A /. CACULATING PURLIN :
1/. Choosing section :
1 . Load on purlin :
Using roof sheet thickness = 0.5 mm
2
Weight of roof sheet qtl = 5.26 Kg/m
Slope i% = 10 %
α = 5.71 ñoä
Purlin spacing b = 1.25 m.
Column spacing l = 12 m.
Loading factor n = 1.05
2
Standard uniform live load qc = 30 Kg/m
q c × b + q tl × b
q = n ×( ) = 46.51 Kg/m.
cos α
qy ×l2
M = = 555.37 Kg.m.
x 12
qx × l2
M = = 55.54 Kg.m.
y 12
Mx
Wx = = 55.02 cm3,
[σ ]
My
W = = 2.64 cm3,
y [σ ]
qc × b + qtl × b
q = n ×( + g) = 56.20 Kg/m.
cosα
Mx = 1155.37 Kg.m.
My = 55.54 Kg.m.
5 qy × l
4
fy = × = 4.828 cm.
384 E × I x
f f 1
⇒ = 0.00402 ≤ = = 0.00556 =====> Ok
L L 180
==>The chosen purlin is ok .
a Building dimention:
Height (Top column) : 11 m.
Span l: 84 m.
h1/l = 0.131
α = 5.7 ñoä
column spacing b = 12 m. Do ñoù : c1 = 0.80
c2 = -0.115
c3 = -0.40
c4 = -0.60
b Building location KCN ÑÖÙC HOØA 3 - LONG AN
Wind zone IIA
Ratio height/span is : H/L = 0.131 < 1,5
No need to caculate gust wild load , just caculate static wind load.
Realibility ratio no = 1.2
Assumtion time for building (years): t = 50
Adjust ratio base on the assumtion time:
α= 1 1008
The static wind load caculated : 756
W = no x Wo x k x c x a x α . 378
2
Wo = 83 Kg/m . 1.092
Relief style A unmasking
Ratio base on height K = 1.092
Ratio base on the changing of pressure at base of column K = 1
(See appendix)
PROJECT: FILLING HOUSE - STORAGE
Internal force :
Combination : ENVE 1C1 + 1C2 + 1C3
N (Kg) Q (Kg) M (Kg.cm)
30,000 17,600 4,600,000 (Fixed at base)
Enccentric e and the height of base column section h :
M 153.3333333 cm.
e = =
x N
l
h= = 91.67 cm.
12
Required area :
N e
77.60 cm2,
Ayc = × 1, 25 + 2, 5 × x =
R ×γ h
tf = 1.1 2.5 Ok
tw
hw = 2.9 5. Ok
wf
N M Kg/cm2,
σ = + x = 922 ≤ γ × R = 2,100 Ok
Ath Wxth
PROJECT: FILLING HOUSE - STORAGE
M
e = = 733.33 cm.
x N
l
h= = 91.67 cm.
12
Required area
N e
Ayc = × 1, 25 + 2, 5 × x = 121.43 cm2,
R ×γ h
tf = 1.14 2.5 Ok
tw
hw = 2.89 5. Ok
wf
Checking strength conditions :
lc J r1 J r 2
n= + =
PROJECT: FILLING HOUSE - STORAGE
The connect joint between column and foundation is spin, we use fomula:
0 . 38
µx = 2 1+ = 2.18
n
lox = µ ×l = 2,401 cm.
Slenderness:
l ox
λx = = 68.93 < [λx ] = 120 Ok
rx
d. Checking the column follow the general bucking condition:
In bending face :
Relativistic enccentricity m:
ex 27.21 cm.
m = =
ρx
Where Wx 26.95 cm.
ρx = =
A
R
λ x = λx × = 2.18 cm.
E
Ac 0.39
=
Ab
Where: Ac = δc ×bc = 4800 mm
2
1 flange area
Ab = δb × (h − 2×δc ) = 12152 mm
2
web area
Ac η value when
Ab 0 <= λ--x <= 5 λ--x > 5
0.1 <= m <= 5 5 < m <= 20 0.1 <= m <=5 5 <= m <= 20
0.25 (1.45 - 0.05m) - 0.01(5-m)λ--x = 0.574 1.2 1.2 1.2
0.5 (1.75 - 0.1m) - 0.02(5-m)λ--x = -0.003 1.25 1.25 1.25
PROJECT: FILLING HOUSE - STORAGE
R
λ y = λy × = 3.293 cm.
E
R
ϕy = 1 − 0,073 − 5, 53 × λ × λ = 0.60
E
Caculating C - Influent factor of bending moment Mx and the section shape to the bucking
of column in the face which perpendicular to bending face . With
Convention moment value M' use to check bucking on out-of frame plane is the maximum
of three factors :
_ M M
M ' = max M ; 1 ; 2
2 2
Where:
__
M = M2 +
(M1 − M 2 )
3
With M1/2 = 4,400,000 (kg.cm)
M2/2 = 2,300,000 (kg.cm)
__
M = 6,000,000 (kg.cm)
==> M' = 6,000,000 (kg.cm)
PROJECT: FILLING HOUSE - STORAGE
M '
=
e' N
m = = 18.5
ρx
x
W x
A ng
R
ϕc = 1− 0,073− 5,53 × λc × λ c =
E 0.60
N Kg/cm2,
σ = = 1,807 ≤ γ × R = 2,100 Ok
C ×ϕ y × A
The chosen column satisfy general bucking condition and strength condition .
e/ Checking partial bucking of column
Flange
PROJECT: FILLING HOUSE - STORAGE
M max
Wyc = =
R ×γ
PROJECT: FILLING HOUSE - STORAGE
M max
Wyc = = 4,190.48 cm3,
R ×γ
tf = 1.60 2.5 Ok
tw
hw = 2.89 5. Ok
wf
Checking strength conditions :
a. Bending strength :
M max ≤ γ × R = Kg/cm2,
σ= = 1,636.0 2,100 Ok
Wx
b. Shearing strength :
Q max × Sc Kg/cm2,
τ = = 183.51 ≤ γ × R = 1,300 Ok
Ιx ×δb
c. Partial stress on web :
Px = 14,500 Kg.
Z = bc + 2 x tw = 32 cm.
Px Kg/cm2,
σ cb = = 453 ≤ γ ×R = 1,300 Ok
tw × Z
Required moment
M max
Wyc = = 1066.67 cm3,
R ×γ
Mmax Kg/cm2,
σ= = 692 ≤ γ × R = 2,100 Ok
Wx
b. Shearing strength :
Q max × Sc
τ= = 78.05 ≤ γ × R = 1,300 Kg/cm2, Ok
Ιx ×δb
c. Partial stress on web :
Px = 4,200.00 Kg.
Z = bc + 2 x tw = 32 cm.