Product manual

GW57 363-550
Horizontal knee disconnectors

Horizontal knee disconnectors


GW57 363-550

2 GW57 363-550 Horizontal knee disconnectors


Contents

03 - 04 Packing, transport and storage

05 Product and application

06 - 24 Installation

25 - 26 Maintenance
GW57 363-550 Horizontal knee disconnectors 3


Packing, transport and storage

Packing Ambient condition:


ABB will prepare, pack and load disconnectors The surrounding air must be free from dust,
according to requirement of customer inspection, smoke, corrosive or inflammable gas, steam or salt
guaranteeing that equipment and packing medium. The temperature is not less than -30.
material are qualified for international freight by Outdoor storage time should be less than 12
sea or by air. months. For long term storage, products must be
packed. Please clean the outer insulation before
Main blade and insulator of disconnector will be assembling.
packed in wood crate; the packing crate will be
treated by steam to guarantee that it will be free Storage in a humid climate, without proper
of insect eggs, plant seeds or animalcule. The ventilation, can lead to discoloring of zinc coated
crate is strong enough for transport under normal surfaces. This discoloring is known as white rust,
conditions by sea and road freight. The drive and consists mainly zinc oxide and zinc hydroxide
mechanism will be packed in a polywood box. and is a result of a chemical reaction between pure
zinc on the surface and moisture. The long term
All parts of the product shall be carefully packed rust protection is not affected because the steel-
and marked to ensure quick identification and zinc layer under the surface remains unaffected.
erection on site. All packing will be seaworthy for
on-deck/under-deck transport. Stacking of cases:
Stacked layers should be confirmed with the
Transport packing requirements (please refer to the
For extreme bad freight condition, purchaser markings on the packing cases). Cases of different
should provide information before award of order widths shall normally not be stacked. If cases of
and special packing can be applied accordingly different widths need to be stacked, a framework
with agreement of the customer. must be used between the cases in order to
distribute the pressure evenly. Stacking of more
When products are transported by trucks, the than two cases is not allowed. It must be noted
speed of trucks shall be steady to avoid that stacking causes instability sidewise and
mechanical damage. therefore the cases must be secured, i.e.,
prevented from tumbling down or rolling over.
Storage
Upon arrival each unit should be checked An approved store is defined as:
according to the shipping documents and the stored in indoor or under the roof to avoid the
order. If damage is discovered or suspected, the exposure to sunshine and rain. The equipment can
case should be opened and photos should be be stored outdoors. If this happens they should be
taken. The package should be opened carefully to protected by at least a tarpaulin. The tarpaulin
avoid the damage on the outer insulation. shouldn't be so tight so that air circulation to zinc
coated surfaces is still prevented.
Upon arrival it is important that the plastic cover
will be removed in order to prevent corrosion due Drive mechanism:
to condensation. If intermediate storage cannot The drive mechanism should be unpacked on
be avoided, please recover the package for safety arrival. If it is not kept in an approved store, the
storage. heating element must be connected and
permanently switched on to prevent the control
Storage site: equipment from corrosion or damage due to
The products shall be stored indoors or under a freezing.
rain-proof cover. The ground should be strong
enough to stand the pressure of packing case. The
product shall be stored horizontally above ground
level to avoid cracking or water damage.
4 GW57 363-550 Horizontal knee disconnectors


Packing, transport and storage

Disconnectors and insulators: Marking


The disconnectors and insulators should be stored Each package will contain one main crate for
in their original cases where they are properly disconnector and one for mechanism. Accessory
protected from damage. The units shall not stand will be packed inside the main crate for
in water. The disconnectors can be stored disconnectors, with optional frame and pole beam,
outdoors. If this happens they should be one set of package can consist up to several boxes,
protected by at least a tarpaulin. The tarpaulin ie disconnector box, mechanism box, insulator box,
shouldn't be so tight so that air circulation to zinc Box and crate will be marked with serial numbers. If
coated surfaces is still prevented. Any condense desired by the customer the necessary information
should easily drip off. The lowest permitted will be marked onto the boxes by our factory
ambient temperature for storage is according to the existing specifications.

