize to Stop (ETS), 12V-DC
Take -off Solenoid
Engine Heater 240V-Ac, 2000 Watts Over speed On Instrument panel with Reset & Test
controls
Water Pump Vee Belt Driven with Belt Guard Starter Controls Dual Solenoids
Heat Exchanger Tube & Shell Type, 4.13 Bar, BSP Fuel Connection Metal tube with Fire Resistant Flexible
Connections & Fresh water compatible Supply & Return Lines
Instrument Panel Digital Panel with Tachometer - Exhaust Flex Mild Steel Flexible Bellow for Exhaust
Hourmeter, Volt meters(Two), Water Connection Connection
Temperature, Oil Pressure
Junction Box for On engine for AC supply wiring Exhaust Heat shield and Blanket on charge air
Engine Heater connection to Engine heater Protection cooler pipe

Switches Low Lub. Oil Pressure, Coolant High & Raw Water Automatic from engine Instrument
Low Temperature, Raw water High Solenoid Panel
Temperature, Low Raw water flow & Operation
Overspeed
Charge Air Cooler Tube & Shell Type with flange Raw water 1.25" Stainless Steel Cooling line with
Connections Cooling Loop flow alarm
Lube Oil Pump Gear Driven Starter 12V - DC
Lube Oil Filter Full Flow with By-Pass Valve Throttle Control Adjustable Speed Control
Lube Oil Cooler Engine Water Cooled, Plate Type Fuel Filter Primary Filter with Spin on type
Tool Kit Standard Tool kit

Page 1 of 1
Product FTA1100J
Description

MarkIII+ Diesel Engine Fire Pump Controller

Standard Features – The following are


included as standard with each con-
troller:
• NEMA Type 2 (IP22) Enclosure with Bot-
tom Entry Gland Plate, Lifting Lugs and
Locking Door Handle
• AC Line & Battery circuit breakers
• Two independent battery chargers, 10A
continuous charge - 500mA Trickle
Charge
• 7.0” LCD capacitive type color touch
screen (HMI technology) software up-
Description – Firetrol® combined auto-
gradeable operator interface powered
matic and manual MarkIII based diesel
by an embedded microcomputer with
engine fire pump controllers are intend-
software PLC logic.
ed for starting and monitoring fire pump
• Push-buttons for Crank from Battery
diesel engines. They are suitable for use
#1, Crank from Battery #2, Stop and
with both mechanical and electronic
Run Test
type engines. The controller is available
• 500 PSI Pressure Transducer (calibrated
for 12 or 24 volt negative ground systems,
for 300 PSI (20.7 Bar) and Test Solenoid
using lead acid or Nickel-Cadmium bat-
for fresh water applications, externally
teries. The controller monitors, displays
mounted with protective cover
and records fire pump system informa-
• Audible alarm buzzer embedded in the
tion.
MarkIII+
• Pressure and Event Recording with Date
Approvals – Firetrol fire pump control- Stamp to System Memory Accessible
lers are listed by Underwriters’ Labora- VIA The User Interface and Download-
tories, Inc., in accordance with UL218, able to a USB Flash Drive
Standard for Fire Pump Controllers, CSA, • Visual Indication for: Engine Run • Main
Standard for Industrial Control Equip- Switch Position • Periodic Test • Crank-
ment (cUL), and approved by Factory ing Cycle • AC Power Available • Pump
Mutual. They are built to meet or ex- Room Temperature
ceed the requirements of the approv- • Visual Alarm Indication for: Pump Room
ing authorities as well as NEMA and the Trouble • Pump On Demand • AC Power
latest editions of NFPA 20, Installation Failure • Charger 1-2 Failure • Battery 1-2
of Centrifugal Fire Pumps, and NFPA 70, Weak • Battery 1-2 Overvoltage • Loss
National Electrical Code. of Continuity on Starter 1-2 • High Fuel
Level • Fuel Tank Leak • PLD Low Suc-
tion Pressure • High Raw Water Temp.
• Low Pump Room Temp. • High Pump
Room Temp. • ECM Warning • Weekly
Test Cut-In Pressure Not Reached •
Check Weekly Test Solenoid • Pressure
Transducer Fault • Invalid Cut-In Pres-
sure • Service Required
Product Description FTA560F

