Professional Documents
Culture Documents
英文TMC IOM ManualVER1.0-2020 Jinguang
英文TMC IOM ManualVER1.0-2020 Jinguang
Table Of Content
1 GENERAL REMARKS...................................................................................................................... 2
1.1 ABOUT THIS MANUAL................................................................................................................................ 2
1.2 GUARANTEE .......................................................................................................................................... 2
1.3 TYPE OF OPERATING MANUAL..................................................................................................................2
1.4 SERVICE DATA - SERVICE CONTRO ......................................................................................................... 3
2 SAFETY..................................................................................................................................................4
2.1 MARKING OF INSTRUCTIONS IN THE OPERATING MANUAL......................................................................... 4
2.2 QUALIFICATION AND TRAINING OF PERSONNEL ....................................................................................... 4
2.3 DANGER ON NON-OBSERVATION OF THE SAFETY REGULATIONS ............................................................. 4
2.4 SAFETY-GUIDED WORKING ..................................................................................................................12
2.5 SAFETY INSTRUCTIONS FOR USER / OPERATOR ...................................................................................12
2.6 SAFETY INSTRUCTIONS FOR MAINTENANCE, INSPECTION AND ASSEMBLY JOBS .................................... 12
2.7 PROHIBITION OF UNAUTHORIZED REBUILDING MEASURES OR ALTERATIONS ........................................ 12
2.8 INADMISSIBLE OPERATING MODES .......................................................................................................12
3 TRANSPORT AND STORAGE...................................................................................................... 6
3.1 TRANSPORT / LIFTING ...........................................................................................................................6
3.2 PRESERVATION AND STORAGE ..............................................................................................................7
4 DESCRIPTION.....................................................................................................................................10
4.1 DESCRIPTION OF THE PUMP.................................................................................................................. 10
4.2 BEARING AND LUBRICATION.................................................................................................................. 10
4.3 ABSORPTION OF THE AXIAL THRUST - BALANCE DRUM............................................................................ 10
TMC-IMO-VER1.0-2007
MC
INSTALLATION,OPERATION & MAINTENANCE MANUAL
1. GENERAL REMARKS
The operating manual must always be available wherever the pump is in use. These instructions must
be read an applied by any person in charge of carrying out work with and on the pump, such as
transport, storage, installation, operation and maintenance.
This manual should be used together with all other machine documentation in order to have
accurate information of your pump. Do not start or operate this pump unless you have
complete understanding
of the pump system and all auxiliary systems (driver, cooling, seal flushing…).
1.2 Guarantee
Guarantee is assumed according to the contractual agreements.
The normal DNB warranty covers manufacturing or material defect, it does not cover the damage
caused by improper storage conditions, incorrect installation, operation and using against designated
use.
During the period of guarantee, repairs or modifications only can be made by our service personnel or
with our agreement.
We reserve all rights in this manual and in the information contained. Reproduction, use or disclosure to
third parties without our approval is strictly forbidden.
Remark
In the case of further questions, of spare part orders and other correspondence please mention always
the S Serial No. and pump type. Both can be gathered from the rating plate of the pump.
TMC-IMO-VER1.0-2007
MC
INSTALLATION,OPERATION & MAINTENANCE MANUAL
TMC-IMO-VER1.0-2007
MC
INSTALLATION,OPERATION & MAINTENANCE MANUAL
2. SAFETY
This operating manual contains basic information, which has to be observed on the installation,
commissioning, operation and maintenance. Therefore this operating manual has to be read before
assembly and commissioning by the service engineer and service personnel in charge respectively user
and has to be available constantly at the site of the machine/installation.
Not only have the general safety instructions to be observed, which are given under this main point
"Safety", but also the special safety instructions given below in the operating manual.
- Safety regulations the non-observation of which may cause danger for the machine and its
operatability are marked by
The safety regulations given in this operating manual which consist of national regulations on accident
prevention, as well as company- internal job, operating and safety regulations issued by the user, have
to be observed.
- Safety guards for rotating parts (e.g. coupling) may not be removed from machine during operation.
- Leakages (e.g. from mechanical seal) of dangerous fluids (e.g. explosive, toxic, hot etc.) have to be
disposed of in such a way as to prevent any endangering of people and environment. Legal
regulations have to be observed.
- Endangering by electricity has to be excluded (details see for example in the regulations by the VDE
and local energy suppliers).
- The special safety instructions in the following paragraphs of this operating manual have to be
observed.
- Basically any works on the machine may be carried out only during shut-down of the machine. The
procedure described in the operating manual for the shut-down of the machine has to be strictly
adhered to. The machine has to be locked against unauthorized or involuntary start-up.
- Immediately following the end of the works, all safety and protective devices have to be
reassembled respectively have to be put to work again.
- On a repeated start-up all points given in the paragraph initial commissioning have to be observed
again.
- The limits given in the data sheet must not be exceeded in any case.
TMC-IMO-VER1.0-2007
MC
INSTALLATION,OPERATION & MAINTENANCE MANUAL
TMC-IMO-VER1.0-2007
MC
INSTALLATION,OPERATION & MAINTENANCE MANUAL
Eyebolts at pump parts and other parts of the unit may not be used for the lifting of the
complete assembled pump or even the whole unit. The eyebolts are only meant for the lifting of
the loosened parts during assembly and disassembly
3.2 Preservation and storage
Preservation for despatch
Standard
When the pumps are shipped, smooth outside faces are sprayed with Tectyl 506 and pump internals
with Mobilarma 524. Attention: this is not suitable as long-term preservation; 6 months are max.
allowed time for storing.
Seaworthy packing
If the pump is despatched with PE-foil welding with moisture absorber (sea-worthy packing) the pump
can be stored up to one year without any special maintenance if the packing is not damaged.
Special packings
On special request the pump can be packed in aluminium foil. In this case the preservation time
amounts to 2 years.