Spare parts: Nameplate:


Spare parts shall be kept indoors in an approved All permanent equipment of the works shall be
storage and in their original packing. This is provided with a securely fixed nameplate maker's
especially important for rubber components (seals name, model, serial number, year of manufacturing,
etc.), which must also be protected from sunlight main characteristic data of the respective
to avoid drying. Frames can be stored outdoors. equipment and further relevant information. All
main equipment should have the nameplates in
English or language upon request.

Packing crate illustration


Product packing and markings (Figure 1)

Figure 1-2 Drive mechanism plywood packing

Figure 1-1 GW57 packing

Figure 1-3 Insulator packing


GW57 363-550 Horizontal knee disconnectors 5


Product and application


Application
Operation conditions
ABB Horizontal knee disconnectors GW57 series
applies highest voltage of equipment 420,550KV Application Outdoor or indoor

and rated frequency of 50 Hz or 60 Hz. It is Ambient temperature Maximum temperature +40℃

appropriate for outdoor installations and it can Minimum temperature -40℃

ensure isolation and connection directly across the Altitude Less than 1000 m*
horizontal gap. Atmosphere conditions There shall be no dust, corrosive
or explosive mediums in the
ambient air that may significantly
Type designation influence disconnectors
GW57-XXX(D) Maximum daily average relative humidity 95%℃
GW57: Horizontal knee disconnectors. Maximum wind velocity 35 m/s*
XXX: maximum equipment voltage,
Note: * or upon request.
ie D: one earthing switch applied.
DII: two earthing switch applied. General
Without D: earthing switch not applied. The disconnector is a two-column and single-arm
horizontal knee outdoor AC disconnector. After
Main technical parameters opening, it has an isolated fracture in the
Technical parameters comply with latest IEC horizontal direction that is clear and convenient to
standard or upon request. Please refer to technical check. The operating insulator drives the drive
datasheet approved by contract and nameplate. crank arm that drives the drive gear and rack
driving transmission mechanism to make the main
Electrical schematic diagram blade for opening and closing operations.
Electrical schematic diagram will be delivered
along with drive. Earthing switches can be fitted at both sides of
the disconnector and swing in a plane, which is
parallel to the close direction of disconnector.
Disconnector and earthing switch have separate
operating mechanisms. The main units are:

1. Fixed contact of main blade


2. Main blade
3. Corona of fixed contact
4. Corona
5. Corona of moving contact
6. Supporting insulator
7. Operating insulator
8. Base (Fixed contact side)
9. Base (Moving contact side)
10. Connecting rod between poles
11. Left earthing switch
12. Operating rod of left earthing switch
13. Right earthing switch
14. Fixed contact of left earthing switch
15. Fixed contact of right earthing switch
16. Vertical rod
17. M16 U–type bolt
18. Output angle steel
19. Electrically operated mechanism of
earthing switch
20. Electrically operated mechanism of
main blade
21. Corona of fixed contact

Figure 2 GW57-550DII structure


6 GW57 363-550 Horizontal knee disconnectors


Installation

Delivery

CAUTION Check the current transformer for any transport


damages immediately upon delivery. Damage to
packaging may be a sign of rough handling. Note
FOR YOUR SAFETY any damage (it is advisable to take pictures).
DO NOT ATTEMPT TO HANDLE, INSTALL, USE
OR SERVICE THIS PRODUCT BEFORE READING
THE INSTRUCTION MANUAL. Products are provided with this product manual,
quality certificate, packing list. Please check the
Failure to read the instruction manual prior to
performing these actions can lead to serious software and accessories along with the product
injury and/or damage. according to the packing list. Be careful not to
damage the product.

Safety notice Check the products as below after unpacking.


This disconnectors should be installed within the design limitations as
described on its rating plate and in these instructions. Follow your Note!
company's safety procedures. Check the product appearance for damage.