Limited Option Jockey Pump Controllers

• Door mounted pressure display/user inter-


face.
• LED indication for pressure above stop setting
(green), pressure between start and stop set-
ting (yellow), and pressure below start setting
(red).
• Start and Stop push-buttons
• Rotary style door mounted disconnect handle
with door interlock

NOTE: FTA560F Jockey Pump Controllers are


only available in the voltage/horsepower
combinations shown below and with the
options shown on the reverse side. For
Description—Firetrol® FTA560F Jockey Pump Con- other combinations and options, see docu-
trollers are intended for use with fire pump sys- mentation for FTA560E series Jockey Pump
tems. They are used for pressure maintenance Controllers.
in fire pump installations to prevent unnecessary
operation of the main fire pump. VOLTAGE 3-PHASE MAX HP Short Circuit
(50/60 Hertz) (MCP) Current
Approvals—Firetrol jockey pump controllers are Rating
listed by Underwriters’ Laboratories, Inc., in ac-
cordance with UL508A, Standard for Industrial -H 200-208 7.5 30kA
Controls, and CSA, Standard for Industrial Control -A 220-240 10 30kA
Equipment. They are built to meet or exceed the -F 380-415V-WYE 15 30kA
requirements of the approving authorities as well -B 440-480V-WYE 20 30kA
as NEMA and the latest edition NFPA 70, National -C 550-600V-WYE 20 18kA
Electrical Code.
VOLTAGE 1-PHASE MAX HP Short Circuit
Standard Features—The following are included (50/60 Hertz) (MCP) Current
as standard with each controller: Rating
• NEMA Type 2/12 (IEC IP22/IP54) Polycarbonate
enclosure (UL50E Construction) -D 110-120 Volts 2 5kA
• Horsepower rated motor circuit protector and -T 200-208 Volts 3 5kA
starting contactor -E 220-240 Volts 5 5kA
• Suitable for use as service equipment
• OFF-AUTO push-buttons
• Minimum run timer
• On-Delay timer
• Control circuit transformer with 24VAC
secondary
• 0-600 psi (0-42 bar) solid state pressure
transducer
• Visual Indication, Controller in AUTO NOTE: Firetrol Brand Jockey Pump controllers DO NOT
CONTAIN MERCURY filled pressure switches.

For Model # Information and Options &


Modifications see Publication SD560F-01

3412 Apex Peakway


Apex, North Carolina 27502
P +1 919 460 5200
F +1 919 460 5250
www.firetrol.com
While every precaution has been taken to ensure accuracy and completeness herein, Firetrol, Inc. assumes no responsibility, and disclaims all liability, for damages result-
ing from use of this information or for any errors or omissions. Specifications and drawings are subject to change without notice. ©2021 Firetrol, Inc., All Rights Reserved.
Publication PD560F-01
MODELO
50B-4KG1KOL Globo
2050B-4KG1KOL Ángulo
Válvula de Alivio de Presión con Trim Anti Cavitación

• Para aplicaciones en plataformas marinas


e instalaciones en tierra
• El Asiento del Trim Anti Cavitación:
- Protege Contra Cavitación
Tamaños 3" a 8" - Reduce el Ruido y la Vibración
- Prolonga la Vida Útil de la Válvula
• Cumple con la norma NFPA 20
Las Válvulas de Alivio de Presión Cla-Val Modelo 50B-4KG1KOL Globo
y 2050B-4KG1KOL Angulo están diseñadas para aliviar los excesos de
LA
BLLED BY
presión en sistemas contra incendio, además de eliminar la posibilidad
ULC de daño interno por cavitación.
U N D E R W RIT

CANADA
OF

La válvula tiene las características de ajustar la presión de apertura a la


E

S E
LAB RI
O R AT O

Tamaños 3" a 8" requerida por el sistema, abrir rápidamente para mantener una presión
2050B-4KG1KOL (Ángulo) controlada y cerrar gradualmente para lograr una operación libre de
fenómenos transitorios (golpes de ariete).

