SHEET : 1 OF: 6

TEST REPORT FOR LEAKAGE PAGE :


CURRENT MEASUREMENT
DATE : 16.08.2021

Client : M/s . Ambuja cements ltd, Farakka.


Project : Maintenance Testing of Electrical Equipments

1. Location : 132 KV Switchyard

2. General Inspection: OK

Measurement of Third Harmonic Resistive Current for Surge Arrester:

Third order Harmonics in the Leakage Current:

When voltage is applied to the arrester, due to non-linear voltage current characteristics of a metal
oxide used in arrester, harmonics in the leakage current is generated. The harmonics component depends on
resistive component of arrester. The resistive component depends on applied voltage and temperature. Thus
due to this resistive component major increase in third order harmonics component is observed. The
magnitude of third order harmonics in the leakage current can be used as indicator of resistive current.

TESTED BY VEPL WITNESSED BY AMBUJA CEMENTS LTD.

NAME Mr. Sathish Kumar NAME Mr.Biswajith


DESIGNATION Sr.comm. Engineer DESIGNATION
SIGNATURE SIGNATURE
DATE DATE
SHEET : 2 OF: 6

TEST REPORT FOR LEAKAGE PAGE :


CURRENT MEASUREMENT
DATE : 16.08.2021

Client : M/s . Ambuja cements ltd, Farakka.


Project : Maintenance Testing of Electrical Equipments

Testing Procedure:

1. Make the connections as per the diagram given below


2. The kit should be properly earthed.
3. Clamp On type CT should be placed above the surge monitor to pick up the total leakage current.
4. Carryout the measurements as per standard procedure supplied by the test kit manufacturer.
5. Note down the system voltage and ambient temperature along with test current value.
6. Avoid measurement during monsoon

Evaluation of Test Result s:


1. ZnO Surge Arrester continuously conducts a small leakage current. The resistive component of this
leakage current may increase with time due to different stresses causing ageing and finally cause
arrester

2. If Harmonics are present in the system voltage, it affects the value of measured third harmonic current.
TESTED BY VEPL WITNESSED BY AMBUJA CEMENTS LTD.

NAME Mr. Sathish Kumar NAME Mr.Biswajith


DESIGNATION Sr.comm. Engineer DESIGNATION
SIGNATURE SIGNATURE
DATE DATE
SHEET : 3 OF: 6

TEST REPORT FOR LEAKAGE PAGE :


CURRENT MEASUREMENT
DATE : 16.08.2021

Client : M/s . Ambuja cements ltd, Farakka.


Project : Maintenance Testing of Electrical Equipments

Compensating device provided to be used to nullify the effect. The value of Third Harmonic Resistive
current shall be less than 30 µA.
3. The measured value of resistive current is converted to standard operating voltage of arrester. The
correction factor is calculated as per the ‘typical information for conversion to standard operating voltage
conditions’ given in IEC 60099-5.

HV Side

Capacitance Non-linear Resistor

Arrester Equivalent Circuit


Temperature Correction Factor:

TESTED BY VEPL WITNESSED BY AMBUJA CEMENTS LTD.

NAME Mr. Sathish Kumar NAME Mr.Biswajith


DESIGNATION Sr.comm. Engineer DESIGNATION
SIGNATURE SIGNATURE
DATE DATE
SHEET : 4 OF: 6

TEST REPORT FOR LEAKAGE PAGE :


CURRENT MEASUREMENT
DATE : 16.08.2021

Client : M/s . Ambuja cements ltd, Farakka.


Project : Maintenance Testing of Electrical Equipments

TEST REPORT FOR LIGHTINING ARRESTERS

LA Ref: Traffo 2 :

Make Crompton
Sl. No. NV
System Voltage 132KV
LA Rated Voltage 120KV
Temperature 35°C
Yom NV

Corrected
Resistive Resistive Total Current
Sr. Phase
No Location Ref Current (IR in Current (ITotal in µA)
µA) (IR in µA)
1 R 1 1 54
2 ICT -1 Y 1 1 7
3 B 1 1 25

 Remarks: Test results are found satisfactory.

TESTED BY VEPL WITNESSED BY AMBUJA CEMENTS LTD.

NAME Mr. Sathish Kumar NAME Mr.Biswajith


DESIGNATION Sr.comm. Engineer DESIGNATION
SIGNATURE SIGNATURE
DATE DATE
SHEET : 5 OF: 6

TEST REPORT FOR LEAKAGE PAGE :


CURRENT MEASUREMENT
DATE : 16.08.2021

Client : M/s . Ambuja cements ltd, Farakka.


Project : Maintenance Testing of Electrical Equipments

LA Ref: CT Side :

Make Crompton
Sl. No. NV
System Voltage 132 KV
LA Rated Voltage 120 KV
Temperature 36°C
Yom 2006

Corrected
Resistive Resistive Total Current
Sr. Phase
No Location Ref Current (IR in Current (ITotal in µA)
µA) (IR in µA)
1 R 89 91 1655
2 Y 10 10 93
ICT-2
3 B 7 7 226

 Remarks : Test results R-Phase to be replaced Y&B are found satisfactory.

Note: The corrected resistive current permissible limits are mentioned below,

1. Below 150 µA, LA is healthy condition.


2. 150-225 µA, LA are observed condition in next one year.
3. 225-300 µA, LA are closed observed condition in next six months.
4. Above 300 µA, LA is replaced condition.

Above the permissible limits are followed as per IEC 60099-5.

TESTED BY VEPL WITNESSED BY AMBUJA CEMENTS LTD.

NAME Mr. Sathish Kumar NAME Mr.Biswajith


DESIGNATION Sr.comm. Engineer DESIGNATION
SIGNATURE SIGNATURE
DATE DATE
SHEET : 6 OF: 6

TEST REPORT FOR LEAKAGE PAGE :


CURRENT MEASUREMENT
DATE : 16.08.2021

Client : M/s . Ambuja cements ltd, Farakka.


Project : Maintenance Testing of Electrical Equipments

LA Ref: Traffo 1:

Make Crompton
Sl. No. NV
System Voltage 132 KV
LA Rated Voltage 120 KV
Temperature 35 °C
Yom 2006

Corrected
Resistive Resistive Total Current
Sr. Phase
No Location Ref Current (IR in Current (ITotal in µA)
µA) (IR in µA)
1 R 7 7 226
2 Y 9 9 60
ICT-3
3 B 3 2 209

 Remarks : Test results are found satisfactory.

 Remarks : Test results are found satisfactory.

TESTED BY VEPL WITNESSED BY AMBUJA CEMENTS LTD.

NAME Mr. Sathish Kumar NAME Mr.Biswajith


DESIGNATION Sr.comm. Engineer DESIGNATION
SIGNATURE SIGNATURE
DATE DATE