Professional Documents
Culture Documents
Iemdc 2001 939272
Iemdc 2001 939272
JMFogarty -
Power Generation Technology
GE - Power Systems, SchenectadyNew York
1 INTRODUCTION
Table 1 - Linkage Between Key Technical Require-
The purchaser of a modem power generator expects it to ments and Generator Performance Characteristics
produce electric power reliably and economically over the
useful life of the power plant. In particular, it is expected Purchaser Related Design or
to operate for significant intervals without requiiing off- Requirement Performance Parameter
line maintenance, and that any maintenance, when re- Overall size and cost of the
quired, can be performed quickly and without significant kVA Rating generator
disruption of the power plant operation. Furthermore, it is
expected to operate efficiently and without significant sup- Armature Voltage Cooling system
port personnel. Exciter rating
Rated Power Factor Cooling system
Successful design and operation of the generator de- Volume of active material
pends on agreement between the generator manufacturer Short Circuit Ratio Efficiencv
and purchaser regdrding the t e c h c a l requirements of the
Operating Temperature
generator. Many of those requirements are published in Limits
standards such as ANSI C50.13 and IEC 34-1 and are
common across broad classes of generators. Additional
technical requirements or specific requirements in lieu of
those covered by the standards are given in the purchase
specification for the generator. Reliabilitv Management of Forces
N@v@I@
kV.4 = -
1000
1
-0/01/$10'2001~IEEE
0-7803-7091
where the voltage and current are phase quantities and the kVA = k32@@MAR [41
number of phases is uniformly three. The selection of an
output rating and armature voltage thus fixes the armature
where k3 is yet another constant. Eq. 4 highlights the fun-
phase current.
damental design trade-off made by the generator designer.
For a given kVA rating, the designer must select either
According to Faraday's Law, the phase voltage pro-
high flux or low flux (larger machine vs. smaller machine)
duced in the armature winding is proportional to the mag-
which then fixes the level of armature reaction MMF. A
netic flux in the machine and the speed of operation. The
low flux machine would be physically smaller but it would
magnetic flux in the machine is
then have a higher level of armature reaction MME.
2
52
and unity power factor requires lesser field current and However, because most generators exhibit some level of
operation in the underexcited region requires the least field saturation, the SCR is slightly less than that indicated by
current. Eq. 5.
The higher field currents associated with the overex- The trend has been toward lower SCRs. SCRs of 1.0
cited region power factors allow the generator to produce to 0.8 were common 70 years ago. In the 1960’s, they were
greater levels of reactive power (VARS) but at the expense in the range of 0.58 - 0.64. Now 0.50 or less is typical. The
of higher losses in the generator field winding and a higher generator designer achieves a given SCR by choosing an
capital cost for the generator and excitation system. The appropriate length of air gap between the rotor and stator.
trend has been to rate smaller turbine-generators at power Higher SCRs require longer air gaps, causing greater gen-
factors of either 0.80 or 0.85. At higher ratings, the power erator field current, higher field winding losses, greater
factor shifts to 0.90 or higher to avoid the excessive size of cooling requirements and lower overall efficiency.
the generator and excitation system
A high SCR was typically specified to achieve desired
stability levels on the power system. Modem static excita-
tion systems with high initial responses, make it possible
1.2 to achieve good stability even with generators of low SCR.
Per Unit Now the purchaser can achieve all of the benefits of a high
kVA
SCR without the “costs.”
1.o
-----Y
,
Underexcite Overexcited
the degradation of the insulation systems. Typically the
working lifetime of the insulation is halved for every 10°C
increase in the operating temperature. For this reason, the
standards acknowledge that at the peak and peak reserve
Field Current (Amps) capabilities assigned to generators, temperature rises be-
yond the capability of the insulation system are permitted
and that accelerated loss of life will occur.
Fig. 1 - Typical Generator Vee Curve The characteristics of modem insulation systems are
such that no appreciable loss of life occurs provided oper-
ating temperatures do not exceed the temperature rating of
6 EFFECT OF SHORT CIRCUIT RATIO the insulation.
The short circuit ratio (SCR) is a measure of the in- The second hazard posed by high temperatures is re-
herent steady state stability of the generator on the power lated to thermal expansion of the heated components.
system. In the absence of magnetic saturation in the gen- Thermal cycling of the field and armature windings is an-
erator the SCR is the inverse of the direct axis synchronous ticipated in the design of the generator and steps are taken
reactance. Thus, approximately, to accommodate it. Nonetheless, higher than expected
temperatures may lead to excessive relative motion among
1 winding components and accelerated wear of the windings.
SCR ~
1151
Xd Through proper design of the stator and rotor and their
windings, one can provide for the effects of thermal ex-
pansion and thus minimize their impact on the life of the
3
53
machine. If a given application imposes extraordinary designed to accommodate the expected thermal expansions
thermal duty on the generator, the specific nature of the but limit radial and peripheral motion. Likewise, compo-
duty should be explicitly defined in the specification to nents can be designed to restrain the windings from fault
ensure the generator is properly designed. forces and to immobilize the winding with respect to run-
ning forces.
