Flowmeter Primer: Two-Wire Coriolis and

Electromagnetic Transmitters
automation.isa.org/2017/11/flowmeter-primer-two-wire-coriolis-electromagnetic-transmitters/

November 1, 2017

This article was written by Nathan Hedrick, flow product marketing manager at
Endress+Hauser.
Two-wire transmitter technology came about from an agreement among various instrument
suppliers in the 1950s to standardize on 4–20 mA current loops as a means of sending a
flow, temperature, pressure, or similar process signal back to control and monitoring
systems. In the 1980s, HART was added to the 4–20 mA signal, providing additional
calibration and diagnostic information. In 1986, 4–20 mA HART was made into an open
protocol, and today it is by far the world’s leading digital instrument communications
protocol.

Although wireless and EtherNet/IP technologies have joined the process transmitter scene
in recent years, two-wire flow transmitters continue to play an important role due to
technological advances in their power management and other systems. This article
describes basic two-wire technology and the advances made using this technology in two
types of flowmeters: Coriolis and electromagnetic meters.

Two-wire basics
The fundamental concept to understand about two-wire technology is that devices using it
are powered by and communicate with the same two wires in a loop. This is why two-wire
technology is often referred to as loop power.

1/7
A loop-powered instrument using a 4–20 mA output regulates its current consumption to
vary in proportion to its measured process variable. Typically, 4 mA is zero, and 20 mA is
full scale. Due to NAMUR standards, which are common in the chemical industry, two-wire
instruments support an alarm state of 3.6 mA, that is, if the output drops to or below 3.6
mA, the control system knows there is a need to investigate what is occurring at the device.

A two-wire instrument using a standard 24 volts direct current (VDC) power supply can
perform with less than 0.1 W of power, a very safe power level. When equipped with an
intrinsic safety barrier to prevent too much current being introduced into the loop, two-wire
transmitters can operate safely in many hazardous areas, eliminating the need for
protective conduit, explosion-proof enclosures, and other safety-related components.

Until recently, the low power available in a two-wire system limited the technology to
relatively unsophisticated flow devices. Coriolis and electromagnetic flowmeters required
too much energy, and therefore needed a dedicated power supply.

In these systems energy was supplied by a four-wire infrastructure, where two of the wires
carried power and two carried the process variable signal. Using four-wire technology in a
hazardous environment required more extensive and expensive safety precautions, and of
course was more expensive because more wiring needed to be run. It was not until 2011
that modern electronics technology made it possible for Coriolis mass flowmeters and
electromagnetic flowmeters for larger line sizes to operate as two-wire devices.

Coriolis flowmeters
The earliest description of the Coriolis measuring principle is attributed to a French
physicist and mathematician, Gaspar Gustave de Coriolis. The principle is based on the
oscillation of the tubes and the linear movement of the flowing fluid (figure 1). This results
in the Coriolis force causing the measuring tubes to “twist” (b, c). Sensors (A, B) at the inlet
and outlet of a Coriolis meter register the difference in time of this movement, which is also
known as the phase difference. A higher mass flow causes a higher phase difference.

2/7
Figure 1. How a Coriolis flowmeter works

Coriolis flowmeters can also measure temperature (with built-in resistance temperature
detectors), mass flow, and density. They measure density by measuring the resonance
frequency of the tubes. While the mass flow rate is directly proportional to the phase shift,
density is inversely proportional to the resonance frequency. A higher density results in a
lower resonance frequency.
3/7
With its 4–20 mA HART output, a two-wire Coriolis meter can send flow, temperature, mass
flow, and density data back to the controller—along with diagnostic, calibration, and status
information.

A Coriolis flowmeter is extremely accurate—typically 0.1 percent of reading—and has no


moving parts that can clog or fail. It is also unaffected by changes in viscosity. Thus, it is an
excellent replacement for more inaccurate flowmeters, and it can use the existing two-wire
cable that powered the older flowmeter.

