Metering Strategy

You might also like

Download as pdf or txt
Download as pdf or txt
You are on page 1of 2

SHEET NUMBER

PROJECT: DIRIYAH SQUARE PROJECT NUMBER


1

PREPARED BY CHECKED BY VERIFIED BY DATE REVISION


TITLE: METERING STRATEGY
WK / MK / KJ AA / FA / MD MA / JR 7/23/2020 0

MEP - PROPOSED METERING STRATEGY OPTIONS FOR DISCUSSION


Metering
S.No. Type of Building Unit Classification Chilled Water Description Remarks
Water Meter Gas Meter Electrical Meter
BTU / Meter
RETAIL
HVAC:
1. Bulk chilled water meter will be located within the 2 nos. of ETS rooms serving retail.
2. BTU/meter for centralized FAHU serving several tenants.
3. Dedicated BTU/meters within the BOH MEP core areas & corridor owned by Landlord and at the entrance to the tenancy.

DEPARTMENT STORE’S / RETAIL’S / PHE:


01 Retail LUXURY / LUXURY FLAGSHIP / BAZAAR Yes N/A Yes Yes 1. One Bulk meter at the incoming main water supply line and dedicated sub water meter will be provided for each tenants with following options.
/ CULTURE Option 01: Centralized water meter room per cluster in Basement -01 (for Basement retails) and in ground floor (for ground and First floor retails). The rooms will have
Water meters for all the retails in that cluster.
Option 02: Dedicated water meters within the BOH areas adjacent to Retails.

ELEC:
1. SEC Low Voltage meter will be provided for each retail and located within the cluster meter room in the back of house MEP core area.

HVAC:
1. Bulk chilled water meter will be located within the 2 nos. of ETS rooms serving retail.
2. BTU/meter and stub-out provision for tenant future equipment: FAHUs, etc.
3. Dedicated BTU/meters within the BOH MEP core areas & corridor owned by Landlord and at the entrance to the tenancy.
02 Retail MINI MAJORS Yes N/A Yes Yes
PHE:
Refer to Item No.: 01

ELEC:
1. SEC Low Voltage meter will be provided for each mini major and located within the cluster meter room in the back of house MEP core area.
HVAC:
1. Bulk chilled water meter will be located within the 2 nos. of ETS rooms serving retail.
2. BTU/meter and stub-out provision for tenant future equipment AHU, FCUs, MAHUs (as applicable).

PHE:
03 Retail CINEMA Yes Yes Yes Yes 1.Refer to Item No.-01.
2. Main SNG Pressure reducing and metering station at ground floor (bulk meter) and Secondary pressure reducing and metering in BOH/ tenancy area.

ELEC:
1. SEC Low Voltage meter will be provided for the cinema complex and located within the cluster meter room in the back of house MEP core area.

HVAC:
1. Bulk chilled water meter will be located within the 2 nos. of ETS rooms serving retail.
2. BTU/meter and stub-out provision for tenant future equipment AHU, FCUs, MAHUs (as applicable).

PHE:
04 Retail FEC Yes Yes Yes Yes 1. Refer to Item No.-01.
2. Main SNG Pressure reducing and metering station at ground floor (bulk meter) and Secondary pressure reducing and metering in BOH/ tenancy area.

ELEC:
1. SEC Low Voltage meter will be provided for each FEC and located within the cluster meter room in the back of house MEP core area.

HVAC:
1. Bulk chilled water meter will be located within the 2 nos. of ETS rooms serving retail.
2. BTU/meter and stub-out provision for tenant future equipment AHU, FCUs, MAHUs (as applicable).

PHE:
05 Retail LEISURE Yes Yes Yes Yes
1.Refer to Item No.-01.
2. Main SNG Pressure reducing and metering station at ground floor (bulk meter) and Secondary pressure reducing and metering in BOH/ tenancy area.

ELEC:
1. SEC Low Voltage meter will be provided for each leisure and located within the cluster meter room in the back of house MEP core area.

