A consumer’s LV installation supplied from TN distribution networks should have a main earthing

terminal (MET) that is connected to the protective conductor of the source and via this to earth
electrodes installed in the electricity distribution supply system. Where the installation provides
electricity supplies to a number of consumers, an independent earth electrode should also be connected
to the MET if the main supply has a combined neutral and protective conductor. In the case of TT and IT
systems the MET should be earthed by an independent earth electrode only. COMMENTARY ON 6.5 The
function of the MET is to provide a reference point for the installation. It consists of a terminal or bar
provided for the connection of protective conductors, including protective bonding conductors, and
conductors for functional earthing. BRITISH STANDARD BS 7430:2011+A1:2015