ACMV1: Air-conditioning Systems
Learning Objectives:
Learner should be able to discuss the requirements for mechanical ventilation systems.
Learners should be able to:
* Describe the functions of air-conditioning
* — Relate an air conditioning system and refrigeration cycle
* — List the different types of air conditioning system
* Explain the difference between an all-air, all-water and air-water system
* — Describe the operation of an air handling unit and a fan coil unit
* Compare CAV and VAV systems
* Describe different types of piping arrangement for all-water systems
* Describe the operation of air-water systems
* — Identify and compare different types of chiller
* Describe the components of a chiller
Abe NWOW
* Describe Cooling Towers, their efficiencies and estimate water consumption
* Explain the proper maintenance of cooling towers and Legionella disease.Types of Air-conditioning System
Introduction
As defined, air-conditionin;
(offices, shops, rooms, etc.) is to control and —
maintained the space at a temperature and
humidity, normally lower than its environment
for human comfort.
Thus, the hot humid air in the space is
removed to the outside which is the
atmosphere.
A fluid or “media” is used to absorb and
transfer the heat and humidity from the air-
conditioned space to outdoor, 2
The common fluids are:
4) Air.
2) Water.
3) Refrigerant.
Depending on types of air-conditioning
system, a combination of the dbove fluids are
used.
Other chemicals (e.g. glycol, eutectic
compounds, absorption gas, etc.) may also be
used for “special” air-conditioning.
Classification of Air-conditioning System
Depending on the'fluid or media involved, air-
conditioning systems are generally classified
into 3 systems. There are
(1) AlLAir System
(2) Air To Water System
(3) All Water systemi ll i memmay
Types of Air-conditioning System
For the common mechanical compression
vapor absorption air-conditioning systems, the
heat and humidity removed from the air-
conditioned space to the atmosphere are
through the following media processes:
1) Space Air to Refrigerant to Qutdoor
This is also classify as an all air system as only
air (and refrigerant) is involved.
In this system, the heat from the air-
conditioning room is transferred to the room
air and the heat of the room air is transferred
to the refrigerant.
Finally ,the heat from the refrigerant is
transferred to outdoor.
(e.g. Window units, DX systems, VRV systems). |
2) Space Air to Water (chilled water) to Air
System
This is also classify as air to water (to air)
system as only air and water (and refrigerant)
are involved.
In this system, the heat from the air-
conditioning room is transferred to the room
air and the heat of the room air is transferred
to the (chilled) water.
The heat from the chilled water is then
transferred to the refrigerant.
Finally, the heat from the refrigerant is
transferred to outdoor.
(e.g. air-cooled chilled water system or air-
cooled chillers).Types of Air-conditioning System
3) Space Air to Water (chilled water) to Refrigerant to Water (condenser water) to
Outdoor
This is also classify as an all water system as water (and of course refrigerant and also air)
is involved.
In this system, the heat from the air-conditioning room is transferred to the room
air and the heat of the room air is transferred to the (chilled) water.
The heat from the chilled water is then transferred to the refrigerant.
The heat from the refrigerant js transferred to the condenser water and the heat of the
condenser water is finally transferred to outdoor through the cooling towers.
(e.g. Water-cooled chillers).eee
Types of Air-conditioning System
All types of air-conditioning systems involve
heat exchangers to transfer heat from one
medium to another and from place to another.
Heat exchangers are termed evaporators and
condensers.
For DX and VRV systems, evaporators (FCU,
AHU) are located indoors and the condensers
are outdoors.
For chillers, the FCU and AHU are indoors
whereas the evaporators and condensers of
the chillers are either indoor (with cooling
towers outdoor) or outdoor with air-cooled
units.
DX denotes Direct Expansion.
VRV denotes Variable Refrigerant Flow.
Advar et
1) Outdoor Condensing Units are air-cooled
and can cool multiple indoor fan coil units,
hence function similar to chilled water system
except the capacity could be as low as 14 kW
cooling capacity.
2) The refrigerant piping length between the
indoor unit in one system can extend to 150.
meters and the difference in height can be as
great as SO meters.
3) Water pumps are not necessary to pump
the chilled water to the FCU.
4) The condensing units could be in modular
form for easier addition of cooling capacity if
required.
5) Easier to install and less costly compared
with chilled water systems.poe
All Air System: Variable Refrigerant Flow (VRV) System
VRV System
As shown in the Figure below, the condensing unit is installed outside the air-conditioned room,
open to the atmosphere in which the hot air is dissipated.
Normally it is either installed
1) on the building flat roof,
2) onsolid ground, or
3) Suspended and mounted on a solid wall.
The evaporator is mounted inside the air-conditioned room.
Interconnecting the condensing unit and the evaporator are the insulated refrigerant supply and
return pipes.
The condensing unit houses the compressor driven by the motor and the condenser cooled by
the fan driven by another motor.
The return air-conditioned air (in the air-conditioned room) passes through the evaporator with
the aid of a fan driven by motor and is thus cooled by the refrigerant in the evaporator.(VRV System Comparable with Water Chiller System)
(Source: Daikin)
@ Heat pump type
150 m
eee
Level dilferoncs’ Actual piping
‘Between indoor Tength
and outdoor units
41 This valua is based on the outdoor unit being located above the indoor uni.
|ithe outdoor unit i located below the indoor uns. the level iference is a rhanirnuin of
40m
442 Tho miaximum actual pining lanth betWeon the incor unit and the fist brasich is 40 m,
43 Equivaient pipe length between outdoor ang indoor unis < 175 m
‘ee Total piping Jength 909 mAdvantages of VRV System
Advantages of VRV System
1) Outdoor Condensing Units are air-cooled and can cool multiple indoor fan coil units,
hence function similar to chilled water system except the capacity could be as low as 14 kW.
cooling capacity.
2) The refrigerant Piping length between the indoor unit in one system can extend to 150
meters and the difference in height can be as great as 50 meters.
3) Water pumps are not necessary to pump the chilled water to the FCU.
4) The condensing units could be in modular form for easier addition of cooling capacity if
required.
5) Easier to install and less costly compared with chilled water systems.
eS —VRV System Comparable with Water Chiller System
(Source: Daikin)
Water Chiller System YRY systemAll Air System: Room Window Unit
Room Air-conditioner
Aroom air-conditioner is an encased assembly
designed as a unit primarily for mounting in a
window or through a wall. These units are
designed for the delivery of cool conditioned
air to the room, either without ducts or with
very short ducts up to a maximum of about
1200.mm. Each unit includes a prime source of
refrigeration, dehumidification, and means for
circulating and cleaning air, and may also
filtering or cleaning, and circulating the room
air. It may also provide ventilation by
introducing outdoor air into the room and/or
exhausting room air to the outside. Also,
comfort may be provided by control- ling the
room temperature through selection of the
pen rns on
Room Air-conditioner
(Source: ASHARE Handbook)
CONDENSER DISCHARGE AIR
oxeomt {| [| T
COMPRESSOR tC ia tn al
ouysee
rt i
Ep atower
om HM SURE aR
T | [=
WAR ROOM AIR,
Ty
COOLED'ROOM AIRselection of the desired thermostat setting.
Warm room air passes over the cooling coil
and, in the process, gives up its sensible and
latent heat. The conditioned air is then re-
circulated in the room by a fan or blower.
The heat from the warm room air vaporizes
the cold (low- pressure) liquid refrigerant
flowing through the evaporator." The vapour
then carries the heat to the compressor, which
compresses the vapour and increases its
temperature to a value higher than the
temperature of the outdoor air. In the con-
denser, the hot (high-pressure) refrigerant
vapour liquefies and gives up the heat from
the room air to the outdoor aif. The high-
pressure liquid refrigerant then passes
through a restrictor, which reduces its
pressure and temperature. The cold (low-
pressure) liquid refrigerant then
All Air System: Room Window Unit.
re-enters the evaporator to repeat this
refrigeration cycle.
1 ‘i ities of .
available room air conditioners range from 1.2
to 10.5 kW.
Room air conditioners are equipped with line
cords, which may be plugged into standard or
special electric circuits. Most units are
designed to operate at 230 V, single- phase,
50-Hz power.Air-water and All-water Systems
Chillers (Air-cooled or Water-cooled|
All chillers normally have SHEWeneraBe Hermetic Centrifugal Compressor
‘exchangers (evaporators and condensers), (Source: Cartes Handbook)
as re-circulating fluids. CONDENSER
However, chillers have different types of oa
compressors. CONDENSER
a waren coupresson
Centrifugal Compressor
Centrifugal compressors are advance and
ranges in capacity from more than a hundred
refrigeration tons (RT) to a few thousand RT.
