DOC.NO| HHIS-WZ-PE-005 (03) © Gicbai Teader Fi: RUN HEX 300 VECTOR INVERTER INSTRUCTION MANUAL A HYUNDAI HEAVY INDUSTRIES CO., LTD. N300 INSTRUCTION MANUAL SAFETY For the Best Results with N300 Series inverter, read this manual and all of the warning sign attached to the inverter carefully before installing and operating it, and follow the instructions exactly. Keep this manual handy for your quick reference Definitions and Symbols ‘Asafety instruction (message) is given with a hazard alert symbol and a signal word, WARNING or CAUTION. Each signal word has the following meaning throughout this manual. that could be dangerous to you or other persons operating this equipment. This symbol means hazardous high voltage. It used to call your attention to items or operations A Read these message and follow these instructions carefully that could be dangerous to you or other persons operating this equipment. This is the "Safety Alert Symbol" This symbol is used to call your attention to items or operations Read these messages and follow these instructions carefully. AN WARNING indicates a potentially hazardous situation which, if not avoided, can result in serious injury or death /A\cAUTION Indicates a potentially hazardous situation which, if not avoided, can result in minor to moderate injury, or serious damage of product. ‘The matters described under |\ CAUTION) may, if not avoided, lead to serious results depending on the situation. Important matters are described in CAUTION (as well as WARNING), so be sure to observe them. NOTE Notes indicate an area or subject of special merit, emphasizing either the product's capabilities or common errors in operation or maintenance. HAZARDOUS HIGH VOLTAGE Motor control equipment and electronic controllers are connected to hazardous line voltages. When servicing drives and electronic controllers, there might be exposed components with cases or protrusions at or above line potential. Extreme care should be taken to product against shock. Stand on an insulating pad and make it a habit to use only one hand when checking components. ‘Always work with another person in case an emergency occurs. Disconnect power before checking controllers or performing maintenance. Be sure equipment is properly grounded. Wear safety glasses whenever working on an electronic controller or rotating electrical equipment. N300 INSTRUCTION MANUAL PRECAUTION |A\ WARNING : This is equioment should be installed, adjusted and serviced by qualified electrical maintenance personal familiar with the construction and operation of the equipment and the hazards involved. Failure to observe this precaution could results in bodily injury. WARNING :The user is responsible for ensuring that all driven machinery, drive train mechanism not supplied by HYUNDAI and process line material are capable of safe operation at an applied frequency| of 150% of the maximum selected frequency range to the AC motor. Failure to do so can result in destruction of equipment and injury to personnel should a single point failure ocour. WARNING : For protection, install an earth leakage breaker with a high frequency circuit capable of large currents to avoid an unnecessary operation. The ground fault protection circuit is not designed to protect personal injury. [A\ WARNING : Hazard of electrical shock. Disconnect incoming power before working on this contol |A\ WARNING : Separate motor overcurrent, overload and overheating protection is required to be provided in accordance with the safety codes required by jurisdictional authorities. CAUTION : These instructions should be read and clearly understood before working on N300 series equipment. |A\ CAUTION : Proper grounds, disconnecting devices and other safety devices and their location are the responsibility of the user and are not provided by HYUNDAI CAUTION : Be sure to connect a motor thermal switch or overload devices to the N300 series controller to assure that inverter will shut down in the event of an overload or an overheated motor. |A\ cauTION : Dangerous voltage exists until charge lamp is off. |A\ CAUTION : Rotating shafts and above ground electrical potentials can be hazardous. Therefore, itis strongly recommended that all electrical work conform to the National Electrical Codes and local regulations. Only qualified personnel should perform installation, alignment and maintenance. Factory recommended test procedures, included in the instruction manual, should be followed. Always disconnect electrical power before working on the unit. NOTE : POLLUTION DEGREE2 ‘The inverter must be used environment of the degree 2. Typical constructions that reduce the possibilty of conductive pollution are, 1) The use of an unventilated enclosure 2) The use of a fitered ventilated enclosure when the ventilation is fan forced that is, ventilation is accomplished by one more blowers within the enclosure that provide a positive intake and exhaust. N300 INSTRUCTION MANUAL Cautions for EMC (Electromagnetic Compatibility) To safety the EMC directive and to comply with standard, follows the checklist below. \ WARNING This equipment should be installed, adjusted, and serviced by qualified personal familiar with construction and operation of the equipment and the hazards involved. Failure to observe this precaution could result in bodily injury. 1. The power supply to N300 inverter must meet these specifications a. Voltage fluctuation + 10% or less. b. Voltage imbalance +3% or less. c. Frequency variation +:4% or less. d. Voltage distortion THD = 10% or less. 2. Installation measure a. Use a filter designed for N300 inverter 3. Wiring a. Shielded wire (screened cable) is required for motor wiring, and the length must be less than 20 meters. b. The camer frequency setting must be less than 5kHz to satisfy EMC requirements. c. Separate the main circuit from the signal/process circuit wiring d. In case of remote operating with connector cable, the inverter does not conform to EMC. 4. Environmental conditions - when using a fier, follow these guidelines: a. Ambient air temperature : -10 - +50 b, Humidity : 20 to 90% RH(non-condensing) ©. Vibration : 5.9 misec®(0.6 G) 10 - 55Hz ( N300- 055 - 220LF / 055 - 220HF) 2.94 misec’ (0.6 G) 10 - 5SHz ( N300- 300 - S5OLF / 300 - 1320HF) d. Location : 1000meters of less altitude, indoors (no corrosive gas or dust) N300 INSTRUCTION MANUAL Conformity to the Low Voltage Directive (LVD) The protective enclosure must conform to the Low Voltage Directive. The inverter can conform to the LVD by mounting into a cabinet or by adding covers as follows. 1. Cabinet and Cover The inverter must be installed into a cabinet which has. the protection degree of Type IP2X. In addition the top surfaces of cabinet are easily accessible shall meet at least the requirements of the protective Type IP4X, or which is constructed to prevent small objects from entering inverter. IP4X cabinet IP20 with louver Fig. Inverter cabinet N300 INSTRUCTION MANUAL UL Warnings and Cautions Manual for N300 series This auxiliary instruction manual should be delivered to the end user. 1. Wiring warnings for Electrical Practices and Wire Specifications A WARNING : “Use 60/75°0 CU wire only" or equivalent. Av WARNING : "Open Type Equipment” For models with N300 750-1320H A WARNING : “Suitable for use on a circuit capable or delivering not more than 10,000 rms symmetrical amperes, 240V maximum. "For models with suffix L. A WARNING : "Suitable for use on a circuit capable or delivering not more than 10,000 rms symmetrical amperes, 480 V maximum." For models with suffix H. 2. Tightening Torque and Wire Range WARNING : Tightening torque and wire range for field wiring terminals are marked adjacent to the terminal or on the wiring diagram. Model Name | Tightening Torque [N:m] Wire Range(AWG) N300-055L 25 8 N300-075L 25 6 N300-110L, 49 4 N300-150L 49 2 N300-185L 49 1 N300-220L 8.8 110 N300-300L 88 210 N300-370L 8.8 3/0 oF 2 parallel of 1 AWG N300-450L 13.7 250kcmil or 2 parallel of 1 AWG(75'C) N300-550L 13.7 350kcmil or 2 parallel of 1/0 AWG N300 INSTRUCTION MANUAL Model Name | Tightening Torque [N-m] Wire Range(AWG) N300-055H 25 12 N300-075H 25 10 N300-110H 49 8 N300-150H 49 6 N300-185H 49 6 N300-220H 49 4 N300-300H 49 3 N300-370H 49 1 N300-450H 88 1 N300-550H 88 110 N300-750H 88 250kemil or 2 parallel of 1 AWG(75°C) N300-900H 13.7 250kemil or 2 parallel of 1 AWG(75°C ) N300-1100H 13.7 350kcmil or 2 parallel of 1/0 AWG N300-1320H 13.7 2 parallel of 2/0 AWG ircuit Breaker / Fuse Size WARNING : Distribution fuse/circuit breaker size marking is included in the manual to indicate that the unit shall be connected with an UL Listed inverse time circuit breaker, rated 600V with the current ratings or an UL Listed fuse as shown in the table below. ‘Model Name Circuit Breaker [A] Fuse [A] N300-055L 30 30 N300-075L 40 40 N300-110L, 60 60 N300-150L 80 80 N300-185L 100 100 N300-220L 125 125 N300-300L 150 150 N300-370L 175 175 N300-450L 225 225 N300-550L 250 250 vi N300 INSTRUCTION MANUAL ‘Model Name Circuit Breaker [A] Fuse [A] N300-055H 15 15 N300-075H 20 20 N300-110H 30 30 N300-150H 40 40 N300-185H 50 50 N300-220H 60 60 N300-300H 70 70 N300-370H 90 90 N300-450H 125 125 N300-550H 125 125 N300-750H - 175 N300-900H - 200 N300-1100H - 250 N300-1320H - 300 A WARNING : “Field wiring connection must be made by an UL Listed and CSA Certified closed- oop terminal connector sized for the wire gauge involved. Connector must be fixed using the crimp tool specified by the connector manuf- acturer.", or equivalent wording included in the manual. vii N300 INSTRUCTION MANUAL Re n History Table Operation Manual No Revision Contents The Date of Issue| Nonbes 1 Initial Release of Manual NEJ 302044 ‘Apr. 2002, NEJ30204A, 2 Manual Cover Contents Modification Oct. 2002 | HHIS-WZ-PE-005(02) 3 Parameter Initial Value Modification ‘Apr. 2004 | HHIS-WZ-PE-005(03) vill N300 INSTRUCTION MANUAL SAFETY PRECAUTIONS {\ CAUTION * Be sure to install the unit on flame resistant material such as metal Otherwise, there is a danger of fire + Be sure not to place anything inflammable in the vicinity. Otherwise, there is a danger of fire P22 sceseseeeees PDD * Do not carry unit by top cover, always carry by supporting base of unit. There is a risk of falling and injury. P22 + Be sure not to let the foreign matter enter such as cut wire refuse, spatter from welding, iron refuse, wire, dust, etc. Otherwise, there