Professional Documents
Culture Documents
Duct Application Guide
Duct Application Guide
Duct Application Guide
Duct Application
Smoke Detectors
A P P L I C A T I O N S G U I D E
Duct Application
Smoke Detectors
Contents
Section 1 Introduction. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2
Foreword
The purpose of this guide is to provide much needed information concerning the proper use of smoke detectors in duct applications. Duct mounted smoke
detectors are designed to provide a specific type of protection that cannot be duplicated by any other type of system. However, there has been a tendency
to misapply these devices in the past — attempting to use them as a substitute for an early warning smoke detection system. This fact, coupled with new
methods of detecting smoke in ducts, has prompted the writing of this industry guide. Fire Protection Engineers, Mechanical and Electrical Engineers,
Fire Alarm System designers and installers should find the contents both educational and informative.
1
D U C T A P P L I C A T I O N S M O K E D E T E C T O R S
1
NFPA 90A-2002, Appendix A 6.4
2
NFPA 72-2002, Section 5.7.4.2.2
3
NFPA 90A-2002, Section 6.4.2.1
2
S Y S T E M S E N S O R
Section 2 Since the primary purpose volume in which they are dispersed. If a return duct has
Characteristics for detecting smoke in the four branches, each with equal air flow (cfm), then after
of Smoke in HVAC system is to automat- they join, the concentration will be reduced to Q/4V.
HVAC Systems ically initiate action to mini-
mize the spread of smoke The preceding assumes uniform dispersion of particles
through the air handling system, it follows that the nature which represents an ideal condition. In reality there is non-
of the smoke to be expected in various parts of the system uniform dispersion and concentration can and does vary
should be understood. The following discussion is a theo- from no smoke to a very high concentration of smoke in
retical description of smoke characteristics as they pertain a cross-section area of a duct. This is especially true just
to this application, as yet, not supported by fire test data. downstream from any point of entry. In a return air duct,
for example, stratification can be expected immediately
Smoke downstream from each return air grill. Text books teach that
Smoke, as defined in NFPA 72, Section A.5.14.4.2, is “the uniform dispersion is reasonably assured at a distance equal
totality of the airborne visible or invisible particles of com- to 10 duct widths downstream for a duct with turbulent air
bustion.” Smoke detectors are designed to sense the pres- flow. (In practical considerations, NFPA 72 accepts at least
ence of particles of combustion, but depending on the sens- 6 duct widths, but the 10 duct width distance should be
ing technology and other design factors, different detectors used when possible.) In those cases where stratification is
respond to different types of particles. Detectors based predominant, uniform dispersion might never be achieved.
on ionization detection technology are most responsive
to smaller, invisible sub-micron sized particles. Detectors Air velocity has no direct effect upon the characteristics of
based on photoelectric technology, by contrast, are most smoke. It does affect the concentration because as velocity
responsive to larger visible particles. Figure 1 shows the is increased, the total volume of smoke being produced
relative sensitivity of the three technologies as a function of and dispersed at some rate, Q/dt (the quantity of smoke
particle diameter, assuming a constant mass of particles. per given time period), increases proportionately. Stated
differently, in a one foot square duct an air velocity of one
It is generally accepted that particle size distribution var- hundred feet per minute would transport one hundred
ies from sub-micron diameter particles predominant in the cubic feet of air each minute. Increasing the velocity to four
proximity of the flame of a flaming fire to particles one or hundred feet per minute would increase the volume of air
more orders of magnitude larger, characteristic of smoke transported to four hundred cubic feet per minute, thereby
from a smoldering fire. The actual particle size distribution reducing the concentration of smoke particles by a factor of
depends upon a host of other variables including the fuel four, assuming that the rate of smoke generation was the
and its physical makeup, the availability of oxygen includ- same in both cases.
ing air supply and fire gas discharge, and other ambient
conditions, especially humidity. Moreover, the particle
size distribution is not constant; as the fire gases cool, the
sub-micron particles agglomerate and the very large ones
precipitate. In other words, as smoke travels away from the
fire source, the particle size distribution shows a relative
decrease in smaller particles. Water vapor, which is abun-
dantly present in most fires, when cooled sufficiently will 10
condense to form fog particles—an effect frequently seen 5
above tall chimneys. Since water condensation is basically
clear in color when mixed with other smoke particles, it
can be expected to change the color of the mixture to a 2
lighter one.