Under ARI standard, centrifugal compressor cmittzo
WATER
can achieve 0.52 kW/RT at 80 % to 100 % load. ae
The efficiency drops below 80 % load. REFRIGERANT REFRIGERANT.
‘VAPOR . Liauia
The figure shows hermetic véntrifugal
compressors as the semi-hermetic and open
compressors have been phased out due to
common refrigerant leakages at the shaft seal
po eeAir-water and All-water Systems
between the compressor and motor.
For Open Centrifugal Compressor, see Figure.
Centrifugal Compressors are:
1) Reliable.
2) Compact.
3) Low maintenance costs.
4) Long life.
5) Ease of operation.
6) Quiet :
However, centrifugal compressors if unldad to
less than 60 %, efficiency drops.
There is also a possibility of surging.
Open Centrifugal Compressor
(source: carer Handbook)
CONDENSER
CONDENSER
WATER
compressor (
svorion | f
bauer ~|
Economzer
coouER
CHILLED
BRINE
REFRIGERANT 7 REFRIGERANT
VAPOR Liawr—
Air-water and All-water Systems (Rotary Screw Chillers)
(Source: ASHRAE Handbook)
‘SCREW ROTOR
OVSCHARGE
PORT
\
me
cnn
Ces *
cs
ZENS outst
Suctlon. During rotation of the main rato, a
typical groove in open communication with the
suction chamber grzdually fills with suction
‘gas. The tooth cf the gaterotorin mesh with the
groove acts as an aspiraling piston.
Compression. As the main ro:er turns, the
gruove engages 4 tooth on the gaterotor and
is covered simultaneously by the cylindrical
main rotor cesing. “he gas is trapped in the
space formed by the tate sides of the graove,
thecasing, and the gateroior toot”. As rotetion
continues, thz groove volume decreases and
compression occurs.
Dischasge. At the geometrically fixed point
véhere the leading edge of fhe groove and the
edge of the discharge port coincide, compres-
sion ceases, and the gas discharges into the
delivery line until the groove volume has bees
reduced to ze".Air-water and All-water Systems (Rotary Screw Chillers)
(Source: ASHRAE Handbook)Air-water ahd All-water Systems (Rotary Screw Chillers)
Rotary Screw Chillers
Rotary screw chillers have beeh in existence for many years except they are normally used
on ships. They are‘now commonly used in buildings.
Advantage of Rotary Screw Chillers
1) Stable (Do not surge).
2) Able to unload to low capacity (10 %) using sliding valve control mechanism.
3) Efficiency is comparable to centrifugal or better at less than 80 % load.
4) Capacity starts from 80 RT.
Posr
Air-water and All-water Systems: Rotary Scroll Chillers
Rotary Scroll Chillers Rotary Scroll Mechanism
Advantages of Scroll Compressors (Source: Emerson)
1) No pistons to compress refrigerant gas,
hence no volumetric efficiency loss
through re-expansion, which occurs
typically with each piston stroke in
reciprocating compressors.
2) Similarly compare with reciprocating
compressors, no valve losses as valves
have been eliminated in Scroll
compressors. .
3) Centrifugal force in Scroll compression
nearly continuous, hence leak free.
4) InScroll, separation of suction and
discharge refrigerant gases reduces heat
transfer losses.
Note: Reciprocating compressors in air-
conditioning have been phased out due to
inefficiencies. They are now replaced with
rotary compressors.Air-water and All-water Systems: Rotary Scroll Chillers
(Rotary Scroll Chillers)
reer Modulation Chamber
A
NX Solenoid
Bleed Hole Valve
Spring
Lift
Piston Assembly ,Air-conditioning Systems
Fan Coil Units (FCU)
1) Filter.
2) Fan (commonly centrifugal).
3) Motor.
4) Cooling coils.
5) Casing.
There is a return air inlet where outdoor air is
mixed and a conditioned air discharge.
The unit is supplied either with chilled water
or refrigerant, depending on the air- . *
conditioning system used.
Not shown is the thermostatic expansion valve
that restrict and control the amount of chilled
water (or refrigerant) into the cooling coil.
Commonly, the fan has 3 speed control: High,
medium and low.
Fan coil units have low static discharge
pressure. If ducted, the ducts should be simple
Fan Coil Unit
(Source: Carrier Handbook)
CONDITIONED AIR
RECIRCULATED
AIRAir-conditioning Systems
Ceiling Cassette FCU
and short so as not to create high duct friction iting Cassette FCU
losses. (Source: Carrier Product Catalpogue)
Linear or slot diffusers should fot be used for
ducted FCU as linear or slot diffusers require
high static pressure to create proper air throw.
Ceiling (flushed) cassette FCU are commonly
used to blend attractively with the decorative
environment without the use of ducts (or
diffusers) as they have inbuilt outlet diffusers
and return air inlets.
Normally, the number of rows of cooling coils
in FCU is limited to a maximum of 3.Air Handling Units are basically the same as
Fan Coil Units with similar basic components
such as a centrifugal fan with motor, air filter,
cooling coils and a metal casing.
The differences of AHU and FCU are:
1) Centrifugal fan and motor is bigger,
allowing high static discharge pressure to
overcome friction losses due to ducts and
air outlet diffusers.
2) The number of rows of cooling coils could
3) Mixing boxes or plenum could be added.
4) More rows of air filters could be added.
5) Special high static filter could also be
used,
6) Variable speed drive (VSD) fan could also
be specified.
7) The centrifugal fan could be specified
either backward curve or forward curve.
Air Handling Unit
(Source: Carrier Handbook)Air Handling Units
(Figure from Carrier Handbook)
8) The AHU could also be specified either draw-thru or blow-thru.
9) The fan is belt driven and (to a certain extent) the speed of the fan could be adjusted.
10) AHU configuration could also be specified to be vertical or horizontal to suit the AHU room
height and space.Air Handling Units
(Figure from Carrier Handbook)
SUPPLY a
HLAHNG Cou
HOT WATER
SUPPLY & RETURN
FILTERS
MIXING PLENUM,
) (RETURN /OUTSIDE AIR)
CHILLED WATER
‘SUPPLY & RETURNAir Handling Units: Horizontal & Vertical AHU
Horizontal AHU Vertical AHU
(Source: Trane Product Catalogue)
(Source: Trane Produet Catalogue)
TRH Gel OREN MAN
Horizontal &
Verticalandling Units
(Source: Trane)CAV and VAV Systems
(Source: Variable Air Volume Manval by Herb Wendes}
Introduction
* — Sun moves from east to west during
daytime.
* Sun movement has dramatic effect on
cooling exterior area of buildings.
* — East, south & west perimeter exposures of
buildings (zones 2,3,4) aré most greatly
affected.
Maximum loads can be double or triple
minimum loads.
* Interior & north perimeter zones directly
under roofs are affected to some degree
whereas these zones in between floors in
multi-story buildings are riot affected.
a. “ acai ns
Effect of Shifting Sun Load on Different Zones of Buildings
Shitting Sun Load
ssa [S| wr
Amat route
(joe so {ate om
(oa. 4a), tan 8
ot
(ast. 2 ra)
(an mh
fs com vig eno ent tt ugh ey, iting sn
ocd has 2 rama coct on the ext area colin reqVariable Air Volume (VAV) System
Variable air volume system operates on the
principle of modulating the arijount of supply
air rather than varying the supply air
temperature to each air-conditioned space.
By definition, the supply air temperature is
held constant for a true VAV system.
Advantages of VAV System
1) Does not waste energy (as the system
responds to the load demand by varying
the amount of supply air into each air-
conditioned space).
2) Requires less AHU room space (as AHU is
usually smaller due to lower supply air
temperature, hence less supply air).
3) Sizes of ductworks are smaller, as less
supply air is transported from the AHU to
the air-conditioned spaces.
4)
correspondingly reduce, resulting in less
energy consumes by the VSD fans.
Disadvantages of VAV System
1)
3)
More difficult to maintain pressure
* relationship between adjacent air-
conditioned spaces due to fluctuating
supply air as load varies.
The minimt i
for the air-conditioned space may be
affected due to lower supply air as the
load reduces.
In temperate countries, some form of
supplementary heating may be
required, as in actual application as the
supply air temperature may also varies.CAV System Compared with VAV System
Constant Air Volume (CAV) System Disadvantages of CAV System
By definition constant air volume maintains The major disadvantage of CAV system (as
the same amount of supply aif to the room to compared with VAV) is energy usage due to:
be air-conditioned and only the supply air 1) More energy (compare with VAV) at.
temperature varies in accordance to the partial load.
demand load of the room. The chilled water 2)
supply (or the chilled water terhperature) \ehsmesuaaga (rooms) that require comfort
: a f air-condition.
varies to match the supply air temperature in
the thermostatically-controlled valve.