The first two-wire Coriolis flowmeter appeared in 2011 (figure 2), thanks to innovations in
device power management. The flowmeter operated on a single, 4–20 mA HART two-wire
loop, was remotely powered by a DC supply, was certified for use in Class I, Division 1
areas, and could be deployed in an intrinsically safe system through the use of approved
safety barriers.

Electromagnetic meter basics


The first electromagnetic flowmeter can be attributed to Swiss cleric and inventor Father
Bonaventura Thürlemann, but the physical phenomenon driving its operation was first
described by English physicist Michael Faraday. Faraday realized that electric charges are
induced in a conductive metal rod of length (L) moved at velocity (v) through a magnetic
field (B), and, consequently, a voltage (Ue) of a few millivolts is generated between the
ends of the rod. He also discovered that the magnitude of the voltage is directly
proportional to the velocity of movement and strength of the magnetic field, as expressed in
the equation:

Ue = B x L x v

In an electromagnetic flowmeter with known length (L), the conductive fluid flowing inside
the measuring tube corresponds to the metal rod in Faraday’s experiment. A magnetic field
of constant strength is generated by two field coils, one on each side of the measuring
tube. Two electrodes on the inside wall of the pipe detect the voltage generated as the fluid
4/7
flows through this field.

The measuring tube is electrically insulated from the fluid and the electrode with a
nonconductive lining (e.g., polyurethane, polytetrafluoroethylene, hard rubber). Given a
magnetic field of constant strength (B), the equation above shows that the induced voltage
(Ue) is directly proportional to the flow velocity (v). Based on the known cross-sectional
area of the pipe, the volumetric flow rate can then be calculated.

Two-wire electromagnetic flowmeters have been available for some time, but advanced
device power management was not incorporated until 2013. The original two-wire devices
were severely limited in size because of the low power available, but new two-wire
electromagnetic flowmeters (figure 3) are now available for line sizes up to 8 inches in
diameter.

Figure 3. How an electromagnetic flowmeter works

Two-wire advantage
Two-wire flow measurement has traditionally been limited to relatively unsophisticated
technologies, such as variable area, differential pressure, positive displacement, and
turbine meters, due to the limited power available to the devices. However, innovation in
device power management has brought significant advancements in the adoption of more
modern two-wire flow measurement technologies such as Coriolis and electromagnetic
flowmeters.
5/7
The first advantage of a two-wire flowmeter is the reduction of required wiring and conduit.
A two-wire device cuts capital costs by a conservative estimate of $1,000 per measuring
point in new installations. These savings come from reduced material costs for wires and
conduit, as well as reduced labor costs.

Plants with existing four-wire installations can also benefit from switching to two-wire
technology. Benefits include lower energy and operating costs. Many four-wire Coriolis and
electromagnetic flowmeters are rated at up to 15 W of power consumption, while a two-wire
transmitter requires only 0.1 W. Using a two-wire flowmeter reduces energy consumption by
96.4 percent compared to a four-wire flowmeter.

Many two-wire flowmeters can operate in an intrinsically safe environment, which inherently
limits the power available through the use of intrinsic safety barriers. This eliminates the
flowmeter as a possible ignition source. Not only does this enhance plant safety, but it also
allows access to the device for programming or maintenance without taking it out of
operation, improving plant productivity and lowering operating costs.

Advances in Coriolis and electromagnetic flowmeters make the adoption of two-wire flow
measurement more attractive than ever before. If a plant chooses to implement these
meters, it can expect savings on both capital and operating costs, increased plant
productivity and revenue, and better risk mitigation through improved safety for plant
personnel, processes, and equipment.

About the Author


Nathan Hedrick has more than
six years of experience
consulting on process
automation. He graduated from
Rose-Hulman in 2009 with a
bachelor’s degree in chemical
engineering and began his
career with Endress+Hauser
as a technical support
engineer. In 2014, Hedrick
became the technical support
team manager for the flow
product line. He has recently
taken on the position of flow
product marketing manager.
Connect with Nathan:

6/7
A version of this article Figure 4. Two-wire electromagnetic flowmeters were once limited in
size. Advances in power management now allow for line sizes up to 8
originally was published at inches.
InTech magazine.

7/7