1
From the above discussion, one can begin to get an idea
of what “smoke” is in the various parts of an air handling 0.5
system. Specifically, the farther away the point of obser- A Scattered light principle
vation from the fire source, the cooler the smoke will be (according to Bol)
0.2
and the more visible because of the growth of sub-micron B Extinction – principle
particles by agglomeration and recombination. There prob- (according to Hosemann)
0.1
ably is some loss in quantity, i.e., the mass of the smoke
particles at the point of entry to a duct system is probably 0.05
Relative Sensitivity
3
D U C T A P P L I C A T I O N S M O K E D E T E C T O R S
Section 3 A duct smoke detector is a Typical smoke detection devices used for duct application
Duct Smoke device or group of devices include smoke detector sensors within a housing mounted
Detection Equipment used to detect the presence outside the duct utilizing sampling tubes (Figure 2), area
of smoke in the airstream smoke detectors listed for in-duct or partial in-duct mount-
of ductwork sections of the ing, a light beam detector consisting of projector and
HVAC air handling systems typically used in commercial receiver mounted within the duct and an air sampling type
buildings. detector. In all cases, alarm contacts are available either
Foam Gaskets
in the detector or in the fire alarm control
unit to initiate air movement control or to
perform other control functions.
Conduit Holes
An externally mounted duct smoke detec-
tor enclosure may incorporate either an
ionization or photoelectric type smoke
Telescoping Tube
Terminal Strip sensor. Air stream sampling is accom-
plished by sampling tubes that penetrate
Telescoping Tube Power Board and traverse either the supply or return air
Self-tapping Screw ducts. The sampling tubes are positioned
Detector Board so air may be drawn through the detec-
tor, sampled, and then returned to the air
stream in the duct (Figure 3).
4
S Y S T E M S E N S O R
Section 4 Heating, ventilating and Exhaust Air Air Returning from Conditioning Space
Section 5 An HVAC system supplies located in the hvac area between 6 and 10 duct-equivalent
How Duct Detection conditioned air to virtually diameters of straight, uninterrupted run.
Systems Are Used to every area of the build-
Control Smoke ing. Smoke introduced into Typical Single Zone HVAC System
this air duct system covers Figure 7 shows a typical single zone HVAC system. A return
the entire building. Smoke air fan is not used in all systems. Detectors may be placed
detectors designed for use in air duct systems are used to in the outdoor air supply to sense if smoke is being drawn
sense presence of smoke in the duct. into the system from outside of the building. It would then
close the outdoor air damper allowing the rest of the HVAC
NFPA 90A system to continue operating.
NFPA 90A, “Standard for Air Conditioning and Ventilating
Systems”, requires that smoke detectors listed for duct In the typical fan system shown in Figure 7, when any duct
installations be installed at a suitable location in the main smoke detector senses smoke, the fan system will be turned
supply duct on the downstream side of the filters to auto- off and all the dampers shown will go to their closed posi-
matically stop the supply fans in systems over 2,000 cfm. For tions. These actions are intended to prevent smoke from
systems over 15,000 cfm additional detectors are required in being distributed via the air handling system to unaffected
the return system of each floor, at the point of entry into the areas of a building.
common return, or a system of smoke detectors is required
to provide total area coverage. In order to obtain a repre- An alternate method that may be used is to only stop the
sentative sample, hvac areas with stratification and dead air supply fan and keep the return fan running. In this method
space should be avoided. Duct smoke detectors should be the outdoor air damper and the mixed air damper go closed
and the (exhaust) air damper is opened. This technique will
Exhaust Air Mixed Air Duct Smoke Optional Return Return Air help exhaust smoke-laden
Damper Detector Air Fan air from the building.