is a danger of fire. P25 * Be sure to install it in a place which can bear the weight according to the ‘specifications in the text. (Chapter 6. Specifications) Otherwise, it may fall and there is a danger of injury. P24 + Be sure to install the unit on a perpendicular wall which is not subject to vibration Otherwise, it may fall and there is a danger of injury. P23 * Be sure not to install and operate an inverter which is damaged or parts of which are missing Othemise, there is a danger of injury. scsesesteeees PLB + Be sure install it in a room which is not exposed to direct sunlight and is well ventilated. Avoid environments which tend to be high in temperature, high in humidity or to have dew condensation, as well as places with dust, corrosive gas, explosive gas, inflammable gas, grinding-fluid mist, salt conn PRD damage, etc. Otherwise, there is a danger off fire N300 INSTRUCTION MANUAL SAFETY PRECAUTIONS 2. Wiring A\ WARNING + Be sure to ground the unit. Otherwise, there is a danger of electric shock andlor fre. seseeeeeones BZD * Wiring work shall be carried out by electrical experts. Otherwise, there is a danger of electric shock and/or fire seereeeeeeoees PZB + Implement wiring after checking that the power supply is off. tt might incur electric shock andiof fire. cesses PZB + After installing the main body, carry out wiring, Otherwise, there is a danger of electric shock and/or injury. - P25 * Do not remove the rubber bush. (5.5 to SSkW) Due to the possibilty that a wire may be damaged, shorted or may have ‘a ground fault with the edge of the wiring cover. sere PR A\ CAUTION + Make sure that the input voltage is: Three phase 200 to 240V 50/60Hz(for models with suffix L) Three phase 380 to 480V 50/60Hz(for models with suffix H) P26 + Be sure not to input a single phase. ce PRB Otherwise, there is a danger of fire P25 * Be sure not connect AC power supply to the output terminals(U, V, W). Otherwise, there is a danger of injury andlor fire. * Be sure not fo connect the resistor to DC terminals(PD, P and N) directly, =------------- 2-5 Otherwise, there is a danger of fire. + Be sure to set the earth leakage breaker or the fuse(s)(the same phase as the main power supply) in the operation circuit seeseseoes P22 Otherwise, there is a danger of fire + As for motor leads, earth leakage breakers and electromagnetic contactors, be sure to use the equivalent ones with the specified capacity(rated). seccesess P22 Otherwise, there is a danger of fre. + Do not stop operation by switching off the electromagnetic contactors on the primary or secondary sides of the inverter. sesscscssses P26 Otherwise, there is a danger of injury and/or machine breakage. + Fasten the screws with the specified fastening torque. Check so that there is no loosening of screws, Otherwise, there is a danger of fire P2-12 N300 INSTRUCTION MANUAL SAFETY PRECAUTIONS 3. Control and operation A\ WARNING While being energized, be sure not to open the front case. Otherwise, there is a danger of electric shook. Be sure not to operate the switches with wet hands. Otherwise, there is a danger of electric shock. even during stoppage. Otherwise, there is a danger of electric shock personnel safety will be secured even if it restarts.) Otherwise, there is a danger of injury. will not restart after power recovery. Otherwise, there is a danger of injury. the key separately from the emergency stop. ‘Otherwise, there is a danger of injury. ‘command is off. Otherwise, there is a danger of injury. Otherwise, there is a danger of electric shock and/or fire. + After the operation command is given, if the alarm reset is conducted, it will restart suddenly. Be sure to set the alarm reset after checking the operation + While the inverter is energized, be sure not to touch the main terminal or to check the signal or put on/off wire and/or connector. seteeeeeeeees PB Otherwise, there is a danger of electric shock + Be sure to tum on the input power supply after closing the front case. coe PBL P.3-1 + While the inverter is energized, be sure not to touch the inverter terminals. ~-------------_ P.3-1 + If the retry mode is selected, it may suddenly restart during the trip stop. Be sure not to approach the machine. (Be sure to design the machine so that P31 Be sure not to select retry mode for up and down equipment or traveling P.3-1 ‘equipment, because there is output free-running mode in term of retry. ‘Otherwise, there is a danger of injury andlor machine breakage. + Even if the power supply is cut for a short period of time, it may restart ‘operation after the power supply is recovered if the operation command is -------------- P.3-4 given. If it may incur danger to personnel, be sure to make a circuit so that it + The stop key is effective only when the function is set. Be sure to prepare P34 P34 + Be sure not to touch the inside of the energized inverter or to put a bar into it - P34 N300 INSTRUCTION MANUAL SAFETY PRECAUTIONS {\ CAUTION * Cooling fin will have high temperature. Be sure not to touch them. ‘Otherwise, there is a danger of getting burned. * Low to high speed operation of the inverter can be easily set. Be sure to ‘operate it after checking the tolerance of the motor and machine. Otherwise, there is a danger of injury. + Install extemal break system if needed. Otherwise, there is a danger of injury. + Ifa motor is operated at a frequency higher than standard setting value (50HZ/60H2z), be sure to check the speeds of the motor and the machine with each manufacturer, and after getting their consent, operate them. Otherwise, there is a danger of machine breakage. * Check the following before and during the test run. Otherwise, there is a danger of machine breakage. Was the direction of the motor correct? \Was the inverter tipped during acceleration or deceleration? Were the rpm and frequency motor coract? Were there any abnormal motor vibrations or noise? so PD P.3-2 secseceseeeees PBR srseseseseees PBR secseceseeeees PBR 4. Maintenance, inspection and part replacement {\ WARNING + After a lapse of more than 10 minutes after turing off the input power supply, perform the maintenance and inspection. Otherwise, there is a danger of electric shock. Make sure that only qualified persons will perform maintenance, inspection and part replacement. (Before starting the work, remove metallic objects from your person(wristwatch, bracelet, etc.) (Be sure to use tools protected with insulation) Otherwise, there is a danger of electric shock and/or injury. ~ PSA ~ P54 5. Others /\ WARNING + Never modify the unit. Otherwise, there is a danger of electric shock andior injury. N300 INSTRUCTION MANUAL Table of Contents } TABLE OF CONTENTS Chapter 1 General Descriptions 4.1 Inspection upon Unpacking 4 Inspection of the unit 41 Instruction manual +4 4.2 Question and Warranty of the Unit 1-2 Request upon asking 1-2 ‘Warranty for the unit 1-2 1.3 Appearance 1-3 Appearance and Names of parts 1-3 Chapter 2 Installation and Wiring 2.1 Installation a4 2.4.1 Installation 22 2.1.2 Blind cover of wiring parts 2-4 2.2 Wiring 25 2.2.1 Terminal Connection Diagram 26 222 Main circuit wiring 28 2.2.3 Terminal Connection Diagram 214 2.2.4 Digital operator wiring 2-16 Chapter 3 Operation 3.1 Operation 3-3 3.2 Test Run 3-4 Chapter 4 Explanation of Function 4.1 About Digital Operator (OPE-S) at 4.2 Code list 45 4.3 Explanation of function 413 4.3.1. Monitor mode Output frequency monitor, Output current monitor, Operation direction monitor, PID feedback monitor Intelligent input monitor, Intelligent output monitor Frequency conversion monitor, Output torque monitor, Output voltage monitor, Input electric power monitor ‘Accumulated time monitor on Run, Power ON time monitor, Trip time monitor, Trip monitor N300 INSTRUCTION MANUAL Table of Contents } 4.3.2 Function mode Output frequency setting, Operation direction, Selection with limits of operation direction, Frequency command selection § $m $a 4-17 Operation command selection, Selection no stop, Selection of stop key 4-18 ‘Adjustable time tt Base frequen¢y § $$ $$$ 7-20 Maximum frequency, Carrier frequency 4-21 External analog input (0, 02, 01) nn Input frequency Start / End 423 Setting analog input fiter, Output voltage gain. ————_____________ 4-24 Control system (Vif Characteristic) § 4-25 Torque boost 827 Direct current braking (DB) _____________________ 4-28 Frequency limiter § $$ NN 4331 Frequency jump function, Acceleration stop function. ———_______— 4-32 PID function 4-33 ‘Automatic energy-saving operation function, —————________________ 4-34 ‘Two-stage acceleration and deceleration on function (2CH) ——————_—_ 4-35 Acceleration and deceleration pattem §—§ —___________________ 4-36 Instantaneous power failure ! under-voltage, 4-37 Open phase protection function selection, Electronic thermal function ————— 4-39 Overtoad restriction / Overload advance notice § 4-44 Start frequency, Reduced voltage start selection 4-43 BRD (Dynamic breaking) function, Cooling fan operating selection 4-44 Inteligent input terminal setting tts Input terminal afb (NO / NC) selection, Multi-speed operation function 4-46 Jogging operation (JG) tt Second / Third control function (SET, SET3), ——_______________ 4-49 Software lock mode selection (SFT), Force operation ope function (OPE) 4-50 Free-run stop (FRS) tit Commercial power source switching (CS) 4-52 Reset (RS)_©_—_§ 74's Unattended start protection (USP), UP / DOWN selection (UP, DWN, UDC) ——— 4-54 External trip (EXT), 3 wire input function (STA, STP, F/R). 4-55 Control gain switch function (CAS), P/PI switching function (PPI) 4-56 Inteligent output terminal setting § 4-57 Inteligent output terminal a’b (NO / NC) selection ————_____________ 4-58 ‘Signal during run (RUN), Frequency arrival signal (FA1, FA2, FA3, FA4, FAS) 4-59 N300 INSTRUCTION MANUAL Table of Contents RUN time / power ON time over (RNT / ONT), Zero speed signal (ZS) ——— 4-61 (Over torque (OTQ), Alarm code output (ACO -AC3)_ ——__—._ 4-62 FM terminal —§—§ — —@—_____________________ 4-63 ‘AM terminal, AMI terminal, Extemal thermistor§ ——— 4-64 Initialization setting, $$$ 4.65 Display selection £2 —_—_—______——. 4-66 Stabilized factor, Motor constant 4-67 Fuzzy most suitable acceleration and deceleration ————_____— 4-68 Braking control function. 