Download as pdf or txt
Download as pdf or txt
You are on page 1of 11

Applied Thermal Engineering 27 (2007) 1394–1404

www.elsevier.com/locate/apthermeng

Application of solar collectors to control the visible plume


from wet cooling towers of a commercial building
in Hong Kong: A case study
S.W. Wang a, S.K. Tyagi a,*
, Atul Sharma b, S.C. Kaushik c

a
Department of Building Services Engineering, The Hong Kong Polytechnic University, Hung Hom, Kowloon, Hong Kong
b
Department of Mechanical Engineering, Kun Shan University, Yung-Kung City, P.O. Box 40-91, Tainan 710, Taiwan
c
Centre for Energy Studies, Indian Institute of Technology, Delhi, Hauz Khas, New Delhi 110016, India

Received 14 July 2006; accepted 7 October 2006


Available online 12 December 2006

Abstract

This communication presents a case study on the application and utility of solar collectors heating system to control the visible plume
from wet cooling towers of a huge commercial building. The visibility of plume from cooling towers depends on the weather conditions,
specially, the temperature and relative humidity of the ambient air. Although the ambient temperature is the main parameter for the
visibility of plume yet the relative humidity also plays a vital role in some cases such as Hong Kong, Europe, Canada and other similar
regions in the world. The present study is on the control of plume from wet cooling towers of a huge commercial building, particularly, in
Hong Kong and can be used as a base for other places in general. The analysis is done based on the hourly weather data available from
the metrological department for a particular year. In this case study the calculations are done using the water cooled and the air cooled
solar collectors and the comparison is also given among the different possible options.
 2006 Elsevier Ltd. All rights reserved.

Keywords: Cooling tower; Plume control; Solar collector; Commercial building; Ambient air temperature; Relative humidity

1. Introduction opment of the cooling tower analysis began in the 19th cen-
tury with the first work carried out by Lewis [1]. Lewis’s
Cooling towers are the enclosed boxes for the evaporat- work for the first time used by Robinson [2] who estab-
ing cooling of water by direct contact with the air, which is lished the general principle applicable to cooling tower
achieved partly by an exchange of latent heat from the design and derived equations for the designers. He also sta-
water evaporation and partly by a transfer of sensible heat. ted a series of fundamental concepts about the mechanism
They are used for heat rejection purposes and are among involved in the transfer of heat between liquid, gasses, and
the important component of any power plant, HVAC on the vaporization of liquid. Merkel [3] used the enthalpy
and industrial applications, especially, where the availabil- potential as a deriving force for air water exchange and
ity of cooling water is not sufficient. Physically they are assumed a similarity between heat and mass convective
often the single largest item of plant at the site and their transfer by means of Lewis number equals to unity which
visual impact is greatly increased if they emit a visible has been used to date.
plume of superheated air into the atmosphere. The devel- Several authors have studied the convection phenomena
occurring in cooling towers. Baker and Shrylock [4] devel-
oped a detailed explanation of the concept of cooling towers
*
Corresponding author. performance clarifying the assumptions and approxima-
E-mail address: sudhirtyagi@yahoo.com (S.K. Tyagi). tions used by Merkel. Sutherland [5] showed that Merkel’s

1359-4311/$ - see front matter  2006 Elsevier Ltd. All rights reserved.
doi:10.1016/j.applthermaleng.2006.10.032
S.W. Wang et al. / Applied Thermal Engineering 27 (2007) 1394–1404 1395

Nomenclature

A area of intersection (m2) Subscripts


COP coefficient of performance Comp compressor
od outer diameter HP heat pump
P power (kW) H heating
Q heating/cooling load (kW) L cooling
RH relative humidity (%) DW dry bulb
Temp. temperature
W humidity ratio (g of water vapor per kg of dry
air)
1, 2 initial, final
dS elementary surface area (m2)