In addition to the require-
ments of NFPA 90A, duct
smoke detectors may also
be used within duct sys-
Typical Floor tems as detection devices in
Return
engineered smoke control
Dampers Heating Coil
systems. These systems are
engineered for the specif-
ic building. They use the
building construction and
air handling systems to con-
Conditioned Air Space tain and reduce the spread
Outside Air Cooling Coil Supply Fan of smoke.
Filter Duct Smoke
Detector NFPA 90A1 requires that
Figure 7: Typical Single Zone System Humidifier
when there is an approved
fire alarm system installed
in a building, required duct
smoke detectors must be
L1
connected to the fire alarm
system so that activation
Line Side L2 Load Side
of any duct smoke detec-
tor will cause a supervisory
L3
signal to be indicated at
Contactor a constantly attended loca-
H N
tion, or will cause an alarm
On signal.
Off
Coil
Typical Fan
Control Circuit
NC Overload Safety
Controls
Figure 8 shows a typical fan
C
control circuit.
Contactor Contactor
Auxiliary
Contact
Duct Smoke Control
Detector Contact
(Opens When Smoke
is Detected)
6
S Y S T E M S E N S O R
The pendant duct smoke detector should be mounted to Figure 10: Typical Duct Smoke Detector Placement
an appropriate electrical box. The box pendant extension
arrangement should be mounted from either the top or side
walls extending to the center of the air duct stream.
Excess Humidity: As with open area detectors, high levels Position holes or openings located along the length of the
of humidity or condensation within the duct can cause false sampling tube into the air flow. Secure tube position with
alarm problems. Duct smoke detectors should be located at locking means provided. A tube visual indicator should be
a minimum of ten feet downstream from humidifiers. provided to indicate the tube hole location without disman-
tling the duct installation.
Air Filters: Air filters within ducts tend to collect paper,
lint and trash — all flammable materials. For this reason, Plug sampling tube end with an air stopper.
duct smoke detectors should be located on the downstream
side of filters. The duct smoke detector enclosure and sampling tubes
should be mounted rigidly to prevent noise chatter and
Air Velocity: Duct smoke detectors are usually designed to mechanical fatigue.
be used in air handling systems having a certain range of
air velocities. Be sure to check engineering specifications to Avoid air leaks. Air leaks in or out of the duct or detector
make sure duct air velocity falls within these parameters. dilute or redirect smoke within the duct. Gaskets and duct
seal can be used to avoid or seal any leaks.
Placement: Duct smoke detector assemblies mounted
within the duct should be located on the sides or top of If duct sampling tube protrudes through opposite side of
a duct. Detectors listed for use in open air applications duct, seal the opening around the tube on the outside of
should not be used inside a duct in place of a duct smoke the duct with duct sealant.
detector.
After mounting the duct enclosure to the duct and installing
Duct smoke detectors mounted in an enclosure with sam- the sampling and exhaust tubes, verify that there is air flow
pling tubes can be installed onto any wall of the duct unless through the duct smoke detector. This is accomplished by
otherwise restricted by the manufacturer’s instructions. measuring the static pressure difference between the inlet
and outlet tubes using a manometer as illustrated in the
Select the proper sampling tube length for duct enclosure instrument section of this manual. If pressure differential
installation. If duct is more than three feet wide drill an cannot be attained, check for leaks, proper orientation of
appropriate diameter hole directly opposite but 2–3 in. hole placement on sample tube, air velocity, and stratifica-
lower to support the sampling tube of lengths longer than tion of airflow in the duct. Relocate the duct smoke detector
three feet. if the pressure differential specified by the manufacturer
cannot be attained after checking all possible fault causing
Exhaust tube length is not usually a critical dimension. It problems.
may vary from a stub to the full width of the duct. Be sure
to follow the recommendations of the manufacturer regard- Prior to completing the installation, clean the duct enclo-
ing the exhaust tube. sure, and check indicators for hole orientation.
