Quick User Guide RESOLUTION 16 bit Communication Specification TRANSMITTER measured input terminal &

Flow Indicator Totaliser -1006H POLARITY Not provided internal circuit, isolated
PROTECTION PROTOCOL Modbus RTU serial from other input/output
MEMORY BACKUP EEPROM STANDARD EIA RS-485 terminals.
MAX. 1200 mtrs. (For 9600 RETRANSMISSION Isolated from other
Loop Power Supply Specification COMMUNICATION bps RS 485) OUTPUT input/output terminals and
DISTANCE TERMINAL internal circuit.
LOOP POWER 24VDC ± 5% @ 50mA COMMUNICATION 2 wire half duplex (RS
METHOD 485) CONTACT INPUT Isolated from other
SUPPLY TERMINAL
DATA FRAME N, 8, 1 input/output terminals and
COMMUNICATION 9600, 19200 bps internal circuit.
Retransmission Output
RATE RELAY CONTACT Isolated from other input
NUMBER OF OUTPUTS 1 MAX. CONNECTABLE 32 O/P TERMINAL /output terminals and
CONTROLLERS/ (DIGITAL INPUT) internal circuit.
OUTPUT SIGNALS 4 to 20 mA DC
1006H Flow Indicator Totaliser INDICATOR RS-485 Isolated from other
LOAD RESISTANCE 500Ω or less ADDRESS RANGE 1 to 99 COMMUNICATION input/output terminals and
Input Type Range TERMINAL internal circuit.
OUTPUT ACCURACY ± 0.25% of full scale +1 Display Unit Specification
0 to 20 mA POWER SUPPLY Isolated from other input /
count
TERMINAL output terminals and
4 to 20 mA RESOLUTION 12 bits (5uA) PV DISPLAY/ 0.56” 6 digit 7-
0 to INTEGRATED TOTAL segment red LED internal circuit.
0 to 5 V 3000 0 DISPLAY display GROUND Isolated from other input/
Contact Input (Digital input)
1 to 5 V PARAMETER DISPLAY 0.56” 6 digit 7- TERMINAL output terminals and
NO OF INPUTS 1 segment red LED internal circuit.
*Pulse Input
USAGE Input 1 : Start Batch /Stop display
Integrated/ 0 to
Batch Environmental Specification
Batch Total 9999 99
INPUT TYPE Non- voltage contact input Power Supply Specification
Table 1.1
or transistor open collector OPERATING 0 to 55C
SPECIFICATIONS input POWER SUPPLY 110 to 230 VAC, 50Hz ; TEMPERATURE
INPUT CONTACT 24VDC,10mA or more (for 24VDC(optional) STORAGE 0 to 70C
NUMBER OF INPUTS 1 CAPACITY non – voltage contact input) POWER <10Va TEMPERATURE
ON/ OFF  For non-voltage CONSUMPTION
ACCURACY ± 0.25% of full scale ± 1 HUMIDITY 30 to 90% RH
DETERMINATION contact input WITHSTANDING  Between primary terminal
Count , (Noncondensing)
ON = contact VOLTAGE and secondary terminal :
**0.45 % - for 1500VAC(For 1 min) WARM UP TIME >10 Minute
Integrated/ Batch Total resistance of 1KΩ or
 Between primary terminal EFFECT OF For Voltage Input: 
BURN OUT Available for 1 to 5VDC, less,
and ground terminal : AMBIENT 0.005% of FS/ C or less
DETECTION 4 to 20 mA, 0 to 10 KHz. OFF = contact
resistance of 20KΩ 500VDC(for 1 min) TEMPERATURE For analog output: 
INPUT RESISTANCE  250 Ohms Internal  Between ground terminal
or more 0.010% of FS/ C or less
for current Input
 For transistor contact and Secondary terminal:
 320K Ohms for
input 500V AC (for 1 minute). Alarm Specification
Voltage Input
ALLOWABE SIGNAL DC input voltage: 1KΩ or ON = 2V or less  (Primary terminal:
Power supply, relay ALARM TYPES Flow high limit, Flow low limit
SOURCE less. Effect from OFF = leak current
output) BATCHING Pre warn and set point
RESISTANCE allowable signal source of 100µA or less
(Secondary terminal: ALARM
Resistance: 0.031 % / MINIMUM About 1 Second
100Ω or less Analog input/output signal SETTING Flow (PV) Alarms:
RETENTION TIME
RANGES FOR Min = Zero of individual I/P type
ALLOWABLE INPUT DC voltage: ±20V DC FOR STATUS terminals, contact input
PROCESS Max = Span of individual I/P
VOLTAGE DETECTION terminal)
VALUE type
NOISE REJECTION Common Mode: >
ALARMS
RATIO 100db Normal mode: > Relay Contact Outputs Signal Isolation Specifications
40db
Display Specification
RESPONSE TIME Input to relay o/p: < 1 NUMBER OF OUTPUTS 2 (Flow alarm relays/ ISOLATION Between power supply
second. Batch relays) RESISTANCE terminal and ground PV DISPLAY/ 6 digit red 7 segment display
Input to Analog o/p: < USAGE Flow alarm / Batch relay terminal: 500 VDC, 50MΩ INTEGRATED for flow rate/Integrated total
1 second or less, 63 % RELAY CONTACT 2(Common, NO) MEASURED INPUT Isolated from other TOTAL
(10 - 90%) (Time TERMINAL TERMINAL input/output terminals. Not
required for o/p to reach PARAMETER Same 6 digit red 7 segment
RELAY CONTACT 250VAC/5Amps isolated from 24Vdc supply DISPLAY display flow rate/Integrated
63% of the maximum RATING (Transmitter power supply) total
excursion when PV
changes from 10% to and internal circuit. STATUS Red LEDs (for alarm & Batch)
90%) 24V DC SUPPLY Not isolated from the DISPLAY
FOR
Doc.Ref. No. m16A/QG/101 Issue No.:00 Page 1 of 2
Other Specification Mode. If user wants to go in EDIT
mode, he will have to enter the  Low alarm and high alarm:
SQUARE ROOT Applicable correct password again. Value of Low alarm should be lower than that
EXTRACTION It is Also use for show Either Flow of high alarm. If user tries to set value of Low
DIGITAL FILTER Applicable Value or Integrated Total. alarm greater than high alarm Value, error
TIME BASE UNIT Second, minute, hour, When Respective Relay LED Lits (In message will be displayed. Similarly, if user
day Red) OR When Channel is set value of High alarm lower than low alarm
CONVERSION 0.00 to 99.99 RL1, RL2 Value, error message will be displayed.
OPEN(Channel no. is corresponding
FACTOR to Relay no.) Alarms value cannot be set greater than Full-
FIVE POINT Applicable scale Value (FS).
LINEARIZATION When Communication on, two LEDs
Rx/Tx  Set point and pre-warn:
LOW FLOW CUT OFF Applicable (In Red) blink.
Error message will be displayed if, set point
MOUNTING DETAILS value is lower than pre-warn and vice versa.
BACK PLATE CONNECTION DETAIL
 Alarm ON-OFF :
User can set alarm/relay availability. If
particular relay is set as ‘yes’, that particular
alarm indication will be present over the
display card and relay action will come into
effect.