theory leads to an underestimation of tower size by 5–15%. tion among the society. Considering all the possible
Braun [6] developed a confined method to model the per- aspects, reliability, potential, and limitations of each and
formance of both cooling tower and dehumidifying coils. every method, explained so far. We have applied the heat-
Effectiveness relationships have been developed, taking into ing strategy of using solar collectors [26–28] to control the
account a saturated air specific heat used for sensible heat plume from wet cooling towers particularly for this huge
exchanger. The results of this method were compared with commercial building which is also applicable for other
numerical solutions of the detailed heat and mass transfer buildings in general for Hong Kong and other places where
models and experimental results. Shelton and Weber [7] the weather conditions are similar [24,25].
used a mathematical model based on manufacturer’s per-
formance data in order to investigate the effect of (low) 2. The formation of visible plume
water and air flow rates. Lebrun [8] presented the funda-
mentals of a new simulations toolkit oriented upward sim- The ambient air passing through the cooling tower
ple solutions for primary HVAC equipment. This toolkit comes into contact with the hot water, takes heat and mois-
used as much as possible, the literature models. Each model ture and exits the tower (Fig. 1) in saturated or superheated
is described by reference to conceptual scheme, in which state as can be seen clearly in Fig. 2(a). This exhaust leav-
very classical engineering components are interconnected. ing the cooling tower remixes with the cooler ambient air
Lebrun and Silva [9] presented an analysis of basic heat and as it cools down the excess moisture condenses in small
and mass transfer processes occurring around a droplet in fog droplets, causing the visible plume (white smoke). Dur-
transient cooling tower. Bernier [10] presented a unidimen- ing winter season, cold, humid ambient air at condition 1
sional analysis of the spray type counter flow tower was (Fig. 2(a)) is warmed up to condition 2 in the tower (after
presented showing the influence of fill height, water reten- absorbing the heat released by the hot water) and then
tion time, and water flow rate on the tower performance.
Some study on heat and mass transfer analysis on cooling
tower were also made by Naphon [11], Klopper and Kröger
[12–14] , Lees [15], Smith [16] and others [17–23] using dif-
ferent methods.
Under the most unfavorable combination of the ambi-
ent conditions, thermal load and topography, such a plume
can extend few hundred meters and sometime causes visi-
bility and darkness [17–23]. The latest literature review
about cooling towers shows different options for reducing
the visible plume using hybrid cooling towers, wet–dry
cooling towers, dry cooling towers and so on, depending
on the need and demand. As mentioned by number of
researchers wet cooling towers are economically and tech-
nically cheap easy to build and need less power to operate
as compared to other types of towers. But they do not have
any control over the visible plume [17–25].
In recent years, the visible impact of releases to the
ambient has become a matter of greater concern due to
the awareness of environmental degradation and protec- Fig. 1. The working principle of a counter flow cooling tower.
1396 S.W. Wang et al. / Applied Thermal Engineering 27 (2007) 1394–1404

ambient temperature and less for higher ambient tempera-


ture. Thus by joining these two points by a straight line on
the Psychrometric chart, we can predict the possibility and
potential of plume. So the potential of fog can be predicted
by calculating the area of intersection as shown in
Fig. 2(b).
The area of intersection can be calculated following
Wang and Tyagi [24] and Tyagi et al. [25]. This area gives
the magnitude for the possible potential of the plume,
based on the inlet and outlet temperatures of the cooling
tower and the relative humidity of the ambient air at a par-
Fig. 2(a). The formation of plume (fog) in a cooling tower. ticular time.

