Professional Documents
Culture Documents
Netsure 801 Series Power Supply System User Manual
Netsure 801 Series Power Supply System User Manual
User Manual
Version V1.1
Revision date December 21, 2018
BOM 31013510
Vertiv Tech provides customers with technical support. Users may contact the nearest Vertiv local sales
office or service center.
All rights reserved. The contents in this document are subject to change without notice.
Address: Block B2, Nanshan I Park ,No.1001 Xueyuan Road, Nanshan District, Shenzhen, 518055, PR
China
Homepage: www.vertivco.com
E-mail: overseas.support@vertivco.com
Safety Precautions
To prevent unexpected problems, please read the operation instructions and safety precautions very carefully
before installation operation. The “Caution, Notice, Warning, Danger” in this manual do not represent all of the
safety points that should be observed, and are only used as supplementary to the operation safety. Therefore,
the personnel responsible for the installation and operation of Vertiv products must be strictly trained to master
the correct operations and all the safety points before actual operation.
When working on Vertiv products, relevant industry safety rules and special safety instructions provided by Vertiv
must be observed.
Electrical Safety
High voltage
Danger
Danger
High voltage power supply provides power for equipment operation, any direct contact or indirect contact through moist
objects with high voltage or AC mains will result in fatal injury.
Relevant industry safety regulations must be observed during the installation of AC power supply
equipment. The people who do the AC standard installation must be licensed to operate high voltage and
AC power.
During operation, metal objects such as watches, bracelets, bangles, rings, etc. must be removed.
In case water or moisture is found on the cabinet, turn off the power immediately. In moist environments,
take strict precautions to prevent water from entering the equipment.
“Prohibit” warning label must be attached to the switches and buttons which are not permitted to be
operated on during installation.
Danger
Danger
Nonstandard or incorrect high voltage operation can present risk of electric shock or burn. The connection and wiring of AC
cables must be in compliance with local rules and regulations. Only those who are licensed to operate high voltage and AC
power can perform high voltage operations.
Notice
Notice
The short-circuit breaking capacity of the rectifier AC input MCB is 6kA. If the expected short-circuit current of AC input
loop exceeds 6kA, please contact Vertiv technical support.
Dangerous energy
Danger
Warning
The power system contains output exceeds 240VA, when installing into end system care must be taken that the output and
appropriate wire may not be touched.
Multi-power input
Danger
Warning
Prevent electric shock and dangerous energy. Even if the AC input power is cut off, there is still dangerous conductive parts
fed by battery existing.
Notice
Notice
Make sure the cable and cable labels are in accordance with actual installation before cable connection.
Tools
Warning
Warning
In high voltage and AC operation, special tools must be used. No common or self-carried tools should be used.
Thunderstorm
Danger
Danger
Never perform high voltage, AC, iron tower, or mast operations on a day with thunderstorms about.
In thunderstorms, strong electromagnetic field will be generated in the air. Therefore the equipment should be solidly
earthed in time to avoid damage by lightning strikes.
Static
Notice
Notice
The static electricity generated by the human body will damage the static sensitive elements on circuit board, such as
large-scale ICs, etc. Before touching any plug-in board, circuit board and IC chip, ESD wrist strap must be worn to prevent
body static from damaging the sensitive elements. The other end of the antistatic wrist strap must be solidly earthed.
Short circuit
Danger
Danger
During operation, never short-circuit the positive and negative poles of the DC distribution unit of the system or the
non-earthing pole and the earth. The power supply equipment is a constant voltage DC power supply. Short circuit will
result in equipment burning and endanger human safety.
Check carefully the polarity of the cable and connection terminals when performing live DC operations.
As the operation space in the DC distribution unit is very tight, please carefully select the operation space.
Never wear a watch, bracelet, bangle, ring, or other conductive objects in operation.
Insulated tools must be used.
In live operations, keep the arm muscle in tense state so that when tool connection is loosened, the free
journey between the human body and tool is reduced to the minimum.
Battery
Danger
Danger
Before working on the battery, read very carefully the safety precautions for battery transportation and the correct battery
connection method.
Non-standard operation on the battery will result in danger. In operation, pay close attention to prevent battery
short circuit and spill of the electrolyte. The spill of the electrolyte will pose potential threat to the equipment and
erode the metal objects and circuit board, thus causing damage to the equipment and short circuit of the circuit
board.
For safety reasons, before working on the battery, pay attention to the following points:
Remove the watch, bracelet, bangle, ring, and other metal objects.
Use insulated tools.
Wear eye protection and take preventive measures.
Wear rubber gloves and apron to guard against spilt electrolyte.
In battery transportation, the electrode of the battery should always be kept facing upward. Never put the
battery upside down or slanted.
After battery installation, check carefully that the battery cable polarity is correct and the connections are solid.
After battery connections are made and before the system is switched on, the battery fuse must be in open state
in case the battery is damaged due to overdischarge in this period.
Others
Notice
Warning
When taking out the rectifier, you should replace with a new one or install a dummy plate immediately.
Notice
Warning
Never walk under the crane arm or the hoisted objects when hoisting heavy objects.
Sharp corners of the objects
Notice
Warning
When moving equipment by hands, wear protective gloves to avoid injury by sharp objects.
Notice
Notice
Do not use too much force in inserting single boards to prevent the contact pins on the motherboard to be twisted. Insert the
boards along the slots to avoid short circuit resulting from the contact of circuit boards. Never touch the connectors of the
boards when holding the boards.
Notice
Notice
Signal lines should be bound separately from heavy current and high voltage lines, with binding interval no less than
150mm.
Contents
Chapter 6 Maintenance...............................................................................................................................................73
6.1 Maintenance Requirements ...........................................................................................................................73
6.1.1 General..............................................................................................................................................73
6.1.2 Maintenance Tools And Equipments ...................................................................................................73
6.1.3 Reference Technical Specification For Maintenance............................................................................74
6.2 Routine Maintenance Items ...........................................................................................................................75
6.3 Routine Maintenance ....................................................................................................................................77
6.4 Basic Inspection............................................................................................................................................77
6.4.1 Handling Controller Fault ....................................................................................................................77
6.4.2 Handling Rectifier Fault ......................................................................................................................78
6.5 Replacing Rectifier ........................................................................................................................................79
6.6 Emergency Treatment ...................................................................................................................................80
Appendix 1 Technical Parameter.................................................................................................................................82
Chapter 1 Introduction
The NetSure 801 CA7 series power supply system (power supply system for short) is a new generation of telecom
power supply with exceptional reliability and performance. It is designed by Vertiv incorporating years of experience in
development and equipment operation on power network.
This chapter introduces the model information, overview and components.
NetSure 801 C A 7
Version number
The number of the rectifier in the typical power supply system. If the number
ranges between 0 ~ 9, the character is represented by a number. If the number
is larger than 9, the character is represented by a letter, for example, A represents
the number 10, B represents the number 11, and so on. A: 10.
Region. C: China.
1.2 Overview
The power supply system is composed of AC distribution cabinet, DC distribution cabinet, AC/DC integrated
distribution cabinet, rectifier cabinet, controller, rectifier and options.
The number of AC distribution cabinet, DC distribution cabinet, AC/DC integrated distribution cabinet and rectifier
cabinet can be configured according to customer requirement. The capacity of the system can be expanded to 6000A
at most. The system composed of one AC distribution cabinet, one DC distribution cabinet and one rectifier cabinet is
shown in Figure 1-2.
Rectifier Controller
Parameter Description
Recitifier cabinet 2000mm × 600mm × 600mm
Dimensions
Controller(M831D) 42mm × 86.60mm × 211.5mm
mm (H × W
Recitifier (R48-5800A、
× D) 88mm × 244mm × 372mm
R48-5800e)
Mechanical Recitifier cabinet (not include
Rack1000-7 ≤ 140;Rack2000-7 ≤ 180
the rectifier)
Weight (kg) Controller(M831D) ≤2
Recitifier (R48-5800A、
≤8
R48-5800e)
Parameter Description
PD48/1600DF-7-Y3: ≤ 400A; PD48/1600DF-7-Y4: ≤ 400A;
Battery charging current
PD48/2500DF-7-Y3: ≤ 500A; PD48/2500DF-7-Y4: ≤ 500A
PD48/1600DF-7-Y3, 22 routes load output:
500A (NT3) × 6, 200A (NT2) × 2, 100A (NT00) × 8, 63A (NT00) × 6
PD48/1600DF-7-Y4, 24 routes load output:
DC output 400A (NT3) × 12, 200A (NT2) × 4, 100A (NT00) × 2, 63A (NT00) × 6
Distribution parameter PD48/2500DF-7-Y3,30 routes load output:
630A (NT3) × 8, 400A (NT2) × 4, 200A (NT2) × 4, 100A (NT00) × 8, 63A
(NT00)× 6
PD48/2500DF-7-Y4,26 routes load output:
500A (NT3) × 16, 200A (NT2) × 4, 100A (NT00) × 2, 63A (NT00) × 4
1.3 Components
1.3.1 Rectifier
The system uses rectifier R48-5800A, the frame structure of which mainly consists of panel, enclosure, handle, and
so on, as shown in Figure 1-3.
There are LEDs, slide switch and handle on the front panel, and AC input socket, DC output socket and
communication port on the rear panel. The front panel is shown in Figure 1-4, and functions of indicators are given in
Table 1-4.
Power indicator Slide switch
Fixing screw
Protection indicator
Handle
Fault indicator
Current indicators
Figure 1-4 Rectifier front panel
1.3.2 Controller
The controller specific content see the M831D Controller User Manual.
Power distribution
LCD
AC mains indicator
Failure indicator
SPD MCB
Class C SPD
Monitoring board
AC output MCB
Signal transfer board
AC sampling board
Cover plate
Neutral busbar
Earth busbar
Buzzer
Knife-blade switch
Buzzer control switch
SPD MCB
Class C SPD
Monitoring board
AC sampling board
Cover plate
Neutral busbar
Earth busbar
ATS
ATS controller
Monitoring board
AC sampling board
AC output MCB
SPD MCB
SPD
Neutral busbar
Earth busbar
The structure and configuration of PD380/630AFH-7/YF is determined by customer requirement. See purchase order
for description.
Power distribution
LCD
Power indicator
Failure indicator
Controller LCD
DC positive busbar
(b) Rear view (open front door and remove rear door)
Figure 1-10 PD48/1600DF-7-Y3 DC distribution cabinet
Controller LCD
Control board
Load fuse
DC positive busbar
(b) Rear view (open front door and remove rear door)
Figure 1-11 PD48/1600DF-7-Y4 DC distribution cabinet
Controller LCD
Control board
Load fuse
DC positive busbar
(b) Rear view (open front door and remove rear door)
Figure 1-12 PD48/1600DF-7-Y3 DC distribution cabinet
Controller LCD
Control board
Load fuse
DC positive busbar
(b) Rear view (open front door and remove rear door)
Figure 1-13 PD48/2500DF-7-Y4 DC distribution cabinet
Rectifier cabinets Rack 1000-7 and Rack 2000-7 are shown in Figure 1-14 and Figure 1-15 respectively.
Controller
Rectifier
Controller
Rectifier
The name, function and use of the cabinet components are given in Table 1-5.
Table 1-5 Part name, function and use
Name Function Cabinet
When the mains input 1 is available, HL1 illuminates; when the mains
AC cabinet, AC/DC cabinet
input 2 is available, HL2 illuminates
Power LED When the AC input 1 is available, HL1 illuminates; when the AC input
Rectifier cabinet, AC/DC cabinet
2 is available, HL2 illuminates
When there is electricity in the busbar, the LED illuminates DC cabinet, AC/DC cabinet
When the distribution cabinet is in normal operation, it is off; it AC cabinet, DC cabinet, AC/DC
Fault LED
illuminates otherwise cabinet
Display the input voltage, current, frequency, running mains input
JYG-12864J9G number, SPD state, output MCB state (AC/DC cabinets have none) AC cabinet, AC/DC cabinet
(R)-YS6L2-VB and alarm information of the AC cabinet
Display Display the busbar voltage, total load current, battery voltage, battery
DC cabinet, AC/DC cabinet
current, load fuse status and alarm information
Measure the AC input voltage, main switch state, output MCB state,
surge protection device (SPD) state; control the position of the main
PD380/400AFH & PD380/630AFH AC
switch, generator start signal output; annunicate audible and visual
cabinet, AC/DC cabinet
alarms when the AC cabinet malfunctions, and simultaneously transmit
A6V6FU11
relevant information to the display of the AC cabinet and the controller
monitoring board
Measure the busbar voltage, total load current, battery voltage, battery
current and load fuse status; annunicate audible and visual alarms
DC cabinet, AC/DC cabinet
when the AC cabinet malfunctions, and simultaneously transmit
relevant information to the display of the DC cabinet and the controller
Transfer the input/output signals of the monitoring board of the AC PD380/400AFH & PD380/630AFH AC
A2V6FX1 signal cabinet cabinet, AC/DC cabinet
transfer board Transfer the input/output signals of the monitoring board of the DC
DC cabinet, AC/DC cabinet
cabinet
This chapter introduces installation requirements, storage conditions, installation preparation and unpacking
inspection.
The environmental conditions of the equipment room must meet the requirements listed in Table 2-1.
Table 2-1 Environmental conditions for the equipment room
Environmental conditions Recommended range
Ambient temperature -5°C to 40°C
Humidity ≤ 90%RH, no condensation
Dust density ≤ 1mg/m3
Sunlight No direct sunlight
Corrosive materials No pollutants, such as salt, corrosive materials, and smoke.
Vibration ≤ 1.5m/s²
Harmful organisms None
Mould None
Dampness Waterproof
The equipment may be prematurely damaged if dust or sand accumulates in it. The following measures are
recommended for dirty environment:
1. The equipment should be installed in an airtight and air-conditioned room. The air conditioner filter should be
adequately maintained without being obstructed. To reduce the dust in the equipment room, unattended equipment
room is recommended.
2. Clean the air filter periodically to provide clean air.
Cabling
The top cable entry system are all introduced from the top of the cabinet, therefore wiring rack should be provided in
the equipment room for top cable entry system, which is recommended to be at least 300mm above the equipment.
For bottom cable entry system, cable trough should be provided in the equipment room, which should be no wider
than the spacing between the equipment mounting holes.
Note
To prevent electric coupling, AC cables should be run separate from DC cables and signal cables.
Installation surface
The installation surface is supposed to be cement floor or incombustible metal subrack.
Antistatic requirement
As for antistatic requirement, the absolute value of the static voltage of the equipment, wall and people to the ground
should be less than 200V. Raised floor is highly recommended for the equipment room. The antistatic earth
resistance should be not greater than 10Ω. Care should be taken regarding antistatic during equipment unpacking,
transportation and operation.
Lighting
Lighting in equipment room may be classified into general lighting and partial lighting. General lighting provides light
for the whole room, while partial lighting is installed above the equipment cabinet or workstation to provide light for a
restricted area. It is recommended to provide both lightings in the equipment room.
Clearance
1. At least 1.5m of clearance should be kept between the front of the power system cabinet and the wall.
2. At least 0.8m of clearance should be kept between the back of the power system cabinet and the wall.
3. At least 0.8m of clearance should be kept the sides of the power system cabinet and the wall.
4. At least 1.5m of clearance should be kept between the back of the power system cabinet and the front of another
piece of equipment.
5. At least 1.2m of clearance should be kept between the back of the power system cabinet and the back of another
piece of equipment.
6. Maintenance passage should be kept between equipment, which should not be less than 2m wide.
Refer to Figure 2-1 for the above requirements. No less than 0.2m of clearance should be kept between the battery
and the wall, and no less than 0.8m of clearance should be kept between batteries.
Clearance
between
cabinet side
Front of the and the wall ≥
cabinet 0.8m
Clearance
between
cabinet back
Clearance and the wall ≥
≥ 1.5m 0.8m
NetSure 801 CA7 Power Supply System (New Skelecton) User Manual
20 Chapter 2 Installation Preparation
General
Mains power should be used as the main AC source in communication field; backup batteries and generator should
be provided according to the actual power source conditions. AC source composed of mains power and
user-provided generator should use centralized power supply mode to supply power, and low voltage AC power
supply system should use three-phase five-line mode.
The AC power cables should be copper core cable and sized to suit for the load. It is recommended that the power
cables outside the equipment room should be buried directly under the ground or by means of cable pipe. Power
cables should be run separate from signal cables.
Capacity requirements
1. Power transformer
Because of the particularity of switch-mode power supply system, the power supply should provide relatively large
redundancy. If the capacity of the power transformer is small, operation of other electric equipment may be affected.
Calculated based on full configuration of the power supply system, the capacity of a dedicated transformer should
exceed 1.25 times of the total capacity of the system. So, considering other electric equipment such as air conditioner,
the capacity of the transformer should be even larger, and the upper capacity level should be selected according to
the specifications.
PD380/400AFH-7-Y2 AC distribution cabinet is not supposed to be directly connected to the secondary side of a
transformer with capacity greater than 800kVA. An extra distribution cabinet should be used between
PD380/400AFH-7-Y2 AC distribution cabinet and the transformer for shortcircuit protection. PD380/630AFH-7-Y3 AC
distribution cabinet is not supposed to be directly connected to the secondary side of a transformer with capacity
greater than 1000kVA. An extra distribution cabinet should be used between PD380/630AFH-7-Y3 AC distribution
cabinet and the transformer for shortcircuit protection.
