SensoMAG MHB50 Datasheet 062020

You might also like

Download as pdf or txt
Download as pdf or txt
You are on page 1of 2

SensoMAG MHB50 EN54-11

Emergency Stop Manual Call Point EN 12094-3

Description
SensoMAG MHB50 is a manual call point for emergency stopping, or temporary
holding and delaying the extinguishing process, providing extra time for evacuation of
the protected area.
The call point is designed to work with extinguishing fire control panels and it is
suitable for surface indoor mounting. The pressing of a non-latching push button
provides the delaying of the extinguishing process on the protected area with a time
programmed in advance in the control panel.
SensoMAG MHB50 is equipped with a transparent protective cover which helps for
minimizing the unwanted activation of the call point.
DoP No: 116

Technical and Environmental Specifications


Operating voltage . . . . . . . . . . . . . . . . . 9 ÷ 30 VDC
Series resistor. . . . . . . . . . . . . . . . . . . . N.A 94m
Installation wires . . . . . . . . . . . . . . . . . . 0.4mm2 ÷ 2.0mm2 mm m
60
Operation temperature . . . . . . . . . . . . . -10°C ÷ +60°C
Relative humidity. . . . . . . . . . . . . . . . . . ≤93% @ +40°C
92mm

Operating element . . . . . . . . . . . . . . . . Button, non-latching; Type B


Material (plastic), color . . . . . . . . . . . . . ABS, blue
Degree of protection . . . . . . . . . . . . . . . IP40
Dimensions (without protective cover) . . . 90x57x90mm
Dimensions (with protective cover) . . . . . 94x60x92mm
Weight . . . . . . . . . . . . . . . . . . . . . . . . . 173g

Packing Information
•Packing box - Kit of 1 unit SensoMAG MHB50, 1 unit special tool, 1 protective cover; dimensions 96x96x65 mm
•Carton box - 48 kits of SensoMAG MHB50, dimensions 486x295x196 mm

Compatible Product Range


•IVY - Extinguishing Conventional Fire Alarm Panel

Contact Information:
Teletek Electronics JSC Tel.:+359 2 9694 800 info@teletek-electronics.bg
14A Srebarna Str, 1407 Sofia, Bulgaria Fax: +359 2 9625 213 www.teletek-electronics.com

06/2020
SensoMAG MHB50 EN54-11
Emergency Stop Manual Call Point EN 12094-3

Connection Diagrams
The connection between the extinguishing fire alarm panel and SensoMAG MHB50 call point depends on the type
for activation of the panel’s HOLD input. Before realizing the connection you have to check the type (NO or NC;
“open” or “close” action is set for activation) of the HOLD input of the extinguishing panel.

Extinguishing Extinguishing
Panel Panel
MHB50 MHB50
HOLD NO NC COM
2.2K HOLD NO NC COM
2.2K
Input Input
NO Type NC Type
(Normal Open) (Normal Closed)

Contact Information:
Teletek Electronics JSC Tel.:+359 2 9694 800 info@teletek-electronics.bg
14A Srebarna Str, 1407 Sofia, Bulgaria Fax: +359 2 9625 213 www.teletek-electronics.com

06/2020

You might also like