3. Odd weather conditions


remixes with the ambient air along the line 2–1. Most of
this mixing occurs in the superheated region. Where there It is observed that the conditions for the visible plume
is more moisture (such as in Hong Kong, Europe, Canada, are the lower ambient temperature and higher relative
etc.) in the air than can be held at equilibrium, the conden- humidity as can be seen from Fig. 3(a). Based on the hourly
sation occurs and a dense and persistent plume formed. On weather data for a typical year [25], a detailed analysis has
the other hand, during hot and dry weather conditions, the been done for different properties of the ambient air. The
ambient air in the cooling tower may be heated and remixes relative humidity versus the ambient air temperature is
along the line 4–3, which is wholly in the sub-saturated plotted as shown in Fig. 3(b) and based on these figures
region and no plume is formed. using the Psychrometric chart, it is found that the potential
As mentioned in above section, the exhaust of the tower of plume is much effective in the winter season. The odd
is generally saturated and during odd whether conditions weather conditions are marked on these figures for the pos-
can not be absorbed fully by the surrounding air, as a sible potential of visible plume and the most critical condi-
result, the access appears as visible fog. As shown in tion for the possible potential of the visible plume are
Fig. 2(a), the larger is the temperature difference between shown in Table 1.
Inlet and outlet air of the tower (i.e. the greater the area Thus using the literature as base, we have chosen the
of the intersection to the left of the saturation curve, winter conditions as the most possible case for the major
Fig. 2(b), the more intense will be the plume. As the potential of plume. Although the weather conditions may
exhaust of the tower is almost saturated, the main param- vary from year to year, but the overall changes may not
eter causing plume is the temperature difference between be much affected for a complete year. Hence, the calcula-
the inlet and outlet air of the tower. From Fig. 2(b) it tions and modeling for a particular year can work for long
can be seen that the intensity of plume is more for lower time with a little or no modification. This can also be

Fig. 2(b). The potential of plume (fog) in a cooling tower.


S.W. Wang et al. / Applied Thermal Engineering 27 (2007) 1394–1404 1397

Fig. 3(a). Hourly variation of relative humidity and ambient air temperature.

Fig. 3(b). Variation of relative humidity versus ambient air temperature.

Table 1 4. The potential of the visible plume


Selected critical weather data for Hong Kong in winter and spring
Winter case Spring case From the critical regions selected in Fig. 3(a) and
Temperature Relative humidity Temperature Relative humidity marked in Fig. 3(b), it is found that the winter conditions
(C) (%) (C) (%) have more potential and frequency of plume than those
13–18 95 21–27 95 of the spring conditions. Also for these conditions men-
tioned in Table 1 and marked in Fig. 3(b). Using standard
readjusted using some manual techniques and/or sensors simulation technique at these particular weather data con-
based online program depending upon the weather condi- ditions it is found that only three chillers are required to
tions. Again for such huge buildings some sensor based fulfill the cooling requirement of this building. Based on
online system can be used to detect and control the plume the range of winter condition given in Table 1, we have
by readjusting the set points temperature and the heating chosen the ambient temperature of 15 C and the relative
requirements. humidity of 95%.
1398 S.W. Wang et al. / Applied Thermal Engineering 27 (2007) 1394–1404

Table 2
Operating parameters of cooling towers for critical winter case (Building cooling load is 17,236 kW)
Towers in use Outlet temperature (C) Consumption of power Heat transfer rate in the chiller COP of chillers
High speed Low speed High speed Low speed Chiller, kW Fans, kW Condenser, kW Evaporator, kW
2 3 26.32 27.42 944.7 270 6625 5680 6.01
5 – 23.70 – 883.8 450 6564 5680 6.43
– 10 – 23.67 877.9 300 6558 5680 6.47
5 5 20.30 21.04 820.9 600 6501 5680 6.92
10 – 19.50 – 801.4 900 6482 5680 7.09

Table 3
Heating required and operating parameters for chiller plants
Towers in use Heating required, kW Power consumption COP of chiller
High speed Low speed Fans, kW Chillers, kW Total, kW
2 3 1988.8 270 2834.1 3486.5 6.01
5 – 1311.0 450 2651.4 3353.3 6.43
– 10 1311.0 300 2633.7 3185.6 6.47
5 5 655.5 600 2462.7 3188.7 6.92
10 – 655.5 900 2404.2 3430.1 7.09

Also the optimum operating parameters such as the cally this depends on the number and speed of the cooling
building load, cooling load, heating load, dry and wet bulb towers. It also can be seen that there is big difference
temperatures, inlet air temperature, relative humidity, between the outlet and inlet temperatures of the cooling
water flow rate, air flow rate are calculated and some of towers, especially for low speed cooling towers. In most
them are given in Table 2. As can be seen from Table 2, of the combinations, the potential of visible plume is found
the outlet temperature of high and low speed towers for to be different for high and low speed towers and in gen-
various combinations are different from one another. Thus eral, for low speed towers, it is found to be more than those
the heating requirements and the operating parameters for of the high speed towers. This is because of the fact that the
chillers, at the critical regions marked in Fig. 3(a) and (b) as exhaust temperature of a low speed tower is higher than
mentioned above, are different for different combination that of a high speed tower and vice-versa. Using these oper-
and are given in Table 3. ating conditions, based on the inlet and outlet temperatures
Again, the outlet temperature of the high and low speed of the cooling towers, the potential of the visible plume are
tower is different for different operating conditions. Basi- drawn on the Psychrometric charts as given in Figs. 4–7.