2. Generator
If the load of the power supply system is more than 50% of the generator capacity, when the higher harmonic current
generated by the rectifiers passes the stator winding of the synchronous generator, the voltage waveform will be
severely distorted, which will have two effects. One is, it will cause unstable running and mechanical vibration of the
generator; and the other is, the harmonic current will make the generator overheat, thus accelerating the insulation
ageing of the generator. This is not only harmful to the generator, but also affects the stable running of the power
supply system. Therefore, the load of the power supply system should not exceed 50% of the generator capacity. It
should be calculated based on the apparent power. A simple calculation of the generator capacity is: output voltage
(taken as 60V) × output current (take the final configuration) × 2.
The power factor and excitation model of the generator should also be taken into consideration when selecting a
generator. Brushless generator of fundamental wave excitation model should be used with caution.
should be no less than 25mm2, the cable should be as short as possible, and so is the earth cable of the Class-B
SPD. The SPDs should be inspected periodically to ensure their normal operation.
Power
supply
5~10m system
A
B SPD
C
N
SPD earth
PE
-
System earth bar
48VDC
DC earth
Class-B SPD
+
SPD earth
DC earth cable
Protective earth
Protective earth cable
Earthing requirement
The earthing system in the communication equipment room is generally designed on the principle of common earth,
that is, DC operation earth, SPD earth and protective earth sharing the same earth. The earth resistance should be in
accordance with the specifications listed in Table 2-2.
Table 2-2 Earth resistance requirements for communication station
Earth resistance Application range
Integrated building, international telecom bureau, tandem station, SPC switching office above 10000 lines,
<1Ω
toll office above 2000 lines
<3Ω SPC switching office above 2000 lines and below 10000 lines, toll office below 2000 routes
SPC switching office with less than 2000 lines, optical cable terminal station, carrier wave repeating station,
<5Ω
earth station, microwave junction center, mobile communication machine station
10Ω Microwave relay station, optical cable relay station, small-sized earth station
<20Ω Microwave passive relay station
Suitable for those whose earth resistance rate is less than 100Ω·m, SPD earth in the interface between
<10Ω
electric cable and aerial electric line
Suitable for those whose earth resistance rate is 100-500Ω·m, SPD earth in the interface between electric
<15Ω
cable and aerial electric line
Suitable for those whose earth resistance rate is 501-1000Ω·m, SPD earth in the interface between electric
<20Ω
cable and aerial electric line
Note: the content in the table is adapted from Installation Design Specifications for Communication Power Supply Equipment
NetSure 801 CA7 Power Supply System (New Skelecton) User Manual
22 Chapter 2 Installation Preparation
Construction survey must be conducted to the equipment room before equipment installation, which should be
focused on:
1. Checking the wiring devices, such as cable trenching, wiring rack, floor, and cabling holes.
2. Checking the environmental conditions, such as temperature, humidity, and dust density.
3. Checking the conditions for installation construction, such as power supply and lighting.
1. Tools required for power supply equipment installation include electric drill, wire cutter, wire presser, various
wrenches, screwdriver, electrician knife, tinning furnace, staircase and steel saw. See 6.1.2 Maintenance Tools And
Equipments for the specifications of the tools. The tools must be well insulated and antistatic handled before they are
used.
2. Materials for electrical connection include AC cables, DC load cables, battery cables, earth cables, and earth
connection cables. The cables accessories are given in Table 2-4. Other cables should be prepared by users in
accordance with relevant specifications in the electrical industry.
Table 2-4 Accessory cables used in cable connection
BOM Description Length Note
No DC cabinet between AC cabinet and rectifier
04110145 W74AASL03 cable suite (AC input cable of the
3.5m cabinet. Internal cabling (≤ 2000A), When the AC
(optional) rectifier cabinet-3.5m)
output EMR1 series MCCB for Vertiv
3. Preparing cables
The cable design should meet relevant industry standards.
It is recommended to use the RVVZ cables as AC cables. The cable should reach at least +70°C temperature
durability. With cable length shorter than 30 meters, the Cross-Sectional Area (CSA) calculation should be based on
the current density of 2.5A/mm2.
The sectional area of the DC load cables and battery cables should be computed with the following formula:
A=ΣI × L / K△U
In this formula: A is the sectional area of the lead (mm 2), ΣI is the total current (A) passing through the lead, L is the
length (m) of the lead loop, △U is the permitted voltage drop in the lead, while K is the conductivity factor. Kcopper=57.
For the sake of distribution safety, the voltage drop on the cables should be compliant with corresponding rules.
The sectional area of the earth cables (including DC earth cable) shall exceed 95mm 2.
The CSA of DC cable depends on the current flowing through the cable and the allowable voltage drop. To select the
battery cable CSA, see Table 2-5. Select the DC load cable CSA according to the Table 2-5.
Table 2-5 Battery cable CSA selection
Specs of the cable Max. cable length (allowable
Battery fuse rated current Max. battery current Min. cable CSA
connector voltage drop: 0.5V)
OT cable connector of
1000A 1000A 2 × 240mm2 10m
M12 or M16 size
Note:
1. The specs are applicable at ambient temperature of 25°C. If the temperature is higher or lower than this, the CSA of the cable
should be increased.
2. The battery cable should reach at least +90°C heat durability. It is recommended to use double-insulated copper-core flame
retardant cable as battery cable
NetSure 801 CA7 Power Supply System (New Skelecton) User Manual
24 Chapter 2 Installation Preparation
The MCB/fuse capacity should be strictly limited so that it can function properly upon load over-current. The
recommended MCB/fuse capacity is 1.5 ~ 2 times larger than the load peak capacity.
The load fuses with capacity over 160A use M12 or M16 OT- shape cable connectors. The load fuses with capacity
equal to or under 160A use M8 OT- shape cable connectors. The load MCBs uses the H- shape cable connectors.
The recommended CSA of AC input cables are shown in Table 2-7.
Table 2-7 AC input cable selection
Specs
Cabinet Connector Remarks
Capacity Connector specs
Eight M12 bolts (suggested cable
AC input MCB 400A The live line of AC power supply
PD380/400AFH-7-Y2 CSA 185mm2)
AC distribution cabinet Grounding
One M16 bolt suggested cable CSA 120mm2 The grounding bar of the room
busbar
Eight M16 bolts (suggested cable The live line of AC power
PD380/630AFH-7-Y3 AC input MCB 630A
CSA 240mm2) supply
AC distribution
Grounding
cabinet One M16 bolt Suggested cable CSA 120mm2 The grounding bar of the room
busbar
AC input MCB Eight M12 bolts (suggested cable
PD380/630AFA-7-Y4 630A The N line of AC power supply
(ATS) CSA 240mm2)
AC distribution
Grounding
cabinet One M16 bolt Suggested cable CSA 120mm2 he grounding bar of the room
busbar
Note
Generally, in design the total current passing through the lead is calculated based on full load configuration.
4. Purchase materials according to the construction materials list and inspect the materials. For example, check the
heat durability, moisture resistance, flame resistance, and pressure resistance of the cables.
5. For the materials that need to be processed by other factories, the materials and the processing drawings should
be provided in advance for processing.
6. The auxiliary materials for power supply installation include expansive bolts, cable lugs, cable ties, and insulating
tape.
Unpacking inspection
To ensure smooth installation, the equipment must be carefully inspected when it is unpacked. The checking should
include:
1. The number and serial number of the packing cases according to the system packing case number.
2. The correctness of the equipment packing according to the packing list.
3. The number and type of the accessories according to the accessory list.
4. The completeness of the equipment configuration according to the system configuration.
5. The conditions of the goods through visual inspection. For example, check if the cabinet and case are damaged, if
the cabinet and case have regained moisture; shake gently the rectifiers and controller to check if the parts and
connections have been loosened during transportation.
NetSure 801 CA7 Power Supply System (New Skelecton) User Manual
26 Chapter 3 Installation
Chapter 3 Installation
436 4-Ф18
4- 18
400
600
600 370
600
600 800
(a) Installation size of the rectifier cabinet (b) Installation size of the AC/DC distribution cabinet
Figure 3-1 Installation size of the cabinet base (unit: mm)
NetSure 801 CA7 Power Supply System (New Skelecton) User Manual
Chapter 3 Installation 27
Tap bolt
Plain washer
Spring washer Cabinet base
Ground
Expansive pipe
If antistatic floor is laid in the equipment room, a supporting rack should be made according to the height of the
antistatic floor.
Floor
Bolt
Spring washer
Plain washer
Expansive pipe
NetSure 801 CA7 Power Supply System (New Skelecton) User Manual
28 Chapter 3 Installation
Supporting rack
After the cabinet is installed, shake the cabinet from different directions. No obvious shake should be felt.
Users need to use connection straps to fix adjacent cabinets at the top, as shown in Figure 3-5. The connection
straps are accessories.
40
80
280
600
80
600 600
54 2-M6 × 16 screw
16.5
54
16.5
800 600
Make sure that the front door header of the rectifier cabinet aligns
horizontally with that of the AC/DC cabinet during parallel connection.
AC cabinet/DC cabinet Rectifier cabinet
NetSure 801 CA7 Power Supply System (New Skelecton) User Manual
Chapter 3 Installation 29
68
600
525
800 800
Make sure that the front door header of the cabinet
aligns horizontally during parallel connection.
AC cabinet/DC cabinet AC cabinet/DC cabinet
Figure 3-5 Parallel connection between cabinets (top view, unit: mm)
AC distribution cabinet and rectifier cabinet are connected by cables, while parallel connections between rectifier
cabinets, between rectifier cabinet and DC distribution cabinet and between DC distribution cabinets are all achieved
by means of parallel connection copper bars. The AC/DC integrated distribution cabinet and rectifier cabinet are
connected by both cables and copper bars.
Take parallel connections between a rectifier cabinet and a DC distribution cabinet for example, the connection
procedures are as follows:
1. Remove the upper side doors between the rectifier cabinet and the DC distribution cabinet.
2. Connect the positive bars and negative bars inside the cabinet respectively by copper bars and screws, as shown
in Figure 3-6.
If users need to parallel connect the rectifier cabinets or the DC distribution cabinets, they need to contact Vertiv for
technical support.
DC positive busbar
DC negative busbar
Nut
Copper bar
A amplification
NetSure 801 CA7 Power Supply System (New Skelecton) User Manual
30 Chapter 3 Installation
The NetSure 801 CA7 power supply system can be expanded up to 6000A. As the max current carrying capacity of
single parallel connection bar is 2000A, when the system capacity exceeds 2000A, the system cabinets should be
arranged in the way that the max current carrying capacity of one parallel connection bar does not exceed 2000A.
It is recommended to place the cabinets in the way of “Rectifier cabinet- DC cabinet- Rectifier cabinet- DC cabinet”.
For a system composed of Rack1000-7 rectifier cabinet, place one rectifier cabinet or two rectifier cabinets as a unit.
For a system composed of Rack2000-7 rectifier cabinet, place one rectifier cabinet as a unit.
Recommended arrangement of 6000A system using Rack1000-7 rectifier cabinet:
DC cabinet
DC cabinet
DC cabinet
AC cabinet
AC cabinet
AC cabinet
AC cabinet
Rectifier
Rectifier
Rectifier
Rectifier
Rectifier
Rectifier
cabinet
cabinet
cabinet
cabinet
cabinet
cabinet
Recommended arrangement of 6000A system using Rack2000-7 rectifier cabinet:
DC cabinet
DC cabinet
DC cabinet
AC cabinet
AC cabinet
AC cabinet
AC cabinet
Rectifier
Rectifier
Rectifier
cabinet
cabinet
cabinet
If the installation site does not permit the cabinet arrangement shown above, it is suggested to use 2 parallel
connection copper bars so that the current carrying capacity of single connection bar does not exceed 2000A. When
using 2 connection bars, only external parallel connection can be used and the connection bars must be specially
made.
The rectifier cabinet and distribution cabinet have two side doors on both sides, as shown in Figure 3-7. According to
distribution situation, cabinet placement and cabinet parallel connection, the side doors are configured in various
ways.
Prior to cabinet parallel connection, check that there is at least one large side door between adjacent cabinets. The
large side doors of the rectifier cabinet and the distribution cabinet are interchangeable. Users can exchange them on
the spot.
Cabinet
NetSure 801 CA7 Power Supply System (New Skelecton) User Manual
Chapter 3 Installation 31
The NetSure 801 power supply system uses integrated monitoring, the DC distribution cabinet can be placed
separate from the system, and typically where loads are grouped, for example, on different floors. When connecting
the DC distribution cabinet to the system, use cable to connect between the parallel connection bars. Pay attention to
the following points:
Use cable rather than copper bar to connect between the parallel connection copper bars of the DC distribution
cabinet and the system to ensure accurate measurement of load current. The connecting points are the
installation holes for parallel connection copper bar.
Communication inside the system uses RS485 mode.
Note
Before electrical connection, turn off all the switches and fuses.
The accessory cables used in cable connection are given in Table 3-1.
Table 3-1 Accessory cables used in cable connection
BOM Description Length Note
No DC cabinet between AC cabinet
04110145 W74AASL03 cable suite (AC input cable of the rectifier and rectifier cabinet. Internal cabling (≤
3.5m
(optional) cabinet-3.5m) 2000A), When the AC output EMR1
series MCCB for Vertiv
No DC cabinet between AC cabinet
04116219 W64AASL03 cable suite (AC input cable of the rectifier and rectifier cabinet. Internal cabling (≤
3.5m
(optional) cabinet-3.5m) 2000A), When the AC output S series
of the ABB MCCB for Vertiv
No DC cabinet between AC cabinet
04110146 W74AASL11 cable suite (AC input cable of the rectifier and rectifier cabinet. Internal cabling (≤
7m
(optional) cabinet-7m) 2000A), When the AC output EMR1
series MCCB for Vertiv
One DC cabinet between AC cabinet
04116341 W64AASL11 cable suite (AC input cable of the rectifier and rectifier cabinet. External cabling,
7m
(optional) cabinet-7m) When the AC output S series of the
ABB MCCB for Vertiv
More than one DC cabinet between AC
041163475 W64AASL12 cable suite (AC input cable of the rectifier cabinet and rectifier cabinet. External
9m
(optional) cabinet-9m) cabling (> 4000A), When the AC output
EMR1 series MCCB for Vertiv
More than one DC cabinet between AC
W64AASL12 cable suite (AC input cable of the rectifier cabinet and rectifier cabinet. External
04116345 9m
cabinet-9m) cabling (> 4000A), When the AC output
S series of the ABB MCCB for Vertiv
W1PK2SL10 cable suite (RS485 signal cable connected to
04119128 5.5m
M821D controller)
W64AASL05 cable suite (RS485 signal cable connected PD380/400AFH & PD380/630AFH AC
04116221 4.0m
between AC distribution cabinet and DC distribution cabinet) cabinet and rectifier cabinet
RS485 signal cable connected
W1PN5SL20-W1PN5Z cable suite (RS485 signal cable
between PD380/630AFA AC cabinet
04111498 connected between AC ATS cabinet and rectifier cabinet, and 5.5
and rectifier cabinet, or between the
connected between AC ATS cabinet)
PD380/630AFA AC cabinet
W64AASL06 cable suite (power cable of A6V6FU11
04116222 4.3m
monitoring board)
04116169 W64AASL09 cable suite (CAN bus) 2.8m
NetSure 801 CA7 Power Supply System (New Skelecton) User Manual
32 Chapter 3 Installation
The power supply system uses common earth. The connection procedures are as follows.
1. Use the earth cable to connect the earth bolt at the rear lower (or rear upper) part of the rectifier cabinet to the
earth bar of the AC distribution cabinet, see Figure 3-8 to Figure 3-10.
Earth terminal
Earth terminal
Earth
Earth busbar
bar
NetSure 801 CA7 Power Supply System (New Skelecton) User Manual
Chapter 3 Installation 33
Earth terminal
Earth terminal
2. Connect one end of the earth cable to the user earth bar, and the other end to the earth bar in the AC distribution
cabinet (See Figure 3-9 and Figure 3-10).
3. Lead out the DC earth cable from the positive busbar of the DC distribution cabinet, and connect it to the copper
earth bar in the equipment room. The sectional area of the DC earth cable increases with system capacity, and
should be at least 95mm2.
For Rack1000-7 rectifier cabinet, choose one 160A MCB inside PD380/400AFH-7-Y2 or PD380/630AFH-7-Y3 or
PD380/630AFA-7-Y4 cabinet as AC input switch of the rectifier cabinet.
For Rack2000-7 rectifier cabinet, choose two 160A MCBs inside PD380/400AFH-7-Y2 or PD380/630AFH-7-Y3 or
PD380/630AFA-7-Y4 cabinet as AC input switches of the rectifier cabinet.
Follow the steps below to install the AC input cables of the rectifier cabinet.
1. If the AC input cables of the rectifier cabinet are routed inside the cabinets, users can use the accessory cables as
the AC input cables. Otherwise users need to prepare armored cables by themselves. If the system capacity exceeds
2000A, users need to prepare extra cables.
2. Add cable lugs to both ends of the cables.
NetSure 801 CA7 Power Supply System (New Skelecton) User Manual
34 Chapter 3 Installation
3. Connect one end of the cable to the output terminal of the selected MCB in the AC distribution cabinet, as shown in
Figure 3-11 and Figure 3-12.
