It shall be contractor responsibility to install Grid conductor length 120Mt. considered laid along the length of
plant area & Grid conductor length 100Mt. considered laid along the width of plant area for earthing
calculation. Approval shall be subject to same.
Galvanizing of GI Earthing strip considered shall be as per IS:2629 as per tender.
Earthing for Lightning system as per IS:2309 shall be provided as per tender / statutory authority requirements.
The earthing strip quantity is reviewed as per the length considered by contractor. Contractor shall have to
provide the earthing strip length / quantity on higher side, if required at site, as per site condition / requirements.
Contractor to ensure that earth resistance shall not exceed 1Ω at any point and shall provide additional earth pits
/ strips, if required at site, as per IS-3043:2018 / Tender specification.
It will be contractor responsibility to demonstrate and to measure earth resistance at any point of Earthing
system shall be less than one ohm / as per latest statutory norms requirements to Engg.-In-Charge of client.
Provide Copper earth strip/ copper cable between PLC Panel and Earth pit as per specification.
For Instrument earth pit provide copper pipe as per specification.