Características y Beneficios del Asiento Anti Cavitación KOL


• Ideal para aplicaciones con altos diferenciales de presión
• Cumple con los flujos establecidos en las normas, requeridos por agencias de
aprobación
• Proporciona un ambiente de trabajo seguro, por prevenir daño en la válvula
• Asiento recubierto de teflón disponible en acero inoxidable tipo 316, monel y Acero
Inoxidable tipo Súper dúplex

Aplicaciones Tipicas
Válvula de Alivio para Plataformas Marinas Válvula de Alivio de Bomba
para Instalaciones en Tierra

WC-1 2050B-4KG1KOL
Waste Cone
Pressure Relief Valve with
Anti-Cavitation Trim

Main
33A High Performance Gate
Combination Air Release Valve
& Vacuum Breaker Valve

Shut-Off

System

Blow-Off
581
Check Valve Tee and
Valve

FLOW

Ver página 2 para lista de materiales


disponibles para aplicaciones
de agua de mar y servicios severos
Especificaciones Dimensiones
Tamaños Globo: 3” a 8” Bridadas; Angulo: 3” a 8” Bridadas
Aprobadas FM, UL y ULC listado B

150 y 300 ANSI


Conexiones
Presión: Clase 150: 175 psi Máximo; Clase 300:
Rangos de Trabajo 300 psi Máximo
G
Temperatura: Agua hasta 180 F Máximo
Rango de Ajuste Disponible en los siguientes rangos de presión de
alivio: 20-200 psi (clase 150)
100-300 psi (clase 300) Modelo 50B-4KG1KOL Globo Modelo 2050B-4KG1KOL Ángulo
Resina Epóxica para proteger superficies A H E
Recubrimiento húmedas de los componentes ferrosos de la
Opcional válvula principal. (Listada UL HNFX EX2855)

Materiales Estándares de la Válvula C


C
Cuerpo Principal y Tapa: Hierro Dúctil ASTM A 536
Internos de la Válvula Principal:
• Asiento de Acero Inoxidable recubierto de Teflón, Vástago de acero
Inoxidable
D F
Sistema de Pilotos de Control: Bronce Fundido con Internos
de acero Inoxidable
Materiales para Aplicaciones con Agua de Mar Recomendamos dejar espacio adecuado alrededor de la válvula para trabajo
de mantenimiento
y Servicios Severos
Tamaño (pulgadas) 3" 4" 6" 8" 10"
Materiales Listados Opcionales Extremos roscados 12.50 --- --- --- ---
• Bronce al Aluminio Níquel – ASTM B 148 Aleación C958000
A 150 Bridadas 12.00 15.00 20.00 25.38 29.75
• Monel - QQ-N-288 Comp B
• Acero Inoxidable 316 – ASTM A 743 GR CF8M 300 Bridadas 13.25 15.62 21.00 26.38 31.12
• Acero Inoxidable Súper Austenitico – UNS S31254 300 X 150 12.88 15.31 20.56 25.88 30.44
• Acero Inoxidable Súper Dúplex – UNS J93404 B 4.56 5.75 7.88 10.00 11.81
• Materiales de los Internos de la válvula y sistemas de pilotos de control
C 12.50 13.00 14.31 16.31 18.00
disponibles de acuerdo a la aplicación recomendada
D 2.66 3.19 4.31 5.31 9.25