A amplification
A处
Figure 3-11 Connection of AC input cables (phase line) of rectifier cabinet in AC distribution cabinet
Neutral busbar
Spring washer
Plain washer
Bolt
Figure 3-12 Connection of AC input cables (neutral line) of rectifier cabinet in AC distribution cabinet
NetSure 801 CA7 Power Supply System (New Skelecton) User Manual
Chapter 3 Installation 35
4. Connect the other end of the cable to the AC input terminal of the rectifier cabinet. The AC input cable wiring is
shown in Figure 3-13. The connection of AC input cables in rectifier cabinet is shown in Figure 3-14.
AC input AC input
cable 1 cable 2
A amplification
Connection requirements
1. The AC in cables are wired from the distribution switch, and connected to the output terminal when the power is to
be switched on. The AC input is fitted with overcurrent, short circuit and lightning protection devices. The capacity of
the distribution switch should be no less than 1.5 ~ 2 times of the load capacity.
2. The yellow, green, red, and light blue AC cables correspond respectively to the AC phase A, B, C and neutral lines.
If the cables are the same color, they should be numbered or identified with insulating tape of different colors at both
cable ends.
3. The AC cables should be run separate from the DC cables, with separation exceeding 150mm.
4. No splice, damage, or scratch on the cables is permitted.
Connection
The AC cables can enter the system from either the cabinet top from wiring rack or the cabinet bottom from cable
trenching.
For AC distribution cabinet:
NetSure 801 CA7 Power Supply System (New Skelecton) User Manual
36 Chapter 3 Installation
After the AC input cables are fed into the cabinet, connect them to the knife-blade switch or air breaker or ATS of the
AC distribution cabinet, as shown in Figure 3-15.
A处
AC input phase C line (red cable) AC input phase B line (green cable)
A amplification
NetSure 801 CA7 Power Supply System (New Skelecton) User Manual
Chapter 3 Installation 37
Emergency
lighting busbar (+)
To emergency
lighting (-)
A amplification
The use of the top cover and the connection of DC load cables are the same with DC distribution cabinet. Taking the
DC distribution cabinet as an example, the cable connection is described below.
The use of the DC distribution cabinet top cover is described below:
NetSure 801 CA7 Power Supply System (New Skelecton) User Manual
38 Chapter 3 Installation
The cable entry holes of the DC distribution cabinet top cover are divided as load cable entry space, communication
cable and dry contact output entry hole, and battery cable entry holes, as shown in Figure 3-18. Users need to use an
electrician knife to cut the protective cover in the cable entry holes to lead in cables.
Note
1. The power supply line should not be spliced. It is highly recommended that the load cables, signal lines and customer cables be
run separate to prevent them from affecting each other.
2. Before connecting, pull out the DC output fuse with fuse puller or turn off the MCB.
4. Connect one end of the negative cable to the output terminal of the fuse, and the other end of the positive cable to
the positive copper bar of the DC distribution cabinet, as shown in Figure 3-19 and Figure 3-20.
Bolt
Plain washer
Negative load cable
Plain washer
Spring washer
Nut
A amplification
NetSure 801 CA7 Power Supply System (New Skelecton) User Manual
Chapter 3 Installation 39
A
DC positive busbar
Spring washer
Plain washer
Bolt
A amplification
Note
The battery negative cables should be connected to the two battery fuses, not the single one.
Negative Negative
电池负极电缆 电池负极电缆
battery cable battery cable
Battery fuse
电池熔断器
Plain washer
Spring washer
Nut
Cable connection finished
Figure 3-21 Battery cable connection in DC cabinet
NetSure 801 CA7 Power Supply System (New Skelecton) User Manual
40 Chapter 3 Installation
NetSure 801 CA7 Power Supply System (New Skelecton) User Manual
Chapter 3 Installation 41
(a) (b)
(c) (d)
Figure 3-22 Installing rectifier
Note
The rectifier is relatively big and heavy, please hold it carefully when mounting and dismounting it.
螺钉
Screw
假面板 panel
Dummy
2. Unscrew the captive screw at the top of the hand of the controller, as shown in Figure 3-24.
Captive screw
Handle
NetSure 801 CA7 Power Supply System (New Skelecton) User Manual
42 Chapter 3 Installation
3. Push the controller into the correct position, and then fix the screws on the panel, as shown in Figure 3-25.
Controller
监控模块
Note
There should be only one controller in the system even there are multiple rectifier cabinets. The controller should be installed on
the right side of the rectifier cabinet. The dummy plate inside the rectifier cabinet without controller should be retained.
3.4.3 The Installation And Wiring Of The Controller IB2 Extension Board
Notice
Notice
The static electricity generated by the human body will damage the static sensitive elements on PCBs, such as large-scale ICs.
Before touching any plug-in board, PCB or IC chip, ESD wrist strap must be worn to prevent body static from damaging the
sensitive components. The other end of the ESD wrist strap must be well earthed.
I2CI2C电缆接口
cable port
监控模块
Controller RS232 port
RS232接口
Once the signal cable is connected, cover the IB2 extension board on the cover, and tighten the captive screws.
Note
The IB2 extension board should be installing in the rectifier cabinet with the controller when there are multiple rectifier cabinets
in the system.
NetSure 801 CA7 Power Supply System (New Skelecton) User Manual
Chapter 3 Installation 43
Alarm外部设备的告警点,DC
output dry contact,DC 15V~60V
15V~60V
J9 J8 J7 J6 J5 J4 J3
DO7 DO5 DO3 DO1
8 7 6 5 4 3 2
- - - J4- -
J5 - J3
-
5 3 1 5 3 1 5 3 1 5 3 1 5 3 1 5 3 1 5 3 1
J12
6 4 2 6 4 2 6 4 2 6 4 2 6 4 2 6 4 2 6 4 2
+
+
+
+
+
+
+
+
DO8 DO6 DO4 DO2 8 7 6 5 4 3 2 1
J11
Digital quantity
数字输入量接口 J2
input port 2
I2IC接口
C port
J1
SW1
Address
地址拨码 DIP
Figure 3-27 IB2 user interface board definition
Note
1. J11 and J12 are temperature sensor ports. They are not used here.
2. J2 is I2C interface, and provides the power.
NetSure 801 CA7 Power Supply System (New Skelecton) User Manual
44 Chapter 3 Installation
Note
Alarm relay contact capacity: Max. 1A@60Vdc and 60W; Min. 10uA@10Vdc.
The steps of connecting CAN communication cables among multi rectifier cabinets are as follows:
1) Remove the matched resistance located on the back of rectifier cabinet, as shown in Figure 3-28.
CAN communication
CAN通信电缆 cable 匹配电阻
Matched resistance
NetSure 801 CA7 Power Supply System (New Skelecton) User Manual
Chapter 3 Installation 45
2. Depending on your controller installation location in the Figure 3-29, Figure 3-30 and Figure 3-31, connect CAN
communication cable between the rectifiers and matching resistance. And install the controller CAN communication
and connection cables according to Figure 3-29. (The controller needs to be placed in the rightmost rectifiers)
When the controller mounted to the rectifier on the right, connect the CAN communication cable between the rectifier
cabinets as shown in Figure 3-29.
CAN CAN
When there
are only 2 Matching resistance
Matching
rectifier
resistance
cabinets, Controller
attach the
matching
resistance
here
Figure 3-29 Rectifier cabinet CAN communication cable connection diagram 1 (rear view)
When the controller mounted to the rectifier in the middle, connect the CAN communication cable between the
rectifier cabinets as shown in Figure 3-30.
CAN
CAN
Matching resistance
Controller
Matching resistance
Figure 3-30 Rectifier cabinet CAN communication cable connection diagram 2 (rear view)
When the controller mounted to the rectifier on the left, connect the CAN communication cable between the rectifier
cabinets as shown in Figure 3-31.
CAN When there CAN
are only 2
rectifier
cabinets,
Matching resistance attach the
matching
监控
resistance
模块
here
Figure 3-31 Rectifier cabinet CAN communication cable connection diagram 3 (rear view)
NetSure 801 CA7 Power Supply System (New Skelecton) User Manual
46 Chapter 3 Installation
3.If there are more than three rectifier cabinets, please increase the number of the CAN parallel configuration
communications cable, and connect as shown in Figure 3-29, Figure 3-30 and Figure 3-31, according to the controller
of the location. CAN cable should use total style wiring, which makes the controller is always located at the beginning
and the end of circuit. Retain the match resistance in the controller, and access a second match resistance on the
other end of the circuit.
Note
As the CAN parallel connection should be operated at the rear of the cabinet, therefore the cabinet arrangement shown in Figure
3-29, Figure 3-30 and Figure 3-31 is from the front view of rear cabinet.
A
A处
NetSure 801 CA7 Power Supply System (New Skelecton) User Manual
Chapter 3 Installation 47
A amplication
Monitoring board
To monitoring module
in rectifier rack
A amplication
Monitoring board
To monitoring module
in rectifier rack
3. When the system has multiple AC cabinets or DC cabinets, connect the RS485 cables between cabinets according
to Figure 3-34. If the cabinet number is different from Figure 3-34, increase or decrease the parallel cables between
cabinets according to Figure 3-34. The connection of RS485 cable should use bus type wiring, and the controller is
always located at the first end or the end of the circuit.
NetSure 801 CA7 Power Supply System (New Skelecton) User Manual
48 Chapter 3 Installation
0V 0V 0V
-48V -48V -48V
A2V4FA1 A2V4FA1
Sampling transfer Sampling transfer
board of AC board of AC
0V 0V 0V
-48V -48V -48V
NetSure 801 CA7 Power Supply System (New Skelecton) User Manual
Chapter 3 Installation 49
J3
J0
J1
8 1
1J2
J2
1J3
J7
J9
J11 J12 J13
3 PGND
J4 2 Signal output
1 +12
J8
PGND 3 PGND
J5 2 Signal output 1J1
Signal output 1 +12
3 PGND J10
+12 J6 2 Signal output
1 +12
A6V6FU11 board
3. AD592BN is current type temperature sensor. Ensure that the sixth position (temperature sensor selection position)
of the DIP switch on the DC distribution cabinet has been set “OFF”. For the setup method, refer to 4.3.1 Setting
DIP Switch.
4. The temperature probe should be put in the battery room where it can best incarnate the battery temperature.
When fixing it, do not connect it to any other exothermic equipment or metal conductor.
NetSure 801 CA7 Power Supply System (New Skelecton) User Manual
50 Chapter 4 Testing
Chapter 4 Testing
This chapter mainly introduces the notes on testing, system power-on, parameter setting, inquiry of alarm and
operation information. For detailed using of M831D controller, please refer to M831D Controller User Manual.
4.2 Power-on
Inspection before power-on
The inspection steps as below:
1. Check that the earth cables of the cabinets are connected reliably and that the wiring and screws in the cabinet are
fastened.
2. Open all the MCBs in the AC distribution cabinet, and then feed the mains supply to the system, measure the
phase voltage of the three phases with a multimeter to confirm the mains condition. If everything is normal, proceed
with the next step.
3. Turn on the knife-blade switch or input air breaker of the AC distribution cabinet, the running indicator of the AC
distribution cabinet should illuminate.
4. Close the input MCB of the rectifier cabinet in the AC distribution cabinet, the power indicator of the rectifier cabinet
should illuminate.
NetSure 801 CA7 Power Supply System (New Skelecton) User Manual
Chapter 4 Testing 51
The first screen of M831D is the language selection screen. You can press ▲ or ▼ to select English or other local
language. Then press “ENT” to enter default interface. It will enter fault interface directly after 30s without any
operation, as the following figure.
Danger
Danger
Before access the battery, check with a multimeter that the battery polarities are correct. When connecting the battery, careful
attention is required to prevent short circuit of the positive and negative poles of the battery. If two batteries are connected at one
time, battery mutual charging due to unequal terminal voltages of the two batteries should be avoided.
4. Set the power supply voltage to the required battery float voltage through the controller (in this case, the rectifier
should not be in current limiting state).
NetSure 801 CA7 Power Supply System (New Skelecton) User Manual
52 Chapter 4 Testing
ON
OFF
1 2 3 4 5 6 7 8
Table 4-1 Setting list of DIP switch for AC distribution cabinet address
Bit 1 Bit 2 Bit 3 Bit 4 Bit 5 Corresponding address in the controller
0 0 0 0 0 64
1 0 0 0 0 65
0 1 0 0 0 66
1 1 0 0 0 67
0 0 1 0 0 68
1 0 1 0 0 69
0 1 1 0 0 70
1 1 1 0 0 71
Note
Address of the AC distribution cabinet default setting from factory is 64, if there are multiple AC screens, set the cabinets address
to 64, 65,…,71.
ON
Position ‘ON’ represents ‘1’, and ‘OFF’ represents ‘0’. See Table 4-3 for details.
Table 4-3 Setting DIP switches of DC distribution cabinet
Bit Definition Setting explanation
Bits 1 is low, Bits 4 is high
AC distribution cabinet address: 00000~11100 (controller address: 64 ~ 71):
Communication 1 2 3 4 1 2 3 4
1~4
address
NetSure 801 CA7 Power Supply System (New Skelecton) User Manual
Chapter 4 Testing 53
Note
The defaults parameter in controller of the system is: ‘LDU mode: NO’, not to change it.
Note
Address of the AC distribution cabinet default setting from factory is 72, if there are multiple AC screens, set the cabinets address
to 72, 73,…,91.
To put the system into service, system setting must be done through the controller, battery group number, battery
nominal capacity, charge current limit and other function requirements according to the actual system configuration.
Otherwise, the system information display and output control cannot function normally.
1. At the default LCD screen (if stay in other screen, press ESC will exit to the default screen) of the controller in AC
distribution cabinet, press ESC to enter the product information screen, as shown in Figure 4-3, check whether the
‘Address’ is within the range of Table 4-1. If the address is out of the range in Table 4-1 or there are two or above AC
screens set to the same address, then reset the address according to 4.3.1 Setting DIP Switch.
Model: LargeDU
Software version:
V1.08
Address: 64
Model: LargeDU
Software version:
V1.08
Address: 72
NetSure 801 CA7 Power Supply System (New Skelecton) User Manual
54 Chapter 4 Testing
3. At the controller MAINMENU screen in rectifier cabinet, press or to move the cursor to the setting icon .
Click the setting icon and input user name (‘admin’) and password (‘1’) to enter the setting screen.
DC DistGroup
4. Enter ‘AC Settings’-->’AC Distrib 1’…… ’AC Distrib n’, check the PD380/400AFH&PD380/630AFH AC coefficients
Over Voltage:
of transformer, the corresponding coefficient of58.5V
PD380/630AFH would be 160 (800/5), the corresponding coefficient
of PD380/400AFH would be 100 (that is 500/5).UnderIf any inconsistencies exist, set the parameters as above.
Voltage:
45.0V
5. Back to theDCsetting screen, enter ‘DC Settings’-->’DC Distrib 1’…… ’DC Distrib n’, check whether the ‘Hall
Settings
Coefficient’ and ‘Load Measure Ty’ are consistent with Table 4-5. If any inconsistencies exist, reset the parameters
DC DistGroup>
DC Distrib1>
according to Table 4-5.
DC Distrib1
Num of Battery:
2
Temp Number:
0
Branch CurrCoeff:
500
Curr Output Num:
32
Load Measure Ty:
Hall
Hall Coefficient:
3000
DC Distrib1
Num of Battery:
2
Temp Number:
0
Branch CurrCoeff:
500
Curr Output Num:
Figure 4-6 Setting number of battery
32
7. Set battery parameters as follows: Load Measure Ty:
Hall
Back to ‘Settings’ screen, enter ‘Batt Settings’-->’Charge’, set the actual connected battery string capacity, then click
Hall Coefficient:
‘Reset Batt Cap’, select ‘Yes’ and press ENT to3000
confirm. Back to the ‘Batt Settings’ screen, enter the ‘LargeDU’ screen
to set the battery current sampling coefficient. (The battery string index is related with the connected DC cabinet
address and battery string number, if the DIP of DC Distrib 1 is set to 72, and the the DIP of DC Distrib 2 is set to 73,
and the battery string number is set to 2, then the battery current coefficient of battery string1 and battery string 2 is
the shunt coefficient of two battery ports in DC Distrib 1, and the current coefficient of battery string 3 and battery
string 4 is the shunt coefficient of two battery ports in DC Distrib 2.)