If the seaworthy or other special package is removed, only the standard preservation
is effective, i.e. if no further measures are taken, the max. storage period will be 6
months.
Intermediate storage
Centrifugal pumps which are not installed and commissioned immediately after delivery can be stored
for the period determined by the dispatch preservation.
To avoid the forming of condensate and consequently corrosion (especially in the
gap areas), bearing damage and contamination, a dry room, possibly with constant
temperature as well as a clean, shock- free storage space has to be selected.
In each case unfavourable climatic circumstances will have a negative influence on
period of proper preservation.
In case the units are not or no longer enclosed in a special packing the following has to be observed:
In case of unfavourable ambient impacts such as moist atmosphere, greatly varying
temperatures (day/night), acidy or alkaline ambience, danger of contamination (dirt
etc.) the connection flanges of the pumps have to be plugged airtight.
Longterm storage – preservation
In case a longterm storage is to be previsaged in the store of the client or on site or pumps affected by a
longer shutdown of the plant or standby pumps are to be preserved, the following instructions have to be
observed:
If pumps have been in service before, pump parts having been in contact with the
pumped liquid must be cleaned and after drying be moistened with a preservative.
For this purpose the disassembly of the hydraulic part of the pump becomes
necessary in most cases.
I. Protection of unencumbered, bright parts of the pump
e.g. - pump shaft
- raised faces of flanges
- coupling
- connections for small conduits etc.
We would urgently advise against using normal lubricating oil as a rust preventative. For the
preservation of bright pump parts, the mineral-oil industry has developed special rust preventatives
which at first are liquid and are applied manually, by means of brushes, spray nozzles or aerographs.
After the evaporation of the solvent, a wax-type cover will remain.
This protective film can be removed by means of solvents or alkaline cleansing agents.
TMC-IMO-VER1.0-2007
MC
INSTALLATION,OPERATION & MAINTENANCE MANUAL
Other rust preventatives of the same quality may however be used as well. The average time of
protection is 1-3 years. Rust preventatives are rust-preventing agents which however do not remove
rust. For this reason, it is a prerequisite for the application of rust preventatives that the parts to be
protected are clean and rustfree. The surface of the parts has to be cleaned carefully before the
respective rust preventative is applied.
TMC-IMO-VER1.0-2007
MC
INSTALLATION,OPERATION & MAINTENANCE MANUAL
corrosion damage at bearings, the pump rotor should manually be turned simultaneously, so that the
preservation oil will be distributed over the running surfaces of the bearings.
According to manufacturers indications, the rust preventative has to be discharged
and the spaces have to be refilled every 12 months*. If the rust preventative is not
renewed within this period the risk is to be taken by the storage keeper. In order to
have a guarantee for the proper execution of the maintenance instructions, we recommend to establish
maintenance sheets.
* If in the case of large pumps interiors are only sprayed preservation has to be repeated not later than
after 6 months.
TMC-IMO-VER1.0-2007
MC
INSTALLATION,OPERATION & MAINTENANCE MANUAL
4. DESCRIPTION
General: Pumps of the DS series are horizontal, multi-stage, ring section centrifugal pumps designed
for boiler feed and other high pressure applications.
The pumps are suitable for pumping clean liquids. The permissible operating
pressures and permissible operating temperatures depend upon the material
specification. See 1.4.8 for safety limit data for the pump supplied.
The materials of construction have been selected for the liquid specified in your
order. Before the pump is operated with other liquids or at other temperatures it is
essential that the manufacturer be consulted.
Casing: The casing is radially split and consists of suction casing, stage casings as required and
discharge casing. The elements are sealed by O-rings and held together by external tie bolts.
Shaft: Accurate machining provides precision fits and clearances for assembly and operation. Machined
shoulders provide positive location of mounted parts.
Impellers: The impellers are key-driven, have closed channels and are sealed against the casing
elements by replaceable casing wear rings. The flow is guided from stage to stage by stationary
diffusers.
Shaft seal: The inner chamber of the pump which is filled with liquid is sealed at the shaft by packed
glands or mechanical seals. See 7.2 or description of the seal manufacturer for further information.
The stuffing box housings are fitted with a cooling chamber as required. In order to
prevent evaporation in the vicinity of the shaft seal, the cooling water quantity given
under 1.4.3 must be assured. Non-compliance can lead to total failure of the shaft
seal.
Coupling: Flexible couplings must be used to connect the pump to the driver: these couplings must be
able to absorb small axial, radial and angular shaft misalignments.
Bearing housings: The bearing housings flanged on both pump sides are equipped with splash oil
lubricated bearings. The lube oil quantity is given under 1.4.2 and 7.3 .
Antifriction bearings: Roller bearings are used as bearings for the massive pump shaft in the bearing
bracket on the drive side, whereas paired taper roller bearings take up the axial forces at the non-drive
side.
Fan: A fan assembly is provided to enhance air cooling of the bearing bracket non-drive side.
Constant Level Oiler: An oiler is installed on each bearing housing. The oiler automatically maintains
bearing housing oil level and provides a means of monitoring and refill. See also 7.3
TMC-IMO-VER1.0-2007
MC
INSTALLATION,OPERATION & MAINTENANCE MANUAL
General
During operation of the pump an axial thrust is exerted on the rotor towards the suction side. This arises
because the area of the back shroud of the impeller is larger than that of the front shroud which is
interrupted by the impeller eye, both being subjected to the same liquid pressure. In multi-stage pumps
the forces per stage are cumulative and considerable axial loads result. These forces are absorbed by
the hydraulic balance device.
Working principle
The balance device consists of a balance drum
rotating with the shaft and a balance drum liner
housed in the discharge casing. The pressure
difference between the pressure within the
pump 'a' (discharge pressure) and the pressure
in the balance chamber 'b' (suction pressure +
frictional resistance in the balance pipe) creates
an axial force 'F' on the balance drum. This
axial force is opposite in direction to the pump
axial thrust. The magnitude of the force 'F'
depends on the area "A" of the balance drum
which is sized such that the axial thrust at the
operating point is almost completely
compensated.