Especificaciones de Compra Extremos roscados 6.25 --- --- --- ---


E 150 Bridadas 6.00 7.50 10.00 12.75 14.88
La Válvula de Alivio de Presión para Bomba Contra Incendio debe modu-
300 Bridadas 6.38 7.88 10.50 13.25 15.56
lar los excesos de presión, manteniendo constante la presión independi-
entemente de los cambios en la demanda del sistema. Debe estar contro- Extremos roscados 4.50 --- --- --- ---
lada por piloto y la presión de regreso no debe afectar su punto de ajuste. F 150 Bridadas 4.00 5.00 6.00 8.00 8.62
Debe ser actuada por la misma presión de la línea y abre de forma rápi- 300 Bridadas 4.38 5.31 6.50 8.50 9.31
da para mantener una presión constante en el sistema, cuando la deman- G & H 7.75 7.88 8.50 9.75 13.25
da en el sistema disminuye. Debe cerrar gradualmente para evitar gener-
ar golpes de ariete y cerrar herméticamente 5% debajo de la presión de Tamaño de Válvula (mm) 80 100 150 200 250
ajuste. Extremos roscados 318 --- --- --- ---
A 150 Bridadas 305 381 508 645 756
La válvula principal debe ser del tipo operada hidráulicamente, controlada
por piloto, tipo diafragma en globo o ángulo. Debe estar equipada con 300 Bridadas 337 397 533 670 790
asiento anti cavitación recubierto de teflón con un vástago ranurado guia- 300 X 150 327 389 522 657 773
do en dos puntos: inferior y superior y un disco resiliente con una sección
B 116 146 200 254 300
rectangular sujetado por 3 de sus partes. No se permiten válvulas con
empaques externos y el diafragma no debe ser usado como elemento de C 1318 330 363 414 457
sello. El piloto de Control debe ser una válvula del tipo diafragma, resorte, D 65 81 109 135 235
de acción directa, ajustable, diseñado para modular servicio que permita Extremos roscados 159 --- --- --- ---
el flujo cuando la presión del sistema excede el punto de ajuste en el
resorte. La válvula debe ser listada UL y aprobada Factory Mutual. Debe E 150 Bridadas 152 191 254 324 378
ser del Modelo 50B-4KG1KOL (globo) o Modelo 2050B-4KG1KOL (ángu- 300 Bridadas 162 200 267 337 395
lo) para Alivio de Presión como la fabricada por Cla-Val Newport Beach, Extremos roscados 114 --- --- --- ---
California.
F 150 Bridadas 102 127 152 203 219

*Nota Especial: 300 Bridadas 111 135 165 216 236


La Válvula Modelo 50B-4KG1KOL/2050B-4KG1KOL está disponible con G & H 197 200 216 248 337
brida de entrada clase ANSI 300 y brida de salida clase ANSI 150 para
sistemas de alta presión donde la clase 300 es requerida, para permitir la Capacidad de la Válvula
adaptación de un cono de descarga (generalmente suministrado con Tamaño de Válvula en Pulgadas 3" 4" 6" 8" 10"
brida clase 150) y de esta forma aliviar presión a la atmosfera. GPM Máximo, Recomendados
La válvula de alivio con bridas 300X150 está disponible bajo orden espe- 500 1000 2500 4000 11000
por NFPA 20
cial y Listada UL y aprobada FM.

Mexico/Central America Oficina


Av Empresarios No. 135, Piso 8 • Col. Puerta de Hierro 45116 Zapopan, Jalisco Ph: 52 (33) 80000579
Email: bmartinez@cla-val.com

PO Box 1325 • Newport Beach, CA 92659-0325 • Ph: 949-722-4800 • F: 949-548-5441 • info@cla-val.com • www.cla-val.com
© Copyright Cla-Val 2014 Printed in USA Specifications subject to change without notice. SE-50B-4KG1KOL (R-11/2014)
WC-1
Waste Cone
MODEL

• Available for Onshore and Offshore Applications


• Manufactured in Accordance with NFPA 20 Requirements
• Designed for use with UL/FM Approved Fire Pump
Pressure Relief Valves

Optional Materials for Seawater and Severe Service Applications:


• Nickel Aluminum Bronze (NAB) - ASTM B148 Alloy C95800
• Monel - QQ-N-288 Comp B - ASTM A494 Grade M30H
• Cast Steel - ASTM A216 Grade WCB
• 316 Stainless Steel - ASTM A743 Grades CF3M and CFM8
• Super Austenitic Stainless Steel - ASTM A351 Grade
CK3MCuN (SMO 254)
• Super Duplex Stainless Steel - ASTM A890 Grade 5A
(CE3MN)

Standards: Flanges
• Fusion Bonded Red Epoxy Coated • 150# Class (FF Standard)
• Ductile Iron - ASTM A536-65 • 300# Class (RF Standard)
• (2) 2’’ 316 SS Sight Glasses per WC-1 • Raised Face and Flat Faced Options
• Single Body Casting (No Welding)

