Acs580 p16

You might also like

Download as pdf or txt
Download as pdf or txt
You are on page 1of 1

16 A B B G E N E R A L P U R P O S E D R I V E S , A C S 5 8 0 , C ATA LO G


Technical data

Mains connection Environmental limits


Voltage and 3-phase, U N 380 to 480 V, +10%/-15% Ambient temperature
power range ACS580-01: from 0.75 up to 250 kW
Transport -40 to +70 °C
ACS580-04: from 250 up to 500 kW
Storage -40 to +70 °C
ACS580-07: from 75 up to 500 kW
Operation area ACS580-01: -15 to +50 °C. No frost allowed
Frequency from 48 to 63 Hz
R1 to R9 from +40 to +50 °C with derating
Power factor cos = 0.98 ACS580-04: -15 to +55 °C. No frost allowed
R10 to R11 from +40 to +55 °C with derating
Efficiency 98%
ACS580-07: 0 to +40 °C. No frost allowed
(at nominal power)
R6 to R11 from +40 to +50 °C with derating
Motor connection
Cooling method
Voltage 0 to U N , 3-phase Air-cooled Dry clean air
Frequency 0 to 500 Hz Altitude
Motor control Scalar and vector control 0 to 1 ,000 m Without derating
1,000 to 4,000 m With derating of 1%/100 m
Torque control Torque step rise time:
<10 ms with nominal torque Relative humidity 5 to 95%, no condensation allowed
Non-linearity: Degree of protection ACS580-01:
± 5% with nominal torque IP21 as standard. IP55 as option
Speed control Static accuracy: (frames R1 to R9)
20% of motor nominal slip ACS580-04:
Dynamic accuracy: IP00 as standard. IP20 as option
1% seconds with 100% torque step (frames R10 to R11)
Product compliance ACS580-07:
CE Cabinet-built frames R6 to R9:
Low Voltage Directive 2006/95/EC, EN 61800-5-1: 2007 IP21 as standard. IP42 and IP54 as options
Machinery Directive 2006/42/EC, EN 61800-5-2: 2007 Cabinet-built frames R10 to R11:
EMC Directive 2004/108/EC, EN 61800-3: 2004 + A1: 2012 IP42 as standard and IP54 as option
RoHS directive 2011/65/EU Functional safety Safe torque off
ACS580-07 (R10–R11) CE (STO according EN 61800-5-2)
Quality assurance system ISO 9001 and Environmental system IEC 61508 ed2: SIL 3. IEC 61511: SIL 3.
ISO 14001 IEC 62061: SIL CL 3. EN ISO 13849-1: PL e
Waste electrical and electronic equipment directive
(WEEE) 2002/96/EC Contamination levels No conductive dust allowed
RoHS directive 2011/65/EU Storage IEC 60721-3-1. Class 1C2 (chemical gases).
UL, EAC, RCM, UL, cUL Class 1S2 (solid particles)*
EMC according to EN 61800-3: 2004 + A1: 2012 Operation IEC 60721-3-3. Class 3C2 (chemical
Frames R1 to R9 with built-in C2 category filter as standard gases). Class 3S2 (solid particles)*
Frames R10 and R11 with preconfigured built-in C3 category filter option
Transportation IEC 60721-3-2. Class 2C2 (chemical gases)
Class 2S2 (solid particles)*

* C = chemically active substances


S = mechanically active substances