Control Valve Calibration (ABB Positioner)
Control Valve Calibration (ABB Positioner)
Open the drain valves before and after the control valve.
Open the front cover of the positioner to access the positioner keys.
While Auto adjust is running, the control loop symbol flashes in the display,
and the current state of Auto adjust is indicated with the messages listed
below.
Once Auto adjust has finished running without encountering any errors,
the device displays the message "RUN" in the bottom line and a code
number in the top line, indicating the step that is currently being executed:
10 Air is completely evacuated from actuator (OUT1). The fully
evacuated position is saved.
20 Air is completely ventilated from actuator (OUT1). The fully
ventilated position is saved.
30 Stroke time determination is prepared.
31 Actuator travels from 100 % to 0 %, stroke time is measured and
saved.
32 Actuator travels from 0 % to 100 %, stroke time is measured and
saved.
40 – 49 Tolerance band is determined and saved (minimum value). PD
parameters for fast control < tolerance band is determined and
saved.
50 - 59 PID parameters for precise control of control deviation <
tolerance band is determined and saved.
200 Auto adjust is complete.
Then give the positioner remote command of 0%, 25%, 50%, 75% and
100% from DCS. Verify its actual position & feedback position on DCS.
Then close the front cover of the positioner.
Ask the operator to close the drain valves and take the control valve back
in service.
Observe the control valve response in auto mode for 2, 3 minutes.