Professional Documents
Culture Documents
Harmonic Impedance of Single-Core Armored Cables
Harmonic Impedance of Single-Core Armored Cables
Cables
Z.H. Yuan and Y. Du
Authorized licensed use limited to: Rolls-Royce. Downloaded on August 26,2021 at 10:04:58 UTC from IEEE Xplore. Restrictions apply.
consecutive sections. Both single-point bonding and cross sequence depending on whether the order was triplen or nor.
bonding methods are normally applicable to the short and The neutral cable was connected to the supply only during the
long single-core cables, respectively. zero-sequence impedance measurement, as illustrated in
Figure 2.
III. EXPERIMENTAL
PROCEDURE
Figure 2 shows the experimental setup of harmonic W. HARMONIC Ih4l’EDANCE
impedance measurement. Three-phase harmonic currents are In the experiment voltage, current and active power of
generated from a harmonic current source. They are applied order h on three cables were recorded with PM3000A. Both
to sample cables under test. Voltages, currents and powers on resistance Rh and reactance xh of order h per phase, then,
the cables were measured with Power Analyzer PM3000A. were calculated by
The recorded data, then, were used to determine harmonic R, =Ph/Ii
impedance of these cables. (1)
The cables under test were four single-core armored cables
to BS6724 [7]. These cables have a conductor size of 185mm2,
X h = .JET77
where vh,I, and Ph are the average values of all phase
and a length of 10 meters. In the experiment the cables run in
voltages, phase currents, and phase powers at order h,
parallel on a non-magnetic surface, and were arranged
respectively. For the simplicity of discussion, both harmonic
according to Figure 1, that is, in the flat and touching
configuration, or flat and spaced configuration or trefoil resistance and reactance of the cables are expressed in terms
of ratios with reference to cable DC resistance and 50%
configuration. The single-core armored cables were connected
together at one end with a copper busbar, and connected to a reactance, respectively.
current source at the other end. The armors of these cables A. Harmonic Resistance
were bonded either at one cable end or at two cable ends Figure 3 shows the ratio curves for positive-sequence
depending whether the single-bonding method or solid resistance of the cables under three different configurations
bonding method is employed. with the single-point bonding or solid bonding method, as
The harmonic current source consisted of one harmonic illustrated in Figure 1. The ratio curves for zero-sequence
signal generator, three power amplifiers and three step-down resistance of the cables are shown in Figure 4. In these figures,
transformers, as illustrated in Figure 2. In the experiment, the abbreviation ‘SPB’ denotes ‘single point bonding’ while
three-phase currents were injected into the cables under test ‘SB’ denotes ‘solid bonding’.
via the step-down transformers. These currents generated
three-phase voltages on the cables.
8
Shortcircuit connection -&-(b)SPB --t(b)SB
cable conductors
6
0
$ 4
0
1 3 5 7 9 11 13 15 17
em sequence current
Harmonic Order h
Fig.2. Experimental setup for harmonic impedance measurement It is noted from these figures that cable resistance
increases with increasing harmonic order. This is because
In the measurement of harmonic impedance distorted both skin and proximity effects become stronger at a higher
voltages were generated from the power amplifiers. They frequency, subsequently the current within the conductor
contained one fundamental component and one harmonic becomes less uniformly distributed. When the armors are
component at the orders up to 17. The ratio of the solidly bonded, the circulating currents within the armors
fundamental voltage to the harmonic voltage remained one for creates additional losses are added on the cables. This results
all orders. The fundamental voltages were positive sequence, in a significant increase of cable resistance at harmonic
while the harmonic voltages were either zero or positive frequencies. The armor loss almost exceeds the conductor
46
Authorized licensed use limited to: Rolls-Royce. Downloaded on August 26,2021 at 10:04:58 UTC from IEEE Xplore. Restrictions apply.
loss at the 3d order, and is up to 4 times the cable conductor
loss at the 17" order, as seen in these two figures.