8 EXTREME AMBIENT CONDITIONS The final source of forces is purely mechanical and
results from cycling each time the rotor is brought to rated
In many instances, generators are expected to operate speed and then stopped. Metallic components in both the
over a wide range of temperatures. In some cases, the rotor and field coils must be designed to withstand the low
minimum ambient temperature may be as low as -30 "C. In cycle fatigue inherent in such operation.
others, the maximum ambient temperature may be as high
as 50 "C. In all cases, the generator must perform reliably
P
and within temperature limits. System
Fault
Forces
The cooling system must be specifically designed to
accommodate a wide range of temperatures. The liquid loo
coolant may be water or fluids such as ethylene glycol.
The choice of coolant will dictate the size of the coolers
and the type of auxiliary equipment supplying the coolers.
Relative
Force Thermal
Other environmental conditions may dictate special Level Expansion
features within the generator. Particularly dusty conditions Porces
or caustic environments would preclude open ventilated
air-cooled units in favor of TEWAC or hydrogen-cooled
configurations. In particularly corrosive environments,
special steps must be taken to protect the generator.
1 -
0 120 Hz
Running
Forces
9 MANAGEMENT OF FORCES
The forces associated with thermal expansion are as- Number of Cycles or Occurrences
signed a reference level of 1.0. The normal double fie-
quency running forces would be approximately one-tenth
as great. The forces from synchronizing out of phase or Figure 2 - Range of Forces Encountered
short circuits would be about 100 times as great. During Operation
4
54
The primary effects of these variations are higher than Hydrogen cooling enables the generator designer to
nominal magnetic loading and excessive heating, both achieve a higher specific output (kVAkg), so a hydrogen-
from the overloaded components and the reduction in cooled generator will be smaller than an air-cooled ma-
cooling that may occur at slower speeds. chine of the same rating. It will also be more efficient be-
cause of the reduced fan and windage losses. Many
Eq. 2 shows the relationship between the magnetic hydrogen-cooled generators would be unacceptably large
flux, armature voltage, and frequency. If the voltage is 5% if designed as an air-cooled generator.
high and the frequency is 5% low at some instant, the flux
in the magnetic portions of the machine is 10% above the
nominal value. The higher flux leads to higher core losses, 13 UNBALANCED LOADING
increased magnetic saturation, significantly higher excita-
tion currents, and higher temperatures. Unbalanced loading generally refers to negative phase
sequence currents (12) flowing from the power system.
It is possible to design the generator to accommodate Those currents produce a magnetic field in the generator
such off-nominal operation. In general, the designer will that rotates in the opposite direction to the rotor. The rela-
provide additional magnetic material and operate the ma- tive motion of the rotor and the magnetic field induces
chine at slightly lower temperatures in anticipation of these double frequency currents in the rotor surface that can be
overloads. Such changes lead to a larger machine and particularly high, leading to damaging temperatures.
higher initial capital costs.
The heating caused by a given level of negative phase
sequence currents is directly related to the armature reac-
11 SUBTRANSIENT REACTANCES tion MMF. See Eq. 3. It was noted that the designer might
select a low level of magnetic flux to achieve small size
Minimum values of the subtransient reactance (X"dv) while accepting a higher level of armature reaction MMF.
are typically specified to limit fault currents the generator The heating level on the rotor surface varies as the square
or high side circuit breakers must handle. Larger genera- of the armature reaction MMF and could be the factor that
tors will typically have rated voltage subtransient reac- limits the armature reaction MMF level.
tances in the range of 15 - 20% on the generator reactance
base. Smaller gas turbine driven generators may have Val- The capability of the generator to withstand short-term
ues of 15% or less. unbalanced loads is expressed as the product of :1 inte-
grated over the transient event and is referred to as I;t.
The subtransient reactance is the sum of the armature Both the ANSI and IEC standards specify minimum levels
leakage reactance (Xlv) and a contribution from the amor- of unbalanced loading capability as a function of the kVA
tisseur and field windings. For generators with solid iron rating of the generator. .
rotors (almost all turbine-generators), the field winding
contribution is insignificant and the amortisseur contribu- In the case of a line-line fault near the generator ter-
tion is only a few percent. minals, the peak rotor surface currents can be extremely
high. A rotor wedge could carry in excess of 100,000 am-
When a minimum subtransient reactance is specified, peres. Although such a fault might be cleared within cy-
the generator designer can increase the reactance by se- cles, such currents are capable of burning contact points in
lecting specific winding pattems. If that step is insuffi- the rotor circuits leading to potential crack initiation sites.
cient, one may deepen the stator slots or lengthen the stator
core, both of which will increase the size of the machine. At higher ratings (> 700,000 kVA) it will usually be
necessary to provide additional capability to carry the rotor
12 COOLING GAS surface currents by including explicit amortisseur windings
and taking steps to minimize contact resistances among the
Hydrogen and air are both used as primary coolants in rotor structural components.
the generator. Hydrogen has been used since the late
1930's and a large experience base exists to justify its use. Similar heating can occur if the armature current con-
tains harmonic components other than the rated frequency
Air-cooling offers simplicity in the design of the gen- currents. These currents will generally be present if there
erator. The stator frame and packaging are designed to are nonlinear loads, such as solid state power converters or
enclose the machine but are not pressure vessels. The gen- electric arc furnaces, on the power system. If a given gen-
erator does not require any additional auxiliary systems erator application also includes such harmonic currents, it
nor shaft seals. Accordingly, air-cooled generators can is important to define those currents in the specification so
operate unattended in remote locations. the rotor can be properly designed.
5
55
Real e
POU
14 UNDEREXCITED OPERATION 0.30 PF Overexcited
6
56