Fig. 4(a). The potential of plume for a low speed tower, case-1, combination-1.
S.W. Wang et al. / Applied Thermal Engineering 27 (2007) 1394–1404 1399

Fig. 4(b). The potential of plume for a high speed tower case-1, combination-1.

Fig. 5. The potential of plume for a low speed tower, case-1, combination-2 which is also similar to case-2, combination-1.

5. Methods to control the visible plume Since the COP of heat pump is much higher than unity,
unlike the electric heater. Keeping this aspect in mind,
Methods of reducing (preventing and/or removing) the Wang and Tyagi [24] and Tyagi et al. [25] made a detailed
visible plume have taken many forms, such as, heating study on the control of visible plume by heating the
the exhaust with natural gas burner, steam coils, installing exhaust of wet cooling tower (from a huge commercial
precipitators, and spraying chemicals on the tower exhaust. building in Hong Kong) using heat pump.
However, such types of solutions in general are expensive As solar energy is clean, free of cost and abundantly
and are not always effective [17,20]. A little can be done available on this planet and can he harness efficiently, pro-
in a wet cooling tower to reduce/remove plume persistence. vided some advance techniques are used. So we have
Theoretically, an access of air has the effect of shortening applied the heating option for the visible plume of wet
the length of the line 2–1 (Fig. 2(a)), thus reducing length cooling towers [24,25] using to different types of solar col-
and frequency and hence, the potential of visible plume. lectors viz. the water cooled solar collectors and the air
But in practice, the gains are small and the cost is high. cooled solar collectors [27]. Thus the present work is a
1400 S.W. Wang et al. / Applied Thermal Engineering 27 (2007) 1394–1404

Fig. 6(a). The potential of plume for a low speed tower case-2, combination-2.

Fig. 6(b). The potential of plume for a high speed tower case-2, combination-2.

further step to utilize the non-conventional energy sources range usually from ambient temperature (say 30 C) to high
in real life problems. The dimensions, temperature differ- temperature (say 1500 C), depending upon the design
ence, number of collectors, the mass flow rate of the fluid, and type of solar collector. The heat can be used for generat-
type of fluids (water/air) are among the important param- ing electric power and/or heating/cooling applications.
eters of the solar collector specifications. Based on the Amongst many available systems, few types of collector sys-
requirements of heating (Table 3) to control the plume tems, viz. flat plate collector, evacuated tube collector, para-
some of the parameters are calculated (Table 4) and given bolic trough collector, central receiver system and parabolic
in Tables 5A and B, respectively, for water and air cooled dish are used depending upon the temperature requirement
solar collectors. and the availability of material required [26–28].
The most common collector for solar water heating sys-
6. Solar collector tem is the flat plate collector. It is a rectangular box with a
transparent cover, installed on a building’s roof. Flat plate
Solar collectors are the devices used to convert the solar solar collector operates on the principle that when a black
radiant energy into heat (thermal energy) in the temperature sheet of metal is placed in the sun, the sheet absorbs sunlight
S.W. Wang et al. / Applied Thermal Engineering 27 (2007) 1394–1404 1401

Fig. 7. The potential of plume for a high speed tower case-2, combination-3.