NetSure 801 CA7 Power Supply System (New Skelecton) User Manual
Battery Test
End Test Voltage:
Batt Settings 45.2V
Charge> End Test Time: Chapter 4 Testing 55
Battery Test> 180min
EndTestCapacity:
Temp Comp> Charge
LargeDU> 70%
Float Voltage:
Constant Curr Test:
53.5V
No
EQ Voltage:
56.4V
Batt CurrTemp
Limit:Comp
0.10C10
TempComp Sensor:
Over Curr Lmt:Charge
None
Float Voltage:
0.30C10
TempComp Center:
53.5VEQ
Auto
25deg.C
EQ Voltage:
Yes Comp Coeff:
Temp
56.4V
Figure 4-7 72mV/deg.C
Setting
Batt Currbattery
Limit: charge parameters
0.10C10 Battery Test
End
OverTest LargeDU
CurrVoltage:
Lmt:
Batt Settings Large
45.2V
0.30C10DUBatt1
Charge> End
AutoTest
2000 EQ Time:
Battery Test> Large DUBatt2
180min
Yes
EndTestCapacity:
2000
Temp Comp>
LargeDU> 70%
Battery Test
Constant Curr Test:
End Test Voltage:
Figure No
4-8 Battery current coefficient
Batt Settings 45.2V
Charge> Back to ‘Batt Settings’ screen, enter ‘Temp Comp’ screen,
End Test Time:set the ‘Temp Comp Coeff’ according to battery factory
180min
requirement. The default value is 72mV/°C (If no temperature Temp Comp
sensor is configured, ignore this item), and set the
Battery Test>
EndTestCapacity:
TempComp Sensor:
‘TempComp Sensor’ to ‘Ldu1 Temp1’, as shown in Figure 4-9. (If no temperature sensor is configured or the
Temp Comp>
LargeDU>temperature compensation function needs to None 70%
be canceled, then set the ‘TempComp Sensor’ to ‘None’). Meanwhile,
TempComp
Constant Curr Center:
Test:
set ‘DC Settings’’DC Distrib 1’Temp Number’ to 1 ~ 3 ( if no temperature sensor is configured or the temperature
25deg.C
No
compensation function needs to be canceled,Temp then set
Comp ‘Temp Number’ to ‘0’), as shown in Figure 4-10.
theCoeff:
72mV/deg.C
Temp Comp
TempComp DC DistGroup
Sensor:
LargeDU
Over Voltage:
None
Large DUBatt1
TempComp
58.5V Center:
2000
Under Voltage:
25deg.C
Large DUBatt2
45.0VComp Coeff:
Temp
DC Settings 2000
72mV/deg.C
DC DistGroup>
DC Distrib1> Figure 4-9 Setting Temp Comp parameter
LargeDU
Large DUBatt1
DC Distrib1
2000
Num of Battery:
Large
2 DUBatt2
Temp Number:
2000
0
Branch CurrCoeff:
500
Curr Output Num:
Figure 4-10 Setting Temp Number
32
Load Measure Ty:
Note
Hall
‘DC Distrib 1’ corresponds to the DC distribution screen that with the lowest address.
Hall Coefficient:
3000
NetSure 801 CA7 Power Supply System (New Skelecton) User Manual
56 Chapter 4 Testing
Back to ‘Batt Settings’ screen, and enter the ‘Charge’ screen, set the ‘Float Voltage’ (default value: 53.5V) and ‘EQ
Voltage’ (default value: 56.4V) according to the recommended value of the battery supplier, as shown in Figure 4-11.
For free EQ charge battery, the EQ voltage can be set 0.1V higher than the float voltage. Set the battery current limit
according to Figure 4-11.
Charge
Float Voltage:
53.5V
EQ Voltage:
56.4V
Batt Curr Limit:
0.10C10
Over Curr Lmt:
0.30C10
Auto EQ
Yes
Figure 4-11 Setting float/EQ voltage
Battery Test
End Test Voltage:
4.4 Batt
Checking
Settings
Alarm And Operation Status
45.2V
Charge> End Test Time:
Battery Test> 180min
4.4.1 Testing Controller EndTestCapacity:
Temp Comp>
LargeDU> 70%
The controller can be tested after the parameter setting
Constant is completed
Curr Test: based on the actual system configuration and
battery management requirements. No
Communication test
Temp Comp
When the system is in normal operation, disconnecting the communication cable of any unit (AC distribution cabinet,
TempComp Sensor:
DC distribution cabinet and controller) will interrupt the communication between the controller and this unit as well as
None
other units in serial connection with this unit, and cause the
TempComp controller to generate communication failure alarm. Real
Center:
time data will be displayed in contrast with the25deg.C
background in LCD. By reconnecting the communication cable, the
system will recover automatically. Temp Comp Coeff:
72mV/deg.C
Boost charge and float charge changeover
LargeDU (‘1’) to enter the ‘Settings’ ‘Maintenance’ screen, set
Click the setting icon, input user name (‘admin’) and password
the ‘Auto/Man State’ to ‘Manual’, as shown in Large
FigureDUBatt1
4-12.
2000
Maintenance
Large DUBatt2
2000
Auto/Man State:
Auto
EQ/FLT Control:
Float Charge
BattTestControl:
Stop
Rect Curr Limit:
121%
When the system is in float charge state, click the setting icon, input user name (‘admin’) and password (‘1’) to enter
the ‘Settings’ ‘Maintenance’ screen, change the ‘EQ/FLT Control’ to ‘EQ charge’, as shown in Figure 4-12. The
system will enter into EQ charge state, and the rectifiers will output EQ charge voltage. Change it back to ‘Float
charge’ and the system will return to float charge state.
Rectifier adjustment
1. Refer to 5.2 Setting The Position Number Of The Rectifier Manually to enter the rectifier setting interface. Test the
switching-on/off of the rectifier, the rectifier switching-on/off should be under control and normal.
2. Set the system float/EQ voltage in the LCD of the controller according to 4.3.2 Setting Basic Parameters For
Controller, the rectifier voltage should be normally adjustable.
NetSure 801 CA7 Power Supply System (New Skelecton) User Manual
Chapter 4 Testing 57
3. Under the condition that all the rectifier outputs are normal, observe and record the rectifier current-sharing
characteristics at different total loads.
Connect some loads to the system and test the battery protection characteristics using the following steps.
1. At the MAINMENU screen of the controller in rectifier cabinet, press and to move the cursor on the setting
icon , click this icon to enter the setting screen.
2. Input user name (‘admin’) and password (‘1’) to enter ‘DC Settings’’DC DistGroup’, change the ‘Under Voltage’ to
52V, as shown in Figure 4-13. Then reduce the load, and open the AC input MCB of the rectifier, the battery will
discharge to the load, and the output voltage will decrease. When the battery output voltage drops below the
undervoltage alarm point, the controller will generate battery undervoltage alarm.
DC DistGroup
Over Voltage:
58.5V
Under Voltage:
45.0V
DC Settings
DC DistGroup>
DC Distrib1>
Figure 4-13 Setting undervoltage alarm point
DC Distrib1
3. Close the rectifier AC input MCB. When the entire rectifiers begin to work normally, the rectifier startup process can
Num of Battery:
be observed. The time for rectifier output current reaching a steady state varies depending on the battery capacity,
2
rectifier quantity and load capacity. By that time, the mains
Temp failure alarm will disappear automatically. With the output
Number:
voltage rising to exceed the undervoltage alarm0 recovery point, the battery undervoltage alarm will disappear
automatically. Branch CurrCoeff:
500
4. After finishing the test, restore the system under-voltage alarm point to the original value.
Curr Output Num:
5. Entering ‘DC Settings’’DC DistGroup’ screen32 to lower the system overvoltage alarm point (for example, 52V), as
Load Measure Ty:
shown in Figure 4-14. When the output voltage of the module exceeds the overvoltage alarm point, the controller
Hall
should generate audio and visual output overvoltage alarms. Restore the system overvoltage alarm point to its
Hall Coefficient:
original value and the output overvoltage alarm3000
should automatically disappear.
DC DistGroup
Over Voltage:
58.5V
Under Voltage:
45.0V
DC Settings
DC DistGroup>
DC Distrib1>
Figure 4-14 Setting overvoltage alarm point
NetSure 801 CA7 Power Supply System (New Skelecton) User Manual
58 Chapter 4 Testing
By now, the system test is completed and the power supply system is in normal operation.
2. In the interface shown in Figure 4-16, click the LAN Settings button to pop up the interface shown in Figure 4-17.
In the above interface, uncheck the proxy option and click OK to finish the LAN setting.
Note
The user only needs to do the above settings when the controller is connected to an intranet and the user has set that the access to
the intranet needs to be made through proxy. If the controller is connected to Internet and the user computer is connected to the
intranet, the user cannot disable the proxy, otherwise you will have no access to the controller.
NetSure 801 CA7 Power Supply System (New Skelecton) User Manual
Chapter 4 Testing 59
3. Select Internet Options from the Tools menu. The “Internet Options” window opens. In the “Internet Options”
window, select the General tab, as shown in Figure 4-18.
4. Click on the Settings button. The following window opens, as shown in Figure 4-19. In the Settings window,
choose “Every time I visit the webpage” and click OK.
NetSure 801 CA7 Power Supply System (New Skelecton) User Manual
60 Chapter 4 Testing
5. In the “Internet Options” window, select the Security tab, as shown in Figure 4-20.
6. Click on Trusted sites. With “Trusted sites” selected, click “Sites”. The following window opens, as shown in
Figure 4-21. Uncheck the “Require server verification (https:) for all sites in the zone:” box if https is not being used.
NetSure 801 CA7 Power Supply System (New Skelecton) User Manual
Chapter 4 Testing 61
7. In the Trusted sites window, type or copy the NCU URL in the “Add this website to the zone:” box, as shown in
Figure 4-22.
8. Click Add. The NCU URL is listed in the Websites: box. Click Close, as shown in Figure 4-23.
9. In your browser, enter http:// and the controller’s IP address and press ENTER. If your site requires secure HTTP
and you were furnished with an M831D configuration with secure HTTP, enter https:// and the controller’s IP address
and press ENTER. The following Web Interface Login window opens, as shown in Figure 4-24. Enter a valid User
Name and Password, and then click LOGIN.
By default, the “User Name” is "admin" and the “Password” is “1”.
NetSure 801 CA7 Power Supply System (New Skelecton) User Manual
62 Chapter 4 Testing
User can view the IP address: Main menu——>Settings (password:1)——>Communication Parameter, and then
press the ENT key.
10. In the Web Interface, after entering a valid User Name and Password and clicking LOGIN, the "Homepage"
window opens, as shown in Figure 4-25.
NetSure 801 CA7 Power Supply System (New Skelecton) User Manual
Chapter 5 Operation 63
Chapter 5 Operation
This chapter introduces the operation of the power distribution LCD, procedures of adding loads and rectifiers.
To Chinese
ENT to Run
ESC to Quit
Screen 2:
AC Distri 1
Stat: Run Normal
Ctrl Mode: Manual
Light Stat: On
NetSure 801 CA7 Power Supply System (New Skelecton) User Manual
64 Chapter 5 Operation
if the Uc voltage exists phase loss there will display phase loss at the back of Uca voltage. The overvoltage alarm at
this time takes place at line voltage.
Screen 4 to screen 6:
The AC 2 and AC 3 information of the screen 4 to screen 6 are similar with AC 1 information.
Screen 7:
AC Distri AC Distri
A Curt: 35.3A
Curt: 12.5A
A Curt: 12.8A
A Curt: 9.9A
or
Indications of AC current depend on the current measurement methods set through the controller: 3-phase
current/1-phase current/no display.
Screen 8:
AC Distri
AC Freq: 50.1Hz
Freq Stat: Normal
Arrester Stat: Normal
DC Distri
Bus Volt: 53.5V
Bus Stat: Normal
Load Curt: 2390.6A
Note
To facilitate the replacement and maintenance, the total load current sampling components of DC distribution cabinet use open
type Hall sensors with measurement accuracy of 2%. Taking into account the general error of the measuring circuit, the displayed
total load current on the controller LCD of DC distribution cabinet may have certain difference (0 ~ 60A) with the displayed
value on the controller in rectifier cabinet.
Screen 12:
DC Distri Batt1
53.5V Normal
30A Normal
Batt1 Fuse: On
Indications of batteries are depended on the battery number set in the controller: two groups/one group or display any
information about battery.
NetSure 801 CA7 Power Supply System (New Skelecton) User Manual
Chapter 5 Operation 65
DC Distri Fuse
01 On 02: On
03: On 04: On
05: On 06: On
The branch fuse state will be displayed according to the DC fuse number in the controller (≤ 64 routes) and their
actual state.
Screen 27 to screen 29:
DC Distri
BranchCur 1: 25A
BranchCur 2: 25A
BranchCur 3: 25A
The branch battery current will be displayed according to the current branch number set in the controller (≤ 6 routes)
and their actual value. When the three branches’ currents in one screen are not set, this screen will not be displayed.
Screen 30:
DC Distri
Temp 1: 25℃
Temp 2: 25℃
Temp 3: 25℃
Indications of temperature will be displayed according to the temperature circuit number set in the controller (≤ 3
routes) and their actual value.
When the number is 0, this screen will not be displayed. While setting the temperature measurement and
disconnecting temperature sensor or the sensor is damaged, it will display 27°C.
2009-01-03
System:Normal
SPD State:Normal
Light State:Off
NetSure 801 CA7 Power Supply System (New Skelecton) User Manual
66 Chapter 5 Operation
3. If no operation is conducted on the controller keypad for 8 minutes, the LCD screen will automatically return to the
first system information screen. The time of that return will be recorded automatically, and can be queried through the
host.
4. At the system information screen, press the ESC key to display monitoring information screen. As shown in Figure
5-2.
Model:HDU-ATS
Comm Addr:190
64
SW Ver:1.09
5. At the system information screen, press and hold the ESC and ENT keys simultaneously for several seconds, the
controller will be reset, and then the system will restart.
Login:
Password:
1. When inputting the password, use the ENT key to get into editing state, use ▲ or ▼ to modify numbers, and use
◄ or ► to move the cursor. After the input, press ENT to confirm.
2. If the password is correct, the next screen will appear. Otherwise, the system will prompt ‘Password incorrect’.
3. During the operation, press the ESC key will return to the main menu screen.
The monitoring unit has three password levels: user level password (default: 1), engineer level password (default: 2)
and administrator level password (default: 640275). See Table 5-1.
Table 5-1 Password levels and operation authorities
Password level Operation authority Default password
User level The authority to change general parameters 1
All the user’s authorities, plus ‘resetting system, resetting password, changing
Engineer level 2
system work mode’ operation authorities
Administrator All the engineer’s authorities, plus ‘changing password, controlling alarm volume,
640275
level browsering parameters set through host’ operation authorities
Once you input the correct password, you never need to input the password again during the operation. If the interval
for adjacent operation is more than four minutes, the system will prompt you to input the password again. If you want
to operate senior settings, you need to input higher level password after four minutes (note that within this four
minutes, you cannot do any key operation). If the password of the higher level and lower level is the same, then
controller will display senior setting menu.
NetSure 801 CA7 Power Supply System (New Skelecton) User Manual
Chapter 5 Operation 67
1. At any one of the system information screen, press the ENT key to enter the main menu screen.
2. At any sub-menu of the main menu screen, press the ESC key repeatedly to return to the higher-level menu, and
ultimately return to the main menu screen.
Active alarm
When a new alarm is generated, and there is no operation on controller keypad for two minutes, the LCD of the
controller will prompt the active alarm screen automatically. If there are multiple alarms in the current system, you can
query alarms through the following steps.
At screen in Figure 5-4, press ▲ or ▼ to select ‘Active Alarm’, then press the ENT key to confirm.
If there is an active alarm, the display shown in Figure 5-5 will appear.
Alarm:1/3
Self-detect Err
Important Alarm
111214 19:49:53
The previous screen includes the alarm serial No./alarm total number, alarm name, alarm level and alarm time. The
alarm generating time determines the sequence it is displayed, with the latest alarm displayed first. Press ▲ or ▼ to
view all active alarms.
Branch information
Branch information menu shows the branch currents and load rate. As shown in Figure 5-6.
Branch: 1/8
-Curr:0.0A
-LoadRate:0%
Alarm:1/3
Self-detect Err
111214 19:49:53
111214 19:56:30
The history alarms of the controller are stored in cyclic order. At most 200 alarms will be recorded, above that, the
earliest alarm will be cleared automatically.
2. Press ▲ or ▼ to view other history alarms.
3. At any history alarm screen, press the ESC key repeatedly to return to the higher-level menu, and ultimately return
to the first system information screen.
NetSure 801 CA7 Power Supply System (New Skelecton) User Manual
68 Chapter 5 Operation
Settings screen
Displayed in many screens, the settings screen is a sub-menu of the main menu. It is used to set system parameters.
The settings screen has password protection, only the correct password allows you to enter it. See Figure 5-8 for the
settings screen.
Settings
AC set
System setting
1. At the main menu screen, press ▲ or ▼ to select the ‘Settings’ menu, and press the ENT key to display the
password confirmation screen.
2. Input the correct password and press the ENT key to enter the settings screen. Press ▲ or ▼ to enter the
operation screen you need.
There are three parameters for setting: DC setting, insulation setting, and system setting. Setting methods are as
follows:
AC distribution
1. At the screen shown in Figure 5-9, press ▲ or ▼ to select the ‘AC Dis’ menu, then press the ENT key to confirm.
AC Input:
-Current: Hall
-HallCoef: 2307A
230A
Branch: 1
2. Press ▲ or ▼ to select the parameter you need, and press ◄ or ► to select the parameter value. Then press the
ENT key to confirm. The controller will automatically save the setting value. See Table 5-2 for parameters of AC
distribution settings.
Table 5-2 Description of the AC parameter setting
Parameter name Setting range Default Description
AC input-Curr None/Hall Nonel Set it according to the actual sensor used by the power system
AC input-HallCoef 1A~5000A 600A Set it according to the actual sensor used by the power system
Branch 1~8 1 Set it according to the actual number of the test load current circuits
Branch-Curr None/Hall Nonel Set it according to the sensor used by the load. Each branch needs to be set
Branch-HallCoef 1A~5000A 50A Set it according to the actual sensor used by the power system
Branch-SW 1A ~ 5000A 50A Set it according to the MCB capacity used by load
Set it according to the user requirements. High load alarm is generated when
Brh HighLoad 50% ~ 100% 60%
load current reaches setting value*load capacity
Set it according to the user requirements. Overload alarm is generated when
Brh OverLoad 50% ~ 100% 90%
load current reaches setting value*load capacity
Note
PD380/800AFA use the 800/1 current transformer, the hall coefficient of the AC input is set to 2307A.