This product is intended to be operated and maintained by qualified Note!


persons who are thoroughly trained and who understand the hazards Check the accessories according to the
involved. This publication is written only for such qualified persons and packing list to ensure they are complete.
is not intended to be a substitute for adequate training and experience
in safety procedures for this device. Note!
Check if the product marking are clear and
correct.

WARNING Note!
When unpack, attention that some
DETAILED DESCRIPTIONS OF STANDARD REPAIR PROCEDURES, SAFETY
components are fragile and may be
PRINCIPLES AND SERVICE OPERATIONS ARE NOT INCLUDED. IT IS
damaged by sudden shocks or careless
IMPORTANT TO NOTE THAT THIS DOCUMENT CONTAINS CERTAIN
handling. Be careful to avoid damages or
WARNINGS AND CAUTIONS REGARDING CERTAIN SPECIFIC SERVICE
deformations of components which may
METHODS THAT COULD CAUSE PERSONAL INJURY TO SERVICE
cause inconvenient assembly.
PERSONAL OR COULD DAMAGE EQUIPMENT OR RENDER IT UNSAFE.
PLEASE UNDERSTAND THAT THESE WARNINGS CANNOT COVER ALL
Note!
CONCEIVABLE WAYS IN WHICH SERVICE, WHETHER OR NOT
Use box cover or plate as a temporary
RECOMMENDED BY ABB, MIGHT BE PERFORMED OR POSSIBLE
storage platform to prevent equipment
HAZARDOUS CONSEQUENCES OF EACH CONCEIVABLE WAY, NOR
damaged or contaminated by sand,
COULD ABB INVESTIGATE ALL SUCH WAYS. ANYONE USING SERVICE
prevent sand entering lubricant nozzle and
PROCEDURES OR TOOLS, WHETHER OR NOT RECOMMENDED BY ABB,
screw holes and prevent damaging the zinc
MUST THOROUGHLY ENSURE ONESELF THAT NEITHER PERSONAL NOR
coating and the main contact.
EQUIPMENT SAFETY WILL BE JEOPARDIZED BY THE SERVICE METHOD
OR TOOLS SELECTED.
Note!
Bolts should be fastened with below table
All information contained in this manual is based on the latest product
except special instructions in the manual.
information available at the time of printing. The right is reserved to
make changes at any time without notice.
Steel to Steel Steel to other materials
Diameter
of bolts Galvanized Stainless Galvanized or
bolt steel bolt stainless steel bolts
M8 23 N.m 22 N.m 22 N.m
M10 46 N.m 33 N.m 33 N.m
M12 79 N.m 56 N.m 56 N.m
M16* 195 N.m 136 N.m 120 N.m
M20 390 N.m 274 N.m 206 N.m
* Max torque of M 16 bolt for a pivot is 120 N.m.
GW57 363-550 Horizontal knee disconnectors 7

Main components list of gang Note!


Correct components selection is the pre-
operation product
condition for correct installation. Below
quantities is only applied for one unit
product with three phase. Attention to
key components designation below which
will be used in installation procedure.
Wrong components installation will
damage equipment.

Scope may adjust according to contract


scope. DIS-Disconnecting switch; ES-
Earthing switch.

Components designation
Item Description Qty/Unit Components photo 363-550 kV
2 ES 1 ES 0 ES

Foundation bolts
1 (Option upon scope) 24 X1D X1D X1D

Steel frame-Phase A/C


(Option upon scope) 3 X2D X2D X2D

X2E

Steel frame-Phase B
2 3
(Option upon scope)

X2F

X2G
8 GW57 363-550 Horizontal knee disconnectors


Installation

Components designation
Item Description Qty/Unit Components photo 363-550 kV
2 ES 1 ES 0 ES

3 X3D

2 ES

Moving contact Left ES


3 X3E
side base

Right ES
3

3 X3F

0 ES

X3G X3G X3G

Fixed contact Left ES/2 ES


side base 3

X3H X3H

Right ES/0 ES
GW57 363-550 Horizontal knee disconnectors 9

Components designation
Item Description Qty/Unit Components photo 363/420 kV 550 kV
2 ES 1 ES 0 ES 2 ES 1 ES 0 ES