Advantages of CAV System
Advantages are: \
1) Simple to design.
2) Easy and reliable to operate.
3) The ability to supply any constant amount
ish ;
IAQ).
rn Soe een
Cav and vav Susiems 4 , 1c(Source: Variable:
For Example,
The building actual peak load is 220 tons and
the design load is 310 tons.
* Fora VAV system a diversity factor could
be used on the design load.
* The diversity factor could be 20% to 30%,
depending on the design of the air-
conditioning system.
CAV and VAV Systems
(
‘Volume Manual by Herb Wendes)
Design Load & Actual Operation Load of a Building
Various Totel Cooling Load Profiles
for Billerent Concilions
sons i
coottte |
gon oun 230 rome, 124,
a pom aa
F
:
:
Acres tn aco cen
Ce oe
200 !
smn oozes sano
120'asy sae ee
i cera to
0 sgn, 00 ee
sorrtie otcenr ro tomo
rm, aoe een L
‘etn irre
* Srecamath ats
voow | pn EDUC
‘nce aan stan fo outing wl coh Pa pe oa rent
semen dung ts ea te inch wa peat loads witmovor accor aio war a.CAV and VAV Systems
C
(Source: Variable Air Volume Manual by Herd Wendes)
* Depending on the type of building the Source: ASHRAE Handbook
cooling load profile varies not only from
zone to zone but also on the time of the
day. rows
* The sun load & the outside air ventilation 0 }-—4+_+-—
load with their rising temperatures &
humidity during the day are the most
Profifes of Different Cooling Load Factore
LeKTING LOA
volatile.
+ The wall, window & roof conduction loads atl =
* Lighting, people & internal equipment
are second in intensity of variation ° | =
loads reach a peak at start of the day, |
remain constant, then drop off sharply at
day’s end. sol
loads have their own peak times. 20} +f} — | |
‘oohouerIaN Wand
tr. |
1
* Cafeteria, kitchen, laboratory exhaust |
W008 ip
Oye mEDNTaT
foun coodhn lant Ir a Halong oF zone varie,
roca Uo wemechty wt th at Sap
rrr ———(VAV Systems)
Multi-zone VAV systems have a single
central AHU.
Each zone has its own thermostat to
control temperature.
Different zone load requirements are met
by mixing hot & cold air through the
dampers.
To vary the air volume in the zones, VAV
terminals are used. The volume of cool air
is reduced to a minimum fitst, then if the
load decreases further, thé cold & hot
deck dampers modulate the
temperatures.
feew
_ Gt en ate
4 rhyme OB) hae etal teen
AHU of Multizone VAY SystemVAV Systems
* — VAV Terminal modulates air flow between
maximum & minimum settings, reduces
velocity & pressure, attenate sound.
* When there is low cooling required, air 7 7
reduces to a minimum flow but always at Pneumatically Controlled VAV Terminal
a constant supply temperature of say, 12
degree C (54 degree F).
* Intake sensor monitors the differential
pressure & the VAV controller modulates
the volume damper. pisciinnse,
* (IF VAV terminal is electric, air compressor
not necessary).
‘Compenents ofa Typical VAV Terminal,VAV Systems it
Datgiwer = grille
sg ° 00
SMASHAIAG. eee 7198 , 990
Deseeser G the Spe ex der
— Anu sae ace)
Ta or
Velume ee
iN
Constant o BER pe Kor
Speak) CAV System
3 , SIBSuyer
piddaser
VAY
AYU Tereniole
atl Supplfaar conch :
CR vay
Space
G cepa) “
VAY Syston
Biber on ore
ean?
gee?jsooo
onal
VAV AHU With Control au ¢
[RSNA Appian Gul To Commission of VAV Sate) ott
als
bore
‘Duct fe.
yt a ee
img
COek Bho, CONTA, ps7?
ries tort amie). rane oanrcn ;
taoicy wows a age gee?
jaf ran
Pee CONSTANT EEO DR oH
TeergnaruRe PRESEIRE Ate
a aerate 2000 19 se00 Fem
2
Lexa] cantaonys °
= way Boe a
sn ean aim vanes wovune or NS
race nuns Cha sone ,
ears *
the
r i
Vow rua aga a
eerieVAV Systems
(2SRIA Application Guide To Commission of VAY System)
* — Static pressure sensors (or air flow VAV System (Cooling Only, Single Duet)
measuring stations) in the main duct
monitor the changing pressure (or flow),
tc
eat acct vsat Deven
ceonetann
won
bre Bhs —,
ae
aggregate = gouieesoS ain n
1
Vane = qero8 se0ch) gf BoeVAV Systems (Frequency Inverters)
(Figure from ASHRAE Hendbook)
Frequency Inverters
The characteristics of frequency inverters are:
1) maintain motor efficiency regardless of
rpm or hp.
2) Motors do not lose power factors & stay at
95%.
3) A 10% increase in temperature ona motor
decreases insulation life 50%.
4) Isolation transformer need to be used to
filter noise interference from computers/
programmable controllers.
5) If motors run at same speed & starting/
stopping times are the same, one inverter can
be used for 2 or more motors.
Frequency Inyerters To Vary the Speed of Fan Motors0
rt
co 26 Lat >
Ft
Note:
Flow Rate of Cooling Tower
= Flow Rate of Chiller’s Condenser
Temperature In of Cooling Tower
= Temperature Out of Chiller’s
Condenser
Temperature Out of Cooling Tower
= Temperature In of Chiller’s
Condenser
o wee
@ * i
Cooling Tower
7
iE
Globe Valve ner»
Condenser
C-Aeb
ca
weve T oC
giz bed.L. Lott zi : - s ape
a ay ATER CER EE
ce‘ASHRAE PSYCHROMETRIC CHART fot
NORMAL TEMPERATURE EVEL
povetnomesnne, —_tougrien
CcopyRici 182
AMERICAN SOCIETY OF HEATING, REFRIGERATING ANO AR-CONDIIONNNG ENGWEENS, NC.
ii i Pat halo
Lape Bie
=)
- é 2: SaoeaToneTE cInstruments For Measuring Properties of Moist Air
(II) Measuring Instruments
The instruments use for measuring
properties of moist air are:
A) Electronic Thermometers
There are many types of rugged, light
weight, battery powered digital
Electronic thermometers that have
Precision accuracy with interchangeable
probes and/or sensors.
Types included are: ,
1) Resistance temperature detectors
(see Figure) ;
2) Thermistors;
3) Thermocouples;
4) Diode sensors, with either liquid
crystal or LED displays.
Response time and ease of use will vary
from model to model and type to type.
Sof. distrur J
Instruments For Measuri= Pr-> ert’EPCATUL PURI WA ES LS fp
Instruments For Measuring Properties of Moist Air
bo
B) Psychrometers
Sling psychrometer can be used in
determining the psychrometric
Properties of the air-conditioned spaces,
return air, outdoor air, mixed air, and
conditioned supply air.
The readings taken from the
sling psychrometer can be spotted ona
standard psychrometric chart from which
all other psychrometric properties of ‘the
measured air can be determined.
The sling psychrometer (see Figure)
consists of 2 mercury filled
thermometers, one of which has a
Wetted cloth wick or sock around bulb.
The 2 thermometers are mounted side
by side on a frame fitted with a handleInstrumehts For Measuring Properties of Moist Air
by which the device can be whirled with Therefore, an instrument with an 18 in.
a steady motion through the surrounding (450 mm) radius should be whirled at a
air. The whirling motion is periodically rate of 2 revolutions per second.
stopped to take readings of the wet and Significant errors will result if the wick
dry bulb thermometers (in that order) becomes dirty or dry, so a constant
until such time as consecutive readings supply of distilled water should be used.
become steady.
Because of evaporation, the wet bulb Digital battery powered versions are
thermometer will indicate a lower available that blow the ambient air over
temperature (wet bulb temperature) the wetted wick.
than the dry bulb thermometer, and the These instruments are accurate and they
difference is known as the wet bulb can be placed into confined areas where
depression. there is insufficient room to whirl a sling
Accurate wet bulb readings require an air — psychrometer.
velocity of between 1000 and 1500 fpm
(5 and 7.5 m/s) across the Wick, or a
correction must be made.
—_—
strlsvents ror Meastinng Pronernias at winicr airC) Electronic Thermo Hygrometers
Unlike the psychrometer, the
thermohygrometer (see Figure) does not
utilize the cooling effect ofthe wet bulb
(as used in Sling Psychrometers) to
determine the moisture coptent in the
air.
A thin film capacitance sensor is used as
a sensing element in mdily instruments.
