4.5.2. Definitions
High Rise Building (SBC 801)- A building with an occupant floor located
more than 23m above the lowest level of Civil
Defense (Facility Fire Department) vehicle
access.
Shall- Indicates a mandatory requirement.
The following table provides the codes, standards, references, and guidelines
to be adopted for the buildings within the project.
Number Title
IBC International Building Code
IFC International Fire Code
NFPA 10 Standard for Portable Fire Extinguishers
Standard for the Installation of Sprinkler
NFPA 13
Systems
Standard for the Installation of Standpipe
NFPA 14
and Hose Systems
Standard for the Installation of Foam-
NFPA 16 Water Sprinkler and Foam-Water Spray
Systems
Standard for the Installation of Stationary
NFPA 20
Pumps for Fire Protection
Standard for the Installation of Private
NFPA 24 Fire Service Mains and Their
Appurtenances
Standard for Water Tanks for Private Fire
NFPA 22
Protection
Standard on Clean Agent Fire
NFPA 2001
Extinguishing Systems
NFPA 70 National Electrical Code
NFPA 72 National Fire Alarm and Signaling Code
Standard for Emergency and Standby
NFPA 110
Power Systems
Standard on Stored Electrical Energy
NFPA 111
Emergency and Standby Power Systems
4.5.4.1.1. Buildings
4.5.4.2.1. Buildings
All the buildings at site are considered as low-rise buildings. The building
height and areas are detailed below:
4.5.6.1. General
The routes for fire department access will meet the following criteria,
The surface of the fire department access route will be designed to support
a stationary load of a 50,000 kgs fire appliance. All portions of the fire
department access road will be located within 50 m (unobstructed) from at
least one fire hydrant. The fire department access road will be provided such
that every part of the buildings will be within 46m.
Aerial fire apparatus access roads in accordance with Section D105 of IFC
“International Fire Code” shall be provided meeting the following criteria
where the building exceeds 9144mm in height:
One of the main elements of the fire strategy shall apply to the project is a fire station to
serve both clusters of “Laydown Yards” and “Batch Plants Yards”.
The fire station will be located inside the laydown yard utilities area & the table below
shows the response time & travelling distance for the different areas as follows:
The figure below shows the proposed allocation of the fire station with a proposed total
built up area is 800 square meters.
The various occupancies for the buildings within the project site are classified
in SBC 201 as follows:
Fire Station 800
SBC 201 Occupancy Classification
m2 (2 x 400 m2
story)
SBC 201
Building Name Occupancy Classification
Section
Laydown Yard
Underground Water Tanks Low Hazard Factory Group F-2 Section 306
Electric Substation &
Generator Buildings Moderate Hazard Factory Group F-1 Section 306
Buried Fuel Storage Tanks Moderate Hazard Factory Group F-1 Section 306
Underground Pump Rooms Low Hazard Factory Group F-2 Section 306
Underground Water Tanks Low Hazard Factory Group F-2 Section 306
Electric Substation &
Generator Buildings Moderate Hazard Factory Group F-1 Section 306
Buried Fuel Storage Tanks Moderate Hazard Factory Group F-1 Section 306
Underground Pump Rooms Low Hazard Factory Group F-2 Section 306
Concrete Batch Plants Low Hazard Factory Group F-2 Section 306
Asphalt Batch Plants Moderate Hazard Factory Group F-1 Section 306
4.5.8. Construction
Where the requirements on SBC varies from IBC, the more stringent
requirement shall apply.
The underground water tanks, & pump rooms are combined into one
structure and is classified as a Factory Group F-2 (occupancy)
facility. Based on the building height, building (footprint) area, and the
requirements of SBC 201, the building is required to be constructed
as Type IIB construction.
The Fuel Depot Area is a Factory Group F-1 facilities. Based on the
building height, building area (footprint), and the requirements of SBC
201, the building is required to be constructed as Type IIA
construction.
The Concrete Batch Plants’ Yards are a Factory Group F-2 facilities.
Based on the building height, building area (footprint), and the
requirements of SBC 201, the building is required to be constructed
as Type IIA construction.
The Asphalt Batch Plants’ Yards are a Factory Group F-1 facilities.
Based on the building height, building area (footprint), and the
requirements of SBC 201, the building is required to be constructed
as Type IIA construction.
The Labs are a Factory Group F-2 facilities. Based on the building
height, building area (footprint), and the requirements of SBC 201,
the building is required to be constructed as Type IIA construction.
The below SBC table 601 lists the building type of construction and fire
resistance rating requirements for the building elements.
LV room 2 hrs
Where fire barriers are required, the requirements of SBC 201, section 707
shall apply. The building construction will be based on, but not limited to the
below requirements.
Penetrations into fire walls, fire barriers, smoke barrier walls shall comply
with the requirements of SBC 201, Section 714.3.1 to 714.3.3.
Fire door and fire window assemblies within required fire barriers shall be
installed in accordance with NFPA 80 "Standard for Fire Doors and Other
Opening Protectives" and shall have the following fire protection ratings in
accordance with IBC 2018, Table 716.5 as below:
In accordance with SBC 201 Table 602, fire resistance rating of exterior walls
are determined based on the occupancy classification and separation
distance between buildings. Buildings that are spaced up to less than 9m
apart will require a fire resistance rating of not less than 1 hour. Buildings that
In accordance with SBC 201, table 1017.2, the maximum travel distance
from any part of the buildings to an exit shall be based on the following:
Occupant loads for the buildings will be based on the following factors
established in SBC 201 Table 1004.1.2:
The below tables reflect the occupant load for each space within the various
buildings determined based on the above occupant load factors.