Upper rotatory
3 X4D X4D X4D
insulator

Lower rotatory
3 X4E X4E X4E
insulator

Upper of support
6 X4F X4F X4F
insulator

Lower of support
6 X4G X4G X4G
insulator

Upper rotatory
3 X4H X4H X4H
insulator

Middle rotatory
3 X4I X4I X4I
insulator

Lower rotatory
3 X4J X4J X4J
insulator

Upper of support
6 X4K X4K X4K
insulator

Middle rotatory
6 X4L X4L X4L
insulator

Lower of support
6 X4M X4M X4M
insulator

Note: Dimension for insulator can be found from product drawing bound to the orders.
10 GW57 363-550 Horizontal knee disconnectors


Installation

Components designation
Item Description Qty/Unit Components photo 363-550 kV
2 ES 1 ES 0 ES

X5D X5D X5D

5 Coupling rod-DIS 3

X5E X5E

Earthing switch
moving contact side
6 (Option upon requirement, 3 X6D X6D
different length with
different voltage)

Earthing switch
fixed contact side
7 (Option upon requirement, 3 X7D X7D
different length with
different voltage)

ES fixed contact
8 moving contact side 3 X8D X8D
(Option upon requirement)

ES fixed contact
9 fixed contact side 3 X9D X9D
(Option upon requirement)

Corona ring on
10 6 X10D X10D X10D
moving contact base

Corona ring on
11 moving contact upper 6 X11D X11D X11D
and lower arm

Corona ring on
12 6 X12D X12D X12D
fixed contact

Corona ring support


13 3 X13D X13D X13D
on moving contact side

Corona ring support


14 3 X14D X14D X14D
on fixed contact side
GW57 363-550 Horizontal knee disconnectors 11

Components designation
Item Description Qty/Unit Components photo 363-550 kV
2 ES 1 ES 0 ES

Corona ring on insulator


15 3 X15D X15D X15D
for fixed contact side

16 Main blade 3 X16D X16D X16D

17 Fixed contact 3 X17D X17D X17D

18 DIS drive mechanism 3 X18D X18D X18D

19 ES drive mechanism 3/6 X19D X19D

20 Vertical Rod 3/6/9 X20D X20D X20D


12 GW57 363-550 Horizontal knee disconnectors


Installation

Installation procedure Note!


Attention to follow below procedure
strictly. Non-conformance may damage
equipment.

1 Install steel frame and plate

1.1 Check foundation dimension (if steel frame is in ABB scope). (Figure 2)

Figure 3 Foundation dimension

363-550 kV
Description Qty/Unit
2 ES 1 ES 0 ES
Foundation bolts 24 X1D X1D X1D
GW57 363-550 Horizontal knee disconnectors 13

1.2 Check dimension of steel frame (if steel frame is not in ABB scope).

1.2.1 363-550kV

Figure 4 Steel frame dimension for 363-550 kV

Note: D1, D2, H1, H2 can be found from product drawing bound to the orders.

1.2.2 Check the dimension of install plate of mechanism

Figure 5 Drive mechanism dimension


14 GW57 363-550 Horizontal knee disconnectors


Installation

2 Base installation

2.1 Applied for Phase operation product

Figure 6 Base installation for 420-550 kV

363-550 kV
Description Qty/Unit
2 ES 1 ES 0 ES
Base - Phase 3 X3D & X3G X3D & X3H; X3F & X3G X3F & X3H
M20*150/195 N.m 24 STD-1 STD-1 STD-1

Notes: adjust the distance between base bottom and top support structure plate is about 50 mm,
and the interphase distance meets the engineering drawing requirements.

