WATTHOUR METER
HLT01(DT862)
TECHNICAL DESCRIPTION
General
The HLT01 three-phase four-wire meter is designed to meet the latest IEC 60521 and BS EN
60521 standards for measuring active energy in three-phase four-wire alternating current
power grids. Connection is direct or by instrument transformers. The average service life
(MTTF) of the meter is 15 years and the maximal overload capacity is 400%Ib.
Constructions
Meter case
The meter case meets the protection requirements set by IP52 of IEC 60529. The series
types of cases and terminal covers are available.
Driving system
It has three electromagnet elements. Each element consists of a voltage element and a
current element, all of which are mounted on the meter frame with two screws. Voltage coil is
enwrapped in a thermoplastic case to ensure fine insulation. In addition, the voltage element
HLT01 Three phase Electromechanical Watthour Meter EDY03SP01AHOLLEY METERING LTD.
3.4 Rotor
The rotor disk is made of a hard and high purity aluminum. The rotor shaft is turned of high
strength brass. There is a small hole on the upper end for storing lubrication and for fitting a
brass bearing. The lower end is cone-shaped to ensure fine guiding of the rotor.
3.6 Frame
The frame is die-casted by high quality aluminum-silicon alloy of stable property to avoid
distortion. The application of static spray-painting on the surface prevents the frame from
oxidation.
3.9 Register
The cyclometer type register consists of six drums. The kWh can be read directly. The drum is
made of polycarbonate. The framework is made of hard aluminum alloy and can be manually
adjusted and fixed with two screws to insure the proper mesh with the worm on the rotor
shaft.
5. Technical data
1 Meter type HLT01(DT862)
2 Applicable Standards IEC60521
Accuracy class CT operated:
3 Direct connected: Class 2
according to IEC60521 Class 2
4 Average service life (MTTF) 15 years
5 Basic current Ib A 1.5 3 2.5 5 10 15 20 30
6 Maximum current Imax A 6 6 10 20 40 60 80 100
7 Rating current of transformer In 5A Direct connection
8 Reference voltage Un 3 57.7/100V, 3 220/380V, 3 230/400V, 3 240/415V
9 Reference frequency fn 50 Hz, 60 Hz
-2-
HLT01 Three phase Electromechanical Watthour Meter EDY03SP01AHOLLEY METERING LTD.
Power losses
10 1.0 W/ 5VA
in voltage circuit at 50 Hz Un
Power losses in
11 0.5 VA
current circuit at 50Hz Un Ib
12 Non-running with no-load 0.8 1.1Un
13 Starting current 0.5%Ib
Mean temperature coefficient:
14 From 0.1Ib to Imax at unity PF 0.10%/
From 0.2Ib to Imax at unity 0.5 lagging 0.15%/
Insulation level:
15 Withstand A.C.voltage for 50 Hz, 1min 2 kV (when bakelite base>4kV)
Withstand impulse voltage 1.2/50 s 6kV (when bakelite base>8kV)
16 Rated load torque at unity PF, Ib 850 Nm
17 Weight of rotor 54 g
18 Weight of meter 3.1kg
19 Meter base Steel, Bakelite
20 Meter cover ABS, transparent PC, Bakelite
21 Terminal cover ABS, Bakelite, PC
22 Register Cyclometer single, Unidirectional
23 Option Reverse running stopper
1 2 3 4 5 6 7 8 9 10 11
1 2 3 4 5 6 7 8 9 10 11 1 2 3 4 5 6 7 8 9 10
L1 L1
L1
L2 L2
Main L2 Load Main Load Main Load
L3 L3 L3
N N N
Current Transformer Operated Direct Connection (I max 40A) Direct Connection (I max 40A)
-3-
HLT01 Three phase Electromechanical Watthour Meter EDY03SP01AHOLLEY METERING LTD.
172
241
L1
5
L2 37
150 124
Note:
Specification L1 L2
Imax 40A 273mm 150 mm
Imax 40A 279mm 156 mm
5
242
270
154
328
328
2- 5.5 1 2 3 4 5 6 7 8 9 10 11
A
B
C
N
157 42
178 132.5
Fig2 Insulating encased meter of protective-class II with
bakelite base, PC cover & extended PC terminal cover
-4-