4-69 ‘Stopping of deceleration at power off $$ 4-74 Offline autotuning function 4.72 Motor constant selegtion § J $______________ 4.75 Online autotuning function —_____________ 4.76 Sensorless vector control, $$ $a $____________________ 4.77 0 Hz domain sensorless vector control 4.78 ‘Torque monitor function 4-79 Torque limit function || iggy Torque LADSTOP funtion 4-82 Communication function § Fen gg 4.4 Protection function list. 2 _____________ 4.97 4.4.1 Protection function §—§ ——____________ 4.97 4.42 Trip monitor display 4-100 4.4.3 Waming Monitor display ________________ g.aoq Chapter 5 Maintenance, Inspection 5.1 Precaution for Maintenance / Inspection 5-4 5.1.1. Daily inspection § $$ it" 5.4.2 Cleaning gy 5.4.3 Regular inspection gg 5.2 Daily inspection and regular inspection —_____________ 5.9 5.3 Megger test. — gg 5.4 Withstand Voltage test. ___________________ 5.3 5.5 The method to check Inverter, converter part ———__________ 5-4 56 Capacitor Life Curve 8 Chapter 6 Specification 6.1 Standard specification fist| 4 6.2 Dimension § 2 _______________________ 6-2 N300 INSTRUCTION MANUAL Chapter 1 General Descriptions 1.1 Inspection upon Unpacking 1.1.1 Inspection of the nuit ‘Open the package and pick out the inverter, please check the following item. Ifyou discover any unknown parts or the unit is in bad condition, please contact your supplier or the local HYUNDAI Distributor. (1) Make sure that there was no damage (injury, faling or dents in the body) during transportation Of the unit (2) After unpacking the unit, make sure that the package contains one operation manual for the Inverter. (3) Make sure that the product is the one you ordered by checking the specification label. Specifications label Picture 1-1 Position of specification label HYUNDAI Inverter model ——»] Model : N300-O5SHF KWi(HP) : 5.51(7.5) Maximum applicable motor ——>| Input ratings >| InpuvEntree: 50Hz, 60Hz 400~480 V tph_A 50Hz, 60Hz 400~480 V 3ph 13A Output ratings >] Output /Sortie 0.1 ~400Hz 3ph 12A Production number ———>| MEG No. Picture 1-2 Contents of specification label 1.1.2 Instruction manual This instruction manual is the manual for the HYUNDAI Inverter N300 Series. Before operation of the Inverter, read the manual carefully. After Reading this manual, keep it to hand for future reference. ‘When using optional units for this inverter ; please refer to the instruction manuals packed with the optional units. This instruction manual should be delivered to the end user. 141 N300 INSTRUCTION MANUAL Chapter 1 General Descriptions 1.2 Question and Warranty of the Unit 1.24 Request upon asking If you have any questions regarding damage to the unit, unknown parts or for general enquiries please contact your supplier or the local HYUNDAI Distributor with the following information. (1) Inverter Model (2) Production Number (MFG No.) (3) Date of purchase (4) Reason for Calling Damaged part and its condition et Unknown parts and their contents etc. 1.2.2 Warranty for the unit ‘The warranty period of the unit is one year after the purchase date. However within the warranty period, the warranty will be void if the fault is due to; (1) Incorrect use as directed in this manual, or attempted repair by unauthorized personnel. (2) Any damage sustained other than from transportation (Which should be reported immediately). (3) Using the unit beyond the limits of the specification, (4) Natural Disasters : Earthquakes, Lightning, etc ‘The warranty is for inverter only, any damage caused to other equipment by matfunction of the inverter is not covered by the warranty. ‘Any examination or repair after the warranty period (one-year) is not covered. And within the warranty period any repair and examination which results in information showing the fault was caused by any of the items mentioned above, the repair and examination cost are not covered. If you have any questions regarding the warranty please contact either your supplier or the local HYUNDA\ Distributor. Please refer to the back cover for a list of the local HYUNDAI Distributors. 1-2 N300 INSTRUCTION MANUAL Chapter 1 General Descriptions 1.3 Appearance 1.3.1 Appearance and Names of Parts Appearance from the front Power lamp ‘Alarm lamp Digital operator Spacer cover Front cover Terminals cover —__ Specifications Label ~ Front cover removed Connector Installation point of self-contained option _— Control circuit terminals - Main circuit terminals Wiring blind cover (Note) When you use cable for remote operation, please remove connector. 1-3 N300 INSTRUCTION MANUAL Chapter 1 General Descriptions 1.4 Application Method for J61 Connector Pin according to Input Power Grounding Condition 1.4.1 Usage of J61 Connector Pin and its application (1) Usage of J61 Connector Pin * For N300 Inverter, a protection circuit is built-in case of lightning while being used, and it can be also protected when J61 Connector Pin is connected. R . Wu Power input S Inverter, v Motor : w ZNRS 23 ust However, the Inverter can be seriously affected according to its grounding condition(grounding oF non-grounding) of input transformer. As a result, when Inverter products are yielded, J61 Connector Pin is separately provided (open condition). Users should choose a set of J61 Connector Pin according to the second grounding condition of input power as the below picture after deep consideration of your field situation. - J61 Connector Pin Applying Condition according to grounding - Applying Condition Grounding Wiring Diagram of Input of J61 Connector Remarks condition er First Second First Second ‘See Application G i. Or Available for J61__| Method of Grouneing Gt. OP Oly Connector Pin | Connector in Chapter 1.4.2 Fist Second First Secord | Running open OfJ61 | Gycing Nongrounding | (Wy) Or y Connector Pin rane EM (not connected) lu (2) Comparison according to J61 Connector Pin Using or Non-using a) Advantage of using J61 Connector Pin * Electronic products are often damaged by lightning or thunderbolt due to its sensitivity for the weather changing. For N300 Inverter, a protection circuit is built-in to protect the inverter from lightning or thunderbolt by using J61 Connector Pin. + A Pre-caution You should confirm the grounding condition of power source. When using the second inverter(inverter power input), you should confirm if Y wiring is in neutral ground system and if A\ wiring is in upper ground system. If you use J61 Connector Pin in rnon-grounding system, Inverter can be easily damaged by excessive noise from being expressed through ZNR 1-4 N300 INSTRUCTION MANUAL ( Chapter 1 General Descriptions b) Features of Non-using J61 Connector Pin * Although any transformer products are not grounded, there is little damage of Inverter due to no corruption in ZNR, as noise is intercepted from electric panel + A\Attention It is not protected from the whether changing such as lightning, ©) Inquiry about J61 Connector * If you have any technical inquires about grounding and J61 Connector, please contact our company. 1.4.2. Application of Connector Pin (1) Location of J61 Connector Pin according to N300 Inverter Capacity a) 5.5KW ~ 11KW Inverter Capacity (the same location as 200V Supply & 400V Supply) Location of J61 Location of J61 1-5 N300 INSTRUCTION MANUAL ( Chapter 1 General Descriptions c) 30KW ~ 132KW Inverter Capacity (the same location as 200V Supply & 400V Supply) Location of J61 (2) Application Method of J61 Connector * Sequencing of Application « * You should turn off the power, after halting Inverter working. * You should open the Inverter cover located in the bottom level. At this very moment, you should use Meta and confirm if DC voltage between P and N is completely discharged. + As J61 is in a different location according to Inverter capacity, you should confirm if J61 is in the Tight location. For J61 Connector Pin, 5.5KW~22KW Inverter capacity is located in the bottom right of IGBT PCB and 30KW~132KW Inverter capacity is in the bottom right of Ro-To PCB. * After checking out its location, you should connect Jump line(ending line) to J61 connector. + You should close the bottom cover after application. * You should operate the machine after turning on the Inverter power. (3) Important items when applying J61 Connector Pin * You should decide if you use J61 Connector Pin for Inverter before applying pane! If using J61 Connector on the purpose of protection for lightning, you should halt Inverter working, turn off the power, and connect to it You may have an electric shock. * Also, You should apply J61 Connector pin, after checking out if DC voltage between P and N is completely discharged by using Meta. * After application, you should tum on the power after closing the Inverter cover. You may have an electric shock. * Ifyou have any inquiries about J 61 Connector, please contact our company. 1-6 N300 INSTRUCTION MANUAL Chapter 2 Installation and Wiring 2.1 Installation {\ CAUTION + Be sure to install the unit on flame resistant material such as metal. Othemwise, there is a danger of fire + Be sure to place anything inflammable in the vicinity. Otherwise, there is a danger of fire. + Do not carry unit by top cover, always carry by supporting base of unit. There is a risk of falling and injury. + Be sure not to let the foreign matter enter such as cut wire refuse, spatter from welding, iron refuse, wire, dust, ect. Otherwise, there is a danger of fre. + Be sure to install it in a place which can bear the weight according to the specifications in the text. (Chapter 6. Specifications) Otherwise, it may fall and there is a danger of injury. + Be sure to install the unit on a perpendicular wall which is not subject to vibration. Otherwise, it may fall and there is a danger of injury. * Be sure not to install and operate an inverter which is damaged or parts of which are missing. Otherwise, there is a danger of injury. + Be sure to install it in a room which is not exposed to direct sunlight and is well ventilated. Avoid environments which tend to be high in temperature, high in humidity or to have dew condensation, as well as places with dust, corrosive gas, explosive gas, inflammable gas, grinding-fluid mist, salt damage, etc. Otherwise, there is a danger of fre. 2-4 N300 INSTRUCTION MANUAL Chapter 2 Installation and Wiring 2.1.1 Installation 1. Transportation This inverter has plastic parts. So handle with care. Do not over tighten the wall mounting fixings as the mountings may crack, causing is a risk of falling. Do not install or operate the inverter if there appears to be damage or parts missing 2. Surface for Mounting of Inverter The temperature of the Inverter heatsink can become very high (the highest being about 150°C). The surface, which you are mounting the Inverter onto, must be made of a non-flammable material (ie steel) due to the possible risk of fire. Attention should also be mabe to the air gap surrounding the Inverter. Especially when there is a heat source such as a breaking resistor or reactor. keep the space enough not tobe (ete 1) prevented te vention of cooing by up and down of wing duct ‘Sem oF more Invertor (Notet) 10cm or mote for 04 to SSK SI Or ern or more for 75 f0 132K (Noie2) 106m or mote for 04 to SSK ‘em or more for 750 132K But for exchanging the DC bus capacitor take a distance, ‘Oem or more for 85 to 11KW Wall 22am or mote for 1510 55K 30am oF more for 75 to 132KW (Note 2) 3. Operating Environment-Ambient Temperature ‘The ambient temperature surrounding the Inverter should not exceed the allowable temperature range (-10 to 50°C). The temperature should be measured in the air gap surrounding the Inverter, shown in the diagram above. If the temperature exceeds the allowable temperature, the component life will become shortened especially in the case of the Capacitors. 