3 Connect the insulator and main blade

Figure 7 ES fixed contact(Option upon requirement) assembly 420-550kV


GW57 363-550 Horizontal knee disconnectors 15

Figure 8 Moving contact and fixed contact assembly, 363/420 kV

Figure 9 Moving contact and fixed contact assembly, 550 kV


16 GW57 363-550 Horizontal knee disconnectors


Installation

Figure 10 Corona ring install position for main blade base and fixed contact 420-550 kV

363/420 kV 550 kV
Description Qty/Unit
2 ES 1 ES 0 ES 2 ES 1 ES 0 ES
Main blade 3 X16D X16D X16D X16D X16D X16D
Fixed contact 3 X17D X17D X17D X17D X17D X17D
Corona ring 6 X10D X10D X10D X10D X10D X10D
Corona ring 6 X11D X11D X11D X11D X11D X11D
Corona ring 6 X12D X12D X12D X12D X12D X12D
Corona ring 3 X15D X15D X15D X15D X15D X15D
Support 6 X13D X13D X13D X13D X13D X13D
Support 3 X14D X14D X14D X14D X14D X14D
Support Insulator 6
Upper Insulator 6 X4F X4F X4F X4K X4K X4K
Middle Insulator 6 X4L X4L X4L
Lower Insulator 6 X4G X4G X4G X4M X4M X4M
Rotatory Insulator 3
Upper Insulator 3 X4D X4D X4D X4H X4H X4H
Middle Insulator 3 X4I X4I X4I
Lower Insulator 3 X4E X4E X4E X4J X4J X4J
M12*35 12 STD-2 STD-2 STD-2 STD-2 STD-2 STD-2
M12*30 12 STD-3 STD-3 STD-3 STD-3 STD-3 STD-3
M16*70 52/100 STD-4 STD-4 STD-4 STD-4 STD-4 STD-4
M16*75 48 STD-5 STD-5 STD-5 STD-5 STD-5 STD-5
M16*60 24/48 STD-6 STD-6 STD-6 STD-6 STD-6 STD-6
M16*30 12 STD-7 STD-7 STD-7 STD-7 STD-7 STD-7
M16*55 12 STD-8 STD-8 STD-8 STD-8 STD-8 STD-8
M12*30 12 STD-9 STD-9 STD-9 STD-9 STD-9 STD-9
M12*35 6 STD-10 STD-10 STD-10 STD-10 STD-10 STD-10
M12*45 12 STD-11 STD-11 STD-11 STD-11 STD-11 STD-11
Note: Dimension for insulator can be found from product drawing bound to the orders.
GW57 363-550 Horizontal knee disconnectors 17

4 Install the main blade and insulator above the base

4.1 Make sure the base be in the open position

Figure 11 Open position of base 363-550 kV

Notes: When the both side interlock rod can move from left to right into the interlock disk, the base is in the open position.

4.2 Install the main blade(with insulator) and fixed contact(with insulator) to the base

Keep the interphase distance meets the


engineering drawing requirements.
Install the coupling rod X5D with the
bolt on this rod between the two base.

Figure 11 Install the main blade(with insulator) and fixed contact(with insulator) on main base
18 GW57 363-550 Horizontal knee disconnectors


Installation

4.3 Install the operation mechanism and vertical rod

Figure 12 Install the operation mechanism and vertical rod for main base

Keep the dimension meets the engineering drawing requirements. Install the operation mechanism at
open position with M16*120 bolt.
GW57 363-550 Horizontal knee disconnectors 19

4.4 Adjustment for main blade

1. Operate the mechanism box manually in the 3. The contact insertion depth meets the
opening position (Confirm the main blade just in requirements that there is a distance 50±5mm
the opening position. Otherwise, it is necessary to between the rear of upper arm plate and the outer
loosen M16 U bolts on the vertical rod to be supporting plate of fixed contact. The driving
adjusted). crank arm passes through the dead point). If the
insertion depth of the main blade does not meet
2. Operate the operating mechanism manually to the requirements, M20 bolts fastening in the base
close the main blade. When the mechanism is in on the fixed contact side or the main blade side
closing place, the main blade is in closing place too can be adjusted to make the insertion depth meet
(Judging criteria: The upper arm of main blade is the requirements.
horizontal, and the lower arm angle is between 0°
and 2°, as shown in the following figures.