The residual axial thrust is absorbed by a thrust
bearing. The pressure difference between 'a'
and 'b' also sets up a flow through the throttling
clearance 'c' into the balance chamber. A
perfect balance is only achieved if there is no
build up of pressure in the balance chamber as
a result of the balance flow being restricted.
Balance pipe
Severe damage to the pump will result, if the instructions for the laying of the
balance pipe are not strictly observed.
To prevent a pressure build-up in the balance chamber there must be a drain for the
admitted liquid. A tapping for this purpose is provided in the pump balance chamber
(the position is indicated on the dimension drawing).
- The routing of the balance pipe depends on the operating conditions. It is either:
returned to the suction tank
or returned to the suction casing.
The data on the installation drawing is decisive for the pump supplied.
Note! With flow returning into the suction tank the following must be observed:
The frictional resistence of the balance pipe must not exceed 0,8 bar (12 psi).
Choose corresponding nominal diameter.
A valve should be fitted in this pipe for maintenance purposes. Steps must be taken
to ensure that this can be locked in the open position to prevent unauthorized and/or
accidental closur
TMC-IMO-VER1.0-2007
MC
INSTALLATION,OPERATION & MAINTENANCE MANUAL
The draining of the pump respectively the disposal of the leakage for pumps delivering toxic,
explosive, hot or in any other ways dangerous fluids, must not lead to any endangering of
operator(s) and environment.
Following manufacture the pump flanges and external tappings are protected by plastic plugs which
should not be removed before the pipework is ready to be attached to the pump. The pump should be
protected, if further site work is necessary nearby.
The foundation or any other necessary building work must be finished, set and dried. Roughen and
clean the foundation. All preliminary work for erection must be completed. With large units, suitable door
and wall openings are to be provided for transport to the installation site.
Grout selection
Select a nonshrinking grout that is compatible with the highest and lowest temperatures to which it may
be exposed. Use concrete from a concrete company with a final strength of 25 N/mm2 (B25) or better.
If the service of a concrete company is not available the figures given below may be taken as a guide.
- The concrete mixture suitable for grouting machine baseplates should contain 300 to 350 kg cement
per 1 m3 of concrete. The sand and gravel proportion for 1 m3 of finished concrete (1.2 m3 mixture) is
as follows:
For grouting of the foundation bolts: 65% Fine sand grain size 1 - 5mm
35% Coarse sand grain size 5 - 10mm
water as required
The use of so called „fast cement“ with short setting time is possible.
For grouting (filling) of the baseplate: 40% Fine sand grain size 1 - 5 mm
60% Coarse sand grain size 5 - 10 mm
100 - 140 liters of water
Only clean, washed sand may be used. The water-cement ratio has a decisive
influence on the final strength of the concrete.
A high concrete strength will be attained with high standard strength of the cement, low water-cement
ratio, and compacting by vibrating.
Installation of pump and driver
With separate baseplates for pump and driver first erect the pump, then align the
TMC-IMO-VER1.0-2007
MC
INSTALLATION,OPERATION & MAINTENANCE MANUAL
driver.
- Roughen and clean the foundation. Walls of the grouting holes must have rough surfaces and must be
free from pollution. Remove any loose particles, dirt or oil-soaked concrete. All baseplate surfaces which
will be in contact with grout must be clean. Remove rust, paint or other extraneous material.
- Attach wire rope slings to the baseplate transport eyes (see 3.1 transport/lifting) and lift the baseplate
with pump and driver. Insert foundation bolts into the holes in the baseplate and tighten the nuts a few
turns.
- Lower the baseplate carefully into position on the foundation. The foundation bolts have to be lowered
into the foundation holes.
Levelling
- Place steel shims under the adjusting screws and align the pump unit horizontally with the aid of the
adjusting screws. Provide proper grouting clearance between foundation and baseplate (see installation
plan).
Check levelling in the direction of the pump axis and also at right angles along the
horizontal flange with a spirit (machinist’s) level. The flanges must be vertical on
horizontal branches. See sketch 5.1.1. Max. permissible variance 0.5 mm over 1m.
- Push steel shims into line to the right and left of the foundation bolts. The shims must be thick enough
so that there will be only minimal clearance between baseplate and shim. The space between baseplate
and shim must be filled with one or two thin parallel sheet metals which must be available in different
thicknesses. See sketch 5.1-2.
- Loosen adjusting screws and check levelling. If required correct levelling.
Do not bend the baseplate since this will cause development of vibration and noise
during operation or the alignment of the coupling will not possible.
- Before grouting the baseplate align the coupling as described under 5.2 (alignment report).
TMC-IMO-VER1.0-2007
MC
INSTALLATION,OPERATION & MAINTENANCE MANUAL
Assembly
TMC-IMO-VER1.0-2007
MC
INSTALLATION,OPERATION & MAINTENANCE MANUAL
The assembly of the coupling must be carried out in accordance with the coupling manufacturer's
instructions. For mounting the coupling halves onto shaft ends see also 7.6.
Check for “soft machine feets”
Before coupling alignment the driver and pump fixation must be checked regarding “soft feet“ issue
Loosen machine feet fasteners one after the other and check with feeler gauge if a gap between
machine feet and baseplate occur. If the gap is larger than 0.05 mm (0.002 in.), then the gap have to be
compensated by shimming.
If the base plate has not grouted jet, the “soft feet” may also be compensated by re-adjustment of the
baseplate.
If the pump or driver are not properly fixed to the base plate higher intermittent
vibrations or excessive misalignment due to nozzle loads can be expected .
Pump foot tightening torques
For the transport the tie bolts have to be tightened at the pump feet. To render possible a tension-free
thermal expansion of the pump during operation, the screws loosened again for the precision alignment
of the coupling must not be screwed so tight on the non-drive side as on the drive side. Essential values
for the tightening torque of tie bolts on drive side and non-drive side are shown in the table below.