Table 4 Table 5A
Specifications of a typical flat plate solar collector Water cooled collectors: temperature difference, number of collectors,
water flow rate, etc. for different heating requirements
Dimensions 1860 mm (length) · 1240 mm (width)
Weight 48 kg (approx) Temperature Number of Mass flow rate of water (kg/s)
Collector box Powder coated extruded aluminium channel 1.6 mm difference (C) collectors QH = 1988.8 QH = 1311 QH = 655.5
thick
kW kW kW
Absorber Black continuously plated tig welded solchrome solar
panel selectively coated fins and tubes: 10 nos. Fin size: 10 20 2.37 1.56 0.78
122 mm (width) · 1700 mm (length); tube size: 12.7 mm 15 3.16 2.08 1.04
(od) · 0.56 mm (thick) · 1715 mm (length) 10 4.74 3.12 1.56
Header Copper tubes 25.4 mm (od) · 0.71 mm 5 9.47 6.24 3.12
(thick) · 1320 mm (length) 8 20 2.96 1.95 0.98
Glazing Toughened/tempered glass 15 3.95 2.60 1.30
Thermal Resin bonded rock wool 10 5.92 3.90 1.95
insulation 5 11.84 7.80 3.90
Efficiency 40–70%
6 20 3.59 2.60 1.30
15 5.26 3.47 1.73
10 7.89 5.20 2.60
5 15.89 10.40 5.60
which appears as heat. The plate will gradually heat up until
its temperature is high enough above the ambient such that 4 20 5.92 3.90 1.95
15 7.89 5.20 2.60
the rate of heat loss from the plate to ambient air just bal- 10 11.84 7.80 3.90
ances the rate of heat gain from absorption of solar rays. 5 23.68 15.61 7.80
However, it is a matter of common experience that if
there is a wind blowing, the heat transfer from the plate
to the air will be so effective that the plate will not be more
than few degrees warmer than ambient. Nevertheless, if the sheet (say 1/16 in. or 0.16 cm thick) has a heat capacity
collector can be thermally insulated from the ambient air, of about 1.57 W/m2. Thus, if the absorbed heat is not car-
the solar heat gain can produce a substantial temperature ried off, the plate will rise at the rate of about 333 C/h in
rise. The simplest mechanism for doing this is to cover the bright sunlight [27,28]. In actual, the plate will begin to
the black plate with transparent cover separated by an lose heat to its surroundings at a faster rate as it becomes
air gap. This will allow most of the incident solar rays to hotter and will eventually reach an equilibrium tempera-
reach the plate but will severely cut down the rate of heat ture where the rate of heat loss exactly balances the rate
loss to the ambient. of heat gain from solar absorption. In practice, a hot metal
In bright sun light near ‘Solar Noon’ solar intensity of sheet is not of any value by itself. A solar collector involves
945 W/m2 is the highest commonly available. A metal movement of a fluid, either as air blown over the plate and/
1402 S.W. Wang et al. / Applied Thermal Engineering 27 (2007) 1394–1404