System Settings
1. At the Settings screen, press ▲ or ▼ to select the ‘Sys set’ menu. Then press the ENT key to confirm, as shown in
Figure 5-10.
Lang: English
Tzone: GMT+08:00
Date: 2009-08-08
Time: 16:26:16
NetSure 801 CA7 Power Supply System (New Skelecton) User Manual
Chapter 5 Operation 69
2. Press ▲ or ▼ to select the parameter you need, and press ◄ or ► to select the parameter value. Then press the
ENT key to confirm. The controller will automatically save the setting value. See Table 5-3 for parameters of system
settings.
Table 5-3 Description of the system parameter setting
Main menu Main menu
Lang Chinese, English Chinese Set it according to your requirements
Tzone - - Set it according to the actual instance
Set the time according to the current actual time, regardless of whether it
Date 2000 ~ 2038 -
is a leap year or not
Time - - Set the time according to the current actual time
38400
19200
9600
485 Baud 19200 Set it according to your requirements
4800
2400
1200
38400
19200
9600
232 Baud 9600 Set it according to your requirements
4800
2400
1200
232 Addr 1 ~ 254 1 Set it according to your requirements
Reset Paras Y, N N Whether resetting the parameter to the default
The password can be 6 digits long at most. If it is shorter than 6 digits,
User PWD - -
end it with space key
When the serial port is needed to upgrade the program or configure files,
ComDownLoad Y, N N
enter serial port download mode first
240V DC system
336V DC system 240V DC
System types Set it according to your requirements
380V AC system system
ATS AC system
History
Empty History alarm Press the’Enter’ two times will empty the historical alarms
alarm
LDU modle Y, N N If you need to communicate with M820D/M831D, set ‘Yes’
NetSure 801 CA7 Power Supply System (New Skelecton) User Manual
70 Chapter 5 Operation
The Power System Status tab displays power system status in a graphical block diagram format. This includes status
of the input power, modules (i.e. rectifiers, converters), DC equipment, and battery.
3. Click on the ‘Rectifier’ icon to access the following window, as shown in Figure 5-12.
Displayed on the Rectifier Device Group status page are the individual rectifiers installed in the system.
4. Click an individual rectifier icon to display its status such as "Current Limit", "Valid Rated Current", etc., as shown in
Figure 5-13.
NetSure 801 CA7 Power Supply System (New Skelecton) User Manual
Chapter 5 Operation 71
5. Hover the mouse pointer on an individual rectifier icon , this icon changes to . Click to set the
individual rectifier information and set the rectifier position number to actual position number, then click the ‘Set’ to
confirm.
6. Click to go back to the individual rectifier status page, as shown in Figure 5-14.
Note
During the setting, you can set the ‘LED Control’ to ‘LED Control’ to make sure the power indicator of the corresponding
module flash, so as to make sure the actual position of that module.
NetSure 801 CA7 Power Supply System (New Skelecton) User Manual
72 Chapter 5 Operation
2. Insert the new rectifier into position along the guide rail and fix it. See 3.4.1 Installing Rectifier.
3. Set the address in the controller of the corresponding rectifier.
4. Close the corresponding AC input switch to feed AC power to this rectifier.
5. Repeat steps 1 to 4 to add all rectifiers.
6. Reset parameters for controller.
Notice
Note
Connection and disconnection of rectifier’s external input cables should be done by maintenance personnel, and the cables must
be connected before switching on the rectifier, and disconnected after switching off the rectifier. The rated current of the rectifier
input MCB is 20A, and its breaking capacity is 6kA.
NetSure 801 CA7 Power Supply System (New Skelecton) User Manual
Chapter 6 Maintenance 73
Chapter 6 Maintenance
This chapter introduces basic maintenance requirements, routine maintenance items, maintenance operations, basic
fixing methods and emergency treatment.
6.1.1 General
To ensure quality power supply and guarantee stable and reliable operation of the communication system, operation
management and maintenance are necessary to the power supply system. Basic requirements for maintenance of
power supply system include:
1. Guarantee uninterrupted quality power supply to the communication equipment.
2. Carry out periodic inspection and overhaul to ensure stable and reliable operation of the power supply system and
prolong its operational life span.
3. Conduct effective troubleshooting to reduce the loss caused by faults.
4. Keep the equipment and environment clean to ensure that the environment in the equipment room conforms to the
basic requirements of equipment operation.
5. Use new technologies and improve maintenance methods to achieve centralized monitoring, little or even no
attendance.
To sum up, the power supply system maintenance includes routine maintenance, periodic inspection and
technological reform. And the maintenance must be carried out in compliance with applicable industry standards and
local regulations.
The common tools and instruments used in maintenance of power supply system are separately listed in Table 6-1
and Table 6-2.
Table 6-1 Common tools for power equipments maintenance
Name Quantity Applications
Shape and coil the naked pins and help to weld and assemble the surface of
Joint pliers 1 piece
intensive device
Diagonal cutting pliers 1 piece Cut extra leads, pins of welding surface, and nylon binding clips
Tweezers 1 piece Help to weld and clean, pick up mini components, and coil tiny leads
Blade screwdriver 1 set Drive and remove plain screws and open boxes
Cross screwdriver 1 set Drive and remove cross screws
Wrench (double end wrench or
1 set Wrench 6-angle or 4-angle bolts and nuts
fork wrench)
A kind of spinning tool used when there is no space for operation on the screw
Socket wrench 1 set
surface
Wrench 6-angle or 4-angle bolts and nuts. Note: when in use, the adjustable
Adjustable wrench 1 set
tongue shall turn to the inside of the spinning direction.
Electric soldering iron 1 piece Weld components
Wash brush 1 piece Clean the equipment and dust inside boxes
Handsaw 1 piece Saw the bus and cables. Note: The saw blade shall not turn to the handle.
Electrician knife 1 piece Peel off the skin of cables, etc.
Electrician rubber mallet 1 piece Rectify cables or equipment location
Auxiliary materials (non-spare Commonly-used auxiliary materials include insulating tape, self-adhesive label, soldering tin,
parts) nylon bandage, etc.
NetSure 801 CA7 Power Supply System (New Skelecton) User Manual
74 Chapter 6 Maintenance
The power supply system consists of AC power supply, DC power supply and earthing system. To ensure
communication quality and power supply security, the power supply quality must conform to some basic quality
standards. Reference standards for AC, DC and earth resistance are shown in Table 6-3, Table 6-4 and Table 6-5.
Table 6-3 Quality standards for DC power supply
Voltage variation range Noise voltage (mV) Maximum permissible
Standard
at the receiving end of Psophometrically Peak-peak Wide frequency noise voltage drop of power
voltage (V)
telecom equipment (V) weighted noise value noise (effective value) supply circuit (V)
≤ 50mV
≤ 200mV @3.4kHz to 150kHz
-48 -40 to -57 ≤ 2mV 3
0 to 20Mhz ≤ 20mV
@150kHz to 30Mhz
24 19.8 to 28.2 ≤ 2.4mV 1.8
Note: The voltage drop at the connectors of DC power supply circuit (including the fuse of the feed line output from the
discharging busbar, and battery connectors) shall be in conformity with the following requirements or the temperature rise shall
not exceed the permissible value: 1. If under 1000A, every hundred ampere≤5mv; 2. If above 1000A, every hundred
ampere≤3mv.
NetSure 801 CA7 Power Supply System (New Skelecton) User Manual
Chapter 6 Maintenance 75
NetSure 801 CA7 Power Supply System (New Skelecton) User Manual
76 Chapter 6 Maintenance
NetSure 801 CA7 Power Supply System (New Skelecton) User Manual
Chapter 6 Maintenance 77
When the faults of the controller affect the DC power supply, turn off the controller.
NetSure 801 CA7 Power Supply System (New Skelecton) User Manual
78 Chapter 6 Maintenance
Note
If a rectifier is pulled out or there is faulty rectifier, users should reset the controller. Or else the batteries cannot be boost
charged.
Power indicator
Protection indicator
Fault indicator
Change the position of the abnormal and normal rectifiers upon abnormity. If the abnormal rectifier still cannot work
normally, refer to Table 6-7 to dispose the faults.
Table 6-7 Disposal methods for rectifier faults
Fault Related alarm Fault cause Proposal
Power indicator off
No alarm No input or output voltage Ensure having input and output voltage
(green)
Remove the object which blocks the
Fan is blocked
fan operation
Main
The vent duct is expedite: there
causes of Remove the blockage at air intake and
are some blockages at air intake
Rectifier over overheat air outlet
or air outlet
temperature protection
High temperature or pyrotoxin is Decrease ambient temperature or
for
near to the air intake of rectifier remove the pyrotoxin
rectifier
The rectifier isn’t absolutely
Reinsert rectifier
inserted into the frame
Protection indicator on Check the rectifier communication
(yellow) whether nomal or not. If not, continue
No current sharing to check the connection of
communication lines. Replace the fault
rectifier when it works normally
Rectifier
Change the position of the abnormal
protection
and normal rectifiers. Replace the
PFC output overvoltage protection
abnormal rectifier if it cannot work
normally all the same
Ensure the AC input voltage whether in
AC input voltage exceeding the normal range
normal range or not
Rectifier
Protection indicator Check the communication lines
communication Rectifier communication failure
flashing (yellow) connection whether well or not
failure
Remove the abnormal rectifier and
Fault indicator on (red) Rectifier failure Overvoltage restart. Replace the rectifier if it occurs
overvoltage again
Fault indicator flashing Rectifier fan
Fan fault Replace new fan
(red) fault
NetSure 801 CA7 Power Supply System (New Skelecton) User Manual
Chapter 6 Maintenance 79
Fault description
1.Internal short-circuit of rectifier
The rectifier will automatically exit the system in case of internal short-circuit.
2.Damage to partial rectifier
In case of damage to partial rectifiers, if the remaining undamaged rectifiers are able to meet the power supply
requirements of loads, just turn off the AC input switches of the damaged rectifiers.
3.Rectifier output overvoltage
The overvoltage of a single rectifier will not cause the overvoltage protection of all rectifiers. However, if overvoltage
protection occurs to all rectifiers, the system cannot recover automatically.
Treatment: turn off the AC input switches of all rectifiers and remover the rectifier to disconnect it. At this time, the
system voltage should be below 56.4V. Then insert rectifier one by one and turn on the AC input switches to observe
the output current of it. When the AC input MCB of a certain rectifier is switched on, its output current is obviously
bigger than that of the others. When the system voltage is higher than 56.4V, the rectifier with bigger output must be
faulty Replace it. If all the rectifiers show the same symptom, you must turn off the monitoring and rectifiers and then
restart the rectifiers.
Note
During the treatment of rectifier fault, delete the address code of the closed rectifier in the rectifier parameters setting through the
controller. Refer to M831D Controller User Manual for deleting method.
Note
Rectifier surface temperature may be high, be careful when you pull out the rectifier.
3.Grasp the handles, pull the module out of the cabinet slowly until it stops, and put the slide switch on position.
Then pull out the rectifier completely. Observe whether there is a appropriate controller alarm.
4.Disconnect the rectifier switch, put the slide switch on position, grasp the handles, and push the rectifier into
cabinet slowly, until it stops, as shown in Figure 6-3.
NetSure 801 CA7 Power Supply System (New Skelecton) User Manual
80 Chapter 6 Maintenance
5.Put the slide switch on position. And then push the rectifier to the bottom until the rectifier panel is on the same
level as the rectifier rack panel, as shown in Figure 6-4.
7.Tighten the fixing screw on the handle to fix the rectifier on the rack, as shown in Figure 6-6.
NetSure 801 CA7 Power Supply System (New Skelecton) User Manual
Chapter 6 Maintenance 81
Power failure
AC power failure is the general case in the operation of power supply system. If the continuous time is not long, the
batteries are feed to DC. However, if the power failure is not clear or the continuous time is too long, restart the
generator to power. And then transfer to feed the power supply system after 5min in order to reduce the effects to the
power supply equipments during the process from starting to transition for generator.
Disastrous accidents
Disastrous accidents refer to communication equipment faults arising from disasters such as lightning strike, flood,
earthquake and fire. For those disasters that may severely affect the safety of communications, emphasis shall be
mainly laid on pervention. Meanwhile, communication exchanges shall have adequate human and material resources
and work out effective countermeasures to deal with these disasters. They shall also prepare emergency
management regulations and grave accidents rush-repair rules.
NetSure 801 CA7 Power Supply System (New Skelecton) User Manual
82 Appendix 1 Technical Parameter
NetSure 801 CA7 Power Supply System (New Skelecton) User Manual
Appendix 1 Technical Parameter 83
Parameter
Parameter Description
Category
Rectifiers can work in parallel and share the current. The unblanceness is better than
Current sharing
±3% rated current. Test current range: 10% ~ 100% rated current
The rectifier can output max. power of 5,800W with input voltage of 304Vac ~ 530Vac.
Derate by input (45°C) The output power will drop to 50% rated power when the input volatage fall to 304Vac ~
260Vac
The startup time is configurable through controller. The time is 8s at 90% rated load, and
Output delay startup
90s at 100% rated load
Rectifier fan speed can be increased when the rectifier temperature and output current is
raising. The fan speed will reach full speed when ambient temperature is more than 45°C
Fan controlling
or full loads output. If the PFC bus voltage exceeds the normal range, for example in the
case of low bus voltage, the fan will stop to work
The rectifier provides overvoltage hardware and software protection. The hardware
protection point is 59.5V ± 0.5V, and it requires manual resetting to restore operation.