HVAC:
1. Bulk chilled water meter will be located within the 2 nos. of ETS rooms serving retail.
2. BTU/meter and stub-out provision for tenant future equipment FCUs, MAHUs (as applicable).

PHE:
06 Retail F&B / Restaurant Yes Yes Yes Yes 1.Refer to Item No.-01.
2. Main SNG Pressure reducing and metering station at ground floor (bulk meter) and Secondary pressure reducing and metering in BOH/ tenancy area.

ELEC:
1. SEC Low Voltage meter will be provided for each F&B/Restaurant and located within the cluster meter room in the back of house MEP core area.

HVAC:
1. Bulk chilled water meter will be located within the 2 nos. of ETS rooms serving retail.
2. BTU/meter for centralized FAHU serving several tenants (gym and other retails)
3. Dedicated BTU/meters within the BOH MEP core areas & corridor owned by Landlord and at the entrance to the tenancy.
07 Retail GYMNASIUM Yes N/A Yes Yes
PHE:
1. Refer to item no.: 01

ELEC:
1. SEC Low Voltage meter will be provided for the gymnasium and located within the cluster meter room in the back of house MEP core area.
HVAC:
1. Bulk chilled water meter will be located within the 2 nos. of ETS rooms serving retail.
2. BTU/meter for centralized FAHU serving several tenants (Medical and other retails)
3. Dedicated BTU/meters within the BOH MEP core areas & corridor owned by Landlord and at the entrance to the tenancy.
08 Retail MEDICAL Yes N/A Yes Yes
PHE:
1. Refer to item no.: 01

ELEC:
1. SEC Low Voltage meter will be provided for the medical unit and located within the cluster meter room in the back of house MEP core area.
HOTEL & BRANDED RESIDENCE - 01
HVAC:
1. Bulk chilled water meter will be located within the ETS rooms serving hotel 1 and residence 1.
2. Dedicated BTU/meters for retails managed by the hotel located within the corridor owned by Landlord and at the entrance to the tenancy.

PHE:
01 Hotel Hotel Yes Yes Yes Yes
1. One Bulk Water Meter at the incoming line for Water supply.
2. Main SNG Pressure reducing and metering station at ground floor (bulk meter).

ELEC:
1. Bulk Medium Voltage meter will be provided for the hotel/branded residence substation within the MRMU room.
HVAC:
1. Bulk chilled water meter will be located within the ETS rooms serving corresponding hotel asset.
2. Dedicated BTU/meters for retails within the residential building (if applicable) located within the corridor owned by Landlord and at the entrance to the tenancy.
3. Dedicated BTU/meters per apartment located within the corridor owned by Landlord and at the entrance of the unit to facilitate future leasing.

PHE:
1. Option-01 :One Bulk Water Meter at the incoming line for Water supply , Hotel and Branded residence sharing the same Bulk meter.
02 Branded residential Branded residential Yes No Yes Yes
2. Option-02:A separate bulk Water meter at the incoming line for Water supply for branded residence.
3. Option-03:One bulk water meter at the incoming line for water supply and separate water meter cabinet at each floor for flexibility.
4. Cooking Shall be using Electrical Appliances. No SNG provided.

ELEC:
1. Bulk Medium Voltage meter will be provided for the hotel/branded residence substation within the MRMU room.

HOTEL & BRANDED RESIDENCE - 02


HVAC:
1. Bulk chilled water meter will be located within the ETS rooms serving hotel 2 and residence 2.
2. Dedicated BTU/meters for retails managed by the hotel located within the corridor owned by Landlord and at the entrance to the tenancy.

PHE:
01 Hotel Hotel Yes Yes Yes Yes
1. One Bulk Water Meter at the incoming line for Water supply.
2. Main SNG Pressure reducing and metering station at ground floor (bulk meter).