Install the sampling and exhaust tubes to the mounting Duct Instrumentation
holes on the duct enclosure. Pressure Reading Instruments
Used for reading:
Tubes may be marked or, as indicated in manufacturer’s • Air velocities in ducts
installation instructions, provided with inhibitors to ensure • Pressure drops across components
that the tubes are installed in their proper duct input and Instrument readings taken by:
output ports. • Inclined liquid manometer
• Vertical liquid manometer
• Pressure differential gauges
• Micrometer liquid hook gauge
Tube support hole only for ducts more than 3 feet wide
Expected air flow direction
Duct width
8
S Y S T E M S E N S O R
Manometer gauges are used in conjunction with pitot tubes, manometer and gauge use. See Figure 13 for manometer
straight metal tubes and various static pressure sensors. type, and Figure 14 for magnehelic gauge.
Pressure drops are best read with a magnehelic gauge. For Air Velocity Reading Instruments
lower velocity readings in the range between 400 and 2000 Used for reading:
fpm a 1⁄4-inch manometer is the most accurate instrument • Air flow through duct openings
to use along with the pitot tube. For higher velocity read- • Air flow through duct filters, coils, louvers
ings in ducts, the 10 inch vertical or the one inch inclined Instrument readings taken by:
manometer is required. See Figure 12 for example of • Velometer
• Thermo-Anemometer (see Figure 15)
Damper Filter
Total Discharge
Cooling Heating
Pressure
Coil Coil
Louver
Pitot Tube
Traverse
RA Total Suction
Pressure
Static Pressure
Readinds Across Total Air Volume
Filters and Coils
Figure 12: After electrical and fpm readings are taken, the total volume of air, fan pressure and pressure drops are read.
Figure 13: 115-AV inclined manometer for velocity pressure readings in low velocity ducts, 400 to 2000 fpm.
Figure 14: Magnehelic gauge for reading static pressures in air systems Figure 15: Thermo-Anemometer
9
D U C T A P P L I C A T I O N S M O K E D E T E C T O R S
10
S Y S T E M S E N S O R
Recommended Testing and described with information on the type of detector, the
Maintenance Log Procedures model number, the serial number (if any), the location, and
It is recommended that a permanent Detector Test Log be set the type of environment. Data entries should include test
up and maintained, with a record for each individual smoke dates, type of test mode, test results, maintenance, and com-
detector in each building. Each detector should be clearly ments. A sample detector test log page is shown below.
Date Tested Test Mode Test Results Maintenance Performed and Comments
11
D U C T A P P L I C A T I O N S M O K E D E T E C T O R S
Damper Pressure
A valve or plate regulating the flow of air or other fluid. The normal force exerted by a homogenous liquid or gas
per unit of area on the wall of a container.
Damper, multiple louver
A damper having a number of adjustable blades, used to Pressure Differential
vary the volume of air passing through a confined section A pressure difference (usually specified in inches of water)
by varying the cross sectional area. between two points in a duct.
Exhaust Tube
Usually a round tube that provides a path for sampled air to Stratification
return from the detection device to the duct. A phenomenon where smoke or other gases travel in layers
at different levels within the duct, rather than being evenly
Fan distributed throughout the duct.
An air moving device comprising a wheel or blade and a
housing or orifice plate. Supply Duct
The duct which distributes conditioned air, i.e., cooled,
Humidifier heated, cleaned, humidified, etc.
A device to add moisture to the air.
Thermo-anemometer
Inch of Water A device used to measure air velocity.
A unit of pressure equal to the pressure exerted by a col-
umn of water at a temperature of 4.0°C (39.2°F). Venturi Principle
A tube with a narrow throat (a constriction) that increases
Inlet Sampling Tube the velocity and lowers the pressure of the liquid or gas
Usually a round tube with holes that collects air from the passing through it, creating a partial vacuum immediately
duct and brings it to the detection device. after the constriction in the tube. The vacuum created has a
sucking effect (eduction), and a Venturi is commonly used
to introduce a liquid (such as a regenerant) or gas (such as
air) into a flowing water stream.
12
©2006 System Sensor. The company reserves the right to change specifications at any time. A05-1004-004