TMC-IMO-VER1.0-2007
MC
INSTALLATION,OPERATION & MAINTENANCE MANUAL
Laser optical alignment is the most exact shaft aligning method. The transmitter is a laser diode
mounted on one side of the coupling and the prism is mounted on the other side. The laser beam
emitted by the laser diode is reflected by the prism to the localizer. The offset can be detected by
rotating the shafts.
Coupling safety guard
The pump only have to operate with mounted coupling safety guard. After each alignment
check the coupling guard must be refitted immediately. Check for correct assembly, fastening
and distance to rotating coupling.
TMC-IMO-VER1.0-2007
MC
INSTALLATION,OPERATION & MAINTENANCE MANUAL
Adjustments must be made to the piping, if these limits are exceeded or serious
damage to the pump may result.
Pipe fittings
A check valve and a shut-off valve should be installed in the discharge line. The check valve, placed
between the pump and the shut-off valve, is to protect the pump from reverse flow and excessive back
pressure. The shut-off valve is used in priming, starting and when shutting down the pump.
In the suction line a shut-off valve should be installed for extended shut downs, repairs and for pump
draining.
Fittings having the same nominal bore of the pipework should be used. If the pump
branches have a smaller nominal bore than the fittings suitable taper pieces should
be installed.
Suction pipe
On flooded suction applications, the horizontal sections of the pipework should descend towards the
pump and on suction lift applications they should steadily rise towards the pump to prevent air locking.
The pieces should be designed and constructed so as not to obstruct the free flow of the liquid. The
transition from small to large pipe diameters must be gradual. As a general guide the length of a
concentric taper piece must be 5-7 times the difference in pipe diameters.
Sudden reductions in pipe cross sectional area and sharp bends should be avoided especially in the
suction or inlet pipework, as these greatly increase the frictional resistance within the pipework. A high
frictional resistance within the suction or inlet pipework leads to reduced pressure available at the
suction branch. Too low pressure leads to cavitation at the impeller inlet.
To prevent turbulent flow into the pump, do not position the shut-off valve in the suction piping adjust to
the pump suction nozzle. The suction valve should be positioned with the handwheel horizontally or
vertically downwards to prevent air pockets forming.
Multi-pump installations should have separate suction pipes to each pump. Excepted are duty and
standby pumps which may have common suction pipework since only one pump operates at any time.
Cleaning the pipework
Before a pumpset is commissioned, all traces of foreign bodies and impurities must
be carefully flushed out of the supply tank and pipework. Where pipework has been
welded, all welding slag etc. must be removed.
Suction strainer
In order to prevent any of the above impurities entering the pump, it may be necessary to install a
suction strainer made of stainless steel in the inlet pipework. The strainer insert should consists of a
supporting strainer (plate with round holes 5 to 8 mm, 0.2 to 0.32 in.) to which a wire screen (wire cloth
0.315 x 0.2 mm, 0.0125 x 0.008 in.) is fixed by welding. The effective area of passage of this strainer
must be at least 1.5 to 2 times the pipe diameter.
Monitor the pressure drop across the strainer by a differential pressure gauge. If at any time, a reduction
in pump suction pressure is observed, the strainer should be removed and cleaned.
The differential pressure ≥0.35 bar (5 psi.) causes ALARM (clean strainer). At max. 0.5 bar (7 psi.) the
pump is SHUT OFF; higher differential pressures may lead to the damage of the strainer result in
serious damage to the pump.
The given values are limits for the load on the strainer. As NPSHavailable at the suction
branch is reduced by the max. admissible differential pressure at the strainer
whereas NPSHavailable has always to exeed NPSHrequired , lower regulation limits for
TMC-IMO-VER1.0-2007
MC
INSTALLATION,OPERATION & MAINTENANCE MANUAL
The following instructions may be used as a guide insofar as they apply to the pump as
delivered.
Ancillary pipework
- Drainage of the pump casing can be effected by leading a pipe into the drip tray of the baseplate or
into a collection pipe. Isolating valves must be installed in the pipe and must have a pressure rating at
least equal to the rating of the casing.
The draining of the pump from toxic, explosive, hot or otherwise dangerous fluids must not lead
to any endangering of operator(s) and environment.
- Gland leakage from the shaft seal can also be led into the drip tray or collection pipe.
The leakage of dangerous fluids has to be drained or quenched in such a way as to prevent any
dangers to persons and environment.
- Cooling through cooling liquid: Connections and scope see installation plan or separate drawing
respectively. Don't confuse inlet and outlet connection. (Inlet lowest, outlet highest point of cooling
chamber). For the adjustment of cooling water quantity regulating valves are installed in the supply
pipings. At open system lead the drain pipings over a funnel.
- Flushing and / or sealing of the shaft seal: Connections and scope see installation plan or separate
drawing respectively. For pipings which lead to a heat exchanger, pressure transmitter or supply
reservoir, a vent possibility is provided at the highest point. In case of thermosyphon revolution the
biggest pipework diameter possible will be used. Supply piping is layed evenly ascending and without
sharp bend.
- Quench: In case the necessity arises to quench any leakage from the mechanical seal see 1.4.7 for
information on quench media and quantity.
Pressure measuring equipment
- The start-up and monitoring of the operating point of the pump is made easier with pressure gauges.
See also 6.1 and 6.3. Pressure gauges should be mounted on a common gauge panel and connected to
the tappings in the pump branches or adjacent pipework using a hydraulic tube with an expansion loop.
Isolating and vent valves should be installed in the pipework for ease of maintenance.
Bearing monitoring (impact impulse measurement, only possible with antifriction bearings)
- Advancing bearing damage can be recognised and monitored by means of impact impulse
measurement. This requires a special measuring unit which is connected near the bearing through
screw fittings (e.g. SKF connecting nipple No. 1649013 and SKF measuring unit MEPA 21 A).
