Standard Report

AQUACIATPOWER LD ST
Andrew Kietzmann (8/18/2022 12:16:11 PM) 1500E

Seasonal Efficiency(3)(4)
Allowed applications for CE mark:
Comfort Cooling : T>=2°C* SEER 12/7°C | ηs cool 4.17 | 164
Comfort Cooling : T>=13°C*
SEER 23/18°C | ηs cool 4.78 | 188
High Temp. Process Cooling : T>=2°C SEPR 12/7°C 4.51

* ECODESIGN Compliant per (EU) N°2016/2281


(4) All
data related to seasonal efficiency are given for standard units and main options (Brine, pump, energy
efficiency…).

Non contractual picture

Operating Conditions Performance Information


System element Cooling Mode Cooling
Water heat exchanger Cooling Capacity (1) kW 393
Fluid Type Fresh Water Cooling Efficiency (EER) (1) kW/kW 3.00
Fouling Factor (sqm-K)/kW 0
Unit Power Input (1) kW 131
Leaving Temperature °C 6.0
Sound power level (LwA) (1)
Fluid

dB(A) 93.0
Entering Temperature °C 13.0 Sound Pressure Level at 10.0m
Fluid Flow l/s 13.4 dB(A) 60.8
(LpA) (1)
Total Pressure Drop kPa 13.1 Minimum Capacity (2) kW 76.6
Air heat exchanger Maximum Capacity kW 393
Air Entering Air Temperature °C 35.0
(1) All performances are compliant with EN14511 – 3 : 2018. Sound power level according to ISO9614 – 1.
Altitude m 1400 (2) Due
to the minimum flow rate allowable, a lower inlet water temperature might have to be specified to
achieve this performance.
Distance from coast km > 3km

Electric Information
Unit Information
Unit Voltage V-Ph-Hz 400-3-50
RefrigerantType R-410A Standby Power kW 0.377
Refrigerant Weight kg 41 Power Factor 0.878
Tonnes CO2 Equivalent Tonnes 86.4 Electrical Circuit Supply 1
Number of Refrigerant Circuit 2 Maximum Current A 319
Number of Passes (Evaporator) 1 Startup Current A 529
Number of Compressor 6
Number of Fan 6
Fan Power Input kW 7.41 Documentation
Fan Speed RPM 951
Technical Description
Fan Air Flow l/s 31200
Operating / Shipping Weight kg 2116/2074
Unit Dimensions (LxWxH) mm 3604x2253x2322

CIAT participates in the ECP program for Liquid Chilling Packages and Hydronic Heat Pumps. Check ongoing validity of
certificate:www.eurovent-certification.com.
Outside the scope of AHRI Air-Cooled Water-Chilling Packages Certification Program, but is rated in accordance with AHRI Standard 550/590
(I-P) and AHRI Standard 551/591 (SI). Page 1/2

Package Chiller Builder-EMEA v5.0.0.0 (date 7/21/2022)


Performance Report
AQUACIATPOWER LD ST
Andrew Kietzmann (8/18/2022 12:16:11 PM) 1500E

Load Line
Unit Performance
Percent of Max capacity % Max 75.0 50.0 25.0
Cooling Capacity kW 393 294 196 98.2
Percent of full load power % 100.0 62.5 34.7 16.8
Unit Power Input kW 131 81.8 45.4 22.0
Cooling Efficiency (EER) kW/kW 3.00 3.60 4.32 4.47
Evaporator Data
Fluid Entering Temperature °C 13.0 13.0 13.0 13.0
Fluid Leaving Temperature °C 6.0 6.0 6.0 6.0
Fluid Flow Rate l/s 13.4 10.0 6.69 3.34
Total Pressure Drop kPa 13.1 7.54 3.44 0.902
Condenser Data
Entering Air Temperature °C 35.0 30.0 25.0 20.0

Values given are interpolated and are not directly measurable under laboratory conditions
Italic values are the ones for the maximum capacity.

CIAT participates in the ECP program for Liquid Chilling Packages and Hydronic Heat Pumps. Check ongoing validity of
certificate:www.eurovent-certification.com.
Outside the scope of AHRI Air-Cooled Water-Chilling Packages Certification Program, but is rated in accordance with AHRI Standard 550/590
(I-P) and AHRI Standard 551/591 (SI). Page 2/2

Package Chiller Builder-EMEA v5.0.0.0 (date 7/21/2022)