4, Operating Environment-Humidity The humidity surrounding the Inverter should be within the limit of the allowable percentage range (20% to 90%). Under no circumstances should the Inverter be in an environment where there is the possibilty of moisture entering the Inverter. ‘Also avoid having the Inverter mounted in a place that is exposed to the direct sunlight. 2-2 N300 INSTRUCTION MANUAL Chapter 2 Installation and Wiring 5. Operating Environment-Air Install the Inverter avoiding any place that has dust, corrosive gas, explosive gas, combustible gas, mist of coolant and sea damage. 6. Mounting Position Mount the Inverter in a vertical position using screws or bolts. The surface you mount onto should also be free from vibration and can easily hold the weight of the Inverter. 7. Ventilation within an Enclosure IF you are installing one or more Inverters in an enclosure @ ventilation fan should be installed. Below is a guide to the positioning of the fan to take the airflow into consideration. The positioning of Inverter, cooling fans and air intake is very important. If these positions are wrong, airflow around the Inverter decreases and the temperature surrounding the Inverter will rise. So please make sure that the temperature around is within the limit of the allowable range. 4.— Ventilation fan 4 Ventilation fan 7 + c ¢_| (Good example) (Bad example) 8. Extemal cooling of Inverter Itis possible to install the inverter so that the heatsink is out of the back of the enclosure. This method has two advantages, cooling of the inverter is greatly increased and the size of the enclosure will be smaller. To install it with the heatsink out of the enclosure, a metal fiting option is required to ensure heat transfer. Do not install in a place where water oil mist flour and dust etc can come in contact with the inverter as there are cooling fans fitted to the heatsink. 9. Approximate loss for each capacity Inverter capacity(kw) 35] 75] | | 85] 2] % | 37 | 4 | & | 7S | 90 | 10 | 122 70% of rated output) | 242 | 312 | 438 | 575 | 98 | 820 | 1100 | 1346 | 1625 | 1975 | 2675] 3375] 3900 [4670 100% of rated output(w) | 325 | 425 | 600 | goo | 975 | 1150 | 1550 | 1900 | 2300 | 200 | 3800 | 4800] 5850 [6650 100% of rated eficiency(%)| 94.4 | 946 | 948 [ 94.9 950 | 950 | 951 | 951 | 95.1 | 05.1 [952 | 952] 052 [52 2-3 N300 INSTRUCTION MANUAL Chapter 2 Installation and Wiring 2.1.2 Blind cover of wiring parts (5.5 to 5SkW) (1) Cable entry through Rubber Bushes The wiring should be done after making a cut in the rubber bushes with nippers or cutters. Wiring cover Rubber bushes (2) Cable entry through Conduit After taking out the rubber bushes, connect the conduit. Zap (Note) Except for when connecting conduit, do not take out the rubber bushes. It is possible that the wiring insulation is broken and a possible earth fault is caused 2-4 N300 INSTRUCTION MANUAL Chapter 2 Installation and Wiring 2.2 Wiring \\ WARNING + Be sure to ground the unit Otherwise, there is a danger of electric shock and/or fire + Wiring work shall be carried out by electrical experts. Otherwise, there is a danger of electric shock and/or fire. + Implement wiring after checking that the power supply is off. It might incur electric shock and/or fire + After installing the main body, carry out wiring, Otherwise, there is a danger of electric shock and/or injury. * Do not remove the rubber bush. (5.5 to 5SkW) Due to the possibilty that a wire may be damaged, shorted or may have a ground fault with the ‘edge of the wiring cover {\ CAUTION + Make sure that the input voltage is: Three phase 200 to 240V SO/60Hz (for models with suffix L) Three phase 380 to 480V 50/60Hz (for models with suffix H) + Be sure not to input a single phase. Otherwise, there is a danger of fire. * Be sure not to connect AC power supply to the output terminals (U, V, W). Otherwise, there is a danger of injury and/or fire. * Be sure not to connect the resistor to DC terminals (PD, P and N) directly. Otherwise, there is a danger of fire. + Be sure to set the earth leakage breaker or the fuse(s) (the same phase as the main power supply) in the operation circuit. Otherwise, there is a danger of fre. + As for motor leads, earth leakage breakers and electromagnetic contactors, be sure to use the equivalent ones with the specified capacity (rated). Otherwise, there is a danger of fre. + Do not stop operation by switching off the electromagnetic contactors on the primary or secondary sides of the inverter. ‘Otherwise, there is a danger of injury and/or machine breakage. + Fasten the screws with the specified fastening torque. Check so that there is no loosening of screws. Otherwise, there is a danger of fire. 2-5 N300 INSTRUCTION MANUAL Chapter 2 Installation and Wiring 2.2.41 Terminal Connection Diagram (sink type) (Sacre Saw Ione ‘Short bar) ‘ Se vw sey a e peal in Intelligent output cara ( 1 & FM output manitor aa! evar a vm | TH SN} : Ttely eu buss = Peon om a ee [one L Dokoma at Option 4 nagar (Analogue ouput) P—] AS rece) ose UP cuore ‘eset 1] rar oe 2-6-1 N300 INSTRUCTION MANUAL Chapter 2 Installation and Wiring 2.2.1 Terminal Connection Diagram (source type) BRD circuit (eee tm Poni (Option) Putand take as terminal substrate Intetigent etay ouput connection (iat tar) / Intligent put (Bcomecton) \ FM output monitor” evar pooroy fh ,Deorontay ay | Fer tain estes a ee [one L Dokoma at Option 4 a (Analogue ouput) P—] AS mecmaeel ose UP cuore ‘eset 1] rar oe 2-6-2 N300 INSTRUCTION MANUAL ( Chapter 2 Installation and Wiring (1) Expianation of main circuit terminals oma Soe ST atl ein power {Cones aerating power S60. ee [ewes = i DC rec ‘Remove he short tr between FO and P connect optional power face recon DCL) et eons boing er ‘Connect opera renal ing sso ( calidon SW we KW) a ana Rot core pr ene bag c oo Shwe (2) Explanation of control circuit terminal ‘Stat Taka Nine Tagenaion of amis “aoa pont] La apenaniat Page etree. 2 0 Sawer L _and analogue ouput, AM “ u Sows |“ [Es Ob gover er a TTA enc ‘Wren nein 060-10 mans fea « © | commen: | MERRIE Scny SSIES oy, | 4, eet Impedance 1h, Freee ‘emnaivtiage) | Sewn Aare rtoer “ Fequcy commend) wen wag OC 0-210, i eta ae 22 | supportvolage) ‘Seen be chem =m se oat or |Feegmey eonend] hen rpaing OC 4-20rA 20nA rerum Foy Fd impetnce 1002 ‘ad omy | Whence Gust spars oboe Aton er eae 2m 8 ‘aw | Dgistmonder ako rezimnum cord 2A g ‘esos Cet one seca tam nr te, teeny amok i Seer Ee ede rp ard “aut | Anaiogue monitor Fequency ‘Alowable output less then a ‘cunn) opodinc 20 chen ru | Opt mone [owas maxima rent an me Cue te pe ep wh gl ee eve enka asaran tency Sate 7 TEOCH pas aren Teo WSS S| Rab nasa ret i Jogi, is connecton input common i 100m A i ‘source | cyay | letace power “Tho common tem i PH emia, 8 tinal TH torial, : ‘Dan Nor at sare be er eT oS 3 pc | Wnetgentincut | paLPLC: Sink ype GMI-PLC: Sours ype a 5 BY) EP | reweccanmans | ata pW ra ON Farad OF ep amma ovale mesie fete 27 g an It ON condon oon Wo tiger eiage is ‘Sect ion om erg acetate ge e5e3) stints op | OFF condition of terminal z a cea fowor3 2 MS piace cen fae [BBS] oun | Sins tesnton tect ne tn ei rable aren |g fae sestemman van AG iret SOA, B) 2 | a0 | commmiemins | 81S conmen tein of am asp tin Nowa iin els ‘ACZHNV, 0.24 AS | Mam ouput ‘Asi ouput funeton. uipulis¢ contact adie iru al en Thais conc oes Tan hte vero oma rina B)B | ne {meguegee | Sesto tence pt no ‘emer ower 10 2 teen | apt omc, 2-7 N300 INSTRUCTION MANUAL Chapter 2 Installation and Wiring 2.2.2 Main circuit wiring (1) Waring on wiring When carrying out work on the Inverter wiring make sure to wait for at least ten minutes before you remove the cover. Making sure to check that the charge lamp is not illuminated. ‘Afinal check should always be made with a voltage meter. After removing the power supply, there is a time delay before the capacitors will dissipate charge. 1. Main power terminals (R, S, T) Connest the main power terminals (R, S and T) to the power supply through a electromagnetic contactor or an earth-leakage breaker. ‘We recommend connecting the electromagnetic contactor to the main power terminals. Because when the protective function of inverter operates, it isolates the powers supply and prevent the spread of damages and accidents. This unit is for three-phase power supply. It isn't for the single-phase power supply. If you require a single phase power supply unit, please contact us. * Don't operate with onioff of the switch set up in the converter side and the inverter side. Do an ‘operation stop by the operation order (FW / RV) terminals. * This inverter becomes the following condition at the time of open phase because open phase prote- ction is being made ineffective by the early data, R phase or T phase, open phase condition: The power isn't tumed on, and it doesn't operate. phase, open phase condition: It becomes single-phase operation condition. Trip operation such as 1a deficiency voltage or over current may be done. Dont use it under open phase condition. + Aconverter module may be damaged in the case shown below. Be careful ‘When an unbalance of the power supply voltage is more than 3%. Power supply capacity, 10 times of the capacity of inverter and case beyond 500kVA. When a change in the rapid power supply voltage occur. (Example) When inverter of the plural is installed with the common electric wire whose it is short by each other. When there is insertion of the condenser or a removal * Onloff of the power supply isn't to do it more than three times in one minute. It has the possibilty that inverter is damaged. 