FACTOR OCCUPANT
(SQ. M./ LOAD
FLOOR LEVEL/ SPACE OCCUPANCY USE FLOOR AREA
PERSON) (PERSONS)
USE (SQ. M.)
Total 6414
Other areas (Fire station & guard rooms) occupant load is 53.
FACTOR OCCUPANT
(SQ. M./ LOAD
FLOOR LEVEL/ SPACE OCCUPANCY USE FLOOR AREA
PERSON) (PERSONS)
USE (SQ. M.)
Total 8580
The requirements for dead end corridors and common paths of travel
below are determined by the individual space/ room occupancy
classification in accordance with SBC 201, table 1006.2.1 and
Section 1020.4.
Rooms
(Occupancy) Un sprinklered Sprinklered Un sprinklered Sprinklered
Business (B) 23 30 15 15
Factory (F) 23 30 15 15
High Hazard Not Permitted 7.5 Not Permitted Not Permitted
Exit signs shall be provided within the facilities in accordance with the
requirements of SBC 201 Section 1013.
Exits, other than main entrances to a building that are obviously and
clearly identifiable as exits shall be marked by an approved sign that is
readily visible from any direction of exit access. Horizontal components
of the egress path shall be marked with directional exit signage where
the continuation of the egress path is not obvious.
4.5.10.1. General
4.5.10.3. Notification
Fire alarm systems shall annunciate at the fire alarm control unit and
shall initiate occupant notification upon activation in accordance with
Sections 907.5.1 through 907.5.2.3.3 of SBC 201/ 801.
Emergency and standby power systems shall comply with SBC 201/
801 section 2702 and shall be installed in accordance with SBC 401,
NFPA 70, NFPA 110 and NFPA 111.
Emergency and standby power systems will be provided for critical fire
protection and life safety systems in all buildings. The systems shall
be capable of operation the following equipment for a time specified
by SBC 201/ 801:
The illumination level under normal power shall not be less than 11 lux
at the walking surface. Illumination level under emergency power shall
be in accordance with SBC 201/801 section 1008.3.5.
The emergency power system shall provide power for a duration of not
less than 90 minutes.
Generators’ Buildings
Battery rooms shall be equipped with ATEX rated duty and standby
exhaust fans to limit hydrogen concentration below 1% of volume.
All HVAC systems will be automatically shut down in case of fire. Fire
and Smoke Dampers
Fire dampers will be provided with fusible link for the Fire
walls/partitions. Motorised Smoke and Fire Dampers will be provided
in ducts penetrating walls/partitions to the rooms protected by
gas suppression system to keep required gas concentration.
Dampers will be normally open and close from signal from the fire
alarm system.
Motorised Fire and smoke dampers for Fire Pump rooms will have a
230V AC supply to power the damper to its normally open position
and a spring closure on loss of power. The actuator will not close the
damper unless the power is lost for a period of 4 seconds or more.
Visual indication of damper status will be in a remote panel. The
damper will have a fusible link and operate independently as a fire
damper.
All buildings within the Laydown & Batch Plants Yards require Portable
Fire Extinguishers.
MV/VFD room.
LV room.Rack equipment room.
Battery room.
Laydown Yard
Pumps
The Laydown Yard Pumping station shall comprise a set of pumps (electrical,
diesel and jokey), pumps are housed in a separate underground pump room,
attached to the storage tank.
The fire pump station will be installed in the potable water pump room.
Storage
The Laydown Fire Water storage for internal firefighting networks shall be 1500
gpm for 60 min.
Pumps
The Batch Plants’ Yard Pumping station shall comprise a set of pumps
(electrical, diesel and jokey), pumps are housed in a separate underground
pump room, attached to the storage tank.
The fire pump station will be installed in the potable water pump room.
Storage
The Laydown Fire Water storage for internal firefighting networks shall be 1500
gpm for 60 min.
The fire protection provisions for each Building / Area based on SBC
201, 801 and IBC are identified herein.
Factory Clean
Gen. Bld. 800 GF Type IB Yes No No
Group F-1 Agent
2 egress
pathways
provided from
Business GF Clean each level
Fire Station 800 Type IIA Yes No No
Group B +1st F Agent 1 hour
passage way
2 hr exterior
resistance
Shall be
verified
by EPC
contract
Factory Clean
Fuel Depot 15000 GF Type IB Yes No or No
Group F-1 Agent
based
on each
plot
layout
Leak
Buried Fuel Factory
280 Buries No No No Detectio
Tank Group F-1
n
Shall be
verified
by EPC
Laydown 137156
contract
Yards (LY-01 Storage (Total Fire
GF Type IIA Yes No or
to LY-07 & LY- Group S-2 Plot Hydrants
based
09 to LY-14 Area)
on each
plot
layout
Shall be
verified
by EPC
50,000
contract
Nesma Camp (Total Fire
Residential GF Residential Yes No or
(LY-08) Plot Hydrants
based
Area)
on each
plot
layout
Factory Clean
Gen. Bld. 800 GF Type IB Yes No No
Group F-1 Agent
Leak
Buried Fuel Factory
735 Buries No No No Detectio
Tank Group F-1
n
Shall be
verified
by EPC
72000
Asphalt Plant contract
Factory (Total Fire
(AP-01 to AP- Yes or No
Group F-1 Plot Hydrants
04) based
Area)
on each
plot
layout
Shall be
verified
by EPC
Concrete Plant contract
Factory Fire
(CP-01 to CP- 120000 Yes or No
Group F-2 Hydrants
08) based
on each
plot
layout
Shall be
verified
by EPC
contract
Pre-cast Fire
Factory 35000 GF Yes No or
Concrete Hydrants
Group F-2 based
on each
plot
layout