Dunham Bush WCFX E R134A
Dunham Bush WCFX E R134A
The Dunham-Bush WCFX-E Water Cooled Rotary Screw Flooded Chillers are available from 70 to
1000 TR [246 to 3517 kW]. These units are supplied with rotary screw compressors that are
backed by more than 40 years of experience. In fact, a one-year parts warranty is provided on the
entire unit at no extra cost.
All units are factory run tested before shipment.
TABLE OF CONTENTS
Page
Introduction ..................................................................................................................................................................................................2
Nomenclature ................................................................................................................................................................................................2
Components ..................................................................................................................................................................................................3
Standard Features .......................................................................................................................................................................................3
Unit Features .................................................................................................................................................................................................4
Operating Benefits .......................................................................................................................................................................................9
Typical Sequence of Operation ..................................................................................................................................................................10
Physical Specifications ................................................................................................................................................................................11
Dimensional Data .......................................................................................................................................................................................13
Floor Loading Diagram ................................................................................................................................................................................19
Water Pressure Drop ..................................................................................................................................................................................20
Sound Pressure Data ..................................................................................................................................................................................26
Electrical Data .............................................................................................................................................................................................26
Typical Wiring Schematic ............................................................................................................................................................................27
Application Data ..........................................................................................................................................................................................32
Equipment ...................................................................................................................................................................................................34
Guide Specifications ..................................................................................................................................................................................34
NOMENCLATURE
WC F X E 10 S AR C3R B4R Q
Screw Compressor
Condenser Code
Generation
WCFX-E Evaporator Code
Model
Electrical Code
AN - 208-230V/3PH/60HZ
S = Single Compressor AR - 460V/3PH/60HZ
T = Two Compressors AS - 575V/3PH/60HZ
Blank= Three Compressors CB - 380V/3PH/60HZ
-2-
COMPONENTS
Economizer to
enhance performance
Bolted construction
for easy knockdown
Vessels designed according
to ASME code
STANDARD FEATURES
Size/Range downtime during rework of faulty or damaged
compressor, Dunham-Bush can arrange to provide a
D 37 Models from 70 to 1000 TR [246 to 3517 kW].
substitute reworked compressors while the faulty
D Multiple compressor units provide redundancy, and compressor is being reworked or repaired.
favorable part load efficiency.
D Vapor injection cycle to increase capacity and improve
D One-year parts warranty at no extra cost. efficiency.
Compressor(s) Evaporator/Condenser
D Improved, quiet, reliable MSC Vertical Rotary Screw D Cleanable and Removable Integral Fin Copper Tubes.
Compressors with up to 2 integral oil separators.
D One, Two or Three Water Passes Available.
D Optimized for R134a and optimized volume ratio for
D Removable Water Heads.
best efficiency.
D Victaulic Groove Water Connections.
D UL listed.
D Vessel designed according to ASME Code, approved
D Improved rpm and noise level.
and certified by JKKP.
D Optimized rotor drive.
D Relief Valves(s) standard - 3/4" FPT or 1” PPT.
D Improved rotor and anti-reverse rotation bearing
D Full Pump Down Capacity in Condenser.
design.
D Optimized VI port position and geometry.
D Multiple rotary screw compressors design for better
Controller/ Electrical
reliability and redundancy. D Proactive Advanced Controller adapts to abnormal
D Welded hermetic design with no requirement for operating conditions.
internal parts service, no periodic compressor tear D Tolerant and accommodating of extreme conditions at
down and overhaul, and eliminates casing leakages. start-up.
D Consistent loading and unloading with dependable D Capable of controlling multiple chillers, cooling towers,
slide valve mechanism. pumps, etc.
D No external oil pump required. D Circuit Breaker on each multiple compressor unit.
D Double-delta motor winding with 1/3 lock-rotor amps at D Unit Mounted Contactor and Time Delay for reduced
start-up. Star-delta motor winding for MSC 226 mm Inrush Start.
series. D Current and Voltage transformers.
D Faulty or damaged compressors reworkable at D Under Voltage Phase Failure Relay.
minimal cost at various Dunham-Bush’s authorized D Indicator lights for Compressor Overloads, Micro
compressors reworked facilities. To ensure minimum Alarm, Control Power, Compressor Control Circuit.
-3-
UNIT FEATURES
DISCHARGE
2ND OIL SEPARATOR OIL DEFLECTOR
CAP
1ST OIL SEPARATOR
MOTOR
REPLACEABLE
SUCTION FILTER
SUCTION
CHECK VALVE
SUCTION
OIL STRAINER
MALE (DRIVE)
-4-
UNIT FEATURES
FIG. A FIG. B FIG. C FIG. D
-5-
UNIT FEATURES
-6-
UNIT FEATURES
-7-
UNIT FEATURES
number of hours that equipment will operate at various 10 26.2 -3.2 0.995 0.998 1.019 1.050
15 22.4 -5.3 0.991 0.997 1.030 1.083
load percentages.