2. Inverter output terminals (U, V, and W) * Wire with thicker wire than the applicable wire to control the voltage drop. Parlicularly when outputting low frequencies, the torque of the motor will reduce by the voltage drop of the wire. * Do not install power factor correction capacitors or a surge absorber to the output. The inverter will tip or sustain damage to the capacitors or the surge absorber. + In the case of the cable length being more than 20 meters, itis possible that a surge voltage will be generated and damage to the motor is caused by the floating capacity or the inductance in the wire (400V especially). An EMC Mains Filter is available, please contact us. + In the case of two or more motors, install a thermal relay to each motor. + Make the RC value of the thermal relay the value of 1.1 times of motor rated electric current. Install output ACL when a life becomes short by the length of wiring 2-8 N300 INSTRUCTION MANUAL Chapter 2 Installation and Wiring 3. Direct current reactor (DCL) connection terminals (PD, P) + These are the terminals to connect the current reactor DCL (Option) to help improve the power factor. + The short bar is connected to the terminals when shipped from the factory, if you are to connect a DCL you will need to disconnect the short bar first. + When you dont’ use a DCL, don't disconnect the short bar. 4, External braking resistor connection terminals (P, RB) + The regenerative braking circuit (BRD) is builtn as standard up to the 11kW Inverter. ‘When braking is required, install an external-braking resistor to these terminals. + The cable length should be less than 5 meters, and twist the two connecting wires to reduce inductance. * Don't connect any other device other than the external braking resistor to these terminals. + When installing an extemal braking resistor make sure that the resistance is correctly rated to limit the ‘current drawn through the BRD. 5. Regenerative breaking unit connection terminals (P, N) + The Inverters rated more than 15KW dont contain a BRD circuit. If regenerative braking is required an external BRD circuit (Option) is required along with the resistor (Option). * Connect extemal regenerative braking unit terminals (P. N) to terminals (P. N) on the inverter. The braking resistor is then wired into the External Braking unit and not directly to the Inverter. + The cable length should be less than 5 meters, and twist the two connecting wires to reduce inductance. 6. Earth (GO) + Make sure that you securely ground the Inverter and motor for prevention of electric shock. * The inverter and motor must be connected to an appropriate safety earth and follow the local standard. Failure to do so constitutes an electrical shock hazard. INVERTER@} INVERTER® INVERTER’ INVERTER © INVERTER@+ INVERTER® 2-9 N300 INSTRUCTION MANUAL Chapter 2 Installation and Wiring (2) Wiring of main circuit terminals The wiring of main circuit terminals for inverter is the following picture. Wiring of terminals Corresponding type R s T U v w (4) | (L2) | (L3) | (74) | (T2) | (T3) po| P| nN | RB|G@| Ge N300-055L FHF G1) / 4) | Ro-To : M4 Short bar Mw Other : MS ™ '@ Charge lamp Ro | To N300-O75LF/HF R|s|T|]U|V]w (LA) | (L2) | (L3) | (14) | (T2) | (TS) pd| P| N | RB| Gelso 1)| 4) | © Short bar Ro-To : M4 “ Se Charge lamp Other : Mé Ro | To Ro-To : M4 Other : M5 N300-100LF/HF N300-150,185LF Ro | To N300-150-370HF Charge lamp \e’ er 2 Ma ce|R|s]T}Ppo}e}Nn | ul v | w]ee|p-— 'N300-300,370LF (LA) | (L2) | (LS) | 4) |) | | 71) | (72) | (73) N300-450, 550HF Ro-To : M4 Other : Mi N300-220LF Ro-To : M4 Earth terminal : M6 Other : M8 N300-450,550LF N300-750-1320HF Ro-To : M4. Ro | To Charge lamp Yo“ (LA) | (L2) | (43) | C4) |) |_| eA) | (42) | (73) Short bar NS Earth terminal : M8 Other : M10 N300 INSTRUCTION MANUAL ( (3) Wiring Equipment tT Chapter 2 Installation and Wiring Refer to (4) Common applicable tools" (Note) The applicable tools indicate for Hyundai standard four-pole squirre-cage Motor (Note2) Select applicable tools for breakers examining the capacity of breakers. (Use Inverter type.) (Note3) Use earth-leakage breakers (MCCB) for safety. (Noted) Use 60/75'C copper electric wire. (Note5) Itreeds bigger wires for power Ines, ifthe distance exceeds 20m. (Note6) Use 0.75mm for Alarm output contact (Note7) Separate by the sum wiring distance from Inverter to power supply, from inverter to motor forthe sensitive current of leak breaker (CCB) Wiig distance [Sensitive Gurren (mA) 100m and less 50 ‘300m and less | 100 (Notes) When using CV wire and wiring by rigid metal conduit, leak flows. (Note9) 1V wie is high dielectric constant. So the curtent increase 8 times. Therefore, use the sensitive current 8 times as large as that of the lef list. ‘And ifthe distance of wire is over 100m, use CV wire. —_ dt] = vane Fin Input reactor(harmonic control Trig partis used when the nubalance voltage rate is 3% or more and power __| electrical coordination, power | 5, is OF more, ar is. ra ‘in| ‘3 . sername | totam ape seabioe tech (act-DI-D000) | Leecoes te Ta ss ay CL TSS OB TS SE (zero-phase reactor) the power lines. This part reduces noise. if Nae er forieeney Tp eos oaon re prod TSS ve g! L pg re ere a (OTK -0000) Be crawerse ao} B | epee nese mee “This part reduces radiation noise emitted from wire at the input Ee ee Sree DOL) [Ta pare toma & Breaking resistor “This partis used for applications that need To incwease the Drake vy Se eg nt | ee ee aapearae a on high inertia load. t apauwae Teo ae LT SE a Re a a a ee (Ovsez -o000) ‘preventing malfunction of sensor and measuring instruments. I“ 1__ | Rado noise fiter(zero-phase | This part reduoes noise generated at the output ofthe inverter. geo. reactor) {tis possibie to se for both input and output) Pane kere lcs eer stearigsr serait uputatemation actor | Crmet power ssp Ts pas naa betwen he ere ano Redon Vinton a ee ee ce renee IM Relay preventing tor song (idm or mero) a cruntamoasa fora matuncion of ho misapplication thermal relay by harmonic due to swihing on inverter taken by insering + ¢ ) reactor, There isthe way to use current sensor instead of thermal rela. Motor LCR filter ‘Sine-wave filter at the output. 2-14 N300 INSTRUCTION MANUAL ( (4) Common applicable tools Chapter 2 Installation and Wiring ‘Applicable Tools cut | fertor | Roquyw | aman | coo | [e" [ recog ‘ew | Moved BEDN™ | Petre | Terma ak break cir 55 | Na00055LF | 55 | 55 | M5 | 20 | HBSGON | SOA | HaMtcz2 75 | Nao0-o75UF | 8 | 55 | MS | 20 | HBSGON | 50A | Hates 1 N300-110LF 14 55 M6 25 HBS100N | 75A HéMc50 15 N300-150LF 22 - M6 25 HBS100N | 100A | HéMc65 & 18.5 | N300-185LF 30 ~ M6 25 HBS225N | 150A | HélMc80 3 22 'N300-220LF 38 - M8 60 HBS225N | 150A | HéMc80 5 | Ns00.3001F hea | - | ve | 60. | Hs225N | 2008 | Havictt0 37 'N300-370LF (20) ~ M8 60 HBS225N | 225A | HelMc130 45 | Na00-450LF | per) | - | mio) 100 | HeS4o0N | 2258 | HaMet80 85 | N300-550LF | oer) | - | Mto | 100 | HBS400N | 350A | Hanc220 5.5 | N300-055HF 35 35 MS 20 HBS30N 304 HéMc18 75 | Na00-07sHF | 35 | 35 | M5 | 20 | HBS3ON | 30A | HéMcté +1 | Na00-10HF | 55 | 55 | M6 | 25 | HBSGON | 50a | Heese 15 N300-150HF 8 ~ M6 25 HBS100N | 50A HéMc40 18.5 | N300-185HF 14 - M6 25 HBS100N | 75A HeMic40 B| 2 | Nao0-220nF | 22 - | me | 25 | Hest00n | 75a | Havics5o 3 |_30 | N300-300HF | 30 =| me | 25 | HBsto0n | 1008 | Haves | a7 | na00-a70HF | 38 = [me | 25 | HBs225N | 1000 | Havtes0 45 | N300-450HF | 50 -— | wa | 60. | Hes225n | 150A | Havet10 55 | n300-ss0HF | 60 - | me | 60 | Hes225n | 1758 | Hatet30 75 | na00-750HF | (3p) | - | mio | 100 | HBsaoon | 2250 | Hanct0 90 N300-900HF (sen) - M10 10.0 | HBS400N | 225A | HéMc220 110 | N300-100HF | pea) | ~ | M10) 10.0 | HBS400N | 360A | HeMicas0 132 | Na00-1320HF [| 80x2 | - | to | 100 | HBS400N | 350A | HaMte300 N300 INSTRUCTION MANUAL Chapter 2 Installation and Wiring 5) Connecting power to the control circuit, separating from main power When the protection circuit of inverter is activated and the electromagnetic contactor on the input supply to the inverter isolates the power supply, the control circuit power supply from the inverter will also switch off and the alarm output signal will not be hold. The power terminals RO and TO are designed to allow a supply to go direct to the control circuit and therefore keep the alarm output signal on. In this case, please connect power terminals RO and TO, to the primary side of the electromagnetic contactor. (inverter unit side of ACL, EMI fier, on using input ACL, EMI fiter). (Connection) [1] Remove the wires connected. [3] Connect power supply for control ircuit power terminals. Pe a ‘The spocficaion othe receting | fo 2) Toke of the wire of 51 200~240V, S1OrtSOIC OHS) (DC 282~: 339V) Ss 380 ~480V + 10%(60160Hz+5%) (0c 537~678v) When you wire the control circuit power source (R0-T0) and the main circuit power source (R, S, T) ‘separately. Please connect the 3A fuse to the power source electric wire, which is for the control circuit, N300 INSTRUCTION MANUAL Chapter 2 Installation and Wiring 2.2.3 Terminal connection diagram (1) Wiring 1 Both the CM1 and L terminal is insulated to both the common terminal of the input and output signals. Do not short or earth these common terminals. . Use twisted screened cable, for the input and output wires of the control circuit terminals. Connect the screen to the common terminal. . Limit connection wires to 20m. When it is necessary to wire over 20m, use a VX applied controller RCD-A (Remoter operation bar) or a CVD-E (Insulated signal transducer) ‘Separate the control circuit wiring from the main power and relay control wiring. . If control and power wires must cross make sure they oross at 90 degrees to each other. . When connecting a thermistor to the TH and CM1 terminal, twist the thermistor cables sepa- rate from the rests. Limit connection wires to 20m. [re few [ca Sequence el - EF (er When using relays for the FW terminal or an intelligent input terminal use a control relay as. they are designed to work with 24Vde. . When the relay is used