Professional Documents
Culture Documents
HOW TO DESIGN AMMONIA REFRIGERATION PLANT USING AAR STANDARD 1 2016 by Ramesh Paranjpey
HOW TO DESIGN AMMONIA REFRIGERATION PLANT USING AAR STANDARD 1 2016 by Ramesh Paranjpey
By
Ramesh Paranjpey
Ramesh.Paranjpey@gmail.com 1. INCRRECT DESIGN
Cell:+91 9822398220
19th January 2018
2. WRONG PIPING
3. WRONG MATERIAL FOR CONSTRUCTION
4. INCORRECT OPERATION/MAINTENANCE
AAR STANDARD TAKES CARE OF ALL ISSUES
WHY NEW STNDARD-WHAT IS THE NEED ? WHY NEW STNDARD-WHAT IS THE NEED ?
1. IS-660 is general safety standard-not specifically for ammonia refrigeration 5. ANSI/ASHRAE -15 -2013 & ANSI/IIAR2-2014-High Pressure (250psig)1724KPa,
and does not cover design & Installation aspects 6. AAR Standard-1 is for 2070KPa (300psig)design pressure for water cooled
2. Ammonia systems are mostly field erected by erection team, that is not applications to suit Indian Ambient conditions of 450C machine room
necessarily skilled, and unaware of issues arising out of incorrect practices. temperatures since at (450C(1130F)-operating pressure or standing pressure is
3. Ammonia, if leaks, and exposed to human beings can cause health & safety (260psig)(1783Kpa) (18.18kg/cm2-absolute)
issues hence need special precautions. 7. For Air cooled Applications with condensing temperature of 600C the design is
4. The existing global standards are not specific to Indian conditions & need for (400psig)/28.12 kg/cm2
changes to meet specific design/testing requirements to suit Indian
conditions.
1
20/03/2018
This chapter indicates what is covered in the standard. Covers definitions of terminologies used in refrigeration
1. It applies to closed circuit mechanical refrigeration systems applications while designing, selecting equipment,
2. Covers design, safety requirements installation and maintenance practices.
3. Covers Normative requirements(Good or Desirable) This Chapter is important in understanding correct meanings
of Different terminologies while designing refrigeration
systems
The Chapter includes many new definitions, not covered in
other similar standards.
2
20/03/2018
4. ASME Sect V III-Div. 1 3. Design Pressure-Corresponding to +170C above wet Bulb for Water Cooled
5. TEMA applications-min. as per EN/ISO standard
4. Corresponding to +170C above Dry Bulb for Air Cooled applications Minimum
6. ISO-5149 5. Suggestion-Please Design for both High and low stage Vessels for above
7. EN 378 pressures to Reduce Ammonia Charge. Ammonia can be then stored in L.P.
vessel & there is no need to pump down every time plant is shut down.
8. OSHA
9. BIS-2825-A very Good standard
6. Add corrosion allowance 0f 1.5 to 1.6mm in calculated thickness IS2002 Grade 2B 12.1kg/mm2- 17206
For steel plates ref:IS4503 page 46-ASME Sec-1 Div-VIII- DO NOT USE IS226 WHICH IS CLASSIFIED AS STRUCTUTAL
7. Fabrication as per IS 2825 or ASME sec. VIII-Div 1./ or EC/97/23 Code practice STEEL
3
20/03/2018
4
20/03/2018
Chapter-6-Machinery room requirements Normal Ventilation rate requirements for Machine room
STANDARD MINIMUM VENTILATION
1. The chapter covers machinery room design requirements,
how it is to be constructed. ANSI/ASHRAE-15 0.5cfm/sq.ft or 2.54l/s per sq.m or
2. It covers what is the equipment allowed inside the 9.44l/s per person
machinery room and which equipment should be avoided ISO 5149 -Formula for Calculations
in the machine room.
BOCA National 6ACPH- (Building officials and & Code Administrators-
3. It gives precautions -while doing refrigerant piping.
Mechanical code USA)
4. It gives safety requirements such as electrical safety,
lighting, location of alarms, sensors, eyewash/showers.
5. Chapter deals with emergency ventilation requirements
Emergency Ventilation rate requirements for Machine room Chapter-7-Areas other than machinery rooms
WHICHEVER IS MORE
5
20/03/2018
Refrigerant Value of F
6
20/03/2018
SIZING OF SAFETY VALVE Typical Set Values & Tolerances 300psig & 250psig systems.
300psig 250psig
For plate heat exchanger or C = 0.5(A/2) C = 0.04(A/2) EPCS set Point(equal or below set point)- 250psig to 275psig 210psig to 225psig
double-pipe condenser Emergency Pressure Control System
where
C = required discharge capacity , lb(air)/min [kg/s] Design system operating pressure(-25% lower 225psig 200psig
D = OD of vessel, ft [m] than relief valve setting when selecting relief
L = length of vessel, ft [m] valves
A = Overall external surface, ft2 [m2]
This program was intended for using the AAR-1 standard for the
purpose of designing the pressure vessels, understanding
requirements of Ammonia Refrigeration systems, various • Thanks
procedures so that the design & installation carried out,
becomes safe and the incorrect practices followed by designers,
erectors out of their lack of knowledge or ignorance are avoided • Any Questions?
and the bad name and adverse publicity by others that
ammonia refrigeration systems is experiencing today is • Ramesh Paranjpey
eliminated. • Ramesh.paranjpey@gmail.com
It is suggested that the designers, erection engineers and • Cell No. 9822398220
operators further read detailed AAR booklets prepared on • Website: http://Ramesh-paranjpey.com
installation, piping, maintenance practices as also design of
ammonia cold storage systems.