Table 5B 7. Discussion of results


Air cooled solar collector: temperature difference, number of collectors, air
flow rate, etc. for different heating requirements
Using the data shown in Tables 2 and 3, the potential of
Temperature Number of Mass flow rate of air (kg/s) plume for different cases and combinations are shown on
difference (C) collectors
QH = 1988.8 QH = 1311 QH = 655.5 the Psychrometric chart as given in Figs. 4–7 while the
kW kW kW requirements of heating are shown in Table 3. Based on
10 20 9.88 6.52 3.26 the requirements of heating, the specifications about the
15 13.18 8.59 4.34 solar collectors such as the temperature difference, number
10 19.77 13.03 6.52
5 39.54 26.06 13.03
of collectors, mass flow rate of the fluid, etc. are given in
Tables 5A and B and the discussion of results is given.
8 20 12.36 8.14 4.07
It can be seen from Table 2 that for a given ambient
15 16.47 10.86 5.43
10 24.71 16.29 8.14 temperature the exhaust temperature depends on the num-
5 49.42 32.58 16.29 ber of tower in use and the mode of operation i.e. the speed
of tower. Using the Intel and outlet temperatures of the
6 20 16.47 1086 5.43
15 21.97 14.48 7.24 tower, the potential of plume is plotted on the Psychromet-
10 32.95 21.72 10.86 ric chart in Figs. 4–7 for their respective cases shown in
5 65.90 43.44 21.72 Table 2. It is clear from these graphs that higher is the
4 20 24.71 16.29 8.14 exhaust air temperature (or lower is the ambient tempera-
15 32.95 21.72 10.86 ture), higher will be the potential of the visible plume. Also
10 49.42 32.58 16.29 higher is the potential of the plume, more will be the
5 98.85 65.16 32.58 requirements of the heat to control it.
The requirements for heating the exhaust of cooling
or the water flowing through tubes attached to the plate, to towers to control the plume are given in Table 3 for all
carry off heat that is collected. Small tubes run through the the possible combinations. These results are based on the
box and carry fluid-either water or other fluid, such as an calculations done for the critical weather conditions
antifreeze solution. marked in Fig. 2 and mentioned above (Table 1). It is seen
The tubes attach to a black absorber plate. As heat from Figs. 4–7 that the potential of plume is higher when
builds up in the collector, it heats the fluid passing through the number of towers are less and vice-versa. In the present
the tubes. The hot water or liquid goes to a storage tank. If case, the potential of plume is the highest when the number
the fluid is not hot water, water is heated by passing it of (high speed) tower is the least as can be seen from
through a tube inside the storage tank full of hot fluid. Fig. 4(a), while it is reverse in the case of highest (high
Fig. 8 shows a typical water/air cooled flat plate solar col- speed) number of cooling towers as shown in Fig. 7. At
lector with the possible option of heating the exhaust of the the same time, the COP of the chiller and the requirements
cooling towers. for heating are found to be the lowest and highest for these

Fig. 8. Schematic of solar collector for heating the exhaust of cooling tower.
S.W. Wang et al. / Applied Thermal Engineering 27 (2007) 1394–1404 1403

two cases, respectively, and can be seen in Table 3. Apart are plotted in Figs. 4–7 and given in Tables 5A and B. Also
from these two extreme cases, the potential of plume, the some useful conclusions are found for these options and are
COP of the chillers and the heating requirements are found summarized herewith along with few recommendations for
to be moderate and change as the number of (high and low the future work in this direction, as below:
speed) towers are changed.
The results obtained for all the heating options given in • Proper and optimized operation (number and speed) of
Table 3 indicate that the total power consumption first cooling towers is an effective means to control and/or at
decreases and then increases while the power consumption least to reduce the potential and frequency of plume
in the chillers decrease, whereas, the COP of the chillers generated by cooling towers at Hong Kong and other
increases, as the number of cooling towers increases. similar climates.
On the other hand, the power consumption in the fan • Since the solar energy is free of cost and can be utilized
which solely depends on the mode of operation of cooling provided advance technology is used but at the same
towers (i.e. high or low speed) increases continuously, time it is intermittent in nature, and sometime there
except for one combination. In other words, the power may be no more sun light due to raining and/or clouding