ELEC:
1. Bulk Medium Voltage meter will be provided for the hotel/branded residence substation within the MRMU room.
HVAC:
1. Bulk chilled water meter will be located within the ETS rooms serving corresponding hotel asset.
2. Dedicated BTU/meters for retails within the residential building (if applicable) located within the corridor owned by Landlord and at the entrance to the tenancy.
3. Dedicated BTU/meters per apartment located within the corridor owned by Landlord and at the entrance of the unit to facilitate future leasing.

PHE:
1. Option-01 :One Bulk Water Meter at the incoming line for Water supply , Hotel and Branded residence sharing the same Bulk meter.
02 Branded residential Branded residential Yes No Yes Yes
2. Option-02:A separate bulk Water meter at the incoming line for Water supply for branded residence.
3. Option-03:One bulk water meter at the incoming line for water supply and separate water meter cabinet at each floor for flexibility.
4. Cooking Shall be using Electrical Appliances. No SNG provided.

ELEC:
1. Bulk Medium Voltage meter will be provided for the hotel/branded residence substation within the MRMU room.

HOTEL & BRANDED RESIDENCE - 03


HVAC:
1. Bulk chilled water meter will be located within the ETS rooms serving hotel 3 and residence 3.
2. Dedicated BTU/meters for retails managed by the hotel located within the corridor owned by Landlord and at the entrance to the tenancy.

PHE:
01 Hotel Hotel Yes Yes Yes Yes
1. One Bulk Water Meter at the incoming line for Water supply.
2. Main SNG Pressure reducing and metering station at ground floor (bulk meter).

ELEC:
1. Bulk Medium Voltage meter will be provided for the hotel/branded residence substation within the MRMU room.
HVAC:
1. Bulk chilled water meter will be located within the ETS rooms serving corresponding hotel asset.
2. Dedicated BTU/meters for retails within the residential building (if applicable) located within the corridor owned by Landlord and at the entrance to the tenancy.
3. Dedicated BTU/meters per apartment located within the corridor owned by Landlord and at the entrance of the unit to facilitate future leasing.

PHE:
1. Option-01 :One Bulk Water Meter at the incoming line for Water supply , Hotel and Branded residence sharing the same Bulk meter.
02 Branded residential Branded residential Yes No Yes Yes
2. Option-02:A separate bulk Water meter at the incoming line for Water supply for branded residence.
3. Option-03:One bulk water meter at the incoming line for water supply and separate water meter cabinet at each floor for flexibility.
4. Cooking Shall be using Electrical Appliances. No SNG provided.

ELEC:
1. Bulk Medium Voltage meter will be provided for the hotel/branded residence substation within the MRMU room.

HOTEL & BRANDED RESIDENCE - 04

File: 20200721_Metering Strategy_Rev 0.xlsx - Metering Print Date: 7/23/2020 page 1 of 2 pages
SHEET NUMBER
PROJECT: DIRIYAH SQUARE PROJECT NUMBER
1

PREPARED BY CHECKED BY VERIFIED BY DATE REVISION


TITLE: METERING STRATEGY
WK / MK / KJ AA / FA / MD MA / JR 7/23/2020 0

MEP - PROPOSED METERING STRATEGY OPTIONS FOR DISCUSSION


Metering
S.No. Type of Building Unit Classification Chilled Water Description Remarks
Water Meter Gas Meter Electrical Meter
BTU / Meter
HVAC:
1. Bulk chilled water meter will be located within the ETS rooms serving hotel 4 and residence 4.
2. Dedicated BTU/meters for retails managed by the hotel located within the corridor owned by Landlord and at the entrance to the tenancy.

PHE:
01 Hotel Hotel Yes Yes Yes Yes
1. One Bulk Water Meter at the incoming line for Water supply.
2. Main SNG Pressure reducing and metering station at ground floor (bulk meter).

ELEC:
1. Bulk Medium Voltage meter will be provided for the hotel/branded residence substation within the MRMU room.
HVAC:
1. Bulk chilled water meter will be located within the ETS rooms serving corresponding hotel asset.
2. Dedicated BTU/meters for retails within the residential building (if applicable) located within the corridor owned by Landlord and at the entrance to the tenancy.
3. Dedicated BTU/meters per apartment located within the corridor owned by Landlord and at the entrance of the unit to facilitate future leasing.