TMC-IMO-VER1.0-2007
MC
INSTALLATION,OPERATION & MAINTENANCE MANUAL
Note: In accordance local-safety standards these instructions must form part of every operating manual.
Safety instructions for pumps which operate in the partial load region. The following information may be
disregarded, if the pump supplied never runs in the partial load region.
In the partial load region (when operating the pump near zero flow) almost the total
pump power is imparted to the flow as thermal energy. If this flow is less than a
certain minimum (see 1.4.1), heating will occur and continue until the liquid boils, causing severe
damage to the balance device, impellers and casing wear rings leading to eventual breakdown of the
pump. To avoid this there must always be a certain flow of liquid through the pump. The following two
situations arise for multi-stage pumps with hydraulic balance of the axial thrust:
1. The balance quantity is sufficient
This means that in cases of relatively low driver power and favourable suction conditions the
balance flow is sufficient as the leak-off to be piped away. If this condition applies to the pump
supplied, it is noted expressly on the data sheet under 1.4.1 that the minimum flow is equal to the
balance flow. The balance pipe must not be connected to the suction casing, but must lead to the
suction tank.
TMC-IMO-VER1.0-2007
MC
INSTALLATION,OPERATION & MAINTENANCE MANUAL
Never operate below pump minimum flow (see 1.4.1). Operation at minimum flow
should be maintained for no longer than 2 hours in any 24 hours of operation.
TMC-IMO-VER1.0-2007
MC
INSTALLATION,OPERATION & MAINTENANCE MANUAL
6. OPERATION
6.1 General
The following recommended start-up and operating procedures apply to the pump only. For information on any
equipment (driver, shaft coupling, shaft sealing system ...) refer to manufacturer’s instructions.
Safety information
Do not start or operate the pump,
- unless the installation has been verified to be correct and all safety and control functions have been
checked.
- unless you have a complete understanding of the location and function of all components of the
pump aggregate including valves and any upstream and downstream equipment that my effect
the flow of medium to or from the pump.
- unless you have a complete understanding of the all auxiliary mechanical, electrical, and
hydraulic systems as well as the function of all monitoring gages and warning devices.
When starting the pump, be prepared to execute an emergency shutdown in case of failure of the
pump or auxiliary system.
6.2 Commissioning
The items described individually have to be carried out, as far as applicable, step by step
during commissioning.
With electric drive it has to be assured by qualified personnel that the necessary protection measures
work. Earthing, reset, residual current failure operated device etc. have to be ready for service acc. to
approval by skilled personnel.
Before commissioning
a. Connections Check bolted connections and plugs. Inspect ancillary pipework for correct installation.
b. Lube Rinse bearing housing with light oil and allow to drain. Fill with lubricating oil, see also 1.4.2 / 7.3 and
lubricant table T3.
c. Shaft seal Check shaft seal (see 7.2). In case of double acting mechanical seal fill and vent sealing
system (refer to manufacturer’s instruction).
d. Filling the pump - feeding operation Filling the Pump - suction lift
Fully open shut-off valve in inlet line Fully open shut-off valve in suction pipe
If existing (see installation plan) Open If existing (see installation plan): Open
vent (not valid for self-venting casing) vent (not valid for self-venting casing)
In case of mechanical seal: Shaft sealing In case of mechanical seal: Shaft sealing
chamber has to be vented (see also 5.4 chamber has to be vented (see also 5.4
Flushing and Sealing) Flushing and Sealing)
As far as existing: Close vent when Fill pump (suction pipe must have foot
pumped medium flows without bubbles valve)
Mount coupling guard As far as existing: Close vent when
pumped medium flows without bubbles
Mount coupling guard
Before starting the pump, the suction piping, pump case and shaft seal chamber must be
TMC-IMO-VER1.0-2007
MC
INSTALLATION,OPERATION & MAINTENANCE MANUAL
TMC-IMO-VER1.0-2007
MC
INSTALLATION,OPERATION & MAINTENANCE MANUAL
TMC-IMO-VER1.0-2007
MC
INSTALLATION,OPERATION & MAINTENANCE MANUAL
If any vibrations, unusual noises or faults are observed stop the pump unit at
once.
Refer to section “Operating faults”.
Number of starts
The pumps are designed for continuous operation. Too many and too frequent starts can accelerate
ageing and result in abnormally high wear and short life time. In case of many starts we recommend an
intensive supervision and maintenance intervals should be shortened. The recommended number of
start-ups are as following:
- Commissioning phase: up to 200 start / stops (max. 6 starts / day)
- Commercial operation: up to 3 starts / day
Cumulated number of starts max. 600 starts / year
Remark: In case of many start / stop cycles we recommend to perform a general overhaul of the pump
after 6 years running time.
The generated pressure must not fall below the value given in the pump data sheet,
otherwise the maximum allowable capacity could be exceeded, the driver could be
overloaded or the suction pressure could fall below the minimum
required by the pump.
Checking the capacity
The capacity is determined from the pump performance curve
and the generated head (m) as calculated above.
- Find the calculated value of the generated head on the
vertical axis of the performance curve.* Draw a horizontal line
through this point until it intersects the curve. The corresponding
capacity is read on the horizontal axis vertically below the point of
intersection.
Hydraulic or mechanical causes can seriously affect the operation of a pump. There are other justifiable
operating faults in the plant.
There is usually a certain connection between the different types of faults. It is, therefore, expedient to
list and compare the symptoms as well as the possible causes. Assistance can be found for individual
operating faults in virtually all cases.
TMC-IMO-VER1.0-2007
MC
INSTALLATION,OPERATION & MAINTENANCE MANUAL
TMC-IMO-VER1.0-2007
MC
INSTALLATION,OPERATION & MAINTENANCE MANUAL
Bearings
For information about lubrication see chapter 7.3.