Asthe moisture contentand
temperature change, the resistance in
the sensor changes proportionally.
Read-out is normally in % relative
humidity.
Because the instruments do not rely
upon evaporation for measurement, the
need for airflow across the wetted wick
Instruments For Measuring Properties of Moist Air '
or sock is eliminated.
The sensing element needs only to be
held in the sampled air.
Typical measuring ranges are 10 to 98%
RH, 32 of to 140 of (0 °C to 60°C).Instruments For Measuring Properties of Moist Air
D) Electronic Thermo Hygrometer with
Flexible Probe
Manufactured by “testo”, this is a
portable measuring instrument to
measure air humidity and temperature.
With a flexible probe, the air conditions
inside the duct could be measured.
Hie te
oLomMXN
Sin SSSRHPsychrometry ‘
(Ill) Psychometry of Air-conditioning Process
(A) Basic Processes in conditioning of air
The 8 basic thermodynamic processes by
which the state of moist air cah be altered are
shown as follows:- ®
i) Sensible heating - OA z
ii) Sensible cooling - OB 8
iii) Humidifying - OC a
iv) Dehumidifying - 0D re
v) Heating & humidifying - OE z
vi) Cooling & dehumidifying -. OF §
vii) Cooling & humidifying - 0G B
viii) Heating & dehumidifying = - OH
DRY BULB TEN TPsychrometry
Sensible heating & cooling, involve only
change in the dry bulb temperature, and there
is no change in the moisture content of the air.
Humidifying & dehumidifying processes
involve a change in the specific humidity and
the dry bulb temperature remains constant.
However, most practical moisture-transfer
processes involve both changes in the
V/ temperature as well as in humidity. -—~—
6 (B) Sensible Heat Process - Héating or cooling | A |
The heat has to be transferred which goes to | |
change the temperature of the airis given by
Gas 2bx attblon (75) % forprrasure clifderuee ) | |
( i
Q.=MC,ty-t,) =12321/ xt) at tS DRY BULB TEN T
= = Naot, Sa
Qss Sensible Het bw)
ion amore CC) =) “H
la = BPH of TA Chain
~ 1
Vs Ss
\
SPECIFIC HUMIDITY Wvse hes
Psychrometry
(C) Latent Heat Process — Humidification or
Dehumidifcation
The amount of water vapour added or
removed from air in a humidifying or
dehumidifying process is:
m,, =m, X (We - We)
where
m,, = water vapour added or removed
(kg/s)
m, = mass flow rate of air (kg/s)
We- Wg = change in humidity ratio (kg/kg
d.a.)
As with the sensible heating process, it is
usually acceptable to assume air at standard i
conditions.
The latent heat transfer is given by ~ DRY BULR TENT
Q,=m, x (he- hy) Vss 6-8 gt Ay de
Or Q.=m, x hig x (We- Wp) > Paw i
where m, = mass flow rate kg/second
hg= latent heat of vaporization of water
at 0°C = 2500 kJ / Kg
a
2
é
SPECIFIC HUMIDITY W
ue
uve
WhPsychrometry
We- Wa = change in humidity ratio kg/kg d.a.
>
Q, =3.0x1/s x Aw(W) or O, =3.010 x xAw (kV)
$
Aw = mositure content difference , kg / kg of dry airPsychrometry
(D) Total Heat Process
Consider a change in the state of air along the
path AC as shown.
Total Cooling Process Load is
OQ, =1.23 x1/s x AhW)
or Or; =1.23x m/s x Ah (kW)
Ah= change in enthalpy of air ,kI Ikg of dry air
DEY BULB TEN T
3
3
SPECIFIC HUMIDITY WPsychrometry: Air Mixing
(IV) Air Mixing Process
The air mixing process is one where two An
streams of air are mixed to form a third comer ha
stream. This process occurs frequently in air- mi ®
% 4 Miyer ty
wt
conditioning, particularly in mixing outside air seael
with return air from rooms.
(A) Air Mixing Process using Calculation a3 1a
The humidity ratio of the mixed air can be
obtained by applying the principle of
conservation of mass.
m, W; =m, W; +m, W,
Or W3= (m,W, +m,W,) /m3
Where m, = m, +m, is the mass of dry air in
the mixture.
Or using flow rate, Q m/s (density of air, p =
mass / volume and p is constant),
W5 = (Q W;+ QW) / Oy yTo find the enthalpy of the mixed air, a heat Hence,
balance may be applied: m3 xC, xt; =m,xC, xt, +m, xC, xt,
hy= (mgh, + mjh,) / ms 0%,
= (Qih, + Qh,) / Q, Also, ty = (mgt + mgt.) / mg
Using the basic heat equation with specific as C, is constant.
heat and air temperature,
Heat of air at duct 1=m,xC, xt,
Heat of air at duct 2=m, x C, xt,
and
Heat of air at duct 3 =m, x C, x ts
where C, = specific heat of air, i
t = temperature of air in duct.
m = mass of air in duct.
yews TH ngs wndlf poured poscune
Caer out dem aAy,: Air Mixing Process Example
In air-conditioning the outdoor air mixes with the return air before going into the cooling coils
and circulate back into the air-conditioning room..
Retuon Aiv Rew
trne
tom. Wri
(CMM}ra ar
% oolne
a Supply Ai
Quidesr Rann
Au: C
(CMM}ca {CMM)s0.
ae dan
Woa Wea
ie rl IXi ogy: Alt Mixing
(B) Mixing Process Using Psychrometric Chart
The mixing process can also be solved on the
Psychrometric, from the following two facts:
1. The mixed air condition will lie along a
straight line connecting the two he
conditions of the unmixed airstreams S
2. The position of the mixture state is such
that it divides the straight line joining
stated 1 and 2 in the inverse ratio of the
masses m, and m, of the two air streams
or flow, and flow, of the two air streams.
SPECIFIC HUMIDITY ¥
aw 8 of
DRY BULH TEN TPsychtometry: Sensible Heat Factor Ration Line
{V) Sensible Heat Factor (SHF)
The ratio of the sensible heat transfer to the total heat transfer is termed as sensible heat
oe a7 ey
factor.
where Q, = sensible heat
Q, = latent heat 3 fe
This SHF ration line can be plotted ii
A lot hot wae Soraysig hose GL tonmter Pron
ye, ond
wo ta howl mM By -wr
the Peychrometric Chart.—_——— — —————— |-—nXnKn—l my TT
Psychrometry
(VI) Air Conditioning Processes
(A) The Air Process
The figure shows a typical air conditioning
process trace on a Psychrometric chart.
1. Return air from the room 1 is mixed with
outdoor air 2
2. This mixture of outdoor and feturn air 3
enters the apparatus where it is conditioned
to 4 and supplied to the space.
3. The air supplied to the spaces moves along @
line (4-1) as it picks up the room loads, and
the cycle is repeated. - oO
Hite ®
BFECRIC HUMIDITY ¥
‘DRY BULB TEX TPsychrometry: Air-conditioning Process
(B) Simple Air-conditioning system and State
And Mass rate of supply air
The rooms in a building gain both sensible
heat and latent heat (The procedure for
calculating these heat gains have been Return Air pee
discussed previously). tem, Wro pedal
In order to maintain the space at the design Samat —
temperature and humidity, the sensible heat } eo
and latent heat must be removed from each eerie fone” NT
room. (ouMdjoa {QasOe0
Woa Wan
When a space is conditioned by using air, this
heat removal is accomplished by supplying air
at a temperature and humidity lower than
that of the room air.
Hence, the problem of air-conditioning a
space essentially reduces to the calculation of
the state and mass rate of air to be supplied to
the space necessary to pick up its sensible and
latent heat loads. =
Consider a space which is to be maintained at
the room design conditions of trm, W,,, -
rr
- 1 SVClMUMetty. Airscanditianina Brarace= “ro. de ec “tion ‘yf tr Wy, 4 ~
Psychrometi onditioning Process ‘
By sensible and latent heat balances given by Q,/ (Q5+Q).
Sensible Heat Balance Any supply air condition that will satisfactorily
RSH = Q, = Ma x Cp x (trm - tsa) remove the proper proportion of room sensible
= 1.23 x I/s x(trm-tsa) (Watts) and latent heat gains will be on this line, and in
Latent Heat Balance addition any supply air condition that is not on
RLH = Qi = Ma x hfg x (Wrm - Wsa) this line will not be satisfactory.
= 3.0 x I/s x (Wrm - Wsa) (Watts)
We have only two equation and three O ender wn aytncrd
independent variables, viz. tsa, Wsa and Oo awl cong
(flow), to solve. Hence one of the three
variables is to be known in advance or fixed
from experience. Generally, it is either the
supply air flow rate, I/s or the supply air
temperature, tsa. The other two parameters
can then be calculated.