Figure 13 Main blade check


Notes: After connecting cables or busbar, it is necessary to check the situation of disconnector again.
20 GW57 363-550 Horizontal knee disconnectors


Installation

5 Installation of earthing switch(Option upon requirement)

Figure 14 ES and connection rod installation

363-550 kV
Description Qty/Unit
2 ES 1 ES 0 ES
Earthing switch moving contact side
3 X6D X6D
(Option upon requirement)

Earthing switch fixed contact side


3 X7D X7D
(Option upon requirement)

Coupling rod Of ES(left ES and 2ES) 3 X5E X5E


ES Drive mechanism 3/6 X19D X19D
Vertical rod 3/6 X20D X20D

Note: Dimension for earthing switch can be found from product drawing bound to the orders.

5.1 Installation steps

1. Check marks on the box or pallet according to a. Correctly install the earthing switch in the
engineering configurations and project drawings. installing position on the base, and connect the
corresponding connecting rod or crank arm.
2. Lift the earthing switch out of the box or pallet.
b. Connect all the flexible connections of earthing
3. Pay attention to distinguishing the difference switch correctly to the installation holes on the
between earthing switches on the moving contact base.
side and the fixed contact side
c. Check the installation position of earthing
4. Install the earthing switch follow a,b,c steps on switch support plate and base supporting plate to
the base. ensure the earthing switch plate is parallel to the
base installation plate.
5. Keep the dimension meets the engineering
drawing requirements. Install the operation
mechanism at open position with M16*120 bolt.
GW57 363-550 Horizontal knee disconnectors 21

Figure 15 Support plate and base plate position


Note: When installing upper bolts on an earthing switch holding seat, it is necessary to lift the earthing switch to a certain angle, and then insert bolts on it.

5.2 Adjustment for earthing switch

1. Operate the operating mechanism box manually If the position of earthing switch relating to the
to the opening position (Confirm the earthing fixed contact of earthing switch does not meet the
switch be just in the opening position. Otherwise, requirements, adjust the relative position of
it is necessary to loosen M16 U-shaped bolts on earthing switch installation plate and base
vertical connecting rod to carry out adjusting). installation plate. The method is to increase
Then, manually operate the operating mechanism adjustment gaskets on the diagonal line of 4
to close the earthing switch, and stop it when fastening bolts between earthing switch
approaching to the guide block of fixed contact installation plate and base installation plate to
for earthing switch. Check the relative position of adjust the relative position of earthing switch and
earthing switch arm relating to the fixed contact fixed contact for earthing switch.
of earthing switch, and ensure the center of
earthing switch arm is aligned with that of fixed
contact for earthing switch, as shown in the
following figure.

Figure 16 ES and ES fixed contact position


22 GW57 363-550 Horizontal knee disconnectors


Installation

2. Continue to switch on earthing switches a. The distance from the upper guide pipe at the
manually to make earthing switch rods contact top of earthing switch to the lower of fixed
with damping pads on fixed contacts of earthing contact for earthing switch is 10±3mm. If not
switch, and check the position relationship of each meeting the requirements, loosen fixed bolts of
part between earthing switch and fixed contact copper tube for fixed contact to adjust the upper
for earthing switch. and lower positions of copper tube for fixed
contact properly.

b. The whole copper tube of fixed contact for


earthing switch is in the inclined plane of guide
pipe for earthing switch arm.

c. Relating to fixed contacts for earthing switch,


the earthing switch arm is centered basically.

10±3

Figure 17 ES and ES fixed contact position

3. Continue to carry out closing manually and make


sure earthing switch completely in dead position.
Check the position of lower driving crank arm for
earthing switch, and pass the dead point as shown
in the following figure. The distance for reference
from the lower end surface of earthing switch rod
to the lower end surface of earthing switch
supporting block is 26±3 mm after the closing is in
place.