Typical Application: 
Fire Pump Relief

CLA-VAL ©
1701 Placentia Avenue • Costa Mesa CA 92627 • Phone: 949-722-4800 • Fax: 949-548-5441 • E-mail: info@cla-val.com • Website cla-val.com
Copyright Cla-Val 2019 Printed in USA Specifications subject to change without notice.
WC-1

Technical Data & Dimensions

ØE ØG
EQUALLY EQUALLY
SPACED SPACED

Ø A Ø AA ØCC ØC

INLET FLANGE BB OUTLET FLANGE

B
6" X 8" SIZE SHOWN

NUMBER DIAMETER NUMBER DIAMETER


SIZE PUMP PRESSURE WEIGHT
ØA ØAA B BB ØC ØCC ØE OF HOLES OF BOLTS ØG OF HOLES OF BOLTS
INLET X OUTLET GPM CLASS (IN LBS.)
(INLET) (INLET) (OUTLET) (OUTLET)

150LB – 7.50 – 8.25 – 10.00 .750 4 .625 .875 8 .750 34


3" X 5" 0 - 450
300LB 8.25 – 9.24 – 11.00 – .875 8 .750 .875 8 .750 53
150LB – 7.50 – 9.00 – 11.00 .750 4 .625 .875 8 .750 41
3" X 6" 450 - 500
300LB 8.25 – 9.69 – 12.50 – .875 8 .750 .875 12 .750 63
150LB – 9.00 – 9.00 – 11.00 .750 8 .625 .875 8 .750 43
4" X 6" 500 - 750
300LB 10.00 – 9.75 – 12.50 – .875 8 .750 .875 12 .750 70
150LB – 9.00 – 10.25 – 13.50 .750 8 .625 .875 8 .750 62
4" X 8" 750 - 1000
300LB 10.00 – 11.06 – 15.00 – .875 8 .750 1.000 12 .875 99
150LB – 11.00 – 10.25 – 13.50 .875 8 .750 .875 8 .750 67
6" X 8" 1000 - 1500
300LB 12.50 – 11.19 – 15.00 – .875 12 .750 1.000 12 .875 110
150LB – 11.00 – 11.50 – 16.00 .875 8 .750 1.000 12 .875 94
6" X 10" 1500 - 2500
300LB 12.50 – 12.63 – 17.50 – .875 12 .750 1.125 16 1.000 150
150LB – 13.50 – 13.00 – 19.00 .875 8 .750 1.000 12 .875 138
8" X 12" 2500 - 3500
300LB 15.00 – 14.25 – 20.50 – 1.000 12 .875 1.250 16 1.125 207
150LB – 13.50 – 14.00 – 21.00 .875 8 .750 1.125 12 1.000 173
8" X 14" 3500 - 5000
300LB 15.00 – 15.25 – 23.00 – 1.000 12 .875 1.250 20 1.125 255

Visit www.cla-val.com to learn


more about Cla-Val Fire
Protection Products

CLA-VAL
1701 Placentia Avenue • Costa Mesa CA 92627
800-942-6326 Fax: 949-548-5441 Web Site: cla-val.com E-mail: info@cla-val.com
CLA-VAL CANADA CLA-VAL EUROPE CLA-VAL UK CLA-VAL FRANCE CLA-VAL PACIFIC
4687 Christie Drive Chemin des Mésanges 1 Dainton House, Goods Station Road Porte du Grand Lyon 1 45 Kennaway Road
Beamsville, Ontario CH-1032 Romanel/ Tunbridge Wells ZAC du Champ du Périer Woolston, Christchurch, 8023
Canada L0R 1B4 Lausanne, Switzerland Kent TN1 2 DH England France - 01700 Neyron New Zealand
Phone: 905-563-4963 Phone: 41-21-643-15-55 Phone: 44-1892-514-400 Phone: 33-4-72-25-92-93 Phone: 64-39644860
E-mail sales@cla-val.ca E-mail: cla-val@cla-val.ch E-mail: info@cla-val.co.uk E-mail: cla-val@cla-val.fr www.cla-valpacific.com

E-WC-1 (R-03/2019)
E-mail: info@cla-valpacific.com
©COPYRIGHT CLA-VAL 2019 Printed in USA Specifications subject to change without notice.

You might also like