Thus we find that there will be one supply air
state corresponding to each supply air rate.
An innumerable number of such combinations
are possible. All the supply air state lie on a
straight line (SHF line), the slope of which isPsychrometry: Air-conditioning Process (Sensible Heat Factor Ratio Line)
The supply air to a conditioned space must
have the capacity to offset simultaneously
both the room sensible and rdom latent heat
loads.
The room and the supply air cohditions to the
space may be plotted on the Psychrometric
chart and these points connected with a
straight line (1-2).
RSHF Line plotted between Room and supply
air condition
This line represents the Psychrometric process
of the supply air within the cohditioned space
and is called the room sensible heat factor
line.
The slope of the RSHF line illustrates the ratio
of sensible to latent loads within the space.
Thus, if adequate air is supplied to offset these
room loads, the room requirements will be
satisfies, provided both the dry and wet bulb
temperature of the supply air fall on this line.
Supply air
DRY BULB TEM T
BPECIFIC HUMIDITY ¥ir-conditioning Process (Sensible Heat Factor Ratio Line)
RSHF =—_RSH 2s
RSH +RLH 0,+0,
1.0
Room
Step 2
RSHF
Supply air
SPECIFIC HUMIDITY W
DRY BULB JEM TPsychrometry: Aif-conditioning Process (Sensible Heat Factor Ratio Line)
Air-Conditioning System with Ventilation Air siz = —8S# Qe
RSH + RLH 0,+0,
Room
Qs
QL
Cuosling Coil
2 a 4
Schematic diagram of system with ventilation air
a) CU
~ veVChrometiy 2Psychrometry
10
Mixture
SPECIFIC HUMIDITY 7
Supply Ar
DRY BULB TEM TPsychrometry: Air-conditioning
Example 1
A lecture theatre is 12 mx12mx6m. Itis
maintained at 23°C DB, and has four air
change per hour of cooled air-conditioned air
supplied at 15°C DB. Calculate the maximum
cooling load that the equipment can meet.
Sau
Nair changes . yy)
3600S
Air flow =
1 ‘
=4x12x12 x6 x —— m/s =0.96 m/s =9601/s
3600
= 1.23 x! x ar=1.23 x 960 (23-15) =9.46 kW
s
Example 2:
An office has a sensible heat gain of 10 kW
when the room air temperature is 25°C DB.
Calculate the necessary volume flow rate of
supply air to maintain the room at the design
temperature when the supply air temperature
can be 13°C.
o=123 x4 eat
5
Q 10,000
co i =6715 1/5
s 1.23xAt 1.23(25-13)Psychrometry:
Example 3
An office has a sensible heat gain of 12 kW
and four occupants each having a latent heat
output of 40W when the room air condition is
23°C DB and 50% RH.
Calculate the necessary volume flow rate of
supply air and its moisture content to maintain
the room at the design state when the supply
air temperature can be 12°C DB. The room air
moisture content is 0.0088 kg/kg of dry air.
Solution:
(a) Calculate the supply air quantity from the
sensible load equation,
ie 12000
fp 8 9 ser iis
S 123xAt 1.23(23-12)
(b) Latent heat gain = 4 person x 40 W/person
=160W
Use the latent heat equation to find the supply
air moisture,
ir-conditioning (For Tutorial).
Q 160
130x887
Aw=—2—
3.0x5
= 0.06013 g/kg of dry air
w, —w, = 0.06013
Ww, = w, 0.06013 = 8.8-0.06013=8.74 g/kg of da
Therefore supply air conditions are 12°C DB,
humidity ratio of 8.74 g/kg of dry air.Psychrometry: Air-conditioning
Example 4
Agiven space is to be maintained at 25.6°C DB and 18.3°C WB. The total heat gain to the
space has been determined to be 17.6 kW of which 12.3 kW is sensible heat.
The outdoor air requirement of the occupants is 236 |/s.
The outdoor air has a temperature and humidity of 32.2°C and 55 % RH, respectively.
If the supply air is supply at 12°C, determine the quantity and the state of the air supplied
to the space and the required capacity of the cooling equipment.
P Pevehrometry: } = } } =Solution
sur =123-07
176
L
sup ply air quantity, —
12300
ware 7 Ss
1.23(25.6 -12)
Return air quantity = 735-236 = 499 1/s
Qyt + Qaty = Ost
Qs
Oil + Ost, _ 236102.24 499956
=27.7°C
735
12
c
26.8 a7 p22
DRY BULB TEM T
SPECIFIC HUMIDITY ¥Psychrometry (Schematic of Example 4)
—~ ectenst
= ; ~ =
Newell
4
Cooling Cell
2/3 4 Spr tee ee
slice ae cl = i249 Gi
cutee ae 1
ze 1/2
Foo hre try ee itio...gDraw a line from 1 with slope SHF =0.7 and
intersect the 12 degree C line at point 2.
Point 2 is 12°C DB and 90% RH (Supply air to
room).
The cooling coil capacity
=123x Ls(ai)= 1.23x735 x(62.8-39.4) W
= 21154 W = 21.15kW = 6 tons
12¢
26.8 py P22
DRY BULB TEM T
SPECIFIC HUMIDITY ¥Psychrometry: Air-conditioning
Tutorial:
Questions
Q1: The weather reports reads 32°C DB & 40
% RH. What is the WB temperature .
Q2: The air leaving a cooling coil is at 16°C
DB and 13°C WB. What is its humidity ratio &
enthalpy.
Q3: Combustion air enters a furnace at 26°C
DB and 23% RH. What is its specific volume.
Answers:
Al : WB = 22°C
A2_ : humidity ratio = 8 g/kg d.a.
A3 :v = 0.855 m3/kg d.a.
Q4: 3 m3/s o fair enters a cooling and
dehumidifying coil at 30°C DB AND 21°C WB
and leaves the coil at 15.6°C DB and 14°C WB.
Determine:
(a) the apparatus dew point of the coil
(b) the bypass factor of the coil
(c) the rate of water condenser in kg/hr
the total heat removed by the cooling coil in
kw.
Q5: An air conditioning unit has a cooling coil
that cools and dehumidifies 9,4 m3 of air from
28° C and 50% RH to 18°C DB and 16°C WB.
Find the sensible, latent an total load capacity
of the cooling coil and amount of moisture
condensed.Psychrometry
Example
The indoor condition of a roo is to be
maintained at 25°C and 50% RH .The outdoor
condition is 33°C DB and 27°C WB. The room
has a design cooling load of 7 kW sensible and
1.5 kW latent load. If the mixing ratio of the
return air to the outdoor air is 3: 1.
Find:
(a) The apparatus dew point.
(b) The bypass factor of the coil.
The condition and quantity of the cooled
air to be supplied to the room in order to
the achieve design condition.
(c
Solution:
Plot the following points on the psychrometric
chart:
(1) Indoor: DB = 25°C, RH =50 %.
(2) Outdoor: DB = 33°C, WB = 27°C.
(3) Room Sensible Heat Factor
= 7/(7+1.5) = 0.82
Plot the SHF line on the psychrometric chart
through the Indoor point & cutting the 100%
RH saturation curve.
(Note: This line shall be parallel to the Sensible
Heat Ratio line drawn on the Semi-Circle,
passing through 0.82)
(4) Determine & plot the mixing air point of
the ODA & RA quantities on the psychrometric
chart using the inverse principle ratio.
All the air properties of the above points
plotted on the chart could now be determined
as tabulated in the Table.ive
PSYCHROMETRIC Inder DB25°C RU SOY
CHART Cwtdeot PB 32°C WHATS
Mixed Air Rocio = RA
eA
tee
44st On a aaxonsrnic |
(PRESSURE Or 10a 25 mbar
HT Room SHE TKw
LY = hSkwD
ea
SRE eae) o
wns
ot
FON 3uepn3s,SSS ‘SPECING ENTHALRY Wiho
Psychrometry: Air-coni
Data From Psychrometric Chart
Item Point bs RH we Spec. Vol Density mc Enthalpy
Degc % Degc m3/ke ka/ma keke da hi/kg da
y Outdoor 33 63 a 0.890 a2 0.0220 85
2) Indoor 25 50 18 0.860 1.16 0.0100 50
3) Mix ir 7 sy 208 0.870 15 0.0125 60
4) ADP 12.6 100 126 0.820 122 0.0080 36
5) Off-Coil aa 90 133 0.825 42a 0.0092 38
Note: Off-Coil Temperature is estimated, normally about 1 to 2 deg. C above ADP.Psychrometry: Air-conditioning
(a) From the psychrometric plot,
the ADP = 12.6°C.
