Professional Documents
Culture Documents
Billinton 2004
Billinton 2004
TABLE I TABLE II
RBTS RELIABILITY DATA BENEFIT OF ADDING 22.5 MW OF WTG UNITS
(4)
TABLE IV
WTG UNITS RELATIVE TO A10-MW CONVENTIONAL GENERATING
UNIT (RBTS)
TABLE V
WTG UNITS RELATIVE TO A20-MW CONVENTIONAL GENERATING
UNIT (RBTS)
Fig. 6. LOLE versus WTG total capacity assuming a 5-MW unit is removed
from the RBTS.
TABLE III
WTG UNITS RELATIVE TO A 5-MW CONVENTIONAL GENERATING
UNIT (RBTS)
TABLE VI
WTG UNITS RELATIVE TO A40-MW CONVENTIONAL GENERATING
UNIT (RBTS)
Fig. 9. LOLE versus WTG total capacity assuming a 20-MW unit is removed
from the RBTS (single-, two-, and three-wind farms).
Fig. 7. Replacement ratio versus mean wind speed multiplication factor
(RBTS).
Fig. 10. Replacement ratio versus the capacity removed from the RBTS
(single-, two-, and three-wind farms).
Fig. 8. Replacement ratio versus mean wind speed multiplication factor independent wind sites is much less, and locating WTG at in-
(IEEE-RTS).
dependent wind sites should be of considerable benefit in im-
proving the WTG reliability performance.
moval. The WTG units required to maintain the LOLE risk cri- Fig. 9 shows that after a 20-MW unit is removed from the
terion of 6.9 h/year were determined in each case. The replace- RBTS, the system reliability level cannot be sustained by the
ment ratios are shown in Fig. 8. As in Fig. 7, the columns with addition of WTG if they all located at a single wind site, but it
diagonal shading indicate that the criterion reliability cannot be can be restored by adding 220 MW of WTG if they are equally
maintained at the wind speeds shown. Replacement ratios exist located at two independent wind sites, or by 150 MW of WTG
and are shown for mean wind speed multiplication factors of 1.4 if they are located at three independent wind sites. The Regina
and 1.5, with a 350-MW unit removal. location wind regime was used in this study.
Figs. 7 and 8 show that the reliability contribution of WECS The same conventional units used in the previous case studies
depends on many factors including the wind conditions and the were removed from the RBTS. Similar analyses were conducted
WTG capacity. The mean wind speed has a very significant in- assuming that the WTG were equally located at two and three
fluence on the ability to replace conventional generation with independent wind sites. It can be seen from Fig. 10 that in-
WTG. creased wind independence has a significant positive impact on
the WTG reliability contribution. The replacement ratios associ-
ated with the two and three wind site studies are always less that
VI. RELIABILITY BENEFITS OF INDEPENDENT those for a single wind site. The studies conducted also show
WIND ENERGY SOURCES that there are decreasing benefits associated with increasing the
number of wind sites. It is important to note that the criterion
A WTG produces no power in the absence of sufficient wind reliability can maintained by adding WTG when a 40-MW unit
and under these circumstances makes no contribution to the is removed, if the WTG are located at three completely indepen-
power system. There is a definable probability that there will dent wind sites. It is also important to realize that 650 MW of
be insufficient wind at a given site. The probability, however, WTG capacity is required in this case. If the mean wind speed
of there being no wind simultaneously at two widely separated at each of the three independent wind sites is increased by 50%,
646 IEEE TRANSACTIONS ON ENERGY CONVERSION, VOL. 19, NO. 3, SEPTEMBER 2004