Bearing housings has to be kept clean on the outside, since the radiation of heat is reduced by deposits
of dust or dirt.
Bearing monitoring: Check the bearing vibration during running.
In case of antifriction bearing, by means of shock impulse method. Carry out checks according to the
operating instructions of the measuring gauge in fixed intervals. During first start-up the initial values
must be recorded to find out deviations of later measurement. After measuring put coloured caps on
measuring nipples distinguishing,
green cap = everything o.k
yellow cap = increased attention
red cap = beginning bearing damage
Vibrations
These can be detected by hand or with electronic equipment (frequency or amplitude analyser).
TMC-IMO-VER1.0-2007
MC
INSTALLATION,OPERATION & MAINTENANCE MANUAL
Horizontal pumps, which are fastened to the foundation with anchors should not exceed a vibration
speed of 4.5 mm/s. Vertical pumps, as well as horizontal pumps being mounted on buffer elements,
should not exceed a vibration speed of 7.1 mm/s.
When determining the measured values pump should operate at design point, see Chapter 1.4 (in case
pump is operating at partial load or overload the vibration behaviour, f.e. by cavitation, will be influenced
negatively). Measured values which are too high can also be caused by the plant (pipings/accessories)
or by other vibration sources (machines). In order to determine the reason for high vibration values
a vibration analysis is necessary.
Noise
Some abnormal noises can be heard immediately, such as those due to rolling element indentations
because of improper mounting; others are progressive. Noise is usually an indication of incipient failure
and varies in intensity and frequency with the extent of damage.
Alignment
During shut-down (according to operating requirements) check the alignment of the coupling (at
least once a year). Re-align if necessary (see 5.2).
Operating log
It is recommended to enter operating data and data on lubrication, repairs etc. in an operating log. An
ongoing operating record will assist troubleshooting and machine service decisions. Analyse machine
performance regularly.
Spare parts
It is recommended that spare parts listed below are always kept in stock. This modest investment can
often prevent minor faults from developing into serious trouble. The following parts should be stocked:
Antifriction bearings, in case of plain bearing (set bearing shells, pads)
Balance drum and liner (set balance discs)
Wear rings and setscrews
Gaskets and O-rings
Mechanical seals
For pumps used in extremely important service or if several identical machines are operating in the
same plant, it is recommended that a complete machine be stocked at job site.
Orders for spare parts should always include the following information:
Type of pump (rating plate or operating manual)
Order number (rating plate or operating manual)
Quantity and designation of parts / article-number (parts list)
Part number (parts list or sectional drawing)
Single-acting mechanical seal (for make, type and size see sectional drawing)
General remarks
In the case of mechanical shaft seals the exit of the medium delivered is prevented by two plane parallel
lapped ring surfaces which are pressed together with the help of spring force and liquid pressure. Seal
rings (stationary and rotating) are sealed against adjacent pump parts with the help of adjoining sealings
(as for example O-rings) serving simultaneously as elastic bearing.
Conditions
In order to have trouble-free operation a liquid film has to form between the slide
faces and therefore the following conditions have to be fulfilled by the medium
delivered:
- sufficient lubricating properties
TMC-IMO-VER1.0-2007
MC
INSTALLATION,OPERATION & MAINTENANCE MANUAL
Maintenance
The maintenance of the mechanical seal is limited to the control of the leakage, of the temperature and,
if fitted, to the auxiliary facilities.
(* The figures for 50 °C (120 °F) correspond to the previous system of lubricants.)
When during operation under extreme conditions (high ambience temperature, high
bearing load etc.) a higher temperature is found at a certain measuring point, oil of
the viscosity class ISO VG 68 has to be used. The max. allowable values given in
the table will then rise by 10 °C (20 °F).
In case of bigger deviations contact the service. Besides we recommend to carry out the lubrication
renewal under extreme bearing temperatures as described above in change intervals of half a year.
Change intervals and oil quantity
TMC-IMO-VER1.0-2007
MC
INSTALLATION,OPERATION & MAINTENANCE MANUAL
In case of first commissioning or of an overhaul, drain an change the oil after 10-15 hours of operation. If
further pollution by foreign substances and water is low, change intervals of 6 months can be adhered
to.
In the case of automatic constant–level-oilers pay attention to refill the reservoir (oiler tank).
Max. allowable temperatures
Measuring spot
Mode
externally at bearing at external bearing race in oil bath
housing near bearing
continuous operation < 80 °C (175 °F) < 90 °C (195 °F) < 70 °C (160 °F)
Alarm at > 90 °C (195 °F) > 100 °C (210 °F) > 80 °C (175 °F)
switch off aggregate > 100 °C (210 °F) > 110 °C (230 °F) > 90 °C (195 °F)
Proper lubrication is particularly important for the operational safety of centrifugal pumps.
If suitable lubricants are correctly applied, an optimum performance is obtained and trouble and
its consequences are avoided. Supplementing the operating instructions, the table gives the
lubricants which are recommended for the lubrication of centrifugal pumps which are suitable for
an ambient temperature between -10 up to +40 oC (15 up to 100 oF).
The lubricants have been listed in alphabetical order which does not say anything about their
quality
CASTROL HYSPIN VG
CASTROL CASTROL HYSPIN VG 68
46
TMC-IMO-VER1.0-2007
MC
INSTALLATION,OPERATION & MAINTENANCE MANUAL
Oil replacement
Warning: Lubrication can cause skin irritation and eye inflammation. Follow all safety
precautions specified by the manufacturer.
For oil replacement proceed as follows:
1. Shut down pump.
TMC-IMO-VER1.0-2007
MC
INSTALLATION,OPERATION & MAINTENANCE MANUAL
2. Put a tray under oil drain to catch the whole quantity of oil securely. (Position of the oil drainage
bores and size of the screw plugs see installation plan or dimension sheet.)
