DATA

Minipack 4800
S48 WEB/SNMP Power System SHEET

FUNCTION

The S48 WEB/SNMP power supply cabinet has been specifically designed to meet the
demand for a very compact power solutions.

The S48 Power Supply cabinet is controlled by the Smartpack Monitoring and Control Unit
with built-in Ethernet & WEB/SNMP function. It is pre-equipped with 2 x battery shelves & 2
x Minipack 800 rectifier modules and can accommodate up to 6 (4,8kW). The maximum
battery capacity is 2 x 190Ah/48VDC.

DESCRIPTION

Cabinet:
• 1200x600x600 indoor cabinet
• Capacity up to 4,8kW max; installed 2 x
800W rectifiers and room for up to 6
• 2 x battery shelves
• Flexible AC connection: 1ph 230VAC or
3P+N 400VAC
• Terminal blocks for easy alarm, AC input &
DC outputs connections

DC Distribution
• 6 x Load MCBs:
 2x30A +4x25A
• Low Voltage Battery Disconnect (150A)
• 2 x 100A Battery breakers

Supervision:
• Smartpack WEB/SNMP (Monitoring and Control Unit)
• USB interface for PC connection
• Temperature sensor

Internal cables
• 2 set of Battery cables

COMPLIANT TO INTERNATIONAL STANDARDS

Electrical safety: IEC 60950-1


EMC: EN 300 386 V.1.3.2 (telecommunication network), EN 61000-6-3
(emission, light industry), EN 61000-6-2 (immunity, industry)

Environment: RoHS compliant

MIFR 01 13.10..2009 Minipack S48 WEB/SNMP indoor


power system
Eltek Valere CM0625.001 Alcatel-Lucent TBD 1/5
ENVIRONMENTAL CHARACTERISTICS
TEMPERATURE RANGE
Operation: - 40°C to + 55°C (-40°F to 131°F) – No temperature de-rating.
Max. output power (800W per rectifier).

+ 55°C to + 75°C (131°F to 167°F) - Output power temperature de-rated


and rectifier will finally stop in auto-protect mode

Storage: - 40°C to + 85°C (-40°F to 185°F)

HUMIDITY
Storage: 0–99 % RH non-condensing (recommended: 10-30 % RH)

Operation: 5–95 % RH non-condensing

OPERATING ALTITUDE
Up to 4000m, for altitudes between 2500m and 4000m, output power may derate at lower
ambient temperatures.

RECTIFIER COOLING
Rectifiers have a speed controlled fan (front to back airflow).
To achieve low acoustic noise and maintain rectifier lifetime, the fan regulate the speed according to
the incoming air temperature and DC power consumption. This will give the lowest possible fan
speed and lowest acoustic noise under normal load and temperature conditions.

The fan speed may therefore vary with system configuration.

A rectifier with a defect fan (no airflow) will shutdown immediately.

MECHANICAL CHARACTERISTICS

Net dimensions and net weights:


Net dimensions Net Weight kg

hxdxw: 1200x600x600 mm Approx 70 kg

MIFR 01 13.10..2009 Minipack S48 WEB/SNMP indoor


power system
Eltek Valere CM0625.001 Alcatel-Lucent TBD 2/5
ELECTRICAL CHARACTERISTICS

Input voltage
(input voltage window) 1 phase or 3 phases + Neutral 400 VAC; 230VAC between phase & neutral (150 –
519VAC), 208VAC 2 phases
Frequency 45 to 66Hz
Maximum number of
MINIPACK rectifier 6
modules
Maximum Input
Current for 1 4.9 Arms maximum at nominal input and full load
MINIPACK rectifier
module
Maximum Input Power
for 1 MINIPACK 889 Watts max at 185 VAC (Single phase)
rectifier module
Maximum Input
Current for the Power The total AC current for 6 rectifiers is 29,4 A .
System
1 pH 230VAC
Maximum Input
Current for the Power Maximum number of rectifiers installed is up to 6, i.e 2 in each phase.
System with
Maximum phase current is 9,8A
3 pH 400VAC + N

Maximum output 48V 4 800 Watts from 185VAC


power 100 Amps at 48VDC and nominal AC input (185-275VAC)
The output power (W) is constant from 48VDC to 56VDC

PROTECTIONS
Note: items listed below are valid for Minipack rectifier
Input protection Output protection
• Soft start • Blocking diode
• Surge protection • High voltage shutdown
• Internal fuses (L & N) • Temp derating/shutdown
• Automatic shut down > 300 VAC , and • Non destructive short circuit
shutdown < 85VAC operation

MIFR 01 13.10..2009 Minipack S48 WEB/SNMP indoor


power system
Eltek Valere CM0625.001 Alcatel-Lucent TBD 3/5
INDICATORS AND ALARMS

Visual indications Green LED indicating that the system is ON/OFF


Red LED indicating an alarm situation (major alarm)
Yellow LED indicating an abnormal situation (minor alarm)
LCD – system status and interrogation via keypads
Digital inputs 6 (Can be used to monitor external equipment)
Alarm output relays 6
Available alarms which can be • Mains failure
configured to alarm relays • Digital inputs (programmable names)
• Load disconnect (voltage or time)
• Load fuse
• Load current
• High battery voltage
• Low battery voltage
• High battery temperature
• Low battery temperature
• Battery capacity
• Battery disconnect
• Battery fuse
• Symmetry failure
• Battery quality indication
• Battery discharge current
• Rectifier failure
• Critical rectifier failure(>1, programmable)
• Rectifier capacity w/ programmable level
• Rectifier current limit
• Rectifier over voltage protection
• Rectifier current
Ethernet / WEB / SNMP Remote monitoring and control via Ethernet,
web or SNMP using RJ45 connector

Ordering information

DESIGNATION SUPPLIER’S CODE ALCATEL’S CODE


Minipack S48 WEB/SNMP indoor power
CM0625.001 TBD
supply
Minipack 800W rectifier 241117.110/130SD 1AF15979AAAA

SUPPLIER NAME
ELTEK VALERE

MIFR 01 13.10..2009 Minipack S48 WEB/SNMP indoor


power system
Eltek Valere CM0625.001 Alcatel-Lucent TBD 4/5
GENERAL ARRANGEMENT

Specifications within this document are subject to change without notice

End of document

MIFR 01 13.10..2009 Minipack S48 WEB/SNMP indoor


power system
Eltek Valere CM0625.001 Alcatel-Lucent TBD 5/5

You might also like