(b) Bypass factor
= (Off-coil DB — ADP)/(Mix-air DB — ADP)
= (14.1 -12.6)/(27 - 12.6)
= 0.104
Or Contact factor
= (Mix-air DB — Off-coil DB)/(Mix-air DB — ADP)
= (27 -14.1)/(27 - 12.6)
= 0.896
(c) Supply air to the air-conditioned room.
Itis to be noted that the supply air conditions
will be any point along the line from the off-
coil point to the room indoor point.
Depending on the supply air duct insulation,
length of duct, location of duct, there is a
temperature rise above the off-coil which is
normally 1 to 2°C.
Using a supply air DB temperature
= Off-coil DB + 1.5°C DB = 14.1 + 1.5 =15.6°C
From the psychrometric chart, at 15.6° C DB,
the specific volume = 0.83 m?/kg.
Hence, p = 1/0.83 = 1.2 kg/m?
Using
Sensible Heat (kW) = 1.2 x m3/s x (25 — 15.6)
Hence, m? /s = 7/(1.2 x 9.4) = 0.62
(Note that if a higher supply air temperature is
used, then the air flow rate is higher. The
density of air hardly change).
per serene rr errr rrr tr
itd rSHRae e8YCrnuMET rue CHAN Od
Te a Pe ReASHRAE PSYCHROMETRIC CHART NO.1
6YA0)) oro rewrenarone Seater
Tarouermcreessine; —soianipn,
ccopyRici snu2
‘AIEFICA! SOCIETY OF HEATING, REFRIGEAATING AND AR-CONDMONNG ENOWNEERS, WC.
‘Ry SULB TEMPERATURE, "0ACMV1: Natural Ventilation & Mechanical Ventilation
Learning Objectives:
Learner should be able to discuss the requirements for mechanical ventilation systems.
Learners should beable to:
1 Define natural and mechanical ventilation.
2 Discuss the need for ventilation.
3 Recall building code requirements
4 List factors which affect human comfort.
5 Calculate the amount of fresh air required for human comfort.
6 Describe different types of fan for mechanical ventilation.
7 Explain the fan performance curve and system curve.
8 Apply the fan laws. +Natural and Mechanical Ventilation
Modes of “Ventilation”
Proper Ventilation is required for all building
premises or rooms so as to remove or dilute
the following elements:
a) heat,
b) humidity, and
c) Odor
For human comfort, all building premises or
rooms are required to have either one of the
following modes of ventilatio
(1) Natural Ventilation
Natural ventilation is removal of heat and
humidity in a space or room through natural
air or wind movement without the use of
equipment such as fans and blowers.
There must be sufficient operjings (such as
windows) provided in the buildings to enable
natural air change per hour in the space.
dat
The characteristics of natural ventilation are:
a) Normally, natural ventilation is only
achievable with natural openings and
windows in which the premises or rooms are
located closed to the facade walls in which
openings to outside could be created.
b) Air voids, located at the centre of the
buildings could also be used in association
with windows open-able to the voids for
natural ventilation.
c) Ideally, more than one sides of the room
wall has natural openings and windows, so as
to create cross-ventilation in which outside air
moves freely across the room.
d) Needless to say, rain water must be
prevented from entering the room at the
openings.
RA ener
mw Meécnanica Venrilation—
Natural and Mechanical Ventilation
There are instances in which a room (or space)
a) cannot be naturally ventilated as the room
(or space) is located away from the
external walls (or voids, if any), or
b) Natural ventilation is inadgquate to
remove the heat and humidity, causing
human discomfort or equipment
inefficiency or worst pre-mature failure.
If the building premises or rooms cannot be
natural ventilated as stated above and they
are not air-conditioned, then the building
premises or rooms have to be tnechanically
Ventilated.
Comparatively, the capital investment on
equipment and energy consuniption of using
air-conditioning is higher than those of
mechanical ventilation.
Whereas, natural ventilation does not need
any equipment investments and energy
consumption,
(2) Air-conditioning
All air-conditioning of the rooms and premises
are required to follow the codes of practice
and requirements on a “Air-conditioning” and
“Indoor Air Quality” for buildings.
(3) Mechanical Ventilation
The 5 Methods to Calculate the Air Volume
required for a Space for Mechanical
Ventilation are:
1) Air change in the volume of the space;
2) Cubic meter per minute or (I/s ) per
square meter of floor area:
3) Number of occupants in the space;
4) Minimum air velocity through the space;
5) Removal of heat released in the space.Mechanical Ventilation
Which of the 5 methods stated above should be selected in a specific application will
depend on the circumstances, i.e. on the main purpose of the ventilation. Sometimes it will
be possible to use two methods and to compare the results.
If any 2 resulting air volumes just about confirm each other, we can be confident that
our calculation was correct.
rGvVYvxwm——
Mecranica: VantiatinnMechanical Ventilation
(A) The Air-Change Method
Considered the easiest and most commonly
used method of determining the required air
volume, the air-change method assumes that
all the air within a specified space must be
changed within a given time span.
The recommended rate of change is based on
fan industry experience and on health
regulations. This method uses the equation
N= Qx 3600 / Volume
where N = the number of air changes per
hour;
Q= the volume flow rate of air in m3/s;
Volume = the space volume in m>.
SINGAPORE STANDARD
CP 13: 1999
(Ges 91.140)
CODE OF PRACTICE FOR
Mechanical ventilation and
air-conditioning in buildings
‘Maree. ties lene span pa te Shamore
Ser yd od aye i
Semeiemenetnsecmeregens owen me
ISBN go7teranraSingapore Standard (SS) CP 13 on Outdoor for Air-conditioning & Mechanical Ventilation for
Buildings
(B) SS CP 13 (Replaced by SS 553)
In Singapore, the Code of Practice for Mechanical Ventilation and Air-conditioning in
Buildings is SS CP 13 (SS stands for Singapore Standard, CP stands for Code of Practice)
which is the guidelines for all those involve in Mechanical Ventilation and Air-
conditioning (ACMV) of Buildings to follow.Outdoor Air Supply for Air-conditioning
The characteristics of SS CP 13 are:
a) CP 13 uses a combination of ASHRAE and
British and Australian standards to suit the
Singapore conditions.
b) Table 1 of CP 13 shows the minimum
requirements of outdoor air requirement for
comfort air-conditioning.
(Note: Outdoor Air is Ventilating Air which is
also termed Fresh Air).
Column 3 of the Table is just a conversion
from L/s to m3/h to enable easier usage:
c) Table 2 of CP 13 shows the minimum
requirements of outdoor all requirement for
comfort mechanical ventilation.
Teble ~ Outdoor ar supply requirement for confor ai-conlining
tion ae inne oar aea
Restaurants 28) 10
Dance hals 5H o
toes’ 06s 23
‘Shops, supermarkets and 1.0 36
department stores
Lobties,conauses anders 025 09
| oassoons 260 92
|Teatesandchenas 200 14
Fades and rstos:
Lit ‘a 4g
eda a 26
sign Hoss ass 18
Hotel ques roms 1$Us per oom 54 mihpet roomMechanical Ventilation
Air change per hour (ACH) is used
internationally to determine the outdoor air
requirements.
(C) How to Use ACH To Obtain Outdoor Air
1) Calculate the volume of the room in m3;
2) Determine the ACH for that particular
occupancy;
3) Calculate Outdoor Air Supply using
formula,
Outdoor Air Supply (Fan Capacity)
= Volume of Room inm?x ACH m3/h
Note: As ACH is the number of times outdoor
air is used to change and replace the
volume of air in the roof per hour,
supply and exhaust air using fans should
be used to meet the requirements in
ACH. F
CP 13: 1999
Table 2 ~ Outdoor alt supply for mechenical ventiation in non air-conditioned buildings
Typect biking!
Occany
sina cud et supoly
Aitchangeh
Offices
Restaurants, canteens
‘Shops, sugemartels and departent ters
Wevshops faces
Classrooms
‘Theatres and cinemas:
Lobbies, concourse, condors, staircases and exits
Tolets™, bathrooms
Kichens omer ational and indstia)
Car Parks
Fre Command Ceres
Chi Defence Sheers
‘Wastewate fecittes)punying installation
* Werethe cling cnees 25 my, ei chane ate lb clodeted base on 25 moon lg,
Foc eavly used pu tole lero Cod of Pacice on Encireta Heal,
————Mechanical Ventilation: Application on ACH
Tutorial 1
The female toilet of an office has a length and a width of 5.0 m by 4.0 m. Its height is 3.0 m.