PARAMETER FLOW DIAGRAM

Bezel Size (in mm): 48(H) x 96(W) x 110(D)

FRONT PANEL DESCRIPTION

Name of
Function
Part
1. It will allow user to enter in EDIT
mode, when instrument is in RUN
SET OR mode.
SHIFT 2. It will scroll menu and submenu
When it is enabled.
3. It will save edited data.
1. It will enter into the submenu,  Batch total:
when main menu is enabled and This is an eight digit totalized value, displayed
shows submenu’s value. as Batch total. As per the selected time base,
2. It will select the digit to modify, Zero and Full-scale settings, this total is
START OR
when value is edited. updated continuously, proportional to input.
SHIFT
3. It will start batch, if pressed, When New Batch Starts or Integration total is
when IT & BT are being displayed reset this value also gets initialized to 0.

1. It will increment value of digit  Integration total:


selected or constant selected. This is an eight digit totalized value, displayed
STOP OR 2. It will stop batch, if pressed, when as integrated total. As per the selected time
INCREMENT BT/IT are being displayed. base, Zero and Full-scale settings, this total is
updated continuously, proportional to input. For operation manual please visit www.masibus.com
It will escape to previous status, with Specifications are subject to change without notice due to
reference to its current status. continuous improvements.
ESCAPE Sequence of status: Masibus Automation And Instrumentation Pvt. Ltd.
IT MENU SUB-MENU B-30, GIDC Electronics Estate, Sector-25, Gandhinagar-
Parameter’s Value 382044, Gujarat, India.
Escape sequence Tel: +91 79 23287275-79 Fax: +91 79 23287281
When Esc key is pressed in Menu, Web:www.masibus.com Email:support@masibus.com
the instrument will come in RUN
Doc.Ref. No. m16A/QG/101 Issue No.:00 Page 2 of 2