26±3

Figure 18 ES closed position


Note: After connecting cables or busbar, it is necessary to check the
situation of earthing switch again.
GW57 363-550 Horizontal knee disconnectors 23

4. Then performs a complete opening operation to 7. Operate the electric closing operation of
check whether there is any abnormality during the earthing switch. Pay attention that there should
opening process. not be any interference or abnormal occurrence in
the process. If yes, stop the operation mechanism
5. Once again, a complete manual closing process immediately. Check the parts that have problems,
is carried out to keep the speed during the closing and carry out troubleshooting according to the
process as much as possible so that the speed is above steps.
the same basically as the time of electric closing.
The movement of earthing switch during the 8. Carry out electric opening and closing for many
closing process is checked, especially the relative times to check the movement of earthing switch,
position of earthing switch and fixed contact for and ensure that the earthing switch can be
earthing switch during the process of earthing opened/closed in place without any abnormality.
switch in the upward process.

6. According to the above steps, perform the


manual closing/opening test again for 3 times,
and check the conditions of each component and
the tightening status of bolts at each connection.
After confirming that there is not any error, open
the earthing switch manually, and switch on the
electric mechanism box.

6 Commissioning

1) Inspect the power of motor for mechanism; Vertical rod

2) Rotate the mechanism to the middle position


between open and close position by manual Before
handle;

3) Check whether the direction of mechanism


match the main blade with motor drive;

4) Measure the circuit resistance of the entire loop After

of disconnector following the table below in the


close position;

5) It is necessary to make open-close cycle for 15


times by motor- drive mechanism to inspect
whether or not the adjustment is proper. After the
test operations, the connections between the
vertical connecting rods and L plate must be
locked.

No Rated current Rated voltage Resistance


1 4000 A 363 kV ≤120 µΩ
2 4000 A 420 kV ≤120 µΩ
3 4000 A 550kV ≤120 µΩ
24 GW57 363-550 Horizontal knee disconnectors


Installation

7 Final inspection

It is necessary to inspect and verify the equipment f. Inspect whether or not the operations,
carefully after its installation and before its lubrication and strokes of all the drive
operation. mechanisms are correct. Check their idle strokes,
mechanical connection, and the excessive
a. Inspect all the insulators to see if any of them clearance during their control or installation.
are broken or defective.
g. Inspect the safety, proper functions and
b. Inspect the positioning conditions of all the operation convenience of all the switch locking
contacts. drive mechanisms (if any).

c. Inspect the tightness of all the bolts. h. Inspect whether or not the insulators and the
moving parts are clean.
d. Inspect the isolation distance, the net safety
distances of live parts of the equipment, and the
stroke of the equipment.

e. Inspect the installation and operation condition


of the earthing switch (if any).
GW57 363-550 Horizontal knee disconnectors 25


Maintenance

Note! General inspections


Abide by all the safety precautions and Ÿ Inspect the equipment and its drive mechanisms
the local or general regulations before to make them under good operation statuses.
maintenance. Make sure all of its power Ÿ Inspect the bolts, nuts and gaskets and make
supplies are disconnected and all drive sure they are in their original positions and in
mechanisms are locked. The both sides of good condition. Replace the seriously worn or
the equipment should be respectively corroded parts.
connected with an earth wire or an Ÿ Inspect all the safety interlocking devices and
equivalent body. test them to ensure their normal operations.
Ÿ Inspect whether or not the insulators are in
good condition and whether or not their
Contacts surfaces are clean.
Clean the contacts. Paste a piece of even Molykote Ÿ Inspect the connecting terminals according to
BR2 film on the surface of each contact and get rid the instructions given by the manufacturer.
of the surplus part. Inspect whether or not the
contact is on the proper making position. If a
contact is damaged or seriously abraded due to
mechanical loads, electric arcs and/or other
factors, it should be replaced.

Lubrication
It is suggestive to use the lubricants of the
following types to lubricate the main bearings and
pivots of the connecting rods.

Castrol - Spheerol Shell - Alvania R2


AP3/LMX
EXXON (ESSO) - Beacon P290 Chevron - Dura-Lith
grease EP

The lubricants of the special types below are


needed under extreme temperatures (from -20℃
to -50℃) and special atmospheric conditions.

