IEEMA Trafotech Workshop Paper WKS Weidmann Electrical Technology AG
IEEMA Trafotech Workshop Paper WKS Weidmann Electrical Technology AG
Abstract: A large solar plant in Europe has With the scope to ascertain the real causes of the
experienced more than twenty transformers events, a multidisciplinary fault analysis was
failures in less than six months. A performed. This analysis was based on the
multidisciplinary fault analysis was required with following activities:
the following activities: transformers inspection,
• transformers inspection;
on-site measurements, network simulations,
transformers manufacturing audit as well as • on-site measurements (to detect possible
dielectric and water content tests on insulation voltage transients);
material taken from failed transformers. The • network simulations (to verify the
paper describes the multidisciplinary approach measurements and to identify other possible
utilized for the transformers fault analysis in order critical events);
to identify the root causes, including those • transformers manufacturing audit;
addressable to operations, system integration • dielectric and water content tests on
and transformer manufacturing. insulation material taken from failed and new
transformers.
Keywords: solar plant, power system,
transformer, fault analysis, transformer 2 TRANSFORMERS MAIN DATA
inspection, measurements, power system
simulation, vacuum circuit breaker, prestrike, The main characteristics of the transformers are
restrike, manufacturing audit, dielectric test, reported in Table 1.
water content.
Table 1 - SP transformers main data
Oil immersed Three-phase
1 INTRODUCTION Type
Transformers
Field experience showed over the past years a Rated power 630 kVA
relatively high number of Solar Plant step-up Frequency 50 Hz
Transformers (hereinafter SP Transformers) Primary rated voltage 21 kV ± 2x2.5%
failures or incipient failures. The consequences Secondary rated
are clear: unplanned outages, loss of assets, and 315 V
voltage
profit losses (undelivered energy). Insulation level MV 24 / 50 / 125 kV; LV 3.6 / 10 kV
1/7
TRAFOTECH WORKSHOP 2016
It is important to point out that these tests are The evident signs of high and diffuse partial
much more severe than the standard routine discharges in the inter-phase barriers called into
tests. All the transformers withstood successfully question the method of assembly, gluing,
these special tests without showing significant impregnation, drying and storage of the materials
PD activity. used.
The visual inspection of the faulty five
4 ON-SITE MEASUREMENTS
transformers pointed out that all of them showed
different degree of damage. In fact, some of them The aim of the on-site measurements was to
presented only slight puncture signs on the characterize the interaction between network and
medium voltage (MV) windings while in the SP transformers, with particular attention to the
others the windings were completely damaged. slow front and fast front overvoltages (including
To be underlined that all the transformers were the possible transient due to vacuum circuit
characterized by the same fault pattern: two- breakers VCB maneuvering), and the
phase passing through the solid inter-phase assessment of the harmonic current injection of
barriers (see Figure 1). In addition, typical traces the SP inverters in order to verify if critical
of PD in significant quantities were found within stresses were present.
the solid inter-phase barriers (see Figure 2). A one month measurement campaign was
decided as second step of the fault analysis.
The measuring equipment system was
connected to the MV and LV terminals of the SP
transformer as shown in Figure 3.
sMV
1.
TSP
sLV
2.
CA/CC
Figure 1 - Transformers inspection: damaged
windings of a SP transformer.
Solar array
From the slightly damaged units, it was • phase-to-ground voltages on the LV system
understood that the dielectric breakdown had its through the existing PTs installed at point 2;
origin inside of the inter-phase barrier, and then • line currents on the LV system through the
spread to the affected windings. existing CTs installed at point 2.
2/7
TRAFOTECH WORKSHOP 2016
3/7
TRAFOTECH WORKSHOP 2016
Slow Front Overvoltage following the VCB opening operation; see Table
3 and compare FFO with the adopted lightning
The most severe events were relevant to double
impulse withstand level, i.e. 125 kV.
phase faults with multiple re-ignitions (these
cases refer to the five failures of transformers in Based on the insulation coordination procedure
service that occurred during the measurement [1] [2] applied to the simulated overvoltages, the
campaign). The maximum slow front overvoltage selected standard insulation levels for short
peak values recorded were of about 62,5 kV (3,2 duration power frequency (50 kV) was deemed
p.u.) phase to earth and 112,8 kV (3,33 p.u.) suitable while the lighting impulse (125 kV) was
phase to phase. not adequate for the purpose when compared
with the expected fast front overvoltages (FFO).
Harmonics
As far as the harmonics were of concern, no Table 3 - Results of network simulations
FFO
relevant values were recorded to justify a deeper TOV SFO (kV)
investigation. (kV) (kV)
VCB opening VCB closing
4/7
TRAFOTECH WORKSHOP 2016
However, two details of the manufacturing inception (≤ 2 pC and > 2 pC) as well as
process were noticed to be critical: the breakdown voltage are reported in Table 4.
application of glue in the assembly of the inter-
phase barriers was carried out with too much Table 4 - Results of test 1
glue (glue drops on the pressboard giving rise to PD level
Applied voltage (kV)
Sample Sample Sample Sample Sample
a possible risk of voids which are not (pC)
1 2 3 4 5
impregnable with oil) and that the drying ≤2 80 70 65 55 90
procedure was not appropriate in order to
>2 105 115 100 90 90
remove the moisture in the layers of the inter-
phase barriers. Breakdown 110 120 110 100 120
5/7
TRAFOTECH WORKSHOP 2016
Breakdown 30 25 25 25 50
30
20
7.1.3 Description of test 3 (sample type 1)
10
6/7
TRAFOTECH WORKSHOP 2016
9 REFERENCES
[1] IEC 60071-1 ed8.1 Consol. with am1 (2011-
03) TC/SC 28 Insulation co-ordination - Part
1: Definitions, principles and rules
[2] IEC 60071-2 ed3.0 (1996-12) TC/SC 28
Insulation co-ordination - Part 2: Application
guide
[3] IEC 60243-1ed2.0 (1998-01) TC/SC 112
Electrical strength of insulating materials -
Test methods - Part 1: Tests at power
frequencies
[4] IEC 60814 ed2.0 (1997-08) TC/SC 10
Insulating liquids - Oil-impregnated paper and
pressboard - Determination of water by
automatic coulometric Karl Fischer titration
[5] IEC 60422 ed3.0 (2005-10) TC/SC 10
Mineral insulating oils in electrical equipment
- Supervision and maintenance guidance
[6] CIGRE Brochure 349- Moistrure quilibrium
and moisture migration within transformer
insulation systems
7/7