1
It is also noted that the cable resistance is the highest when
the cables are arranged in flat and spaced configuration. This
is because of the highest currents induced within the armors 0.75
under this configuration. Usually the induced current is higher
when the cable spacing is larger. It is noted that the difference
among the resistance curves under three different
3 0.5
2 L
Y
3
0.75
01
1 3 5 7 9 1 1 1 3
' I
Harmonic order h
I
2 0.5
-
Fig. 4 Harmonic Resistance ( 2 r o Sequence)
0.25 -0- (a) SPB -0- (a) SB
(d) Flat and touching formation
(e) Flat and spaced formation &(b)SPB --&-(b)SB
(f) Trefoil formation (C) SPB --f (C) SB
B. Harmonic Inductance
Cable inductance against order h is presented in Figure 5
and 6. It is noted that cable inductance is frequency-
dependant, and generally decreases with increasing frequency.
Fig. 6 Harmonic Inductance (Zero Sequence)
The decreasing inductance is mainly due to the induced (a) Flat and touching formation
current within the cable conductor and armor. For example, (b) Flat and spaced formation
the induced current circulating within armors cancels partially (c) Trefoil formation
the flux from the current flowing along the cable conductors.
This leads to a reduction of flux linkage of the cable IV. CONCLUSIONS
conductors, subsequently a reduction of cable inductance. The This paper investigated experimentally harmonic
induced current becomes stronger at a higher frequency. impedance of 185mm2 single-core armored cables. The
Accordingly the reduction of cable inductance is larger at the impact of cable configurations and armor bonding methods
higher frequency. were revealed.
The reduction of flux linkage to cable conductors is even It is noted that the solid bonding method is widely used in
stronger if the armors are solidly bonded, as seen in these local buildings for the concern of safety. However, this
figures. The induced current circulates within the loops method causes significant power losses when the cables carry
formed by armors, and greatly reduces the flux linkage to the rich harmonic currents. But it generates less harmonic voltage
cable conductors. The cable inductance is reduced by 25% at drops on the cables than expected.
the 3d order, and up to 70% at the 17" order under the flat Single-point bonding method is recommended if the power
and spaced formation. losses in distribution circuits are the issue of concern. The
There is no significant discrepancy among three different single-point bonding method is accepted from the viewpoint
cable configurationswhen the armors are bonded at one point. of safety if the cables are short in length. When the cables are
But the discrepancy is significant if the armors are solidly longer than the permitted length, the cross bonding method
bonded. As the inductance reduction is affected by the should be adopted to neutralize the induced voltages on the
induced current, the flat and spaced configuration leads to the armors. Of cause, the cable installation becomes complicated.
most significant inductance reduction.
47
Authorized licensed use limited to: Rolls-Royce. Downloaded on August 26,2021 at 10:04:58 UTC from IEEE Xplore. Restrictions apply.
Generally speaking the flat and spaced configuration is not
recommended when the solid bonding method is employed.
This method makes the cable losses to increase significantly.
Although the effect of magnetic shielding by armors is better
than others, it cannot compensate the increase of the magnetic
field caused by the increase of the cable spacing.
v. REFERENCES
[ 11 IEEE Guide for the Application of Sheath-bonding Methods for
Single-conductor Cables and the Calculation of Induced Voltages
and Currents in Cable sheaths, ANSVIEEE Std. 575, 1988.
[2] Requirementsfor Electrical Installations, British Standard 7671,
1992.
[3] K. Ferkal, M. Poloujadoff and E. Dorison, “Proximity Effect and
Eddy Current Losses in Insulated Cables,” ZEEE Transactions on
Power Delivery, Vol. 11, No. 3, pp. 1171-1178, July 1996.
[4] George J. Anders, Rating of Electric Power Cables---Ampacity
Computations for Transmission, Distribution, and Industrial
Applications, New York IEEE, 1997.
[SI Y. Du and J. Bumett, “Experimental Investigation into Harmonic
Characteristics of Low-Voltage Power Cables,” IEE Proc. -
Gener. Transm. Distrib. Vol. 147, No. 6, pp. 322-328, Nov. 2000.
[6] Y. Du and J. Burnett, ‘Warmonic Characteristics of Low-Voltage
Single-Core Power Cables,” HKIE Transaction, Vol. 9 No. 8,
pp.46-51, August 2002.
[7] Specificationsfor 600V/I OOOV and 1900V/330V armored electric
cables having thermosetting insulation and low emission of smoke
and corrosive gases when affected by fire, British Standard 6724,
1997.
48
Authorized licensed use limited to: Rolls-Royce. Downloaded on August 26,2021 at 10:04:58 UTC from IEEE Xplore. Restrictions apply.