What is the flow rate in m3 /s of the exhaust fan required to mechanically ventilate the toilet?Mechanical Ventilation: Application on ACH
Solution
From CP 13, to ventilate an office toilet, the ACH required is 10.
Hence,
Flow rate of fan =5 x 4x 3x10
= 600 CMH
= 600/3600
= 0.1667 m3 /s.Mechanical Ventilation: Application on ACH
Tutorial 2
Ifa room of 8 m by 4m anda height of 3 m requires a fan of flow rate 0.2133 m3 /s to
mechanically ventilate it, what Is the air-change per hour (ACH) required?Mechanical Ventilation: Application on ACH
Solution
Air Change Per Hour (ACH) = Flow Rate in CMH / Volume in M3
Volume of room = 8x 4x3 = 96 m?
But Flow Rate in CMH = (0.2133 m? /s) x 3600
= 767.88 CMH
Hence,
ACH = 767.88 / 96
=8Mechanical Ventilation: Application on ACH
Tutorial 3
A restaurant kitchen of 8.0 m by 12.0 m with a height of 3.0 m is to be mechanically ventilated
with two similar exhaust air fans.
What is the flow rate in m? /s of each exhaust fan required to mechanically ventilate this
kitchen?Mechanical Ventilation: Application on ACH
Solution
From CP 13, to ventilate a kitchen, the ACH required is 20.
The volume of the kitchen = 8 X12 x3
= 288 m?
Hence,
Total air flow rate required = 288 x 20
= 5760 CMH
= 5760/3600
=1.6 m3 Is
But 2 fans are used.
Therefore,
Flow rate of each fan = 1.6/2
=0.8 m3 /s.Mechanical Ventilation: Application on ACH
Tutorial 4
Ifa room of 8 m by 4 mand a height of 3 m requires a fan of flow rate 0.2133 m3 /s to
mechanically ventilate it, what is the air-change per hour (ACH) required?Mechanical Ventilation: Application on ACH
Solution
Air Change Per Hour (ACH) = Flow Rate in CMH / Volume in M3
Volume of room =8 x 4x3 =96 m*
But Flow Rate in CMH = (0.2133 m3 /s) x 3600
= 767.88 CMH
Hence,
ACH = 767.88 / 96
=8Mechanical Ventilation: Application on ACH
Tutorial 5 (used)
The dimensions of the basement car park in a shopping complex are 60 m x 30 m x 2.4 m height.
As this basement car park has insufficient natural ventilation openings, mechanical ventilation is
required. It is proposed to ventilate this basement car park with two (2) exhaust fans. What
should be the capacity in cubic meter per second (mi / s) of each fan?Mechanical Ventilation: Application on ACH
Solution
The volume of the basement car park = 60 x 30 x 2.4 = 4320 m3.
From Table 2 of CP 13, to mechanical ventilate car parks, the ACH is 6.
Hence, the air flow capacity required = 4320 x 6 = 25920 CMH = 25920 / 3600 = 7.2 m3 /s,
As 2 fans are used, hence the capacity of each fan = 7.2 / 2 = 3.6 m3/s.
Dn rrr
Mechanical Venvilation Racad an Hast land [ToJb
Mechanical Ventilation Based on Heat Load (To calculate Fan Capacity)
(D) Heat Removal by Mechanical Ventilation
Mechanical ventilation using fans could be
used to remove heat (sensible & latent) in the
rooms (or spaces).
The characteristics of heat removed by
mechanical ventilation are:
a) All heat sources (people’s, équipment, solar
and transmitted heat from building.
structures) are able to be removed by
mechanical ventilation.
b) For effectiveness, both supply and exhaust
fans should be used.
c) However, the supply inlet must be located
at a minimum distance of 5.0 nj from the
Exhaust outlet so as to prevent cross-
contamination of the supply air from the
exhaust air.
(E) Calculation of Air Flow (Fan Capacity)
The air flow required to remove this heat is
given by the formula:
Q=Heat / (AT x Air Density)
where Q = air flow in m3/s
Heat = heat gain in kW
AT = Designed Temperature Rise in Room
against Outdoor Air Temperature in °C.
Air Density = 1.2 kg/m?
(F) Calculate Air Change Per Hour (ACH)
From above, the ACH can be derived as
follows:
Air flow = ACH x Room Volume
where Room Volume is in m?
Or ACH = Air flow / Volume of Room
But
Air flow = Heat / (AT x Air Density)
= (3600 x Heat) / (AT x Air Density)
m3/s
CMHMechanical Ventilation Based on Heat Load (To calculate Fan Capacity)
Hence,
ACH = (3600 x Heat) / [(AT x Air Density) x Room Volume]
where
Heat = kw
AT=°C
Air Density = 1.2 kg/m?
Room Volume = m?Mechanical Ventilation Based on Heat Load: Example
Example
An elevator motor room on the roof of a high-rise building houses elevator’s equipment for six (6)
number of lifts in a building. From lift manufacturer's data specification, the heat output of each
of the 11 persons (750 kg) elevator at a nominal speed of 90 m/min and its accessories in
the lift motor room is 1700 keal/hr. Two (2) exhaust air fans are used to mechanically ventilate
the room. Supply air is obtained from natural openings of the room.
The maximum allowable temperature in the elevator room is 37° C and the outdoor air
temperature is 33°C. f
Calculate:
(a) The minimum air flow in m/s for each fan.
(b) The ACH of the elevator room if the room volume is V m?Mechanical Ventilation Based on Heat Load: Example
Solution
(a) From the elevator manufacturer's data
specification, the heat output of each of the
11 persons (750 kg) lift at 90 m/min. and its
accessories in the lift motor room is 1700
kcal/hr.
Hence,
Total Heat Output of 6 Lifts
= 6x 1700 = 10,200 kcal/hr
= 10,200 x 1.1621 W = 11.854 kw
The air flow required to remove this heat is
given by the formula
Q=Heat / (Temp Rise x Air Density)
where Q = air flow in m3 /s
Heat = heat gain in kW
Temp Rise = temperature rise in room against
outdoor air temperature in °C
Air Density = 1.2 kg/m?
Using an outdoor air temperature of 33° C
and the maximum allowable air temperature
in the lift motor room of 37°C,
Therefore
Air Flow, Q = 11.854 / (37-33) x 1.2
= 2.47 m3 /s
As 2 number of exhaust fans are used, the air
flow of each = 2.47 / 2 = 1.235 m3/sMechanical Ventilation Based on Heat Load: Example
Air Flow Per kW Heat Removed
From the above calculations, this means that
to remove 11.854 kW of heat requires 2.47
m? /s of air flow in order to maintain a
temperature difference of 4° C between the
outdoor air temperature (33° C) & the indoor
air temperature (37° C).
Or for rough estimation
2.47 / 11.854 = 0.21 m3/s pet kW heat at a
temperature difference of 4°C.
Air Change Per Hour (ACH)
Let the volume of the room be V m3.
Hence,
2.47 m? /s = 2.47 x 3600 = 8892 CMH
But,
Air Flow = ACH x V
where air flow = CMH
Therefore,
8892 = ACH XV
or ACH = 8892 /V
If V, the volume of room to be mechanically
ventilated is known, then the air change per
hour required can be calculated.Mechahical Ventilation Based on Heat Load: Example
Basement Workshop : Machine and People’s Heat
Example
In a basement workshop of area 300 m3 which could not be naturally ventilated and it is
costly to air-conditioning it, there are 30 workers. Light bench work is performed by
these workers in which the heat output of each worker is 0.22 kW. Lighting of 0.25 W per
m? is provided in the workshop. The equipment heat load is 25 kW and the total x
heat transmission through the building structures is 15 kW. N ong bw
To mechanically ventilate the Workshop,
calculate:
(a) The air flow required in CMH,
(b) The ACH
Use a indoor design temperature of the workshop = 36° C and outdoor = 33°C.
The height of the workshop is 3.0 m.
“3M Lased Gu dear vad, cxamureMechanical Ventilation Based on Heat Loa
: Example
Basement Workshop : Machine and People’s Heat
Solution [or
Heat Load Estimation ae
The total heat to this workshop
= (30 * 0.22) + (0.025 * 300) + 25 +15
= SALW, 9 5. NS. 035/09
Air Flow Requirement
Using a designed outdoor temperature of 33°
Cand a maximum indoor temperature of 36°C
hen the air flow volume required,
Q=544/ [(36-33) x 1.2]
we = 35-03-m? /s = 54,100 CMH
Air cHBNBE Per Hott (ACH)
The floor to floor height of the basement level
is 3.0 m.