as an intelligent output, connect a diode for surge protection parallel to the coll ). Do not short the analogue voltage terminals H and L or the intemal power terminals PV24 and CM1. There is risk of Inverter damage. (2) Layout of control cirouit terminals 8 5] 3] 1] 4) 13] 1 H | 02 | am | Fw] TH | FW | (ayy! CM] 2cr9) (icy | (RS) (TO) (OL) |(FAt)| ALT Tle] 4 [2] 1s 12 © | oF | amr] P24 | Pte | cmt | ce] crayleRs)| (ary | cP) | CM2 RUN] ALO | AL2 The terminal screw size : M3 N300 INSTRUCTION MANUAL ( Chapter 2 Installation and Wiring (3) Change of input logic type The logic type of intelligent input terminals is written following list (Factory Default) N3OO-XXXLF/HF Sink type The input logic type can be changed by changing the Short bar connection of control terminal Sink ype ‘Belween P24 and PLC on the control terminal ‘Source ype ‘Between PLC ang Gmion the control terminal (4) The connection to the input programmable logic controller (sequencer) To use interface power within inverter To Use outside PoWertTale of he sr bc con enna) 5 ea pea Ce ep Hs me be | Ls Output module over Output modulo evar pas, “coal | [ie ry Sink type boceay LA He LA lou sl N300 INSTRUCTION MANUAL Chapter 2 Installation and Wiring (5) The connection to the output programmable logic controller(sequency) Sink type ‘Source type Irv LL tert 2.2.4 Digital operator wiring For operating this inverter, it can use digital operator OPE- SR, OPE-SRE, OPE-S, SRW-0J and ‘SRW-0EX.For remote operating, put off digital operator from inverter and use connector cable NOP-1A(1.5m) or NOP-3A(3m). (Note 1) When using connector cable, be sure to use less than 3m length. Othemise, there is a danger of malfunction. (Note 2) In case of remote operating with connector cable, the inverter dose not conform to EMC. N300 INSTRUCTION MANUAL. Chapter 3 Operation A WARNING + Be sure not to touch the main terminal or to check the signal or put on/off wire and/or connector. Otherwise, there is a danger of electric shock. + Be sure to tum on the inout power supply after closing from cover. While being energized, be sure not to open the front cover. Otherwise, there is a danger of electric shock. + Be sure not to operate the switches with wet hands. Otherwise, there is a danger of electric shock. + While the inverter is energized, be sure not to touch the inverter terminals even during stoppage. Otherwise, there is a danger of electric shock. + Ifthe retry mode is selected, it may suddenly restart during the trip stop. Be sure not to approach the machine.(Be sure to design the machine so that personnel safely will be secured even ifit restarts.) Otherwise, there is a danger of injury. + Be sure notto select retry mode for up and down equipment or traveling equipment, because there is output free-running mode in term of retry. Otherwise, there is a danger of injury and/or machine breakage + Even if the power supply is cut for a short period of time, it may restart operation after the power supply is recovered if the operation command is given. fit may incur danger to personnel, be suer to make a circuit so that it will not restart after power recovery. Otherwise, there is a danger of injury. + The stop key is effective only when the function is set. Be sure to prepare the key separately from the ‘emergency stop. Otherwise, there is a danger of injury. + After the operation command is given, ifthe alarm reset is conducted, it will restart suddenly. Be sure to sset the alarm reset after checking the operation command is off Othenwise, there is a danger of injury. + Be sure not to touch the inside of the energized inverter or to put a bar into it Otherwise, there is a danger of electric shook andor fire. N300 INSTRUCTION MANUAL. Chapter 3 Operation /\ cauTION + Cooling fin will have high temperature. Be sure not to touch them. Otherwise, there is a danger of getting burned. + Lowto high speed operation of the inverter can be easily set. Be sure to operate it after checking the tolerance of the motor and machine. Otherwise, there is a danger of injury. + Install external break system if needed. Otherwise, there is a danger of injury. + If amotoris operated at a frequency higher than standard setting value(50Hz / 60Hz), be sure to check the speeds of the motor and the machine with each manufacturer, and after getting their consent, operate them. Otherwise, there is a danger of machine breakage. + Check the following before and during the test run. Otherwise, there is a danger of machine breakage. Was the direction of motor correct? Was the inverter tripped during acceleration or deceleration? ‘Were the rpm and frequency meter correct? Were there any abnormal motor vibrations or noise? N300 INSTRUCTION MANUAL. Chapter 4 Explanation of function 2. Operating method (1) Method to display monitor mode, basic setting mode, extension function mode Power ON Display of monitor contents set © Display monitor code No. (Display 0.00 in intial state) (Display 4001) HYUNDAI Sti HYUNDAL Sit ©e ee @H8®@ 688 + When power is tumed off while the basic Retum to the state of setting mode or the extension setting mode \s displayed. The display will be different from Nantactonbiome sme san G) AR Ym © (6 times) Tee @ Display monitor code Ne © Display extension function mode (Display c007) (isplay A---) HYUNDAI Sa] HYUNDAI Sta 6O@e@® SO@®8 + Monitor mode is displayed by pushing + Extension function mode FUNC (Function) key once when dispiay of Display inthe order of Monitor mode No. Aer ber CerHerPery “OTE Oo “OTS @ Display code No. of basic seting mode (Display 2002) “ey © Display code No "a ie ram = 2 ® CO OO pm Note) Refer to (3) setting method of function code. N300 INSTRUCTION MANUAL. Chapter 4 Explanation of function (2) Setting method of function ‘Change operation command part. (Operator > Control terminal) © Display extension function mode HYUNDAI cms) moe AL Make monitor display "A ~~ ~* by referring to (1) lsplaying method. Now operating command part is by the operator, 0 operating command display lamp should slurnato J Push (aie © Display code No. of function mode HYUNDAI J Push the (RNC) key. @ Display contents of function mode HYUNDAI Sa (02(operator). Operation command part displays Program(PRG) light on by displaying contents of function mode. © Display extension function mode (Display A - - - ) HyuNpal Sti jC S68e@ Itis possible to shif to other extension function modes, monitor modes and basic modes in this state. t Push the (ae @ Display code No. of monitor mode. (Display A002) HyUNoA! Sti ee The changed set value is confirmed by pushing the STR key. Operation command display lamplight will switch off so that operation command is now changed to the control terminal t Push the (STR) key. ee S890 Change operation command part to control terminal 01 N300 INSTRUCTION MANUAL. Chapter 4 Explanation of function (2) Setting method of function code Code No. of monitor modes, basic setting modes and extension function codes can be set easily. Indicate the method to change code No. d001 of monitor mode to function code No. ‘A029 simply. © Disply code No. of monitor mode. © Change first figure of (Display 4001) (Display A021) function code No.. HYUNDAt ee d001 8 ee ee 2@8O GaSe vnnan 225hanine 6) key. a Second figures, "2 blinks. First figuro,"1™ blinks. Push to ZN) rey togahor Pasntie® of) te Push tho ZA) key. (2tme) game) (2time) @ Change second figure of (Display A0z9) ‘© Change extension function mode function code No. eal =] va] Hyunpal Si oom Hyunoal 325 ee meeCaoa1 js Ge COGE COG@ 9" of first figure blink * "d" blinks. ‘Second figure "2" blinks. rasitne Ge) Push the (ZN) ey tT < sen® nnn mae ® Finish setting function code @ Change third figure of jo: (Display A001) function code No. rvunoat 22 UNDA 2 oa he |, 225] key. (Confirm"A") * Finish setting A029 "A" blinks. Third figure "0" blinks. (Note) When you input code No. tir Don't change third figure and there isn't in the code list,"A" Theta ighraisdoctes Den change tid fy SFeenins sin Co yang STR toy bush ne cae att 44 N300 INSTRUCTION MANUAL. Chapter 4 Explanation of function 4.2 Code list Monitor Mode (Note1) Setting | Change Display 'N300 monitor or data range Initial Page spy) Function name (digital operator) ata | 2 ing (ann oot | Outputtreauency | 0.00~99.99/100.0~400.0(liz) -[- =| 413 ‘utut eurrant 002 imonior 0.0~999.9(A) - | = =| 418 003 | Operator aecion | Forward) / O(stopyitreverse) — {= — Pans (0.00~98,99/100.0~ 999 9/1000. ~ 9999 4004 |PID feedback monitor in So reat Same -|- — | 443 ele) Inteligent input on rh 7.2. r0N ere sa 324 (Beane) Intelligent output “mnt 12,11:0N 006 | terminal montor 8 a A As. woe | - | — | ata aw Frequency conversion | 0,00~99,987100.0~998-9/7000. ~ 99087 doo7 | Fes irentor 1000~ 3996 cfs = 4s 012 [torque monitor | -300.~+300.% == = [as dora | Ouputvatace [o.0~s000v = [= =| 415 O14 [input eloctrc power mono} 0,0~ 999.9 Kw = [= = [a5 d016 | Accumulatedtms | 9.9999,/1000~9999100~{999 hr — — - 4-16 monitor during RUN 017 | Power ON tme mentor | 0,~9999/1000~9989/(100~(099 hr [a — [ate 4080_[Number ofr ime monic, 0, ~9999./1000~ 6563(10000~65530)(imes)| — | — = | 446 081 | Trip monitor 4 =| = [446 <4082_| Trip monitor 2 =p — [ate d083_| Trip monitor 5 TripCode, frequency(tk), curent(A), = [= = [6 [ssa renner wo | x | x few ‘A004 | Maximum Frequency | 30. ~400. (Hz) 60. x x | 421 ‘azoa| Maximum Frequency, | 59, ~ 400, 4) 60. x | x | aan 1asoa Maximum Frequerey. Jao, ~400. wo. | x | x [aa A005 AT ternal selection | SY Chardig 0 ars Orit AT termina 00 x | x | 422 pnileconain —_(iaerammoninn pesto. cugmrmnia| wo | x | [a § | aott|ostar 0.00~$0:99100.0~400.042 oo | x | o | az = [A012 |0.ona (0.00 ~98 98/100.0~ 400.062) oo | x | o | az 1g [A013 |ostarato (= 400%) 0 | x |e [az & | a014|0 end rate (0~ 100.00%) ro. | x | o | 423 A015 | 0 start selection 00{extermal starting frequency)/01(0liz) on x © | 423 {A016 |0,0L02 sampling | 1.