3. Remove screw plug, drain oil thoroughly. Tighten screw plugagain securely.
4. Fill bearing bracket with fresh oil as described above.
Dispose of used oil according to statutary regulations.Do not put into waste water by any
means.
7.4 OVERHAUL - DISMANTLING OF THE PUMP
When overhauling a pump it is advisable to procure all necessary spare parts (wearing parts) well
beforehand to minimize the down time. When ordering spare parts it is essential to give an exact
description of the part, its part number, the pump type and serial number (see the duty plate).
References Refer to specific drawings (section drawing(s), parts lists, installation plan).
Note: A pump should only be disassembled by qualified specialists with suitable tools and by strictly
observing the instructions.
Preliminary work
- Close the suction and discharge valves and secure them against unauthorized opening.
- Let hot pumps cool down to ambient temperature before disassembly.
- Isolate the driver to prevent start-up.
With electrical driver: Remove residual current (take away safety fuses). Have electrical
connections disconnected by an electrician.
- Drain the pump (position of drain screw see installation plan)
The draining of the pump from toxic, explosive, hot or otherwise dangerous fluids must not lead
to any endangering of operator(s) and environment. Observe legal provisions for disposal.
In case the pump delivered aggressive, toxic or otherwise dangerous media, it has to be flushed
carefully, to be cleaned on the outside and to be decontaminated in the case of radioactivity.
If the pump is sent to the manufacturer to be repaired, the cleaning / decontamination has to be
carried out before transport.
The service personnel will have to be careful however inspite of this, as even in the case of a thorough
flushing and cleaning, residues of the fluid may leak out.
- Remove the coupling guard and separate the coupling halves.
- Remove any instruments and ancillary pipes.
- Drain off oil from bearing brackets.
Dispose of used oil acc. to legal regulations. Never put it into the sewage system.
Remark: Maintenance, inspection and repair works on the bearing
shaft seal and balance device does not require hydraulic pump part
dismantling.
- Disassemble pump and take it to assembly site.
Pay attention to hazardous situations during
disassembly, i.e. take care to stand firm, secure
assembly parts against dropping, support or prop loose
parts etc.
- Remove coupling half on pump side (see sketch 7.4-1), take off
key .
To avoid damage to the bearings or to the shaft
centering thread use a suitable puller and protect
the shaft centering thread by a disc. The bearings must by no means
be subjected to any pressure or shock.
Dismantling of bearing - non-drive side
- Remove screws for the fastening of the fan cover and take off fan cover. Take circlip out of shaft
groove by means of spring ring pliers, push fan off the shaft and remove key.
TMC-IMO-VER1.0-2007
MC
INSTALLATION,OPERATION & MAINTENANCE MANUAL
- Remove hexagon socket screws from bearing cover . Take off bearing cover, push shaft seal ring off
the shaft.
- Bend lockwasher tang out of bearing nut and screw off bearing nut. Take off lockwasher .
- To dismantle the bearing bracket, remove dowelling (tapered pins) on bearing bracket flange. Screw in
(tighten) hexagon nuts to break the tapered pins out of their seats. Loosen adjustment screws on the
bearing bracket flange.
- Screw off hexagon nuts of the bearing bracket fastening, mount puller (see sketch 7.4-2) and draw off
bearing bracket together with antifriction bearings .
- Remove hexagon socket screws and take off bearing cover . Dismantle antifriction bearings from
bearing bracket.
TMC-IMO-VER1.0-2007
MC
INSTALLATION,OPERATION & MAINTENANCE MANUAL
TMC-IMO-VER1.0-2007
MC
INSTALLATION,OPERATION & MAINTENANCE MANUAL
TMC-IMO-VER1.0-2007
MC
INSTALLATION,OPERATION & MAINTENANCE MANUAL
The max. permissible variance in the vicinity of the shaft outer diameter (shaft shoulders, hubs, sleeves
etc.) should not be more than 0.01 mm (0.0004 in.). If this value is exceeded, re-machine: e.g. turn on
mandrel (without clamping) or grind with the minimum possible reduction in the hub and/or sleeve
length.
Repeat concentricity check as described above. Upon satisfactory completion of concentricity check,
dismantle rotor. Mark impellers in sequence so that they can be refitted in the same order when
assembling the pump. Remove the special components used for the concentricity and keep to use in
future overhauls.
- Insert O-ring seal in the groove of the balance drum bore and slide balance drum onto shaft.
TMC-IMO-VER1.0-2007
MC
INSTALLATION,OPERATION & MAINTENANCE MANUAL
- Push balance drum liner with O-ring seal into delivery casing and allow the cylindrical dowel pin
preventing rotation to engage in the hole.
Assembly of the shaft seal housings
On both sides of the pump
- Insert key that drives the shaft sleeves into shaft.
- Insert O-ring seal on the spigot of the stuffing box housings . Locate stuffing box housings on delivery
casing and suction casing using hexagon socket screws.
- In case of cooling: Insert O-ring seals into the grooves of the cover and push cover into stuffing box
housing.
- Insert O-ring seal in the groove of the shaft sleeve bore and push shaft sleeve onto shaft.
In order to achieve the most favourable hydraulic efficiency of the pump, the impellers and diffusers
must be placed in the optimum position to each other. For this purpose and in order to avoid lateral
distortion of the rotor, the theoretical axial position of the rotor is to be measured and set. The
construction tolerances make it possible to keep the correction of the axial rotor position within very low
limits.
Remark: All assembly works for the measurement have to be carried out without use of seal rings and
with greatest possible care.
Remark: New throwers are supplied with oversize, they must be machined to the calculated dimensions.
When repair work is done the nominal dimension can be gained by applying supplementary discs.
The thrower sleeve shoulders must be parallel to each other within 0.01 mm after
Machining
TMC-IMO-VER1.0-2007
MC
INSTALLATION,OPERATION & MAINTENANCE MANUAL
- On the drive-side: Check the length dimension of the thrower while the rotor is moved to the non-drive
side. See sketch 7.6-3.