The software protection point is between 56V and 59V, and can be set through the
Rectifier
controller
When the output voltage of rectifier is higher the overvoltage protection point, the rectifier
will shutdown. The overvoltage protection point is between 56V and 59V, and can be set
Overvoltage protection
through the controller. The alarm indicator (red) will be on when rectifier occurs
mode
overvoltage protection. The protection event will be set to the controller which will deal
with this alarm. If the rectifier happens four times overvoltage in 5min, it requires manual
resetting to restore the operation
There are two software setting modes through the controller on rectifier:
1. Restart by hand
2. Restart automatically after overvoltage protection in 5s
Temperature below 45°C, outputs full power: 5,800W
Temperature above 45°C, outputs power as following::
Temperature derating
At 50°C, output power is 5,400W
At 65°C, output power is 4,640W
Conducted emission
Class A EN300386
Radiated emission
Immunity to ESD Level 3 EN/IEC 61000-4-2
EMC Immunity to EFT Level 4 EN/IEC 61000-4-4
Surge Level 4 EN/IEC 61000-4-5
Immunity to radiation Class A EN/IEC 61000-4-3
Immunity to conduction Class A EN/IEC61000-4-6
The AC input side can withstand five times of simulated lightning voltage of 5kV at
10/700µs, for the positive and negative polarities respectively. It can withstand five times
Lightning
At AC side of simulated lightning surge current of 20kA at 8/20µs, for the positive and negative
protection
polarities respectively. The test interval is not smaller than 1 minute. It can also withstand
featires
one event of simulated lightning surge current of 40kA at 8/20µs (test with AC cabinet)
At DC side The DC side can withstand one time of simulated lightning current of 10kA at 8/20μs
Safety regulation Compliant with IEC60950
Noise The noise is not more than 60dB (A) when ambient temperature is 25°C
Protection level IP20
At temperature of 15°C ~ 35°C and relative humidity not bigger than 90%RH, apply a
Insulation resistance test voltage of 500Vdc. The insulation resistances between AC circuit and earth, DC
circuit and earth, and AC and DC circuits are all not less than 10MΩ
Remove the SPD, controller and rectifiers from the system before the test
Other AC circuit to earth: 50Hz, 2,500Vac
AC circuit to DC circuit: 50Hz, 3,000Vac
Insulation strength DC circuit to earth: 50Hz, 1,000Vac
Assistant circuit (not directly connected to the host circuit): 50Hz, 500Vac
For all the four tests above, there should be no breakdown or flashover within 1min, with
leakage current not bigger than 10mA
MTBF 200,000hr
ROHS compliant with R5 requirement
Rectifier cabinet 2000 (H) × 600 (W) × 600 (D)
Mechnical Dimension (mm) Controller M831D 42 (H) × 86.6(W) × 211.5 (D)
Rectifier R48-5800A, R48-5800e 88 (H) × 244 (W) × 372 (D)
NetSure 801 CA7 Power Supply System (New Skelecton) User Manual
84 Appendix 1 Technical Parameter
Parameter
Parameter Description
Category
Rack1000-7 ≤ 140
Rectifier cabinet (not including rectifier)
Rack2000-7 ≤ 180
Mechnical Weight (kg)
Controller M831D ≤2
Rectifier R48-5800A, R48-5800e ≤8
NetSure 801 CA7 Power Supply System (New Skelecton) User Manual
Appendix 1 Technical Parameter 85
Parameter
Parameter Description
Category
The AC input side can withstand five times of simulated lightning voltage of 5kV at
10/700µs, for the positive and negative polarities respectively. It can withstand five times
Lightning protection
of simulated lightning surge current of 20kA at 8/20µs, for the positive and negative
feature
polarities respectively. The test interval is not smaller than 1 minute. It can also withstand
one event of simulated lightning surge current of 40kA at 8/20µs
Safety regulation Compliant with IEC60950
Overvoltage type II class device
Noise The noise is not more than 60dB (A) when ambient temperature is 30°C
Protection level IP20
At temperature of 15°C ~ 35°C and relative humidity not bigger than 90%RH, apply a
Other Insulation resistance test voltage of 500Vdc. The insulation resistances between AC circuit and earth, DC
circuit and earth, and AC and DC circuits are all not less than 10MΩ
Remove the SPD, controller and rectifiers from the system before the test
AC circuit to DC circuit: 50Hz, 3,000Vac
AC circuit to earth: 50Hz, 2,500Vac
Insulation strength DC circuit to earth: 50Hz, 1,000Vac
Assistant circuit (not directly connected to the host circuit): 50Hz, 500Vac
For all the four tests above, there should be no breakdown or flashover within 1min, with
leakage current not bigger than 10mA
MTBF 200000hr
ROHS Compliant with R5 requirement
Dimension (mm) 2000 (H) × 800 (W) × 600 (D)
Mechnical
PD380/400AFH-7-Y2, PD380/630AFH-7-Y3 ≤ 240, PD380/630AFA-7-Y4 ≤ 250,
parameters Weight (kg)
PD380/630AFH-7/YF ≤ 270
NetSure 801 CA7 Power Supply System (New Skelecton) User Manual
86 Appendix 1 Technical Parameter
Parameter
Parameter Description
Category
Battery 2 overvoltage alarm point Default 58Vdc, configurable through controller, 0.5Vdc hysteresis
Alarm Battery 2 undervoltage alarm point Default 58Vdc, configurable through controller, 0.5Vdc hysteresis
parameters Battery 2 overcurrent alarm point Default 100A, configurable through controller, 0.5A hysteresis
Overtemperature alarm point Default 50°C, configurable through controller, 2°C hysteresis
Conducted emission
Class A EN300386
Radiated emission
Immunity to ESD Level 3 EN/IEC 61000-4-2
EMC Immunity to EFT Level 4 EN/IEC 61000-4-4
Surge Level 4 EN/IEC 61000-4-5
Immunity to radiation Level 2 EN/IEC 61000-4-3
Immunity to conduction Level 2 EN/IEC61000-4-6
The DC side can withstand one time of simulated lightning current of 10kA at
Lightning protection feature
8/20μs
safety regulation Compliant with IEC60950
Noise The noise is not more than 50dB (A) when ambient temperature is 30°C
Protection level IP20
At temperature of 15°C ~ 35°C and relative humidity not bigger than 90%RH,
apply a test voltage of 500Vdc. The insulation resistances between AC circuit
Insulation resistance
and earth, DC circuit and earth, and AC and DC circuits are all not less than
Other
10MΩ
Remove the SPD, controller and rectifiers from the system before the test
DC circuit to earth: 50Hz, 1,000Vac
Insulation strength Assistant circuit (not directly connected to the host circuit): 50Hz, 500Vac
For all the two tests above, there should be no breakdown or flashover within
1min, with leakage current not bigger than 10mA
MTBF 200,000hr
ROHS Compliant with R5 requirement
Dimension (mm) 2000 (H) × 800 (W) × 600 (D)
Mechnical PD48/1600DF-7-Y3 ≤ 280, PD48/1600DF-7-Y4 ≤ 280
parameters Weight (kg) PD48/2500DF-7-Y3 ≤ 290, PD48/2500DF-7-Y4 ≤ 290
PD48/2500DF-7/YF, PD48/1600DF-7/YF ≤ 290
NetSure 801 CA7 Power Supply System (New Skelecton) User Manual
Appendix 2 Alarm List 87
NetSure 801 CA7 Power Supply System (New Skelecton) User Manual
88 Appendix 2 Alarm List
Alarm Related
SN Alarm name Alarm category Alarm description
device relay
21 Grid is on Observation
22 Hi Ambient Temp Observation
23 Lo Ambient Temp Observation
24 Sensor Fault Observation
25 DI1 Alarm Critical
26 DI2 Alarm Critical
M831D
27 DI3 Alarm Critical
system
28 DI4 Alarm Critical
29 DI5 Alarm Critical
30 DI6 Alarm Critical
31 DI7 Alarm Critical
32 DI8 Alarm Critical
33 IB Comm Fail Critical
This alarm happens when rectifier AC
34 Multi-Rect Fail Critical Relay 4
power fails.
The controller can memorize the number
of rectifiers. If the number of detected
rectifiers is less than the number
35 Rectifier Lost Major Relay 4
memorized by the controller, then this
Rect Group
alarm occurs. This alarm can only be
ceased manually
36 ECO Active Observation
37 AllRectCommFail Major
38 ECO Cycle Alarm Observation
This alarm happens when rectifier AC
39 AC Failure Major Relay 4
power fails
This alarm happens when rectifier has
40 Rect Temp High Observation None
over temperature fault
41 Rect Fault Major Relay 4 This alarm happens when rectifier fails
This alarm happens when DC output
42 Over Voltage Major Relay 4
over voltage occurs
This alarm happens when rectifier is
43 Rect Protected Observation None
under protection
This alarm happens when rectifier fan
44 Rectifier Fan Failure Major Relay 4
fails.
This alarm happens when rectifier limits
45 Current limit Observation None
its output current
This alarm happens when rectifier
46 Rect Comm Fail Major Relay 4
communication fails
The alarm happens when rectifier power
47 Derated Observation
limit occurs
The alarm happens when rectifier current
48 Curr Shara Alm Observation
unbalance occurs
49 Low AC Protect Major
50 ShortBatTestRun Observation The alarm happens during short test
The alarm happens during pre-boost
51 EQ for Test Observation
charging
The alarm happens during manual
52 Battery Manual Test Observation
battery test
Group
The alarm happens during planed battery
53 Planned Test Observation
test
The alarm happens during AC power
54 AC Fail Test Observation
failure test
NetSure 801 CA7 Power Supply System (New Skelecton) User Manual
Appendix 2 Alarm List 89
Alarm Related
SN Alarm name Alarm category Alarm description
device relay
The alarm happens during manual
55 Manual EQ Observation
battery test
The alarm happens during auto boost
56 Auto EQ Observation
charging
The alarm happens during timed boost
57 Cyclic EQ Observation
charging
The alarm happens when discharging
58 Dsch Curr Imb Observation
current is unbalanced
When the boost charging time is longer
than “boost charging protection time”,
then system changes to float charging, at
this time, the controller checks if the
59 Abnl Batt Curr Observation
battery current meets the conditions for
Battery
transfering to boost charging condition,
Group
and this alarm happens if this condition is
satisfied 3 times
The alarm happens when temperature
60 TempComp Active Observation
compensation is enabled
The alarm happens during current
61 Battery Disch Observation
limitation process
The alarm happens if the battery test is
62 Battery TestFail Major ended because the voltage is reduced to
“Voltage of end of battery test”
63 VHi Batt Temp Observation
64 High Batt Temp Observation
65 Low Batt Temp Observation
66 TempSensorFail Observation
The alarm happens if battery charging
67 Batt Fuse Fail Critical Relay 3 curren is bigger than “battery current
Large DU limiting point”
68 Batt Batt Over Volt Critical Relay 3
69 Batt Under Volt Critical Relay 3
70 Batt Over Curr Critical Relay 3
Large DU
71 Mains Failure Major Relay 2
AC Dist
72 Mains 1 Fail Critical Relay 2
73 Mains 2 Fail Critical Relay 2
74 Mains 3 Fail Critical Relay 2
75 M1 Uab/Ua Fail Critical Relay 2
76 M1 Ubc/Ub Fail Critical Relay 2
77 M1 Uca/Uc Fail Critical Relay 2
78 M2 Uab/Ua Fail Critical Relay 2
79 M2 Ubc/Ub Fail Critical Relay 2
80 M2 Uca/Uc Fail Critical Relay 2
81 M3 Uab/Ua Fail Critical Relay 2
82 AC M3 Ubc/Ub Fail Critical Relay 2
83 distribution M3 Uca/Uc Fail Critical Relay 2
84 cabinet Over Frequency Observation None
85 Under Frequency Observation None
86 M1 Uab/Ua OverV Observation Relay 2
87 M1 Ubc/Ub OverV Observation Relay 2
88 M1 Uca/Uc OverV Observation Relay 2
89 M2 Uab/Ua OverV Observation Relay 2
90 M2 Ubc/Ub OverV Observation Relay 2
91 M2 Uca/Uc OverV Observation Relay 2
92 M3 Uab/Ua OverV Observation Relay 2
93 M3 Ubc/Ub OverV Observation Relay 2
94 M3 Uca/Uc OverV Observation Relay 2
NetSure 801 CA7 Power Supply System (New Skelecton) User Manual
90 Appendix 2 Alarm List
Alarm Related
SN Alarm name Alarm category Alarm description
device relay
95 M1 Uab/Ua UnderV Observation Relay 2
97 M1 Ubc/Ub UnderV Observation Relay 2
98 M1 Uca/Uc UnderV Observation Relay 2
99 M2 Uab/Ua UnderV Observation Relay 2
100 M2 Ubc/Ub UnderV Observation Relay 2
101 AC M2 Uca/Uc UnderV Observation Relay 2
102 distribution M3 Uab/Ua UnderV Observation Relay 2
103 cabinet M3 Ubc/Ub UnderV Observation Relay 2
105 M3 Uca/Uc UnderV Observation Relay 2
106 Input MCCB Trip Critical Relay 2
107 Output MCCB Trip Critical Relay 2
108 SPD Trip Critical Relay 2
109 Comm Fail Critical Relay 2
110 DC Over Volt Critical Relay 3
111 DC Under Volt Critical Relay 3
112 Output1~64 Discon Critical Relay 3
113 Comm Fail Critical Relay 3
114 T1 Over Temp Critical Relay 3
115 DC T2 Over Temp Critical Relay 3
116 distribution T3 Over Temp Critical Relay 3
117 cabinet T1 Under Temp Major Relay 3
118 T2 Under Temp Major Relay 3
119 T3 Under Temp Major Relay 3
120 T1 Sensor Fail Observation None
121 T2 Sensor Fail Observation None
122 T3 Sensor Fail Observation None
NetSure 801 CA7 Power Supply System (New Skelecton) User Manual
Appendix 3 Terminologies 91
Appendix 3 Terminologies
NetSure 801 CA7 Power Supply System (New Skelecton) User Manual
92 Appendix 3 Terminologies
NetSure 801 CA7 Power Supply System (New Skelecton) User Manual
Appendix 4 Engineering Design Diagram 93
654.0
912.0 880.0
1036.0
1134.8
2000.0
206.2 387.5
800.0
NetSure 801 CA7 Power Supply System (New Skelecton) User Manual
94 Appendix 4 Engineering Design Diagram
800
250 100
303
663
833
994
2000
240 257
NetSure 801 CA7 Power Supply System (New Skelecton) User Manual
Appendix 4 Engineering Design Diagram 95
654.0
912.0 880.0
1036.0
1134.8
2000.0
206.2 387.5
800.0
NetSure 801 CA7 Power Supply System (New Skelecton) User Manual
96 Appendix 4 Engineering Design Diagram
800
250 100
303
663
833
994
2000
240 257
NetSure 801 CA7 Power Supply System (New Skelecton) User Manual
Appendix 4 Engineering Design Diagram 97
The engineering design diagrams PD380/400AFH-7YF and PD380/630AFH-7/YF varies according to practical
configuration.
305.7
672.2
769.4
926.7 920
156 2000
156
107.5
174.8
65 230
584.5
625.5
800
979.5 969
2000
217.2
547.5
800
NetSure 801 CA7 Power Supply System (New Skelecton) User Manual
98 Appendix 4 Engineering Design Diagram
99.5
648.5
694.0
1088.5
2000.0
40.0
40.0
153.5
800.0
NetSure 801 CA7 Power Supply System (New Skelecton) User Manual
Appendix 4 Engineering Design Diagram 99
93.1
437.0
2000.0
NetSure 801 CA7 Power Supply System (New Skelecton) User Manual
100 Appendix 4 Engineering Design Diagram
120.6
115.5
227.5 270.0
99.5
652.5 694.0
1235.0
2000.0
800.0
NetSure 801 CA7 Power Supply System (New Skelecton) User Manual
Appendix 4 Engineering Design Diagram 101
93.1
437.0
2000.0
NetSure 801 CA7 Power Supply System (New Skelecton) User Manual
102 Appendix 4 Engineering Design Diagram
115.5
120.6
227.5 270.0
99.5
652.5 694.0
1235.0
2000.0
800.0
92.1
437.0
2000.0
NetSure 801 CA7 Power Supply System (New Skelecton) User Manual
Appendix 4 Engineering Design Diagram 103
115.5
120.6
227.5 270.0
99.5
652.5
694.0
1235.0
2000.0
800.0
93.1
437.0
2000.0
NetSure 801 CA7 Power Supply System (New Skelecton) User Manual
104 Appendix 4 Engineering Design Diagram
The engineering design diagrams PD48/1600DF-7/YF and PD48/2500DF-7/YF varies according to practical
configuration.
