SAFETY, HEALTH AND ENVIRONMENTAL DO NOT SCALE - IF IN DOUBT ASK


REFERENCES INFORMATION
In addition to the hazards/risks normally associated with the types of work Atkins Limited
Chadwick House, Birchwood Park, Warrington,
H786-AC-BECKS1ZZ-FST-DR-CE-2300 detailed on this drawing, note the following: WA3 6AE
H786-AC-BECKS1ZZ-FST-DR-CE-2304 Direct: 01925 238319

H786-AC-BECKS1ZZ-FST-DR-CE-2308
CONSTRUCTION
H786-AC-BECKS1ZZ-FST-DR-CE-2331 1. HIGH GROUND WATER LEVELS/PERCHED WATER TABLE MAY
BE PRESENT.
H786-AC-BECKS1ZZ-FST-DR-CE-2373
2. EXISTING GROUND AND FST BASE DRAINAGE SYSTEM WILL BE
NOTES
H786-AC-BECKS1ZZ-FST-DR-CE-2376 INTERRUPTED. 1. THIS DRAWING RELATES TO THE CIVIL AND STRUCTURAL
H786-AC-BECKS1ZZ-FST-DR-CE-2390 3. WORKING IN THE VICINITY OF EXISTING SERVICES. REQUIREMENTS ONLY. FOR DETAILS OF THE MECHANICAL AND
H786-AC-BECKS1ZZ-FST-DR-CE-2391 ELECTRICAL INSTALLATIONS REFER TO THE RELEVANT
H786-AC-BECKS1ZZ-FST-DR-CE-2393 DISCIPLINE DRAWINGS AND SPECIFICATIONS.
2. WORKS TO BE CARRIED OUT IN ACCORDANCE WITH THAMES
+7.750 TOW +7.750
H786-AC-BECKS1ZZ-FST-DR-CE-2521 MAINTENANCE/CLEANING WATER UTILITIES LIMITED ASSET STANDARDS AND CESWI 7
H786-AC-BECKS1ZZ-FST-DR-CE-2730
A H786-AC-BECKS1ZZ-FST-DR-CE-2731 1.GROUNDWATER MONITORING MAINTENANCE WILL BE REQUIRED.
WITH THAMES WATER CESWI 7 AMENDMENTS.
3. ALL DIMENSIONS IN mm AND ALL LEVELS IN mAOD UNLESS
TOP OF BELL MOUTH LEVEL
IL +7.450 IL +7.450 H786-AC-BECKS1ZZ-FST-DR-CE-2732 NOTED OTHERWISE.
28 +7.370 4. ALL CO-ORDINATES ARE TO NATIONAL GRID.
H786-AC-BECKS1ZZ-FST-DR-CE-2733
28 H786-AC-BECKS1ZZ-FST-DR-CE-2734 DECOMMISSIONING/DEMOLITION 5. EXISTING SERVICES TO BE CONFIRMED AND PROTECTED OR
TWL +7.110 DIVERTED WHERE REQUIRED DURING CONSTRUCTION.
H786-AC-BECKS1ZZ-FST-DR-CE-2736
6. ACCESS, LIFTING AND MAINTENANCE PROVISION SUBJECT TO
H786-AC-BECKS1ZZ-FST-DR-CE-2737 DETAILED SUPPLIER DESIGN UNDER MECHANICAL SCOPE.
1500 WIDE FOOTPATH H786-AC-BECKS1ZZ-FST-DR-CE-2738 7. ALL MECHANICAL AND ELECTRICAL DETAILS SHOWN ARE
27
H786-AC-BECKS1ZZ-FST-DR-CE-2739 It is assumed that all works will be carried out by a competent contractor INDICATIVE ONLY.
H786-AC-BECKS1ZZ-FST-DR-CE-2747 working, where appropriate, to an approved method statement 8. EXISTING ASSETS HAVE BEEN MODELLED FROM PROJECT 8W8F
FGL +6.450 H786-AC-BECKS1ZZ-FST-DR-CE-2757 AS-BUILT PDF RECORDS WHERE AVAILABLE.
BOTTOM OF BELL MOUTH LEVEL FGL +6.400 9. INSITU CONCRETE SHALL COMPLY WITH THE REQUIREMENTS
H786-AC-BECKS1ZZ-RDS-DR-CE-2370
+6.267 OF THE CONCRETE SPECIFICATION DOCUMENT.
10. CONCRETE FINISHES SHALL BE:
33 34 a. TOP SURFACES TO HAVE A POWER FLOAT FINISH
b. TOP SURFACES UNDER SCREED TO HAVE A TAMPED FINISH;
c. ALL BURIED FORMED SURFACES TO HAVE A ROUGH FINISH
TO 150 BELOW F.G.L. ALL OTHER FORMED SURFACES TO
50 THICK BLINDING 200 THICK CONCRETE SURROUND HAVE A FAIR WORKED FINISH;
d. TOP OF WALLS & EXPOSED VERTICAL EXTERNAL ARISES TO
SUB BASE HAVE 25 X 25 CHAMFER, EXCEPT AT LOCATIONS WHERE THE
26
2700 INTERNAL DIA PRECAST 225 DIA HOLE FOR 200 DIA PIPE TO BE TOP SURFACE IS TO BE CONTINUOUS WITH FLOORING OR
CONCRETE RINGS CORE DRILLED ON CENTRE LINE +7.550 WHERE WEIR PLATES ARE REQUIRED.
FST 90 GEOCOMPOSITE DRAINAGE LAYER ON FST +5.094 mAOD. ANNULUS TO BE SEALED WITH 11. UNLESS SHOWN OTHERWISE ALL SURFACES TO CONSTRUCTION
HANDRAIL
WALL. REFER H786-AC-BECKS1ZZ-ASL-DR- REINFORCEMENT CONCRETE WALL TO MOUNT LINK SEAL, WITH TIGHTENING BOLTS JOINTS SHALL BE ROUGHENED WITHOUT DISTURBING THE
CE-2393 FOR DETAILS 32 PENSTOCK. SIZE TO BE CONFIRMED BASED ON POINTING OUTWARDS AND REMAINING COARSE AGGREGATE PARTICLES.

