• Complies with 2011 NEC requirements • Selectable audible alert for impending shutoff
• Detection Signature Processing eliminates false triggers and • In automatic mode, sensor returns automatically to Auto-ON
provides immunity to RFI and EMI after lights are turned off manually; ideal for presentations
• Zero-crossing on both relays for long relay life • Four occupancy logic options give users the ability to
• Vandal resistant lens combines precise coverage with customize control to meet application needs
durability • Optional light level sensing with simple setup
• Choice of Manual-ON or Auto-ON operation, selectable for • Service mode allows sensor to operate as a service switch
each relay in the unlikely event of a failure
• Selectable walk-through mode turns lights off three minutes • Sensor coverage tested to NEMA Guide Publication
after the room is initially occupied if no motion is detected WD 7-2000
after the first 30 seconds • Compatible with decorator wall plates
• Test mode allows quick and easy adjustments
1 WWW.LEGRAND.US/WAT TSTOPPER
SENSORS | Occupancy and Vacancy
SPECIFICATIONS
• 120/277 VAC; 50/60 Hz • Ultrasonic Frequency: 40kHz
– @ 120 VAC, 0-800 W ballast or tungsten, 1/6 hp • Sensitivity adjustment: PIR (high/low), Ultrasonic
– @ 277 VAC, 0-1200 W ballast (fully variable)
• Time delays: 5, 15 or 30 minutes, walk-through, test-mode • Dimensions: 2.73” x 1.76” x 1.83”
• Coverage: (69.3mm x 44.7mm x 46.5mm) L x W x D
– Major motion, PIR 35’ x 30’, Ultrasonic 20’ x 20’ • UL and cUL listed
– Minor motion, PIR 20’ x 15’, Ultrasonic 15’ x 15’ • Five year warranty
CONTROLS & SETTINGS
Product Controls DIP Switch Settings
ON/OFF Buttons On Mode
Time Trigger Relay 1
Relay 1 Delay Mode Audible Alert 7
Time Delay 1 2 Relay 2
Relay 2 Test/20 min Enabled
ON
5 minutes Disabled
Ultrasonic Sensitivity 1 2 3 4 5 6 7 8 9
Adjustment Trimpot 15 minutes
Relay 1 On Mode 8
75,**(5
'(/$<
30 minutes
3,5
5/<0$1
:$/.
5/<0$1
$/(576
Auto On 2
Occupancy
Occupancy
Re-trigger
Maintain
Enabled
Initial
Detection LEDs Disabled
Trigger Relay 2 On Mode 9
Mode 5 6 Manual On
Red = PIR Standard Both Either Either
Auto On
Green = Ultrasonic PIR Sensitivity 4 Option A PIR Either Either
Low, 50% Option B PIR PIR PIR Factory Settings:
PIR Lens
High Option C Both Both Both
=ON =OFF
Ground Green
20’ 20’
(6.1m) (6.1m)
15’ Neutral White
(4.5m)
Brown Secondary
Neutral White
4’ Load
(1.2m)
Ground Green
0 20’ 35’
(6.1m) (10.6m)
Neutral White
ORDERING INFORMATION
Catalog # Color Voltage Load Rating
DW-200-W White 120/277 VAC; 50/60 Hz @ 120 VAC, 0-800 W ballast or tungsten,1/6 hp
@ 277 VAC, 0-1200 W ballast
DW-200-LA Light Almond
DW-200-I Ivory
DW-200-G Gray
DW-200-B Black