consumption in the fans increases (except for one combina- weather. In such a case, this cannot be the ideal solution,
tion) as the number of towers increases and is found to be so there should be some alternative to assist this plan.
the highest when all the 10 towers operate at high speed • For large temperature difference either the number of
while it is reverse in the case of two high speed towers as collectors and/or the mass flow rate of the fluid are
can be seen from Figs. 4(a) and 7. higher which is reverse in the case of smaller tempera-
Again in the case of all 10 towers at low speed, the con- ture difference. Also for the same specifications, the
sumption of power in fans is found to be the second lowest mass flow rate of water is much less than that of
while the consumption of total power is found to be the the mass flow rate of the air, which is basically due to
lowest one. But the COP is found to be moderate (Table the large difference in the specific heat and other physical
3) while the potential of plume is found to be significant and chemical properties the two fluids. Again for the
as can be seen from Fig. 5. On the other hand, in the case water cooled collector there is a need of pump, while it
of all 10 towers at high speed, the fans power consumption needs an air compressor and/or fan/blower in the case
and the COP are found to be the highest and the total of air cooled collector and costs more energy input.
power consumption is the second highest (Table 3) while Thus the water cooled collectors can give a better output
the potential of plume is found to be the lowest (Fig. 7). provided optimum configuration is used.
Except these two main combinations mentioned above, • The total power consumption first decreases and then
either the potential of the plume or the total power con- increases while the power consumption in the chillers
sumption is higher and/or the COP of the chillers is lower, decrease, whereas, the COP of the chillers increases, as
especially when the total number of towers in operation is the number of cooling towers increases. On the other
five. hand, the power consumption in the fan (which solely
As we can see from Tables 5A and B it is clear that the depends on the mode of operation of cooling towers
for large temperature difference either the number of collec- i.e. high or low speed). In other words, the power con-
tors and/or the mass flow rate of the fluid is higher and it is sumption in the fans increases (except for one combina-
reverse in the case of smaller temperature difference. Also tion) as the number of towers increases and is found to
for the same specifications, the mass flow rate of water is be the highest when all the 10 towers operate at high
much less than that of the mass flow rate of the air, which speed while it is reverse in the case of two high speed
is basically due to the large difference in the specific heats towers.
and other physical and chemical properties the two fluids • The potential of plume is the highest when the number
[27,28]. Again for the water cooled collector there is a need of (high speed) tower is the lowest, while it is reverse
of pump, while it needs an air compressor and/or fan/ in the case of highest (high speed) number of cooling
blower in the case of air cooled collector and costs more towers. At the same time the COP of the chillers and
energy input. Thus the water cooled collectors can give a the requirements for heating are found to be the lowest
better output provided optimum configuration is used and highest for these two cases, respectively. Apart from
27,28]. Thus proper and optimized operation (number these two extreme cases, the potential of plume, the COP
and speed) of cooling towers is an effective means to con- of the chillers and the heating requirements are found to
trol and/or at least to reduce the potential of plume gener- be moderate and change as the number of cooling tow-
ated by cooling towers at Hong Kong and other similar ers changed.
climates. • The power input is lower and the COP is moderate when
all 10 towers with low speed are in use but the potential
8. Conclusions of visible plume is significant. So the case of all 10 tow-
ers operated at high speed, can be a better option to con-
Based on the calculations and discussions of results trol the plume even if there is some fluctuation in the
among different combinations, mentioned above, the results temperature and relative humidity in the surrounding
1404 S.W. Wang et al. / Applied Thermal Engineering 27 (2007) 1394–1404

