Professional Documents
Culture Documents
Flammability Limit
Flammability Limit
Flammability Limit
Minimum Ignition
Energy in Mj
expressed as percent by
volume in air
LEL in % UEL in %
Autoignition
by volume of by volume NFPA Note, for many chemicals it
Substance Flash point Temperature
air of air Class takes the least amount of
ignition energy midpoint
between
the LEL and UEL
The explosive limits of some gases and vapors are given below. Concentrations are given in percent by volume of
air.
Class IA liquids (Flash Point less than 73°F (22.8°C); Boiling Point less than 100°F (37.8°C) are NFPA
704 Flammability Rating 4
Classes IB (Flash Point less than 73°F (22.8°C); Boiling Point equal to or greater than 100°F (37.8°C)) and IC
liquids (Flash Point equal to or greater than 73°F (22.8°C), but less than 100°F (37.8°C)) are NFPA 704
Flammability Rating 3
Classes II (Flash Point equal to or greater than 100°F (37.8°C), but less than 140°F) and IIIA liquids (Flash Point
equal to or greater than 140°F (60°C), but less than 200°F (93.3°C)) are NFPA 704 Flammability Rating 2
Class IIIB liquids (Flash Point equal to or greater than 200°F (93.3°C) are NFPA 704 Flammability Rating 1
Lower Explosive Limit (LEL): The explosive limit of a gas or a vapor is the limiting concentration (in air)
that is needed for the gas to ignite and explode. The lowest concentration (percentage) of a gas or a
vapor in air capable of producing a flash of fire in presence of an ignition source (arch, flame, heat). At
concentration in air below the LEL there is not fuel to continue an explosion. Concentrations lower than
LEL are "too lean" to burn. eg: Methane gas has a LEL of 4.4% (at 138 degrees C) by volume, meaning
4.4% of the total volume of the air consists of methane. At 20 degrees C the LEL is 5.1 % by volume. If
the atmosphere has less that 5.1% methane, an explosion cannot occur even if a source of ignition is
present. When methane (CH4) concentration reaches 5% an explosion can occur if there is an ignition
source. Each combustible gas has its own LEL concentration.
These percentages should not be confused with LEL instrumentation readings. Instruments designed and
calibrated to read LEL also read as percent values. A 5% displayed LEL reading for methane for example
would be equivalent to 5% multiplied by 5, or 0.25% methane by volume at 20 degrees C.
Upper Explosive Limit (UEL): Highest concentration (percentage) of a gas or a vapor in air capable of
producing a flash of fire in presence of an ignition source (arch, flame, heat). Concentration higher than
UEL are "too rich" to burn. Also called UFL
NFPA 704 Hazard Identification System
The National Fire Protection Agency (NFPA), in section 704 of the National Fire Code, specifies a
system for identifying the hazards associated with materials. Information contained on this and linked
pages comes directly from the 1990 edition of NFPA 704. Although the system was developed
primarily with the needs of fire protection agencies in mind, it is of value to anyone, including
someone enrolled in a chemistry laboratory course, who needs to handle potentially hazardous
material.
The hazard identification signal is a color-coded array of four numbers or letters arranged in a
diamond shape. An example is shown below. You will see hazard diamonds like this on trucks, storage
tanks, bottles of chemicals, and in various other places around campus and around town. The blue,
red, and yellow fields (health, flammability, and reactivity) all use a numbering scale ranging from
0 to 4. A value of zero means that the material poses essentially no hazard; a rating of four indicates
extreme danger. The fourth value (associated with white) tends to be more variable, both in meaning
and in what letters or numbers are written there. Please note that in the introductory chemistry labs
at the University of Oregon, we do not use the NFPA-specified symbols in the white field. Instead, we
use an alternative set of symbols that indicate the kind of protective gear that should be used when
handling the material. These alternative symbols are drawn from the HMIG system, which differs
somewhat from the NFPA system.