EXXON (ESSO) -Beacon 325 Neste -Rasva 606

Other lithium base lubricants meeting the


following requirements might be used.
Ÿ High hydrophobicity Strong oxidation stability.
Ÿ Very low start-up and operation torques under
any temperatures.
Ÿ Containing an anticorrosion additive.
Ÿ Being adaptive to the local temperature
condition.
26 GW57 363-550 Horizontal knee disconnectors


Maintenance

Maintenance plan

Minimal maintenance is required. However, routine Preventive maintenance schedule is made below.It
checks and necessary maintenance are is recommended to follow below procedures on
recommended to ensure good performance. schedule.

Items Action to perform in compliance with the instructions 10,000 times-operation

MINOR INSPECTION
A1) Verify the mechanical parts of the equipment and of the protection surfaces
are not damaged.
A2) Verify the shell of the low voltage cables and the earthing cables are not damaged.
A3) Verify the insulators are not damaged and there is no filth deposition
A on the surfaces. A4) Verify equipment and drive mechanisms in good status.
During site routine
Disconnector A5) Verify the bolts, nuts and gaskets in their original positions and good condition.
inspection or, in any
in service Replace the seriously worn or corrosion parts.
case, every 2 years
A6) Verify all interlock components and test to ensure them in good condition.
A7) Verify terminals connecting according to this manual.
A8) Verify the sealing of gear box if aging. Keep gear box clean.
A9) Verify the drive mechanism is not damaged.

OPTIONAL:
Check the heater with thermal detector.

INSPECTION ON DISCONNECTOR
B1) Carry out checks A1-A9 described in section A.
B2) Verify and clean all live parts.
B3) Measure resistance of live parts.
B4) Verify bolt tightening.
B5) Verify operation of local controls.
B6) Verify manual operation.
B B7) Verify correct coupling of main contact.
Every 5 years or every
Disconnector B8) Verify surface condition of contacts.
1500 operations
out of service
INSPECTION OF THE DRIVE MECHANISM
B9) Verify that all mechanical and electrical components, cables and earthing
connections are not damaged.
B10) Verify lubrication of gears.
B11) Verify the correct operation of the following electrical components:
Heating and anti-condensation resistance;
Motor protection automatic switch;
Electromechanical interlock.

MAJOR INSPECTION
C1) Full check of the disconnector as per section B;
C2) Check the condition and the wear of the main components, the conditions
C
of the insulators and the mechanical adjustments performed during installation
Disconnector Every 15 years or every
(see installation manual). If you find any deviation, restore the required conditions.
out of service 10.000 operations
In case replacement of units or components is required, comply with procedures
in the installation manual. In case of troubles or doubts on how to restore
correctly the required conditions, please contact ABB

ABB High Voltage Switchgear
Co., Ltd., Beijing
Add.: No.12 Jingyuan Street,
Beijing Economic-Technological
Development Area Beijing, 100176,
P.R.China
Tel: +86 10 6781 8000
Fax: +86 10 6781 8001

ABB Jiangsu Jingke Instrument


Transformer Co., Ltd.
Add.:No.9 Gucheng Road Su-Su Industriial
Park, Suqian,Jiangsu, 223800
P.R China
Tel: +86 527 8288 0810
Fax: +86 527 8288 0868

www.abb.com.cn

Copyright 2018 ABB. All rights reserved.

© Copyright 2018 ABB. All rights reserved.


C

Note: We reserve the right to make technical changes or


3211-5865CNTHB REV.1 2018-09

modify the contents of this document without prior notice.


With regard to purchase orders, the agreed particulars shall
prevail. ABB does not accept any responsibility whatsoever
for potential errors or possible lack of information in this
document

We reserve all rights in this document and in the subject


matter and illustrations contained therein. Any reproduction,
disclosure to third parties or utilization of its content - in
whole or in parts - is forbidden without ABB's prior written
consent.