PHE:
1. Option-01 :One Bulk Water Meter at the incoming line for Water supply , Hotel and Branded residence sharing the same Bulk meter.
02 Branded residential Branded residential Yes No Yes Yes
2. Option-02:A separate bulk Water meter at the incoming line for Water supply for branded residence.
3. Option-03:One bulk water meter at the incoming line for water supply and separate water meter cabinet at each floor for flexibility.
4. Cooking Shall be using Electrical Appliances. No SNG provided.

ELEC:
1. Bulk Medium Voltage meter will be provided for the hotel/branded residence substation within the MRMU room.

HOTEL ASSET-05
HVAC:
1. Bulk chilled water meter will be located within the ETS rooms serving hotel 5.
2. Dedicated BTU/meters for retails managed by the hotel located within the corridor owned by Landlord and at the entrance to the tenancy.

PHE:
01 Hotel Hotel Yes Yes Yes Yes
1. One Bulk Water Meter at the incoming line for Water supply.
2.Main SNG Pressure reducing and metering station at ground floor (bulk meter).

ELEC:
1. Bulk Medium Voltage meter will be provided for the hotel/branded residence substation within the MRMU room.
HOTEL ASSET-06
HVAC:
1. Bulk chilled water meter will be located within the ETS rooms serving hotel 6
2. Dedicated BTU/meters for retails managed by the hotel located within the corridor owned by Landlord and at the entrance to the tenancy.

PHE:
01 Hotel Hotel Yes Yes Yes Yes
1. One Bulk Water Meter at the incoming line for Water supply.
2.Main SNG Pressure reducing and metering station at ground floor (bulk meter).

ELEC:
1. Bulk Medium Voltage meter will be provided for the hotel/branded residence substation within the MRMU room.
MOSQUE
HVAC:
1. Bulk chilled water meter will be located within the ETS rooms serving hotel 5
2. [to be confirmed] Dedicated BTU/meter for retail at the north of the mosque and to be located within the internal back corridor owned by Landlord and near the
tenancy

01 Mosque Mosque Yes No Yes Yes PHE:


1. One Bulk Water Meter at the incoming line for Water supply and dedicated sub metering for the retails in BOH/tenancy areas.

ELEC:
1. Bulk Medium Voltage meter will be provided for the mosque substation within the MRMU room.
2. SEC Low Voltage meter will be provided for each retail and located within the retail meter room in the back of house area.
MUNICIPAL OFFICE
HVAC:
Option 1: One landlord/operator for the entire asset.
1. Bulk chilled water meter will be located within the office ETS rooms serving all offices buildings.
Option 2: One landlord and one operator/tenant per office building.
1. Bulk chilled water meter will be located within the office ETS rooms serving all offices buildings.
2. Dedicated BTU/meter cabinet at ground floor areas owned by Landlord and per building.
Option 3: One landlord and three operator/tenants per floor per building.
1. Bulk chilled water meter will be located within the office ETS rooms serving all offices buildings.
2. Dedicated BTU/meter cabinet at ground floor areas owned by Landlord to serve building core spaces (pantries, toilets, break rooms, reception...) and dedicated
FAHU for these spaces on the roof.
01 Office Office Yes No Yes Yes
3. Dedicated BTU/meters on the roof to serve the three individual tenant's Fresh air heat recovery AHU dedicated equipment (to be installed by tenant).

PHE:
Option -01 : One Bulk meter for the asset.
Option -02 : One bulk meter for the asset and one water meter cabinet per floor / per core considering three tenant per floor for each building.

ELEC:
1. Bulk Medium Voltage meter will be provided for the offices substation in MRMU room (This is for Landlord services via Subtraction)
2. SEC Low Voltage meters to be provided for office tenants within a dedicated meter room per each floor.

File: 20200721_Metering Strategy_Rev 0.xlsx - Metering Print Date: 7/23/2020 page 2 of 2 pages