Engineering design diagram for rectifier cabinet
600
600
67.5
67.5
30.5
30.5
121.7
121.7
2000
2000
NetSure 801 CA7 Power Supply System (New Skelecton) User Manual
Appendix 4 Engineering Design Diagram 105
309.8
309.8
1599.3
1599.3
NetSure 801 CA7 Power Supply System (New Skelecton) User Manual
106 Appendix 4 Engineering Design Diagram
600
600
67.9
67.9
30.5
30.5
121.7
121.7
2000
2000
NetSure 801 CA7 Power Supply System (New Skelecton) User Manual
Appendix 4 Engineering Design Diagram 107
309.8
309.8
1156.6
1156.6
NetSure 801 CA7 Power Supply System (New Skelecton) User Manual
108 Appendix 5 Spare Part List
NetSure 801 CA7 Power Supply System (New Skelecton) User Manual
Appendix 6 Wiring Diagram 109
49
Rear view PD3
SPD13DZ
PE 0V -48V 53
PE
JX4
W25
PE
+0V PE排
W26 52-49
-48V
Controller device rear view
52-46
52-4 W26
W26 52
50-J2-1
50-J2-3
50-J2-4
1 1
2 2
52-2
ACU+
51-4
51-3
51-7
51-2
51-1
1 1
W01(04116174) W12
2 2
PE W01(04116174) matching resistance
W28 PE
1 1
2 2
1 1
matching resistance W28 1 1
2 2
2 2 +0V -48
W06 W06
21 1-2
1 1
2-2
2 2
22 PE PE
1-4 W04
-48
+0V
W09 H2 3 4
2-4 H1 3 4
49 47 45 43 41 39 37 35 33 31 29 27 25 23 21 19 17 15 13 11 9 7 5 3 1
8 7 6
W09 8 7 6
- CAN+ CAN- PE
+ 2-6 - CAN+ CAN- PE
+ 1-6 50 48 46 44 42 40 38 36 34 32 30 28 26 24 22 20 18 16 14 12 10 8 6 4 2
RECT.2 RECT.1
9 1 9 1
W04
CAN+
50-J2-2
CAN-
485+
485-
51-5
W12
-48V
1 1 1 1
+0V
2 2 2 2
24
1 2 W06
PE
4-2 23
1 2
PE 3-2 W26
H4 3 4
4-4 H3 3 4
3-4 W04 Connect to the CAN bus
W09 -
8 7 6
4-6
W09 -
8 7 6
3-6 W26
+ +
W26
CA N + CA N - P E CAN+ CAN- PE
RECT.4 RECT.3
9 1 9 1
W04
Tie to the right of the cabinet
1 1 1 1
2 2 2 2
W06 W06
26
1 2
PE 6-2 25
1 2
PE 5-2
W09 H6 3 4
6-4 H5 3 4
5-4 W04
8 7 6
W09 8 7 6
- CAN+ CAN- PE
+ 6-6 - CAN+ CAN- PE
+ 5-6
RECT.6 RECT.5
9 1 9 1
W04
1 1 1 1
2 2 2 2
W06 W06
8-2 27 7-2
1 2 1 2
28 PE PE
H8 3 4
8-4 H7 3 4
7-4 W04
W09 8 7 6
W09 8 7 6
54
- CAN+ CAN- PE
+ 8-6 - CAN+ CAN- PE
+ 7-6
RECT.8 RECT.7 JX5
9 1 9 1
W04
PE
PE排
1 1 1 1
2 2 2 2
W06 W06
10-2 29
1 2 1 2
30 PE PE 9-2
H10 3 4
10-4 H9 3 4
9-4 W04
W09 8 7 6
W09 8 7 6
- CAN+ CAN- PE
+ 10-6 - CAN+ CAN- PE
+ 9-6
RECT.10 RECT.9
9 1 9 1
W04
W12 W12
1 1 1 1
2 2 2 2
1 PE
2
8 7 6
3 4
- CAN+ CAN- PE
+ B
C
9 1
-48V +0V
NetSure 801 CA7 Power Supply System (New Skelecton) User Manual
Appendix 6 Wiring Diagram 110
Rear view
41 47
JX1 PD1
A B C N
SPD12Z
1 3 5 7
Rear view
2 4 6 8 L1 L2 L3 N PE
IB2 extension board assembly
41-C
41-A
41-B
W02
41-N
47-L1 47-L2 47-L3 47-N
3-1 3-3 3-5 W02
W02
W01 8-1 8-3 8-5 44 51
HD1
Chassis
W02 JX3
W02 W02
43 W26
52-10
MA4C5U31 extension
52-1
52-3
52-7
52-9
FU1 board(optional) 50
41-C
41-A
41-B
W01 JKB
Three-phase bus bar J2 1 5
52-13 52-11 6 9 8
3 4
W26 52-15 52-12 W26
1 3 5 1 3 5 1 3 5 1 3 5 1 3 5 1 2
1 2 3 4 5
52-5
QF1 2 4 6 QF2 2 4 6
QF3 2 4 6
QF4 2 4 6
QF5 2 4 6
24-1
24-3
24-4
25-1
25-3
25-4
21-1
21-3
21-4
22-1
22-3
22-4
23-1
23-3
23-4
1 3 5 1 3 5 1 3 5 1 3 5 1 3 5
6 7 8 9 10
QF6 QF7 QF8 QF9 QF10 2
2 4 6 2 4 6 2 4 6 2 4 6 4 6
W04
27-1
27-3
27-4
29-1
29-3
29-4
W04
26-1
26-3
26-4
28-1
28-3
28-4
30-1
30-3
30-4
W04 W04 W04
49
Rear view PD3
SPD13DZ
PE 0V -48V
Rear view
PE W25
+0V 53
JX4
-48V
PE
W26
52-4
52-49
52-46
W12
PE bar Controller assembly
1 1
2 2
52-2 W26 W28 PE W01(04116174) matching resistance
W26
1 1
2 2
1 1
2 2 W01(04116174) matching resistance
W28 PE
+0V -48V 1 1
52
1 1 2 2
2 2
50-J2-1
50-J2-3
50-J2-4
W06 W06
+0V -48V 22
1 2
PE 2-2 21 1 2
PE 1-2
2-4 H1 1-4 W04
H2 ACU+
51-4
51-3
51-7
51-2
51-1
3 4 3 4
W09 -
8
CAN+ CAN- PE
7 6
+ 2-6
W09 -
8
CAN+ CAN- PE
7 6
+ 1-6
RECT.2 RECT.1
9 1 9 1
W04
1 1 1 1
2 2 2 2
W06 49 47 45 43 41 39 37 35 33 31 29 27 25 23 21 19 17 15 13 11 9 7 5 3 1
23 3-2
1 1
4-2
2 2
24 PE PE
50 48 46 44 42 40 38 36 34 32 30 28 26 24 22 20 18 16 14 12 10 8 6 4 2
H4 3 4
4-4 H3 3 4
3-4 W04
W09 8 7 6
4-6
W09 8 7 6
- CAN+ CAN- PE
+ - CAN+ CAN- PE
+ 3-6
RECT.4 RECT.3
9 1 9 1
CAN+
W04
CAN-
50-J2-2
485+
51-5
485-
1 1 1 1
2 2 2 2
W06 W06
26
1 2
PE 6-2 25
1 2
PE 5-2
5-4 W04
-48V
+0V
H6 3 4
6-4
W09 H5 3 4
W09 8 7 6 8 7 6
-
9
CAN+ CAN- PE
+
1
RECT.6
6-6 -
9
CAN+ CAN- PE
+
1
RECT.5
5-6 W26
W04
W26 Connect to the
1 1
2 2
1 1
2 2 W26 CAN bus of the
28
1 2 W06
PE 8-2 27 1 2 W06
PE 7-2 module
H8 3 4
8-4 H7 3 4
7-4 W04
W09 -
8
CAN+ CAN- PE
7 6
+ 8-6 W09 -
8
CAN+ CAN- PE
7 6
W04
1 1 1 1
2 2 2 2
W06 W06
10-2 29 9-2
1 2 1 2
30 PE PE
H10 3 4
10-4 H9 3 4
9-4 W04
W09
8 7 6
W09 8 7 6
- CAN+ CAN- PE
+ 9-6
RECT.10 RECT.9
9 1 9 1
W04
1 1 1 1
2 2 2 2
W06 W06
32
1 2
PE 12-2 31 1 2
PE 11-2
H12 3 4
12-4 W09 H11 3 4
11-4W04
W09 8 7 6 8 7 6
- CAN+ CAN- PE
+ 11-6
RECT.12 RECT.11
9 1 9 1
W04
1 1 1 1
2 2 2 2
W06 W06
34
1 2
PE 14-2 33 1 2
PE 13-2
W09 8 7 6
H14 3 4
14-4 W09 8 7 6
H13 3 4
13-4W04
- CAN+ CAN- PE
+ 13-6
RECT.14 RECT.13
9 1 9 1
W04
1 1 1 1
2 2 2 2
W06 W06
16-2 35 15-2
1 2 1 2
36 PE PE
54
H16 3 4
CAN+ CAN- PE
6
+ 16-6 -
8 7
CAN+ CAN- PE
6
+ 15-6
JX5
RECT.16 RECT.15
9 1 9 1
W04 PE
1 1
2 2
1 1
2 2 PEbar
W06 W06
38
1 2
PE 18-2 37 1 2
PE 17-2
H18 3 4
18-4 W09 H17 3 4
17-4W04
W09 8 7 6 8 7 6
- CAN+ CAN- PE
+ 17-6
RECT.18 RECT.17
9 1 9 1
1 1
W04 1 1
2 2 2 2
W06 1 W06
40
1 2
PE 20-2 39 2
PE 19-2
H20 3 4
20-4 W09 8 7 6
H19 3 4
19-4W04
W09
8 7 6
- CAN+ CAN- PE
+ 19-6
RECT.20 RECT.19
9 1 9 1
W04
+0V -48V +0V -48V
W12 W12
1 1 1 1
2 2 2 2
1 2 PE
8 7 6
3 4
- CAN+ CAN- PE
+ B
9 1 C
-48V +0V
NetSure 801 CA7 Power Supply System (New Skelecton) User Manual
Appendix 6 Wiring Diagram 112
41
JX1
Front view 42
JX2
A B C N A B C N
1 3 5 7 1 3 5 7 Front view
2 4 6 8 2 4 6 8
W02
W01
47-L1
2-1
47-L2
2-3
47-L3
2-5
W02 47-N W02 48-L1
11-1
48-L2
11-3
48-L3
11-5
W02 48-N
W02 IB2 extension board assembly
6-1 6-3 6-5 44 W01 14-1 14-3 14-5 46
HD1 18-1 18-3 18-5 HD2
W02 W02 51
W02 W02 JX3
43
FU1 45
FU2
W26
52-10
47
52-1
52-3
52-7
52-9
48 MA4C5U31 扩展板(选配)
PD1 50
PD2 JKB
SPD12Z SPD12Z
41-A
41-B
41-C
J2 1 5
(yellow) (green) (red) (blue) (Yellow-green) Three-phase bus bar (yellow) (green) (red) (blue) (Yellow-green)
52-11 6 9 8
52-13
L1 L2 L3 N PE W01 L1 L2 L3 N PE 3 4
W26 52-15
1 2 52-12 W26
52-5
1 3 5 1 3 5
1 2
QF1 QF2
42-A
41-A
42-B
42-C
41-B
41-C
41-N
42-N
2 4 6 2 4 6
W02 W02
21-1
21-3
21-4
22-1
22-3
22-4
Chassis W04 Chassis
41-A
41-B
41-C
42-A
42-B
42-C
Three-phase bus bar
W01 W01
1 3 5
11
1 3 5 1 3 5 1 3 5 1 3 5 1 3 5 1 3 5 1 3 5 1 3 5 QF11
3 4 5 6 7 8 9 10
QF3 2 4 6
QF4 2 4 6
QF5 2 4 6
QF6 2 4 6 QF7 QF8 QF9 QF10 2 4 6
2 4 6 2 4 6 2 4 6 2 4 6
24-1
24-3
24-4
25-1
25-3
25-4
W04
23-1
23-3
23-4
27-1
27-3
27-4
29-1
29-3
29-4
26-1
26-3
26-4
30-1
30-3
30-4
28-1
28-3
28-4
W04 W04
31-1
31-3
31-4
42-A
42-A
42-B
42-C
42-B
42-C
W01 Three-phase bus bar
1 3 5 1 3 5 1 3 5 1 3 5 1 3 5 1 3 5 1 3 5 1 3 5 1 3 5
12 13 14 15 16 17 18 19 20
QF12 2 4 6 QF13 2 4 6 QF14 2 4 6 QF15 2 4 6 QF16 QF17 2 4 6
QF18 2 4 6
QF19 2 4 6
QF20 2 4 6
2 4 6
W04 W04 W04 W04 W04 W04 W04 W04 W04
40-1
40-3
40-4
38-1
38-3
38-4
39-1
39-3
39-4
32-1
32-3
32-4
33-1
33-3
33-4
34-1
34-3
34-4
35-1
35-3
35-4
36-1
36-3
36-4
37-1
37-3
37-4
10-2
27 1
22
25 26 DL W6 W6 W6 W6
W7 HL1
40-L1
40-L2
40-L3
W14 28
40-N
K1 K2 33-J9-1 2
32-J10-1
PA1
32-J25-3 11
11-2 W13
7
Yellow 1 39
1 1 24 12
QF0
1
LCD W7 HL2 40-1 14
2 32-J25-2 2 27-2 33-J9-5 W18
8
W13 W12 2
W
2 JP2
N
V
3 32-J25-1 3 32-J10-2 32-J10-3
W13 W14 1
W5 W5 W5 W5
23
26-2
Black
W14 HD 41
32-J10-4 2 XT3 W22
40-PE
W12
32-J25-4
W18 W6W6 W6 W22
41-PE
39-1
39-3
39-5
39-14
31
2 32-J1-2 J3
PA2
J0 1 32-J1-1 W16 40 L1 L2 L3 PE
29-PE
1
2
6 32-J1-8 1 SPD
32-J1-7 1J2
32-J1-6 5
J1 32-J1-5 W16 W22
32-J1-4
1 32-J1-3 N
1
39-7
1J3
8 32-J2-8 5
32-J2-7 W15
A6V6FU1 W6
J2
1
JP2 JP1 1J1
1
5
Left front door
W1
Cabinet
W25
W23 32 Right front door Cabinet
W23
PA3
JP2 JP1 Left rear door
W26
Cabinet
J25 40-2
4 39-11
33-J5-1 8 25-2
W13 W15 W27
33-J5-2
1 25-3
W14 Right rear door Cabinet
33-J4-10 33-J4-6 8 8 31-J2-8
4 4 23-2 31-J2-7
33-J4-5 4 23-1
J15 -48V 33-J4-8 33-J4-4
0V W29 33-J4-3 26-3
1 1 33-J4-2 8 31-J1-6 1 27-1
31-J1-5 J14
33-J4-1
J2
1 31-J1-4
J9 W11 J8
31-J1-3
31-J1-2
J10 1 1
31-J1-1 W16
31-J0-2 1 4 J12 1 4 J13
1 31-J0-1
32-J12-2
32-J12-1
A2V6FX1
14-95
15-95
36-1
36-3
W8 W19 W20
35-3
35-1
J1
1-W2
1-W1
1-N2
1-N1
1-N
1-V2
1-V1
1-A
11-1
24-2
10-1
22-2
W21 W7 6 W10
38-4
J6 38-2 33
J8 3 1 J9 8 1
1
PA4
J5 2 1 10 1 J4
32-J8-7
32-J8-8
32-J8-4
32-J8-3
32-J9-4
32-J9-2
32-J8-6
32-J8-5
32-J8-2
32-J8-1
NetSure 801 CA7 Power Supply System (New Skelecton) User Manual
Appendix 6 Wiring Diagram 114
W19 W19 W7 W7
33-J9-3
33-J9-4
33-J9-1
33-J8-3
32-J12-4
32-J13-2
10-1
U1 V1 W1 N1
33-J8-1
2 3 2 3
35 36 1
1XK 2XK QS
1 1
32-J12-3
32-J13-1
33-J9-7
33-J9-8
33-J9-5
11-1
U2 V2 W2 N2
B11
LH1
B11
1-U1,33-J9-2
1-U2,33-J9-6
W2 W3 W4
39-2 39-4 39-6
W5 W5 W5
37-1
37-2
W2 W3 W4
U V W 1 1 1 3
Three-phase bus bar
2 4
33-J6-3
33-J6-4
B12 B14 B12 B14 2 2
14 15
22-1
24-1
QF11 QF12
B11
B11
W24
32-J13-3
32-J13-4
2 3 4 5 6 7 8 9 W10
QF1 QF2 QF3 QF4 QF5 QF6 QF7 QF8
30
W20 W20 XT2 N bar
29
XT1 PE bar
12 13 39-8
QF9 QF9 QF10 QF10 W5
41-PE
W22
14 QF11 QF12 15
QF11 QF12
27 10-2
1 22
26 DL W6 W6 W6 W6
25 HL1
W14 W7
40-L1
40-L2
40-L3
28
40-N
K1 K2 33-J9-1
32-J10-1
PA1 2
7
1 1 Yellow 1 39
24 12
W7 HL2 QF0
2 32-J25-2 2 27-2
1
LCD 33-J9-5 W18
40-1 14
8
W13 W12 2
W
2 JP2
U
V
N
3 32-J25-1 3 32-J10-2 32-J10-3
W13 W14 Black 1
23 W5 W5 W5 W5
26-2
W14 HD 41
32-J10-4 2 XT3 W22
40-PE
W12
W18 W6 W6 W6 W22
32-J25-4
41-PE
39-1
39-3
39-5
39-14
31
2 32-J1-2 J3
PA2
J0 1 32-J1-1 W16 40
29-PE
L1 L2 L3 PE
2
6 32-J1-8 1 SPD
32-J1-7 1J2
32-J1-6 5
J1 32-J1-5 W16 W22
32-J1-4
1 32-J1-3 N
1
39-7
1J3
8 32-J2-8 5
32-J2-7 W15
J2
A6V6FU1 W6
1
JP2 JP1 1J1
5
1
Left front door
W1
Cabinet
W23 32 W25
W23 Right front door Cabinet
PA3
JP2 JP1
40-2 Left rear door
W26
J25 4 39-11 Cabinet
33-J5-1 8 25-2
W13 W15
33-J5-2
1 25-3 W14 8 31-J2-8
4 4
33-J4-10 33-J4-6 23-2
8
31-J2-7 W27
33-J4-5 4 23-1
Right rear door Cabinet
J15 -48V 33-J4-8 33-J4-4
0V W29 33-J4-3 26-3
1 1 33-J4-2 8 31-J1-6 1 27-1
31-J1-5
J14
33-J4-1
J2
1 31-J1-4
J9 W11 J8
31-J1-3
31-J1-2
J10 1 1
31-J1-1 W16
31-J0-2 1 4 J12 1 4 J13
1 31-J0-1
32-J12-2
32-J12-1
A2V6FX1 J1 16-95
17-95
36-1
36-3
W8 W19 W20
35-3
35-1
1-W2
1-W1
1-N
1-A
1-V2
1-N2
1-V1
1-N1
11-1
24-2
10-1
22-2
W21 W7 6 W10
38-4
3 1 8 1 J6 38-2 33
J8 J9
1 PA4
J5 2 1 10 1 J4
32-J8-7
32-J8-8
32-J8-4
32-J8-3
32-J9-4
32-J9-2
32-J8-6
32-J8-5
32-J8-2
32-J8-1
NetSure 801 CA7 Power Supply System (New Skelecton) User Manual
Appendix 6 Wiring Diagram 116
W19 W19 W7 W7
U1 V1 W1 N1
33-J9-3
33-J9-4
33-J9-1
33-J8-3
10-1
32-J12-4
32-J13-2
33-J8-1
2 3 2 3
35 36 1
1XK 2XK QS
32-J12-3
32-J13-1
13-96
12-96
33-J9-7
33-J9-8
33-J9-5
11-1
U2 V2 W2 N2
B12 B14 B12 B14
12 13 W19 W19 W7 U V W7 W
QF9 QF10 37 38-1 1 N
10 11 38
B11
B11
LH1 FU1 FU2 XT3
38-3 2
3-1 3-2 3-3 W7 W17
W2 W3 W4
39-2 39-4 39-6
W5 W5 W5
1-U1,33-J9-2
1-U2,33-J9-6
37-1
37-2
W2W3 W4
1 1 1 3
U V W
Three-polarity busbar
2 4
B12 B14 B12 B14
14 15
33-J6-3
33-J6-4
2 2
QF11 QF12
B11
B11
22-1
24-1
W24 W10
2 3 4 5 6 7 8 9
QF1 QF2 QF3 QF4 QF5 QF6 QF7 QF8
30
XT2 N bar
29
B12 B14 B14 B14 XT1 39-8
PE bar W5
17 B14 12 13
B11
B14
B14
14 QF11 QF12 15
W20 B14 QF11 QF12
17 QF13 QF14
QF13
43-X4-RS485+
43-X4-RS485-
W40 W13
RS485 cable W40 LCD
66/70-B11
41-J39-2
W13 W14 2 32
45-11
1 31
23-1
23-2
22
NC NC RTS NC 2 32
HL1
CAN-HCAN-L 31
RS485A RS485B RS485A RS485B CAN-H CAN-L 1 HGND 5V
10-2
OGND DTR TXD RXD DCD
DI1+ DI1- DI2+ DI2- DI3+ DI3- DI4+ DI4- 12V+ LIGHT
J40 1
J22 J21 J23 J20 J28 LCD J37
J26
RS485-2 CAN-2 J19 RS485-1 CAN-1 Reserved DI Alarm GND AI1 12V- 12V+ GND AI2 12V- 12V+
to R1 board W24 Left front door W1 Cabinet
J1 J2 11-2
MODEM/RS232 terminal J43 2
Busbar sampling terminal
BI1+
BI1-
42-J4-3
42-J4-6
42-J4-2
42-J4-1
W36
BI2-
52-2
BI2+
2
BI3-
BI3+
GND AI7 12V- 12V+ GND AI8 12V- 12V+
J7 J8
23 Right rear door W27 Cabinet
41 Shunt sampling port
HD
HDU1U11 PD2 J44
BI4+
BI4-
Load alarm contact J9
GND AI9 12V- 12V+ GND AI10 12V- 12V+
J10 41-J28-1
1
NC
NC
detection terminal
LI1-
W14
LI1+
J34
AC signal sampling terminal
FA15 FA14 FA13 FA12FA11 FA10FA9 FA8 FA7 FA6 FA5 FA4 FA3 FA2 FA1
41-J28-2
65/69-B11
39-11
43-X4-DO3
43-X4-DO3
43-X4-DO2
43-X4-DO2
-48V
43-X3-LLP-COM
43-X3-LLP-NO
0V
43-X4-ALM-NO
43-X4-ALM-COM
48V parallel cable
W13 W13
W37
40-PE
46-PE
Note: install W7 to the controller according to cable mark.