To do so measure with depth gauge from the circlip in the bearing bracket (stop anti-friction bearing
outer race) to the front face of the spacer sleeve dimension “C”. The measuring result should
correspond to the dimensions given in the following table.
Serious damage can be caused if the pump is started with off-center rotor
TMC-IMO-VER1.0-2007
MC
INSTALLATION,OPERATION & MAINTENANCE MANUAL
- On the non-drive side: Remove Bearing housing again. Push thrower with normal dimension onto
shaft and mount bearing housing again.
- Loosen all adjusting screws and put bearing housings in the lowest position possible.
- Tighten fastening of bearing housing and loosen them once again, so that the bearing housing can be
shifted by the adjusting screws which are at the bearing housing flange.
- Horizontal adjustment: Adjust bearing housing by the lateral adjusting screws. Measure between
shaft and bearing housing bore by means of an inside spring caliper until shaft is in the horizontal
center. See sketch 7.6-4. Tighten and secure lateral adjustment screws in such a way as to fix the
bearing bracket in horizontal position and allow vertical movement.
- Vertical adjustment: Attach a measuring gauge vertically near the bearing (the measuring pin has to
be positioned at right angle to the shaft) to ascertain at the bearing area by what dimension the shaft
can be lifted. Divide the result by two and note. See sketch 7.6-5
Do not bend the shaft!
TMC-IMO-VER1.0-2007
MC
INSTALLATION,OPERATION & MAINTENANCE MANUAL
If check of free –running is satisfactory dowel bearing housings in new position. Existing taper pin
holes can be reaimed to the next size taper pin or, if required, drill new holes (mark old holes).
Assembly of antifriction bearings
On both sides of the pump
- Loosen all fastening and adjusting screws for the bearing housings. Insert taper pins through bearing
housing flange. Support bearing housing and seat taper pins, then properly tighten bearing housing
fasteners evenly and crosswise.
Assemble thrust bearing – non-drive side
- Build in outer race of inboard taper roller bearing with bearing support ring into bearing housing bore
(make sure that one bore of the bearing support ring points downwards). Warm taper roller bearing inner
races with rolling elements in an oil bath to approx. 80-100 oC and push them up to shaft stop (against
thrower. Fit outer race of outboard taper roller bearing.
In case of renewed taper roller bearings:
Use only paired taper roller bearings, never replace only one bearing of a unit.
The bearing design number is given in the pump parts list.
- Install spacer disc, lock washer and shaft nut. Apply lubricant to the contact face of the bearing nut.
Tighten shaft nut and bend lockwasher tang into one of the shaft nut slots.
Do not over tighten bearing nut.
- Install ring with hexagon socket screws and tighten fasteners with torque wrench
evenly and crosswise. During tightening turn rotor by hand. After tightening the rotor reaches its final
axial running position.
Assemble radial bearing – drive side
- Heat inner race of roller bearing in oil bath up to 80 oC and and push them up to shaft stop (against
thrower. Build in outer race with rollers into bearing housing bore.
- Install spacer disc , lock washer and shaft nut. Apply lubricant to the contact face of the bearing nut.
- Tighten shaft nut and bend lockwasher tang into one of the shaft nut slots.
Do not over tighten bearing nut.
Check and correct the thrust bearing axial clearance (end play)
To allow the forming oil films between bearing parts and for heat expansion, it is
necessary to provide a correct bearing end play. The bearing end play must be
checked after every disassembly of the taper roller bearings.
- Place clock gauge axially on the front of the shaft on the non-drive side; check axial clearance of the
taper roller bearing unit by axially moving the rotor into its final positions. See sketch 7.6-6. Tap lightly
on the bearing bracket (non-drive side) with a rubber hammer to straighten twisted rolling elements.
- If there is no noticeable clearance the bearing elements may be twisted, turn rotor slowly in both
directions and measure once again. If the measure axial clearance is smaller than 0.04 mm (0.0016 in.),
the fault may be corrected by tightening the thrust bearing shaft nut more strongly. Correct mistake.
- Remove device for bearing end play measurement.
If the taper roller bearing temperature after overhaul rises >90 oC (195 oF), as a first
measure check bearing end play.
TMC-IMO-VER1.0-2007
MC
INSTALLATION,OPERATION & MAINTENANCE MANUAL
Final assembly
- On the drive side bearing housing: Fit gasket on the bearing cover . Install bearing cover and tighten
bearing cover fasteners evenly and crosswise. Push outboard thrower onto shaft, adjust gap between
bearing cover and thrower to 1 mm and tighten setscrew .
- On the non-drive side bearing housing: Push shaft seal ring onto shaft and lube seal ring lip. Fit
gasket on the bearing cover , install bearing cover and tighten bearing cover fasteners evenly and
crosswise. Insert key for fan into shaft, slide on fan and place circlip in shaft groove. Place fan cover and
fasten with cylindrical screws.
Install pump
- Move the pump to installation place and mount pump onto baseplate. Connect main lines.
Coupling
- Mounting the coupling half: see sketch 7.6-7
To do so, remove heat-sensitive parts (e.g. rubber buffers and
seal rings etc.) and heat up the coupling half to approx. 80 oC
(180 oF) by means of uniform dry heat (e.g. oven or hot plate).
Slide the coupling half onto the shaft and fit removed parts
again after it has cooled down. Couplings with bores up to a
diameter of 50 mm (2 in.)can also be fitted cold with an
appropriate attachment.
The bearings must by no means be subjected
to any pressure or shock
Ancillary equipment
- Install auxiliary lines (balance-, circulation-, cooling lines...)
and instruments (thermometers, constant level oiler, pressure
gauges...)
Driver
- Couple the driving unit.
- Check alignment of coupling and tighten foot fasteners with torque wrench (see 5.2), check free
running of the rotor.
- Fit the coupling guard.
TMC-IMO-VER1.0-2007