air. On the other hand, the adjustment for the heating [7] S.V. Shelton, E.D. Weber, Modeling and optimization of a commer-
will change and hence, the manual readjustment is cial building chillers/cooling tower systems, ASHRAE Trans. 97
(1991) 1209–1216.
needed to get the optimum operating performance. [8] J. Lebrun, A toolkit for primary HVAC energy calculations,
• Also the temperature of the refrigerant is much higher at ASHRAE Inc., Atlanta, 1993.
the exit of the compressor i.e. at the entering of the con- [9] M.A. Bernier, Cooling tower performance – theory and experiments,
denser. So a desuperheater can be used to heat the ASHRAE Trans. 100 (1994) 114–121.
exhaust of the cooling towers. It not only will save [10] J. Lebrun, C.A. Silva, Cooling towers – model and experimental
validation, ASHRAE Trans. 108 (2002) 751–759.
energy but also can reduce the load of the cooling tower [11] P. Naphon, Study on the heat transfer characteristics of an
and hence, the overall building load. Another way to evaporative cooling tower, Int. Comm. Heat Mass Transfer 32
solve this problem is that one or two chiller can be used (2005) 1066–1074.
as air cooled condenser and that air at high temperature [12] J.G. Kloppers, D.G. Kröger, A critical analysis into the heat and
can be mixed with the exhaust of the cooling tower mass transfer analysis of counter flow wet-cooling tower, Int. J. Heat
Mass Transfer 48 (1998) 765–777.
before being released to the ambient. [13] J.G. Kloppers, D.G. Kröger, Cooling tower performance evaluation:
• One more option is that one or two chillers can be the Merkel, Poppe and e-NTU methods of analysis, J. Eng. Gas Turbine
dual, in other words, a condenser can be cooled using Power 127 (2005) 1–7.
both air and water as per the requirement. In winter [14] J.G. Kloppers, D.G. Kröger, The Lewis factor and its influence of the
when the possibility and potential of plume is high, air performance prediction of wet-cooling towers, Int. J. Therm. Sci. 44
(2005) 879–884.
can be used as coolant. This air can be mixed with the [15] M. Lees, The economics of wet versus dry cooling for combined cycle,
exhaust of the tower and/or to heat the exhaust of the in: IMechE, Symposium on Condenser and Cooling Towers for
cooling tower to remove the plume. Since the perfor- Combined Cycle, London, 1994.
mance of water cooled chiller is better than an air cooled [16] W.W. Smith, Prediction of cooling tower performance, ASHRAE
chiller and the possibility for the major potential of Trans. 6 (1954) 27–36.
[17] ASHRAE 1996, ASHRAE Handbook-HVAC Systems and Equip-
plume is for a short period. In such a situation the chiller ments, ASHRAE Inc., 1996, Chapter-36.
can be cooled by water during the normal period while [18] F. Bouton, R.J. Winter, Mechanical drought cooling towers with
during the odd weather conditions it can be cooled by visible plume abatement. Inst. IMechE, Second Seminar on CCGT,
air and that air can be mixed with the exhaust of cooling London, 1992.
towers to reduce the potential of visible plume. In this [19] M. Bennett, S. Sutton, D.R.C. Gardiner, An analysis of lider
measurements of buoyant plume rise and dispersion at five power
way a better performance of the chiller in particular stations, Atmos. Environ. 26A (1992) 3249–3263.
and the buildings in general can be achieved. [20] B.E.A. Fisher, Predicting cooling tower plume dispersion, Int.
IMechE, Symposium on Condenser and Cooling Towers for Com-
bined cycle, London, 1994.
Acknowledgements [21] R.J. Winter, Control of visible plumes form cooling towers, Proc.
Inst. Mech. Eng. 211A (1997) 67–72.
[22] B.E.A. Fisher, Predicting cooling tower plume dispersion, Procs.
Financial support through Post Doctoral Fellowship Instt. Mech. Engrs. 211A (1997) 291–297.
due to The Hong Kong Polytechnic University is duly [23] A. Corti, E. Carnevale, Environmental impact from wet plume in
acknowledged. Some fruitful suggestions and recommen- combined cycle power plants, Appl. Thermal Eng. 18 (1998) 1049–
dations made by one of the Referees are also appreciated. 1057.
[24] S.W. Wang, S.K. Tyagi, Report on the prediction, potential and
control of plume from cooling towers of International Com-
References merce Center, The Hong Kong Polytechnic University, Hong Kong,
2006.
[1] W.K. Lewis, The evaporation of liquid into gas, ASME Trans. 44 [25] S.K. Tyagi, S.W. Wang, Z.J. Ma, The prediction, potential and
(1922) 325–340. control of plume from cooling towers of commercial buildings: A case
[2] C.S. Robinson, The design of cooling towers, Mech. Eng. 15 (1923) study, Int. J. Energy Res., in press.
99–102. [26] S.C. Kaushik, M.K. Singhal, S.K. Tyagi, Solar collector technologies
[3] F. Merkel, Verdunstungskiihung, VDI Forschungsar beiten, No. 275, for power generation and space conditioning, Internal Report, Centre
Berlin, Germany, 1925. for Energy Studies, Indian Institute of Technology, Delhi, India,
[4] D.R. Baker, H.A. Shrylock, A comprehensive approach to the 2000.
analysis of cooling tower performance, J. Heat Transfer 83 (1961) [27] A.K. Singhal, Indoor-outdoor testing of flat plate solar collectors,
339–349. Technical Report, Solchrome Systems India Limited 61, Sector V,
[5] J.W. Sutherland, Analysis of mechanical draught counter flow air Parwanoo (H.P.) India, 2003.
water cooling towers, ASME Trans. 105 (1983) 576–583. [28] D.W. Lee, A. Sharma, Thermal performances of the active and
[6] J.R. Braun, Methodologies for the design and control of central passive water heating systems based on annual operation, Solar
cooling plant, Ph.D. thesis, University of Wiscosin, Madison, 1988. Energy, in press.

You might also like