W37
AI1+ Left Right
41-J5-1 41-J27-7
U1A(L)
37-S1 AI2+
PD3
GND
J5 J4 GND
37-S2 AI2-
44-X1-U1B
W10 A1V8FA1 IV1
41-J5-3 W36
U1B
X3
AI3+
IV2
44-X1-U1C X1 40 39 45 46
IV3
11-1 1QF2
U1C(N)
2SPD
COM
AI3-
1SPD 1QF1
J3
DRV1
45-7
39-7
46-2
44-W2
51-1 DRV3
44-U2
44-N2
44-V2
U2A(L)
45-14
46-1
40-1
44-W1
39-14
44-U1
44-N1
44-V1
40-2
N N
DRV4
44-X1-U2B
DRV5
14
U2B
7
14
1
1
2
1
2
44-X1-U2C X2
DI1+
52-1
C2000 front view
U2C(N)
DI1-
11
PE
8
L1 L2 L3
11
W7
8
DI2+
43 L1 L2 L3 PE
46-L1
46-L2
46-L3
46-N
40-L1
40-L2
40-L3
41-J26-1
40-N
DI2-
LCD
41-J29-1
ATS-C
C2000 controller
45-1
45-3
45-5
39-1
39-3
39-5
47-PE
34-PE
DI3+
W6 W6 W6 W6 W6 W6 W6 W6
DI3-
X4 W13 W6
Top
W6 W13
DI4+
DI7 DI7 DI6 DI6 DI5 DI5 FIRE- FIRE+ PGND DGND RS485- RS485+GEN-NOGEN-COMGEN-NC DO3 DO3 D02 DO2 DO1 DO1 ALM-COM ALM-NO
DI4-
41-J27-3
41-J27-2
41-J27-1
41-J27-5
41-J27-6
NetSure 801 CA7 Power Supply System (New Skelecton) User Manual
Appendix 6 Wiring Diagram 118
W07
User power supply-1 User power supply-2
43-X1-U1C
43-X1-U2C
43-X1-U1A
43-X1-U1B
43-X1-U2A
43-X1-U2B
Top
U1 V1 W1 N1 U1A(L) U1B(L) U1C(N) U2A(L) U2B(L) U2C(N) X1 U2 V2 W2 N2
MCB alarm terminal connection( AC output 2~6) W39(ATS standard cable)
W5 W5 W5 W5 W5 W5 W5 W5
Right
39-2
39-4
39-6
39-8
45-2
45-4
45-6
45-8
DRV5
DRV4
DRV3
DRV2
DRV1
COM
DI4-
DI4+
DI3-
DI3+
DI2-
DI2+
DI1-
DI1+
44 X2
ATSE
B12 B14 B12 B14
61 62
QF9 QF10
B11 B11
ATSE
U V W N
B12 B14 B12 B14
AC ATS 42-J5-5 S1
63 64 37
QF11 QF12 LH1
B11 B11 42-J5-4
S2
10 11 51 52
FU1 FU2 FU3 FU4
W100 W100 MCB three-phase busbar
65
B12 B14
66
B12 B14 U V W U V W ( AC output 1) W7 W7
QF13 QF14
B11 B11
43-X1-U1C
43-X1-U2C
43-X1-U1A
43-X1-U2A
QF1 QF3 QF4 QF5 QF2 QF6 QF7 QF8 1 1 1 1
22-1
22-2
24-1
24-2
QF9 QF10
W24
B12 B14 B12 B14
69 70
71 72
QF17 QF18
B11 B11 QF19 QF20
41-J26-3
W13 W13
29
GND PE bar
N bar
30
NBUS
W32
MCB quantity ≤3
W33
Technical requirement:
W34 1. Under this circumstance, no need to use busbar,
just use cable for connection directly as shown in the left figure.
U V W
2. Upon wiring, follow the sequence of U--1, V--2, W--3.
1 2 3
MCB quantity > 3
Technical requirement:
W32
W33 1.Under this circumstance, busbar should be used under the MCB,
W34 choose the busbar pole according to actual configured MCBs.
2. Upon wiring, follow the sequence of U--1, V--2, W--3.
U V W
3.If there are more MCB poles and longer busbars, the cable
should be connected to the position near the middle of the busbar.
4. If the entry cable is more than one group, make sure that the
output MCB quantity of each entry cable is equal.
1 2 3 1 2 3 1 2 3 1 2 3 1 2 3 1 2 3 1 2 3 1 2 3
NetSure 801 CA7 Power Supply System (New Skelecton) User Manual
Appendix 6 Wiring Diagram 120
4 W11
1 2 Left front door HA +0V 38-2
48V(+)
1HL 红 2HL 绿
8-J10-3 +0V Yellow Black
1 1
1 2
W09 W08 W09 8-J10-1 6-2
8-J10-4 -48V 5 6 -48V
2 2
K1
W09 K2 8-J15-3 8-J15-4
8-J15-2 W08 8-J11-2 W08 8-J11-4
Fault alarm Buzzer ON
W08 2-2 8-J7-5 W08 8-J7-4 2
1 1 1 1 2 10 1 1 12
W10 9 11
8-J25-1 4-2 2BFU RB2
2 2 1BFU RB1 2 2
W13 2 2
8-J7-1 W13
8-J25-2 8-J10-2 8-J7-2 8-J11-3 1
3 3 8-J11-1 W08 1
W09 W08 W08
AC cabinet 48V power AC cabinet 48V power
Fault silencer Buzzer OFF
LCD
3 13 2-1 8-J15-1
JYG-12864J9G(R)-YS6L2-VB
TA
W08 W08
PD1
8-J21-1
8-J21-2
1 +0V
W08 2
8-J21-3 14 15 16 17 18 19 20 21
3
8-J21-4 FU1 FU2 FU3 FU4 FU5 FU6 FU7 FU8
4 W04
38 8-J3
-48 J3
48V(-)
8-J1-2
01
08
06
07
02
03
04
05
6
5
8-J1-8
+12
8-J1-7 signal lamp
RJ45
J1 43
8-J1-6 signal lamp
8-J1-5
-12
W01 1 1 1 1 1 1 1 1
2 8-J1-4
GND
SPD13DZ 2
8-J1-3 +12
1 38-1 2 2 2 2 2 2 2
8 8-J2-8 W11
7
6
8-J2-7
8-J2-6
Emergency lighting control
7
1 8
RS485 1J2
BLVD PD2
PE 0V -48V J2 54
3
8-J2-5
8-J2-4
8-J2-3
W02
Battery 2 LVD 22 23 24 25 26 27 28 29
2 8-J2-2
8-J2-1 Battery 1 LVD FU9 FU10 FU11 FU12 FU13 FU14 FU7 FU8
1
A6V6FU11 W05
6 Cell 4 current BI4-
5 Cell 4 current BI4+
RS485 8-J4
-48V
3 current BI3+
PE
2 Battery 4 voltage-
1 Battery 3 voltage-
16
09
10
11
12
14
13
J11 J12J13 New temperature sensor input
15
3 PGND 1
J4 2 Single output COM
1 1 1 1 1
1 +12 3
1 1
W11 3 PGND
J5 2 Single output
New temperature sensor input
18
20
22
23
24
21
19
17
PD3
JP2 JP1
W06
8 10-1 J25 4 37-2 29-1 21-1
8-J5 30 31 32 33 34 35 36 37
4 9-1
8 8
36-2
8
28-1
8
20-1 FU17 FU18 FU19 FU20 FU21 FU22 FU23 FU24
-48V 5-3 35-2 27-1 19-1
11-2
12-2 1 +0V 1 5-2 W10 34-2 26-1 18-1
33-2 25-1 17-1 Door W12 Cabinet
32-2 24-1 16-1
11-1 J15 W08 10-1 31-2 23-1 15-1
1 12-1 4 10-2 1 1 30-2 1 22-1 1 14-1 Earthing wire (four)
9-1
J7 9-2 J6 J5 W06 J4
W05 J3 W04
W08 1
J11
W08
13-4 8 7-J2-8
4 13-3 8 7-J1-6 4 1-2 7-J2-7
7-J1-5 1-1 7-J2-6
13-2 W08 7-J1-4 7-J2-5
1 13-1 7-J1-3
6-3 W09
The total load current 7-J1-2 W01 1 4-1 7-J2-4
7-J2-3
J21 Hall signals 7-J1-1 7-J2-2
7-J0-2 J10
7-J0-1 1 7-J2-1
1
A2V6FX1 J1
J2
W02
8-J1-2 -48 J3
J0 21 8-J1-1 0 W01 New LCD connecter
6
5
8-J1-8
+12
8-J1-7 signal lamp
RJ45
J1 43
8-J1-6 signal lamp
8-J1-5
-12
W01
2 8-J1-4
GND
8-J1-3 +12
1
8 8-J2-8
7
6
8-J2-7
8-J2-6
Emergency lighting control
7
1 8
RS485 1J2
BLVD PD2
J2 54
3
8-J2-5
8-J2-4
8-J2-3
W02
Battery 2 LVD
2 8-J2-2
1 8-J2-1 Battery 1 LVD
A6V6FU11
6 Cell 4 current BI4-
5 Cell 4 current BI4+
Cell 3 current BI3-
J7 43 Cell 3 current BI3+
RS485 1J3
2 Battery 4 voltage-
1 Battery 3 voltage-
J11 J12J13 New temperature sensor input
3 PGND 1
J4 2 Single output 3
COM
1 +12 New temperature sensor input
NetSure 801 CA7 Power Supply System (New Skelecton) User Manual
Appendix 6 Wiring Diagram 122
+0V W11
1 2 4 38-2 48V(+)
1HL 红 2HL 绿 Left front door HA
8-J10-3 +0V
1 1
黄 黑
W09 W08 1 2
8-J10-4 2 -48V W09 8-J10-1
6-2
2
5
W09 6 -48V 8-J15-3
W08 8-J11-2
8-J15-4
K1 K2 W08 8-J11-4 8-J7-4
8-J7-5 W08 2
Fault alarm Buzzer open 2
W08 8-J15-2 9 1 1 11 10 1 1 12
W10 8-J25-1
1 1
W08 2-2 1BFU RB1 2BFU 2 2
RB2
4-2 2 2
8-J7-1 1
W13
2 2 W13 8-J11-1 8-J7-2 1 8-J11-3
8-J25-2 8-J10-2 W08 W08 W08
3 3
LCD W09 AC cabinet 48V power
AC cabinet 48V power
Failure silencers Buzzer close
JYG-12864J9G(R)-YS6L2-VB 3
13
PD1
TA
W082-1 8-J15-1
W08
8-J21-1 1
8-J21-2 2 14 15 16 17 18 19 20 21 +0V
W08 8-J21-3 3 FU8
W04 FU1 FU2 FU3 FU4 FU5 FU6 FU7
8-J21-4 4
38 8-J1-2 -48 J3
W01
01
06
07
08
J0 21 New LCD connecter
48V(-)
PD4
02
03
04
05
8-J1-1 0
6
5
8-J1-8
+12
8-J1-7 signal lamp
RJ45
J1 43
8-J1-6 signal lamp
8-J1-5
-12
W01 1 1 1 1 1 1 1 1
2 8-J1-4
GND
SPD13DZ
8-J1-3 +12
1
2 2 2 2 2 2 2 2
8 8-J2-8 38-1
7
6
8-J2-7
8-J2-6
Emergency lighting control
7
1 8
RS485 1J2
W11
BLVD PD2
PE 0V -48V J2 54
3
8-J2-5
8-J2-4
8-J2-3
W02
Battery 2 LVD 1 1 1 1 1 1 1 1 1 1 1 1 1 1
2 8-J2-2
1 8-J2-1 Battery 1 LVD
A6V6FU11 2 2 2 2 2 2 2 2 2 2 2 2 2 2
6 Cell 4 current BI4-
-48V
20
21
22
10
11
12
14
15
16
17
18
19
13
09
2 Battery 4 voltage-
PE
1 Battery 3 voltage-
3 PGND
J11 J12J13
1
New temperature sensor input W05
J4 2 Single output
1 +12 3
COM
PE 8
W03 W03 PD3
JP2 JP1
+0V W11
1 2 4 38-2 48V(+)
1HL 红 2HL 绿 Left front door HA
8-J10-3 +0V
1 1
W09 黄 黑
W08 W09 8-J10-1 1 2
8-J10-4 2 -48V 6-2
2
5
W09 6 -48V 8-J15-3
W08 8-J11-2
8-J15-4
K1 K2 W08 8-J11-4 8-J7-4
8-J7-5 W08 2
Fault alarm Buzzer open 2
W08 8-J15-2 9 1 1 11 10 1 1 12
RB2
W10 8-J25-1
1 1
W08 2-2 1BFU RB1 2BFU 2 2
4-2 2 2
8-J7-1 1
W13
2 2 W13 8-J11-1 8-J7-2 1 8-J11-3
8-J25-2 8-J10-2 W08 W08 W08
3 3
LCD W09 AC cabinet 48V power
AC cabinet 48V power
Failure silencers Buzzer close
JYG-12864J9G(R)-YS6L2-VB 3
PD1 13 2-1 8-J15-1
TA
W08 W08
8-J21-1
8-J21-2
1 +0V
W08 2
8-J21-3 14 15 16 17 18 19 20 21
3
8-J21-4 FU1 FU2 FU3 FU4 FU5 FU6 FU7 FU8
4 W04
38 J3
J0 21
8-J1-2 -48
W01 8-J3
PD4 8-J1-1 0 New LCD connecter
48V(-)
6
5
8-J1-8
+12
8-J1-7 signal lamp
RJ45
01
08
06
07
W01
02
03
04
05
J1 43
8-J1-6 signal lamp
8-J1-5
-12
2 8-J1-4
GND 1 1 1 1 1 1 1 1
SPD13DZ
8-J1-3 +12
1
8 8-J2-8
38-1 2 2 2 2 2 2 2 2
7
6
8-J2-7
8-J2-6
Emergency lighting control
7
1 8
RS485 1J2 W11
BLVD
PE 0V -48V J2 54
3
8-J2-5
8-J2-4
8-J2-3
W02
Battery 2 LVD
PD2
2 8-J2-2
1 8-J2-1 Battery 1 LVD 22 23 24 25 26 27 28 29
A6V6FU11 FU9 FU10 FU11 FU12 FU13 FU14 FU7 FU8
6 Cell 4 current BI4- W05
-48V
1 Battery 3 voltage-
J11 J12J13 New temperature sensor input
3 PGND 1
16
09
J4 2 Single output COM
10
11
12
14
13
15
3
1 +12 New temperature sensor input
W11 3 PGND
J5 2 Single output Old LCD connecter 1J1 1 1 1 1 1 1 1
1
1 +12
3 PGND 2 2 2 2 2 2 2
J6 2 Single output 2
1 +12
Connect to the signal transfer board Connect to the signal transfer board
JP2 JP1
1 1 1 1 1 1 1 1
PE 8 2 2 2 2 2 2 2 2
W03 W03 PD3
18
20
22
23
24
21
19
17
JP2 JP1
W06
8 10-1 J25 4 37-2 29-1 21-1
4 9-1
8 8 8 8 8-J5 30 31 32 33 34 35 36 37
36-2 28-1 20-1
-48V 5-3 35-2 27-1 19-1 FU17 FU18 FU19 FU20 FU21 FU22 FU23 FU24
11-2 5-2 W10 34-2 26-1 18-1
12-2 1 +0V 1 33-2 25-1 17-1
32-2 24-1 16-1
11-1 J15 W08 10-1 31-2 23-1 15-1
12-1 4 10-2 30-2 22-1 14-1
1 1 1 1 1
9-1
J7 9-2 J6 J5 W06 J4
W05 J3 W04
W08 1
J11
W08 Door W12 Cabinet
8 7-J2-8
4 13-4 8 7-J1-6 4 1-2 7-J2-7
13-3 7-J1-5
7-J1-4
1-1 7-J2-6 Earthing wire (four)
13-2
13-1
W08 7-J1-3
6-3 W09 7-J2-5
7-J2-4
1 7-J1-2 W01 1 4-1
7-J2-3
The total load current 7-J1-1
J21 7-J2-2
Hall signals 7-J0-2 J10
7-J0-1 1 7-J2-1
1
A2V6FX1 J1
J2
W02
NetSure 801 CA7 Power Supply System (New Skelecton) User Manual