JKT02-JO-SHD-STR-2422 - Concrete Structure Equipment - Detail Plan Conc. Structure Genset Trench Type D-1A Rev B

You might also like

Download as pdf or txt
Download as pdf or txt
You are on page 1of 3

A1 A B C D E F G H I J K L M N O P Q R S T Review Status: Revised and Resubmit

Date: 31 August
SHOP 2022
DRAWING
1
The plinths are not covered as part of
this review as the GC will need to
update the plinth layout and
dimensions to suit JKT02the calculations of
2 the hold-down anchors.
Datacenter Indonesia
Karawang International Industrial City (KIIC)
West Java, Indonesia

GC to provide details of trench Engineer

ladder, cover, sump pit with weep


holes including sealing of plinth 152 Beach Rd, #16-00 Gateway East, Singapore 189721

openings.
3 Note :
Consultant Comment

AUR:
REFER TO GROUND REINFORCEMENT TOP PLAN GENSET
Status

Approved Revise and resubmit

TRENCH TYPE D-1A DRAWING ON THE NEXT PAGE


Approved with comment Rejected

4 Signature : Date :

Security

111 SomeSet Road, Unit #07-10 TripleOne SomeSet


Singapore 238164
Note :
Consultant Comment

Status

Approved Revise and resubmit

Approved with comment Rejected

N
Signature : Date :

6 Architect

143 Cecil Street, GB Building, #12-00, Singapore 069542


Note :
Consultant Comment

Status

Approved Revise and resubmit

Approved with comment Rejected

Signature : Date :

Construction Supervision

International Financial Centre, Tower 2 Lt. 26,


Jl. Jenderal Sudirman, Kuningan, Kuningan Tim., Kecamatan
Setiabudi, Jakarta, Daerah Khusus Ibukota Jakarta 12920
Note :
Consultant Comment

Status

Approved Revise and resubmit

Approved with comment Rejected

Signature : Date :

General Contractor

10

AUR:
REFER TO FOUDATION T
Jl. Pancoran Timur II no 3
Pancoran, Jakarta 12780, Indonesia
(021) 7982223 , (021) 7944142

GENSET TRENCH TYPE D


Contractor Design Team

DRAWING ON THE NEXT


Drawn By
SPN
Checked By
AA
11

Revisions
No. Date Description

A 25 JUNE 2022 FOR APPROVAL

B 15 AUGUST 2022 FOR APPROVAL

12

Reference Drawing
No. Dwg. No.

1 JKT02-S-D-120-0_Ground Plan Genset - Sheet 1

2 JKT02-S-D-121-0_Ground Plan Genset - Sheet 2

3 JKT02-S-D-122-0_Ground Plan Genset - Sheet 3

4 JKT02-S-D-123-0_Ground Plan Genset - Sheet 4


13 5 JKT02-S-C-185-0_GA Plan Cooling Tower Floor Sheet-1

6 JKT02-S-C-186-0_GA Plan Cooling Tower Floor Sheet-2

7 JKT02-S-D-200-0_GA Plan Water Tank

8 JKT02-S-D-300-0_GA Plan Switch Room


9 JKT02-S-C-121-0_GA Plan Mech Plant Building Sheet-1

10 JKT02-S-C-121-0_GA Plan Mech Plant Building Sheet-2

Key Plan
LOCATION
14
AUR:
REFER TO GROUND REINFORCEMENT BOTTOM PLAN
GENSET TRENCH TYPE D-1A DRAWING ON THE NEXT PAGE

0 4 8 12 16 20
15
m NORTH

Drawing Title

CONCRETE STRUCTURE EQUIPMENT


DETAIL PLAN CONC. STRUCTURE GENSET TRENCH TYPE D-1A
Scale at A1
As Indicated
Discipline
STRUCTURE
16 Suitability
ISSUED FOR APPROVAL
Drawing Number Rev

JKT02-JO-SHD-STR-2422 B

Do not scale CONFIDENTIAL INFORMATION : This drawing/document and all design, details, inventions or developments covered or derived thereby are confidential and the exclusive property of the owner (or its affiliates), which reserve all rights in the is drawing/document. Copying, reproduction, duplication, or distribution to a third party, in whole or in part, is forbidden unless expressly authorised in writing.
FOUNDATION TOP PLAN GENSET TRENCH TYPE D-1A FOUNDATION BOTTOM PLAN GENSET TRENCH TYPE D-1A

AUR:
REFER TO JKT02-RFI-CSS-317

GROUND REINFORCEMENT BOTTOM PLAN GENSET TRENCH TYPE D-1A GROUND REINFORCEMENT TOP PLAN GENSET TRENCH TYPE D-1A