~20.imes) 3 | x | o [az note) Mul-sheed selection] ioe nga to aapespeewih Tiemnagy | |X |X | #° £ | n020| Muti- speed 0 (0.00, sraring Fequency ~ maximum. frequency) | 000 | o | o | 446 S A220) Hu Spee! °- (0.00, staring frequency ~ 2nd maximum. Frequency] 000 | o | o | 446 A 1azq| Mut speed 0. Yan, starting tequeney ~ Sdmatmun Fearon] oo | o | 0 | 440 E | acat| Mut- speed 1 0.00, stating frequency ~ maximum. Frequency(z)] 000 | o | o | 446 e ‘A022| Mati-specd 2 __[000, staring teqiency ~ maxinum Frequeneyiin] 000 | | © | 440 + [A023 | Mut - speed 3 (0.00, staring frequency ~ maximum. Frequency(t)| 0,00 o | o | 445 & [anza|uw-spoos 4 0.00, staring tequeney ~ maximum. Frequency] 000 | o | 0 | 446 8 cs|nar-ncis [oon aamenmey Soran Foxman] ow To To [os = [A026] Muti-speed 6 [000, staring requeney ~ maximum Frequency] 000 | o | 0 | 446 ‘A027|Muti-epeed 7 | 000, tating fequency ~ maximum. Frequencyiin] oco | © | © | 446 Note1) Valid for tve connection of OPE-SR N300 INSTRUCTION MANUAL. Chapter 4 Explanation of function Function Mode [change Code | Function name Setting range Initia data |Setn9) mace | Page oinn ‘A028 |Muli-speed 6 [0.0 staring fequency ~ maximum Frequenayia] 000 | o | © | 446 jp [A029| Mati epoed ® (000, stating frequency ~ maximum Frequenogiei| 000 © 6 3 “A030 | Mult - speed 10 0.00, starting frequency ~ maximum. Frequency(!iz)] 0.00) ° o | 446 3 [nosi|Mun-specd 11 [0.00, staring tequoncy ~ maximum Frequenayti] 000 | © | © | 446 3 |[A032|Muti-speed 12 [0000 starting frequency ~ maximum. Frequency(\] 0.00 | > | © | 446 £ [ana3|Muti-speed 13 [0.00, stating trequency ~ maximum. Frequency] 000 | © | o | 446 5 (ADGA | ul speed 14 [000 staring frequency ~ maximum Frequencyézj] 000 | | © | 448 3 [A035 |tmutt-speed 15 __[0.00, staring requency ~ maximum. Frequencyti} ooo | o | © | #46 ¥ | Anse name feaserey | 000, saring ewency ~ 88H) 10 |] > | 448 & ‘Ofree-un on JG stopfinvalid on running)O1(stop a ecoleraing on JG sopfnvalié on tunning)O2DC £ braking on JG stopinvak! on runin g)0(ee-run on 2 | A039) oaging selecton | 56 copia on runinglJG air sop deceteratngly| 09 | X | © | #48 2 ‘4(ctop decelerating on JG stop valid on running) (0 braking on 1G stoptvalid on ope rating) ‘A0At | Torque boost selection | OO(mandal torque boosi/Oi (automatic torque boos) | oo | x | x | 427 Ags [Toru boost seecton.| oq(manual txque boosi\O1(automatc torque boost)| 00 | x | x | 427 [A042 |Manual torque boost | 0.0~20.00%) 10 | © | © |e a Manual torque boost, | 9 9. o | o § [22 Sena 0.0~20.0(%) 10 a2 ‘Manual torque Boost | 5 gw, > le 8 sels 0.0~20.0¢%) 10 427 Manual torque boost | 5 9 oe 5 |aoas Now 0.0~50.0(%) 50 wr Manual rave Bos | 9 5 Aza | Manual teravebo08t | 9 9~ 50.09%) so | o | © | aa Manual torque boost | 9 9 aaa Meme 0.0~50.0(%) so | o | o | 427 DORVCVOTEVPA TpowerOdIfee Vf setingyORSIVY A044 1st contol oeacasqos o | x | x | as DORVCVOTVPT TpowerjOdifree Vf satingyOOTSIVY A244 2st conto! a o | x | x | a5 ‘Aaa [3st conto COqvGyOK(VPH-7power) oo | x | x | 4s ‘A045 [Output wotage gain _|20.~ 100. woo. | o [© | 42 A051] DC braking selection [OOUnvabayOT (ald oo | x | © | #28 [A052] DC braking frequency [0.00~60, 0042) 080 | x [0 [428 [A059] 0C braking wat ime [0.0~505) oo | x | 0 | 420 & [Ag64]0C rang power —_[.~ 100%) 0 x Le | 428 § [ros [octane [00-F0u8) oo [x [| 428 A056 [Dlg ele sae |00(6age acon vO Tevel action) ee B [sr [DC kia powering]. ~ 1001(%) = 0~ 801%) 0. x_| © | 428 & [A058 [OC trang int sg tra[0.00~60 15) oo | x | o [42s ‘A059 DC camer frequency [0.5~ 15(te) Daraing <0. ~ 10> soca | x | x | 428 N300 INSTRUCTION MANUAL. Chapter 4 Explanation of function [orange Code | Function name Setting range Initia data |Setn9) mace | Page onnn 061 FoR Ma oon Rogureyloner terminate] 000 | x | o | ast ast ‘maxim 000231 Frequency Tower Imfer-2nd saling maximum 2 ir maueney frequencyis) oo | x fe | ‘An62| st feqvensy, [0.00 start requency-tst frequency maxmumiimtertiz] ooo | x | o | aa IB [azz|2e towne, oo stat teweney2nd teqeny naxrumtniertz] 000 | x | o | 431 BADD ure eave 7 c00—seseno00-a000r | 000} x mn |S g] A064 | ump frequency with 1 (0.00— 10000042) os | x 432 'B | Anes [ump frequency 2 (0.00~99'99/100.0~4000H2) oo | x | o [4x 31 056 [ium Fequoncy wah 2 (000~ 1000002) osm | x | [ew 5 [A067 [sump trequency 3 (0.00 98:99/100.0--400.0(H2) oo | x | o | 4a ‘A068 | un requanoy wih 3 (0.00 10.00(%2) os | x | o | 4a ecelaraion stop ~ ~ ga | Aeceerae 0.00~88 99/100.0~400.0(+2) oo | x | o [4s ‘ROTO [Acceleration stop tine (0.00~ 60.08) oo | x | o [42 | AUT |PI section Ooginvalsy0%(vald) o | x |e [os | A072)PI0 gain 02~60 to | eo | o [as 3 haar |Pi0 ean =) so fe fe pass a ‘A074 [PIDD gain 0.00 100.05) oo fo | o | 43 AO7S|PID scale 0.01 96.95(%) 10 | x | ° [40 ‘AOTG|PID feedback selection] OOfecdbackO1)07(feedbackO) o | x |e [as ‘A081 [AVR selection OO{ON awvays)ONOFF alvayspO2(OFF on decorating} 02 | x | x | 420 © | A082 | Motor vatage selection] 200r216/550/220°40/, se0icooiarsaaoonie0 | z204a0 | x | x | 420 Operaion mode] OiTnarmal operation (enoray-Saving operavony 08S | section oaquazzy) o | x | x |e Eneray saving ‘A0a6 | expanse accracy 00-1000 soo | o | o | 434 adjustment § ‘AQ92 | Acaloraion time 2 0.9 easeri000~seesni000.~3600(6) | 1800 | © | © | 435 é ‘Acceleration tme 2 ~ ~ ~ ° | o 1g [222 Gn oy 0.0~-99,99/100.0~909.971000.~3600(8) | 15.00 435 £ Accekeraion te 2 = — = | A392 moto 00~-v9.99r100.0~s99.9"1000.~3600(8) | 1500 | o | o | 435 & | A093] Decoration time 2 0.0~va99r1000~s99.9/1000.~s600(8) | 1500 | © | © | 435 g Decsteration me 2 = 99.8971000~ 360046) o |e & |a2s0| Groen 0.0~-2a99/100.0~se9.8/1000.~3600(5) | 15.00 435 & | poss Cereaean ime? 0.0~99,90/100.0 ~999.9/1000.~3600.s) 1500 | o | o | 495 & | none 2nd sage adstable [ooicnange wit 2CH torminayor(change win sata] oo | x | x | 439 2nd stage agustble 1204 | Sectontand maton |0O(Change with 2CH terminalyO1(change with settng} 00 x | x | 435 ‘Aga | 2nd Acceleration 0.00~98.99'100.0~ 400.0(H2) oo | x | x | 43s N300 INSTRUCTION MANUAL. Chapter 4 Explanation of function [oranae Code | Function name Setting range Initia data |Setn9) mace | Page onnun Bra Raoolaration : A295] foquoneytond motor) 0.00~98,99/100.0-400.0¢H2) oo | x | x | 43s 2d deceleration zoo ote |g | Avse| peas (0.00.98 9100.0 ~400.0¢+2) oo | x | x | 435 BS poe |2m5 doooteration 5 8|A206|pecsenornd moto) (0.00~99.98/100.0~400.0(H2) oo | x | x | 435 8 | agar [Acceleration patien OSaghT neyOT S caNVeyOUGaNEy [Be 0% estecten or ajreverso U.cuve) oo | x |X | ae Deceleraton pattem (aight ney (S-cuveyO2U- uve noes scene were revese Uae) oo | x | x | a8 ‘A101 [Ol start 10.00 99.98/100.0 -400.0(H2) oo | x | | 42 ‘A102[O1 end (0100~99,98/100.0 ~400.0(H2) oo [x | © | 42 IB |A103)01 start rate 0.~100(%) 20, x | o | 423 1S §| A104 or end rate 0.~100.(%6) 400. x [o [42s [8 5 610501 start stocion stat equensy)O(0H2) ox 42 ce HOO. ~ 100.798 9~0.00~98,967T0000 IE BL AMtt [02 sran {extemal 0 ~400.0(H2) ooo | * |e | 4 i [Art2|o2 na 400 ~100/:99~0.00~9998/100.0~40000%2) | 000 | x | © | 423 A113|02 start rato 100.~ 100(%) xo [| x | © [42 ‘A114)02 ond rato 400.~100(%) to. | x | o | 423 Lag Art [Acozetaton curve 01(emall swelling) 10{arge swoling) o | x | o | 40 gE 132 [Deceleraton curve 01 (small sweting)~ 10(arge sweting) a | x | o | 438 O0(rinxOT(ORz starpOa{start afer equal Fequer 200" ety seocion | ogtipatorensainpreqensyanideciecionsen)| 00 | x| o | 437 | none Alounderaa= 03—1.06) so | x | o | asr El bons [ety waite 03~ 10076) vo | x |e [ar FS og [ponertulraunder | — cogmaki aided 7 ower feilurelunder valid) 1(vaid)02(evalid during stop an Bg eo evosaton by sop command) mo | x | o | as 52|__ {stp 5") instantaneous LE | ons [Power fllaedander (00(16 timesyot ree) o | x | o | asr Wwotage retry time [selection 1006 [Open phase selection oxivaliyO1 (valid) oo | x | o | 4s 007 |Freavency setting 0.00~99.99/100.0~400.0(H2) oo | x | o | 437 | b012 [Elecronic thermal evel] O2constantcurent=120°constant curentia) — [Radeurent [> | 49 5 0212 [pe moey | ozconstantcurent~1.20'constant cuenta) [Bbc] x | 6 | 4.30 3 Elecronic thrmal vel constant curent— Raed cura ° Q ata [Besar 0.2"constat curent—1 20°constant cuenta) | F3 x 439 £ ‘electronic thermal _ | OO((educod charactorsicy0 (constant Torque > 8 [0013 | characteristic selection characierstc)02(ree setting) of x 439 Brig [2 eectonie thermal OO edced charaensicy0 (Constant Torque mtx |e aso characteristic selection Characteristic}02\fee sating) N300 INSTRUCTION MANUAL. Chapter 4 Explanation of function [oranae Code | Function name Setting range Initia data |Setn9) mace | Page onan [rd electronic thermal | OO(reduced charactersticy01 (constant torque o | a 5313 charactors selection charactorstic02(toe setting) os “ Froo eiocrone 5015 | ermal reavency 1 0.40042) 0°. x | o | 440 i | pore [Free electronic 0.0~-10001) oo | x | o | 440 E thermal current 4 s Free elocionic é 0017 ie eon 2 (0. 400,¢2) °. x | © | 440 8 borg | Free electronic 0.0~1000,A) 00 x | o | 440 i | D019 Fee ny (0.~ 400,(H2) 0. x | o | 440 ao [Fi locos, 0.0 T000;0) oo | x | leo ‘oiaRGYOT enabled on scocleraton/constant 21 Overload resticton | paed)ozlenabied on constant speeaydstenabiedon| =, | x |g | gay selecton Scceleratoniconstant speedspeed increasing at regenaraing made) ‘Overload restiction | 0.50"rated curent~Z00'reted curentiaye~t0" | Rated > 2022 ("evel rated curen{A)> invert so] “ z (Overioad restiction 30.0040) 19028 | Qvetoad rest 0.10—30.0048) to | x | o | oat 3 ‘OviAWaIGYOT enabied on accalraton constant ¥ | bz4 |Overioad restcton 2. | speedy0z(enabied on constant speed)/03{enabied o |x | laa 3 ‘selecton {on accleratonleonstant speea[speed increasing at ‘egenerating mode)) 12.00"red aurentfA 1 Rated vo2s |prgget resection Jostratescurenzorraesarrewan~s0r | ataty | x | o | aa o26 | Overload restriction 0.10~30.00(8) 100 | x | o | 4a [impossible to change the data excepts fom eran 3 1 data except sating frequency tem when 3 | vost |Sotware lock made | rminal is ONV0Zimeossble fo change the data oa | x | o | 450 selection ‘except this item)03,impossibie to change the data except seting frequency fem /1O(posabie t change (aia on operating) 'b034 [RUN sime/Power ON] _o ~ ac09 1000 ~8563(100000~655300)h ° x | © | 461 03s | Operation drecton | cofreverse is vaidyO1(Only fomardyOa(Oniyreverse)| 00 | x | © | 417 Oj Sian reduced votlage ime smal = 2036 [Start reduced votago | QS" reduced votage time smal) o | x | o | 443 5 ' fon | all dispiayO1(each function displayy > 5 | 037 Pispay select 02{User setingimain setting) o | * “60 3 [que ini made 000 quadrant mode )O7(Tarninal oparaTany : 040 | celcen {2 (log iu)'03{Ont0n 1 YO4{ Option 2), o | % “78 Torque liritievel 1 ‘i 0.=200,(%ninvaie) ° boat Sd eatent mosey <0~ 480% /n0 > | * ae gue itive? setting(Reverse 0.=200,%potnvai 082 genarating at 4 Torque lint evel 4 vosa| seta owas 0.