3406C Generator Set 9ES00001-UP(SEBP2752 - 15) - Document Structure Página 1 de 3

Shutdown SIS

Previous Screen

Product: GENERATOR SET


Model: 3406C GENERATOR SET 9ES
Configuration: 3406C Generator Set 9ES00001-UP

Testing and Adjusting


VR6 Voltage Regulator
Media Number -RENR2480-04 Publication Date -01/12/2007 Date Updated -17/12/2007

i02655660

Voltage Adjustment Range - Calibrate


SMCS - 4467-524

Illustration 1 g00825354

VR6 Voltage Regulator

(1) Factory calibration adjustment

https://sis.cat.com/sisweb/sisweb/techdoc/techdoc_print_page.jsp?returnurl=/sisweb/s... 16/02/2009
PDF created with pdfFactory trial version www.pdffactory.com
3406C Generator Set 9ES00001-UP(SEBP2752 - 15) - Document Structure Página 2 de 3

(2) Voltage adjustment

Illustration 2 g01021519

The Cat VR6 presents an electrical shock/electrocution hazard. This


hazard will cause serious injury or death.

Service by trained personnel only.

The terminals and heat sinks are live at hazardous voltages when power
is applied and for up to 8 minutes after power is removed.

NOTICE
Do not operate generator at a voltage greater than 5% above the name
plate rating.

The factory calibration adjustment (1) should be used by the factory technicians only. The following
procedure can be used if the factory calibration has been disturbed:

1. Remove the seal from the factory calibration adjustment (1) .

2. Start the genset.

3. Run the genset at no load.

https://sis.cat.com/sisweb/sisweb/techdoc/techdoc_print_page.jsp?returnurl=/sisweb/s... 16/02/2009
PDF created with pdfFactory trial version www.pdffactory.com
3406C Generator Set 9ES00001-UP(SEBP2752 - 15) - Document Structure Página 3 de 3

4. Turn the factory calibration adjustment (1) in a fully counterclockwise direction.

5. Turn the voltage adjust potentiometer (2) in a fully clockwise direction.

6. Slowly turn the factory calibration adjustment (1) CW until the voltage on 20-22-24 is 252 ± 1
VAC for 60 Hz (226 ± 1 VAC for 50 Hz).

7. Turn the voltage adjust potentiometer (2) CCW.

8. Verify that the voltage on 20-22-24 is between 156 VAC and 180 VAC. The unit is calibrated.

9. Seal the factory calibration adjustment (1) .

Copyright 1993 - 2009 Caterpillar Inc. Mon Feb 16 15:18:38 EST 2009