Generator operating in parallel with the electricity supply The parallel operation of mains excited
asynchronous or synchronous generators with an incoming mains supply provided by a distributor is
generally permitted. If there is a neutral point on the generator windings it should not be earthed. The machine framework, associated exposed-conductive-parts and extraneous-conductive-parts should be connected to the main earth terminal of the installation including the distributor’s earth terminal if provided. Synchronous and self-excited asynchronous generators may be operated in parallel with the supply if protection is provided to disconnect the incoming supply in the event of its loss or partial failure. Problems of neutral/earth circulating currents arise when a generating set is operated in parallel with an incoming supply; where the magnitude of the circulating currents would be excessive or if the generating set is also required to op