CIVIL MECH
PENSTOCK FRAME SIZE BY SUPPLIER GAP TO BE FILLED WITH 12. ALL PRECAST CONCRETE RINGS MUST BE SEALED IN
50N/mm2 NONSHRINK GROUT OR BLANK FLANGE TO BE ACCORDANCE WITH PRECAST MANUFACTURERS DETAILS.

MECH
SIMILAR INSTALLED D/S OF VALVE AND
DN500 PENSTOCK WALL MOUNTED VALVE TO BE KEPT AT
LOCKED POSITION

CIVIL
150 ID uPVC PERFORATED GROUNDWATER
DRAIN PIPE TO CONTROL PERCHED WATER TOW +7.750
RISING ABOVE 3.00 mAOD. REFER H786-AC- GATE VALVE FOR FST +4.125 25
B BECKS1ZZ-FST-DR-CE-2393 FOR DETAILS DRAINDOWN 30 IL +3.925 FLOW

31 +7.550

+3.450

36
37 38
IL +2.900 LEGEND
32
PROPOSED CIVIL SCOPE
LINK SEAL OR FGL FINISHED GROUND LEVEL
SIMILAR APPROVED
EGL EXISTING GROUND LEVEL
PRECAST WALL
50N/mm2 NONSHRINK
GROUT OR SIMILAR TO BE CONFIRMED/SUBJECT TO DESIGN
DN500 DI ACTIVATED TOW TOP OF WALL
29 SLUDGE PIPE TO EXISTING
SLUDGE PIPEWORK. REFER PIPE SUPPORT IJ INSPECTION JOINT
H786-AC-BECKS1ZZ-FST-DR- BRACKET BY FST FINAL SETTLEMENT TANK
CE-2736 SUBCONTRACTOR
FOR DETAILS
PUDDLE FLANGE PLACED HB2
CENTRAL IN MASS KERB
CONCRETE
GEN 3 MASS CONCRETE SLOPE 1:100 3D / BIM MODELS USED FOR DRAWING CREATION
BENCHING TO OUTLET +6.450 H786-AC-BECKS1ZZ-FST-M3-CE-New_FST
PIPE +6.390

