Professional Documents
Culture Documents
Datasheet Minipack S48 WEB - SNMP Indoor Cabinet
Datasheet Minipack S48 WEB - SNMP Indoor Cabinet
Minipack 4800
S48 WEB/SNMP Power System SHEET
FUNCTION
The S48 WEB/SNMP power supply cabinet has been specifically designed to meet the
demand for a very compact power solutions.
The S48 Power Supply cabinet is controlled by the Smartpack Monitoring and Control Unit
with built-in Ethernet & WEB/SNMP function. It is pre-equipped with 2 x battery shelves & 2
x Minipack 800 rectifier modules and can accommodate up to 6 (4,8kW). The maximum
battery capacity is 2 x 190Ah/48VDC.
DESCRIPTION
Cabinet:
• 1200x600x600 indoor cabinet
• Capacity up to 4,8kW max; installed 2 x
800W rectifiers and room for up to 6
• 2 x battery shelves
• Flexible AC connection: 1ph 230VAC or
3P+N 400VAC
• Terminal blocks for easy alarm, AC input &
DC outputs connections
DC Distribution
• 6 x Load MCBs:
2x30A +4x25A
• Low Voltage Battery Disconnect (150A)
• 2 x 100A Battery breakers
Supervision:
• Smartpack WEB/SNMP (Monitoring and Control Unit)
• USB interface for PC connection
• Temperature sensor
Internal cables
• 2 set of Battery cables
HUMIDITY
Storage: 0–99 % RH non-condensing (recommended: 10-30 % RH)
OPERATING ALTITUDE
Up to 4000m, for altitudes between 2500m and 4000m, output power may derate at lower
ambient temperatures.
RECTIFIER COOLING
Rectifiers have a speed controlled fan (front to back airflow).
To achieve low acoustic noise and maintain rectifier lifetime, the fan regulate the speed according to
the incoming air temperature and DC power consumption. This will give the lowest possible fan
speed and lowest acoustic noise under normal load and temperature conditions.
MECHANICAL CHARACTERISTICS
Input voltage
(input voltage window) 1 phase or 3 phases + Neutral 400 VAC; 230VAC between phase & neutral (150 –
519VAC), 208VAC 2 phases
Frequency 45 to 66Hz
Maximum number of
MINIPACK rectifier 6
modules
Maximum Input
Current for 1 4.9 Arms maximum at nominal input and full load
MINIPACK rectifier
module
Maximum Input Power
for 1 MINIPACK 889 Watts max at 185 VAC (Single phase)
rectifier module
Maximum Input
Current for the Power The total AC current for 6 rectifiers is 29,4 A .
System
1 pH 230VAC
Maximum Input
Current for the Power Maximum number of rectifiers installed is up to 6, i.e 2 in each phase.
System with
Maximum phase current is 9,8A
3 pH 400VAC + N
PROTECTIONS
Note: items listed below are valid for Minipack rectifier
Input protection Output protection
• Soft start • Blocking diode
• Surge protection • High voltage shutdown
• Internal fuses (L & N) • Temp derating/shutdown
• Automatic shut down > 300 VAC , and • Non destructive short circuit
shutdown < 85VAC operation
Ordering information
SUPPLIER NAME
ELTEK VALERE