20 17.8 -7.9 0.988 0.996 1.044 1.121
The Air Conditioning and Refrigeration Institute (AHRI) 25 12.6 -10.8 0.984 0.995 1.060 1.170
30 6.7 -14.1 0.981 0.994 1.077 1.219
has established a system, in AHRI Standard 550/590-
35 0.0 -17.8 0.977 0.992 1.097 1.275
2011, for measuring total chiller performance over full and 40 -10.0 -23.3 0.973 0.991 1.116 1.331
part-load conditions. It defines the Integrated Part-Load 45 -17.5 -27.5 0.968 0.990 1.138 1.398
Value (IPLV) as an excellent method of comparing diverse 50 -28.9 -33.8 0.964 0.989 1.161 1.466
types of equipment on an equal basis. The IPLV is a
single number estimate of a chiller's power use weighted Table 2 : Propylene Glycol
for the number of hours the unit might spend at each part- % P. G. Freeze C2 K2 G2 P2
By Weight Point Capacity kW Flow P.D.
load point. IPLV's are based on Standard Rating
Factor Rate Factor Factor
°F °C
Conditions.
10 26.1 -3.3 0.988 0.994 1.005 1.019
The formula for calculating an IPLV is: 15 22.8 -5.1 0.984 0.992 1.008 1.031
20 19.1 -7.2 0.978 0.990 1.010 1.051
25 14.5 -9.7 0.970 0.988 1.015 1.081
30 8.9 -12.8 0.962 0.986 1.021 1.120
1
IPLV = Table 3 : Evaporator Fouling Factor
0.01 + 0.42 + 0.45 + 0.12
Fouling Factor Capacity kW
A B C D Correction Correction
hr.ft².°F/BTU m².°C/kW Factor Factor
-8-
OPERATING BENEFITS
-9-
TYPICAL SEQUENCE OF OPERATION
The Dunham-Bush Water Cooled Screw Flooded Chiller to match applied load and hold leaving chilled water
depends mainly on its on-board controller for control. temperature at setpoint.
Operation described is for a two- compressor unit and is
If the applied load is greater than one compressor can
very similar for single or three-compressor units.
handle, it will load fully and then the controller will call for
For initial start-up, the following conditions must be met: a second compressor. After one minute, the second
D Power supply to unit energized compressor will start in the same manner as the first.
D Compressor circuit breakers in the "on" position Then both compressors will be commanded to adjust load
to 50%. They are gradually loaded up together until the
D Control power switch on for at least 15 minutes.
applied load is satisfied. In this way the two compressors
D Compressor switches on
share the load equally.
D Critical alarm is cleared at display panel
If the applied load decreases to the point that both
D Chilled water pump running and chilled water flow
compressors are running at about 40% capacity, the
switch made
controller shuts down the lag compressor and loads the
D Leaving chilled water temperature at least 2°F above remaining compressor to about 90%. If applied load
setpoint decreases further, the remaining compressor unloads-
D All safety conditions satisfied proportionally. If applied load decreases to less than the
minimum capacity of one compressor, the leaving chilled
After all above conditions are met, the controller will call
water temperature will decline to 2°F below setpoint, at
for the lead compressor and the condenser water pump
which time the lead compressor will shut down. It will
to start. After a one-minute delay, the first contactor (e.g.
restart automatically if leaving chilled water temp rises to
1 M-1) is energized followed by the second contactor
2°F above setpoint and both 15 minute anti-recycle and
(e.g. 1 M-2) after one second time delay. This provides
one minute start delay timers are satisfied.
reduced inrush stepped start.
During operation, the controller monitors the difference
The compressor 15-minute anti-recycle timer is initiated
between condenser and evaporator pressures to insure
at compressor start.
that a minimum of 30 psi differential is available for
The controller monitors compressor amps, volts, leaving compressor lubrication. If the difference falls below a
water temperature, and evaporator and condenser minimum of 30 psi, the controller closes refrigerant flow
pressures. The compressor cooling capacity is controlled control valves, starving the evaporator, causing
by pulsed signals to load and unload solenoid valves on evaporator pressure to drop, increasing differential
the compressor. When the compressor starts, it is fully pressure. This is especially helpful at startup, when warm
unloaded, about 25% of its full load capacity. As the chilled water and cold condensing water would cause a
controller gives it load signals, capacity gradually low head situation. This feature is called EPCAS:
increases. The rate of compressor loading is governed by Evaporator Pressure Control at Startup. It is one of
ramp control which is adjustable in the computer. several proactive control features of the controller which
overcome potential problems while continuing operation.
The controller responds to leaving chilled water
temperature and its rate of change which is proportional Two additional proactive features are low suction and
and derivative control. If leaving chilled water temperature high discharge pressure override. If operating pressures
is within the deadband (+/-0.8°F from setpoint), no load or approach trip level, compressors are unloaded as
unload commands are given. If chilled water temperature necessary to continue operation.
is above deadband, the controller will continue loading
the compressor until a satisfactory rate of decline is
observed. If leaving chilled water temperature is below
the deadband, the compressor is commanded to unload.
Thus the compressor capacity is continuously modulated
- 10 -