FST 90 DE-SLUDGE
C CHAMBER

200mm
END SECTION OF PIPE TO 24 FOR CONSTRUCTION
HAVE TYPE S1 BEDDING
COMPACTED TO 85% MOT CURRENT REVISION INFORMATION
FOR CONSTRUCTION ISSUE

22 150 THICK HARDSTAND 50 THICK BLINDING


IN ACCORDANCE
23 WITH TW STANDARD
AM-DRG-CIV-02001

225 DIA HOLE FOR 200 DIA PIPE TO BE CORE


28 DRILLED ON CENTRE LINE +7.550 mAOD.

150
IL -1.045 ANNULUS TO BE SEALED WITH LINK SEAL, WITH
TIGHTENING BOLTS POINTING OUTWARDS AND
-1.315
REMAINING GAP TO BE FILLED WITH 50N/mm2 HANDRAIL SECTION Q-Q
NONSHRINK GROUT OR SIMILAR SCALE 1 : 10 C01 A FOR CONSTRUCTION RPN AG SB 01.02.22
37 38
P01 S3 FOR INTERNAL REVIEW AND COMMENT SK AG SE 20.09.21
TOW +7.750 Revision Status Suitability Description Authored Checked Reviewed Date
1150
+7.550
IL +7.450
Thames Water Utilities
FLANGE TO BE CAST INTO OPEN/ PIPE SUPPORT BRACKET
STRAIGHT PIPE AND BEND TO BE 35 BY SUBCONTRACTOR 150 THICK HARDSTAND IN ACCORDANCE
INSTALLED AS ONE PIECE WITH TW STANDARD AM-DRG-CIV-02001

100
IJ. FOR TYPICAL DETAILS REFER H786- 1 INCH BSP CONNECTION Clearwater Court
DN600 DI SLUDGE DRAW OFF PIPELINE. REFER 75 THICK CONCRETE BLINDING AC-BECKS1ZZ-IFL-DR-CE-0110 WITH BALL VALVE Vastern Road, Reading RGI 8DB
H786-AC-BECKS1ZZ-FST-DR-CE-2733 FOR
PIPEWORK DETAILS 4550
FST 90 DE-SLUDGE HB2 KERB
SLOPE SLOPE Location Code: OS Reference: Security Reference:
CHAMBER
1:100 +6.426 1:100 BECKS1ZZ TQ445825 UBR
PILED DE-SLUDGE CHAMBER BASE
SECTION O-O Project Group: Sub Process:

SCALE 1 : 25 TREATMENT WASTE WATER


D
Location/Town:

FOR PIPE FITTING SCHEDULE BASED ON SAINT GOBAIN JENKINS LANE, BARKING, IG11 0AD
PRODUCT INFORMATION, REFER H786-AC-BECKS1ZZ-FST-DR-CE-2747 Site Name:
50 THICK BLINDING NEW 300 x 300 DRAIN GULLY
BECKTON STW

50
WITH GRATING.
Project Name:

H786 WWNI BECKTON STW AMP7 UPGRADE


TO BE CONNECTED TO SITE DRAINAGE Drawing Title:
WARNING NOTICE (CDM 2015) SCALE 1 : 10
100mm 0 1m NETWORK. REFER H786-AC-BECKS1ZZ-FST- EXTENSION TO ASP4
A 'DESIGNER' IS ANYONE WHO SPECIFIES, MODIFIES OR CHANGES DR-CE-2571 FOR DRAINAGE MODIFICATIONS FST 90 DESLUDGE CHAMBER
DESIGNS; OR INSTRUCTS OTHERS UNDER THEIR CONTROL TO DO SO.
GENERAL ARRANGEMENT SECTION
PLEASE ENSURE ANY CHANGES ARE APPROVED AND RECORDED BY SCALE 1 : 25 Scale: Sheet Size: Status:
THE 'APPOINTED DESIGNER', PRIOR TO IMPLEMENTATION. 0.5m 0 2m AS SHOWN A1 A
SECTION P-P Drawing Number: Revision:
SCALE 1 : 25 H786-AC-BECKSIZZ-FST-DR-CE-2740 C01

0
c Thames Water Utilities Ltd 2017