Hence,
the volume of these service areas
=300x3
= 900 m3
Therefore,
ACH = 15400 / (900 * 1.2)
= 14 approx.
wo
pate A
aneFactors on Human Comfort
Human Comfort
The factors that affect human comfort are:
(1) Dry Bulb Temperature
(2) Relative humidity
(3) Air velocity
Human Body and Its Environment
The human body always loses heat to the surroundings, irrespective of whether the surroundings
are at a higher or lower temperature than that of the body.
The|normalhtemperaturerofithe*humansbody:is:36-:9°Cx
When the surrounding temperature is low, say 10° C, the body loses heat.
However, inside the body is continually creating heat, so the normal body temperature is
maintained.
When the surrounding temperature is high, say 40°C, the body still needs to lose heat. €
If heat is gained from the surroundings, the body temperature will rise; and a rise of a few
degrees in body temperature can be fatal.
Thus perspiration takes place and this moisture evaporates, absorbing latent heat from the body.
This will then keep the body temperature at normal.
In general while moderately clad & moderately active, 19°C to 24° C range of temperature at
which most people feel comfortable.fell
Factors on Human Comfort
Humidity and Comfort
50% RH can be considered to be comfortable.
However, this humidity is difficult to attain and maintain.
When the RH is below 40 %, most people feel dry or parched.
When it is above 70 %, they suffer an oppressive sultry feeling because the perspiration from the
body cannot evaporate to cool the body.
Ventilation Arid Air Movement for Comfort
Airwelocities within the'range of 0-1 - 0:25 m/s can be considered to be'satisfactory.-~-"
However, the quantity of-fresh air required depends upon the type of space for which air
conditioning is required.
Effective Temperature
As stated, the rate at which heat is lost from the body depends not only on the surrounding
dry-bulb temperature, but also on humidity & air movement.
Consider a space in which the air movement is 0.1 m/s & the dry-bulb temperature is 23°C.
If the relative humidity changes from 50 % to 95%, then the feeling of warmth experienced
by the occupants will change. In fact, they will feel too hot, because the high humidity will
prevent evaporation of perspitation, so decreasing the heat loss from the body.Factors on Human Comfort
An increase in air movement will cause heat to be removed from the body at a faster rate.
Thus at a dry-bulb temperature of 23°C, relative humidity of 50% and air velocity of
0.25 m/s, a person may feel cooler than at the same dry-bulb temperature and RH, but a
decreased air velocity of 0-1 ri/s.
The effective temperature for human comfort is the combined effects of the followng factors
1) Air movement,
2) Relative Humidity (RH), and
3) Dry Bulb (D8) Temperature.
With different combinations of DB temperature, relative humidity and air movement, it is
possible to obtain the same effective temperature.
BCMA Caminet Pana (AveACMV : Comfort Zone (Outdoor & Indoor Conditions) .
Dewpoint temperature
Figure
0.015
9.010
Humidity ratio
0.005
16
20°
He
0.0
60 70 90 F
20, 25 300
Operative temperature
‘Acceptable ranges of operative temperature and humidity for people in
typical summer and winter clothing ducing light and primarily sedentary
activity (<1.2 met). (Reprinted by permission from ASHRAE Standard
55-92, 1992)Comfort Zone (Outdoor & Indoor Conditions)
ALIGHNNH SALLWTBE
is
¢
z
2
3
°
w
§
iN
De SUNLVUSIWAL GING-LAM,
DRY-BULB TEMPERATURE °C
COMFORT CHART—FOR AN AIR VELOCITY
OF OF m/s.etc
Fans and Air Distribution
Fans
Purpose of Fans
* Fans are necessary for the movement
of air through ducts and air-
conditioning apparatus.
* Fans are also used for exhausting
smoke and gases from a space, for
ventilation, for air circulation, for
pressurisation, and depressurisation
within a space.
* Essentially, a fan consists of a rotating
wheel, with blades of special shape,
inside a housing. The wheel is driven
by means of an electric motor, or
other source of power, coupled to it
either directly or through belt drive.
The action of the blades on the
surrounding air creates a pressure
difference; this causes air flow.
* Fans may function either as blowers
or exhausters: blowers push the air
through a space by creating a positive
pressure at their outlets; exhausters
remove gases by creating suction.
Types of Fans
The common fans used commercially
may be classified as follows:
1. Propeller. —~ juve smal
2. Axial. en
35 pare ed i
gustFans and Air Distribution @ (kil pa
Propeller Fans
Propeller fan (see figure) is suitable
for Operation against small pressures
only (approx. 125 Pa), and is not
suitable for installation in ducts.
Propeller fans are mostly used for
exhausting or ventilating, and are
mounted in openings in walls or attic
spaces.
Economy and simplicity are the
prime factors for their great
popularity as exhaust fans.
OQ hee
SZ wash =
2 lee? Po.
a
Are
Pascal ( pu)
U .
5 vey Smo
|Bor = jer Pasest (ea)
>7 sical
Fans and Air Distribution
Axial Fans
Axial-flow fans fall into two, categories:
(a) tube-axial fans (see Figure).
(b) vane-axial fans. Tube-axlal Fan
Both can operate against relatively high ae
pressures (approx. 625 kPa) compared to
the propeller fan, and are suitable for
mounting in ducts.
Tube-axial fan main disadvantage is -
noise, produced by the turbulent flow of )
air. Thus the tube-axial fan is suitable for
applications in which noise is acceptable EERE!
or normally with the use of silencers.
In both the tube-axial and vane-axial
fans, the driving motor is situated inside
the duct. This is a disadvaritage in that
the heat of the motor is added to the air.Fans and Air Distribution
An advantage of these fans is that they
do not take up any floor space.
Sometimes these fans are manufactured
ready-mounted inside a duct section.
This makes installation easy, as all that is
required is just the connection of the
section to the duct work.
‘| ey
The Figure illustrates a vane-axial fan, in GUIDE VANER!
which air flow is streamlined by vanes. It | aii:
is thus quieter in operation. 0)
VANE AXIAL FANFans and Air Distribution
Centrifugal Fans
Centrifugal fans consist of a wheel, called
the impeller, rotating inside a shell-
shaped housing. The flow of air is radial;
that is, from the centre outwards (see
Figure).
The impeller is coupled to an electric
motor, either directly or through a belt
drive. As the impeller rotates, air
particles are picked up by the eye of the
Impeller (1).
Due to centrifugal force, the air particles
are thrown outwards and leave the tip of
the impeller (T) with high yelocity.
As the air passes through the passage in
the housing, the velocity of the air is
converted to pressure (due to the
(CENTRIFUGAL FANFans and Air Distribution
increasing cross- sectional area) and the
air leaves the housing with high pressure.
3 types of blades can be used in the
Impeller,
(a) forward curved,
(b) radial, and
(c) backward curved; (see Figures).
Forward-curved Blade
The tip of the blade curves in the snip QLyp UZ
direction of rotation. a yaa
a
Backward-curved Blade bain Radial
See ee ae ane Cure Blades
+ : Blades Backward
The tip of the blade curves in the Curve Blades
opposite direction to rotation.
Radial blades are, of course, straight.
The forward-curved blade is capable of
producing a greater volume rate of air
flow than the others under similar
—————____________., . |
Fans and Air Distribution
conditions. This is due to the scooping make the backward-curved blade the
action of the blades. For the same duty, one most extensively used in centrifugal
the forward-curved blade can be either fans.
smaller in size or run at a lower speed
than the other two types.
The disadvantage of the forward- curved
blade is that it can easily become
overloaded, because at high speeds, the
loss of power due to eddy formation can
be considerable.
Radial blades are self-cleaning and can
be designed for high structural strength,
pressures and speeds.
The backward-curved blade is more
efficient than the other two, is quieter in
operation, and rarely becomes
overloaded. These good characteristicsFans and Air Distribution
Power Requirements of Fans
When a fan is fitted to a duct system, air
flows through the duct due to the
pressure created by this fan,
The power required to drive the fan
depends upon the volume rate of air
flow and the pressure against which the
air flows, assuming there is no restriction
or pressure drop at the inlet to the fan.
The'static-pressure, velocity pressure and
total pressure can't be be measured: pressank
Node: Total, ae
Strictly speaking, th the’ fan works against
the total pressure.
However, in actual-practice, the fan is
assumed to work against the static
pressure only.
The resistance the fan must overcome is
the difference between the total
pressure at the entrance to the duct
and that at the exit from the duct which
is approx. equal to the static pressure,
as the velocity pressure at the entrance
to and exit from the duct is
almost equal (due to the X-sectional
areas at these points being very similar).
Static power =p,xq W
Total power = p,xq W
where
P, = static pressure (Pa)
P, = total pressure (Pa)
q = volume rate of air flow (m3/s).
The static power and total power
calculated by these formulae are ideal.