-200,9%ynotnvale) wo. | x | o | az quadrant mace) Torque LAD-STOP =0= 18%] m0 > 0485 | lecton oo{invaidyO4 Va) oy} ls Boag | Reverse nn (o(tavaliyO1( Valid) o | x | o Secon of non op 2050 | iorareouspover oo(ivalieyOvaks) o | x | x jan 05: Froriop nen sting .0~ 1000.) oo | x | x Jam [OV LAD-STOP lovel 052 |of non-stop function 0.0~1000(v) oo | x | x | an seting 05S nse cating! 0.07-98.9/100.0-909.9'1000.-3600 (S) 10 | x | x an Decoration Fequeney 054 | wth ef nn.sop uncon 0.00~10.00¢%2) oo | x | x Jar sting 8 [bono patna os a © Fp084 [Fa Adjustment 0-255, oo |e | eo | ss boa | Sar feaueney 0.10~-2.994H2) oso | x | o | 44s 0083 | Sing “*UeneY 0.5~ 15.02) Derationg enable, <05~t0H8> | s0ca0>| x | x | a2t Se a (County code for 08s | Pann coo (interior yO 1ECYO2(USA) o | x | x | 465 bose | equa salar o1-208 io | > | © fas 087 | STOP key enable 00(valyOT (inva) o | x | o [aw bogs | Resume on FRS 00(042 startV0 (Start equaling) 00 x | oe | ast 090 [BRD usage ratio (0.0 100.0%) oo | x |e | aa 1091 [Stop mode salocton 00(deceleraton stopy1(Free-nn stop) o | x | x [aw woz seems | Me eee eae | w_[ x | x [ow ‘oawalayO 1 valcinvala during sk 2095 [BRD eaocon aaa ng p>) wo |x |e as 'b096 [BRD ON evel 330 380/660 ~760(V) seorz0 | x | © | aa N300 INSTRUCTION MANUAL. Chapter 4 Explanation of function code | Function name Setting ange ie dat st no | Poe 5 098 | Thermistor selection 00(invalidy/01(PTC)/02(NTC enable) 00 x o | 464 © | 5099) Thermisior errorlevel 0.9999. (Ohm) soo. | x | © | ase 100 [Free Vi tequency 4 0-~ Free Vit frequency 22) o | x [ x | a Dt01 |Free Vi votage 1 0800.0) oo | x | x | 42 1102 |Free Vi requency 2 0 = Free Wi frequency a2) 0 | x [x |e 103 Free Vi votage 2 08000) oo | x | x [42 0104 Free Vit requency 3 0.~ Free Vit requency (Hz) o | x | x | aa | b105 [Free vit votage 3 (0.~800.0) 00 x | x | 426 & | 5106 | Free vir requoney 4 0-~ Free Vit requency 52) o | x [x | a [pia |roe vives 0 ena) oo x | x [as E | b108 [Fee vit requency 5 0.~Free Vf frequency 6(H2) 0. x | x | 426 109 ree Vi votage § 0= 8000) oo | x [x [4a 110 |Free Vit fequency 6 0-~Free Vit frequency 7H) o | x | x | a iit [Free vit wotage 6 0~ 8000) oo | x [x [42 112 |Free Vi Fequency 7 0=4000V) o |x [x [as 113 [Free Vi votage 7 08000) oo | x | x [4a 20 peace ‘o(invaayot(vaid) oo | x | o | 49 ores ane, 000-500) oo | x | @ |e formation 5 b122 ating tne for 0.00~5.00(S) 0.00 x o | 469 2 Toa wating ane eran Goon 50) co Px Pe fee oz | Wa re ose 000=5008) oo | x | © | «a 125 Releasing fecuency 10.00 —98.98/10000~400.06%) oo | x | | 469 126 | Rossing net ee a N300 INSTRUCTION MANUAL. Chapter 4 Explanation of function hang code | Function name Sting ange Inia data Sete pct | Page onan Inicigentingut 1 soting| cI Reems ciaCrimmpee NoxCraMa — | 18S) © | 44s e cot Toei | tate itso inmpegic ws) | x SgreyDe Earl sey OWSETZ" ont) © | Cong] ntaigentinut2 sating| SHG noaupe saute mec PRSesns wean | x | o | 445 E cS Gamsea uty Soh 6a AAs E | coos raoouiar sate] HeStammaemsseremmmaeion Tous) | x | 0 [as s SEGA PS oue hn) PRO over A (put cating] wma) ZSPD Ponsa vanes) 2qPOCPD z com ratweroacer| soeeetecccammrennes | ve | x | 0 | a = (Pureeas menos ents DOV acon § | coos) meigentinntsseting| iociendsamniaarces)soreomyyopeaer | CH) | x | o | 445 3 SOF tor sgwtBjosra Manegnt oH" se $ | co006|hictaentints coting| MEFIMEeerbayaSreMaeectiicesrs mu | ocr) | x | o | 445 BotRovetod ata deeehOT ores) C007] netgentinaut7seting| siiroriousintemanjitrantacintsmiey | ocr) | x | o | 445 GrettinoLAc AD cnccbatpclsason er cea ao a C008 |itetigentinput8seting| Setar Pemtsncl pace a MNONG sep ou [| x | oo | 445 cont] REN aaon o(NoyorNC) 00 x | o | 446 & [cor meee egaz9> ORONO) wo |x po es = [oom] meareasan DANO) wo Px pe pee © |COt4| NOIRE section” oo(noyorNe) 00 x | o | 446 § [com naeerratse TonONDAN) wo |x pe fas 2 [cone] igen rats = doNoyOHN) w |x |» paw 5 [com] Retgetreatz ab Oo(noyorNC) oo | x | o | 446 2 (RONG) sdecton 2 |cov| sees vata 00 DaNOHOWN) wo |x po pes corg| EW abINOINC) OoNoyOrNC) 00 x | o | eas Inetigent output 11 | cape nnngyO\ At ease aa ype saa) ° (021 slocton GOFAL over seg tequerVoseL Oreos atone | OWFAN) |X +46 Trtigent pat 2 |Get sna) Cry ing een) RUN) 2 eoeeraernmee craremay.| ew | | ° Ae B cresltpiprnoama | vente enema mye § | 0923] sctecton ‘oa hon sraTavoER Bs ra 5 loam | oan ceotaad: [wow] » |» few E Bs Gretbad chase nobos agatha cut B | cozs| nteligent output 15 ELE Gra reel eT oa) | x | o |4s7 = (Goreme tube ey wher sar cd eas 3 | co2e| Namrety ouput | Seieseoin 0s) osm [x | © [esr 3 ‘00(Output frequency V01(Output curent)02(Ouaput torque) 7 = | co2r| Fa selection {aig aust fesvensyiouGupahctageosinpa | 00 «| x | © ase 5% tie poms healed es) OTLAD equa) 2 | coz8|AM selection Coogalcntfenersitounawlegsoted | 00 | x 463 = SOE pone eral bd aOTLAD Peas) ca29| a sot Gog omarcengytacupteiaessiee” | op | x | o [es Oa pone oral bed a OTLAD Pease) N300 INSTRUCTION MANUAL. Chapter 4 Explanation of function [orange code | Function name Seting range Initial data S84) race | Page onan coat siege utp 11 SoINOVOHNC) wo | x | © Jes cose] eeenyontP 12 Oo(NOVO(NC) 00 x | o | 458 Intligent output 13 ° ‘C033 !tetisnt ut oo(NoyoH.NC) o | x 458 Intligent output 14 cosa | netigent ou Oo(NoyOrNC) 00 x | o | 458 Inteligent ovipa 15 C05 | tigen output Oo(NOVOHING) o | x | o | 458 ‘Nam relay Ou ., [omss| omnes oRNOVOHNE) wo | x [© [4s 2 [Overcad advance noe! 00(On ascal_ And decd, constant speedy § | 040 signal ouput made Of(Only constant speed) oo} fe [ss 3 ‘Overload advance 1 Trverter [con owes 0.0-20'rated curent(A) ret | x | 0 | aaa 3 [core |eceauer are, (0.00~ 99.89/100.0~400.0¢+2) oo | x | o | 4az 2 ‘rival Frequency ~ = | £043} sting for decseraton 0.00 ~£19.99/100.0~400.0(H2) oo | x | o [459 | cosa AO govaton seting (0.0~ 100.0(%) 30 x | o | 450 Froquay arial st = A000) ° da g C045 Frege amg ene (0.00 -99.99/100.0—400.0(Hz) 0.00 x 434 3 | cow in 1100 ~ 0.971000 40.00) om | x | o | 459 £ Over torque vel se 0.0 ~200.00%) 5 | cos Seana = a we |x [= [os 8 cose Over ave lve cating 0.0 200.0% ° cael Oat aaa wo. | x |e [ae Over torque vel sting (0.020009) © 6097 | Revues ds) 0520000 100. | x 462 ‘Over torque evel seting| 0.0~20000%) ° Seo oma wo | x |e [ow coer | meres 0~100,%) wo | x |e | 440 6062] Alarm code selection ‘oxinvatidyo1 (302/458) oo | x | o [ase oss) eter 0.00~99.997100.¢42) oo | x | o | ae 6070 | Data command AajoperatonvOB(RSAB5VOA options yOS(opton2) | a2 | x | x | 462 [Communica ‘2(oop back test) __| 0071] transmission speed |03(2400bpsyo4/4800eps)O%e0OEpsYOR(18200b—s)] 04 |X |e | 482 «ara oomnevan om = pepe tee 83] C073| Communication bit TArbityB(Bbi) 7 x | o |4e2 E g C074] Communication paty | 00(n0 party nameyOt(even pariyy02(edd pariyy | 00 | x | 0 | 42 (=| C075] communication stop bt “yeiy2t) 1 x | o | 482 [Communication ~ ° C078 | orig 0.~1000,(ms) o x 482 Note) <> indicate the setting range of 75 to 132kW N300 INSTRUCTION MANUAL. Chapter 4 Explanation of function Function Mode code} Function name Seting range inal data Sting fem Page 20810 acjustment e.~saea/1000—~e5a5(10000-e55a0) | Seton To] o | 2082] Or acumen ec (6083 | 02 aqustment 0.~soa2/1000—535(10000-5580 | Selinger! 5 [ e | — (C085| Themistor adustment 0.01000 1050 | o | © | 46 (C086 | AM Ost ajustment 0.0~10.00%) oo | o | o | 4a | C087] AM! adjustment 0.255, 80 o | o | 468 & | cows [an ofeat oauetnoe a 200m) Bama] [> [aoe Cr = fe tel= B | Ctot|UPOWN setecion | _O0(No Frequency datayOr(Keep frequency data) | 00 | x | © | 454 2 [croa|raiooccin | RRB RS] oo |» | [ass cr Fate (oe STARTYOT(Stat equaling wo | x | > |ass cin | Netaat averce 00-20raied cane) rere] x | o | aaa 121) 0 zero adjustment sone 1000-essaroo0o-essn0) |, Sea.| o | o | — C122 orza adustrent ee a Ps c2s|02zmoadusnent | 0-eoserio00-essacone0-essm, | 849, 0 |» | — 1001 [Aotning seecion ] OOWORUaRSOT aCe matey doxs notre) | gq |x | x | are Hoo ser corsiant Onde genera purpose motor aiyoriaeunra] gg | x | x | ars H202| Zimaier consiant | OO amoung ea winenire astanegy?| 00 | Xx | x | 475 ~~ [Hong alowabie motor (0.20~75.0(4}<0.2~ 160KI> fomacing| X | x | 475 2 Ha03| 27 glowable motor 0.20~75,0¢4)<0.2~160kt> foitna| x | * | 475 5 [H004] 1" motor pole selection 214/6/8(pole) 4 x | x [475 2 | ant |r ae sole 2A) «Lx px pes Hoos | 1 speed response 0.001 ~9.999110.00~65.53 1s | o | o | 476 205] 2,gP2ed response 0.001~9.990110.00~65:53 150 | o | o | ava HO06 | stabilized factor 0.~ 256. ro. | o | o | sar H206 | 2" stabilized factor 0.~255. 100. o o | 467 1306 |" staitzed factor 0.~255. to. | o | o | ao7 N300 INSTRUCTION MANUAL, Chapter 4 Explanation of function Function Mode [orange Code | Function name Setting range Initial data | SeMOl mage | Page onnun H020| 1*motor constant Rt 01000~9:999110,00~65.53(2) fomaving| * | X | 475 1220] 2" motor constant 1 '0.000~9.999110.00~ 65.549) foontg| x | x | 475 = ‘Seton O21] T*motor constant R2 (0,000 ~9.996110.00~65.53(2) founmg| x | x | 475 1221] motor constant R2 (0.000 ~9.999110.00~ 65532) fomcng| x | x | 475 H022| ‘motor constant L (0,00 ~09.99/100.0~686.3(mH) fomaning| Xx | x | 475 H222| 2“motor constant L (0.00~99.99/100.0~655.31mH) fomaving|_* | x | 475 1023) 1*motor constantio 0.00~99.99/100.0~655.31A) forging] x | x | 475 1223] 2 motor constantlo (0.00~ 89.89/100.0~655.3/4) fomnring| x | x | 475 H024| 1*motorconstants | 0.001~9,999/10,00~99.99/100,0~9999.(kgr’) toning x | x | 475 H224| Pmotorconstats | _0001~9.999/1000~90.971000~99908(@n) [ySeemng| x | x | 475 “Tinotor constant RT ‘Seton Ho3o] motor constant (0.000 ~9.996/10.00~65.53(2) forwarding] * | *_| 475 motor constant RT Seton 11230 fauna ca ‘0.000 ~9.896/10.00~65.55(2) towaring| * [x [475 ‘motor constant R2 Seton = [Host] (ater constns (0.000 ~9.990110.00~65.53(2) forwarding] * | X | 475 z ‘motor constant RZ ‘Seton 2B [Haat] Francona ‘0.000 ~9.990/10.00~65.53(2) eg] x | x [475 5 ‘motor constant L 7 - Seton 3 [ Hosa) (rotor constant (0.00 ~99.99/100.0~885.3(mH) forwarding] * | X | 475 2 2% motor constant. 7 ~ Seton Haz) Famer constant 0,00 ~99.99/100.0~656.9(mH) fomsiting| X | x | 475 “motor constant o| ~ | ‘Seton 1033) (autotuning data) 0.00 88-99/160.0~ 855314) forwarding] * | % | 478 motor constant lo ~ 7 Seton tesa 2 atx constan 0.00~ 99 99/100.0~655.3(8) ceten,| x | x [47s “Fmotor constant J ~ ~ 7 > | , Seton Ho34] Frmaterconsiant | qoo1~ssearioc0~sasaron0~aeea am) | ,S%9] x | x | 47s motor constant J Seton Haga] Zimatorconstantd | go91~9:996/10.00~99.90'1000~9900kan") | formacing]| X | © | 475 "7 P-contol proportion ~ ~ ole oso] 1 conto 0.00~99.29/100.0~299.9/1000 (%) 1000 458 50] pt egee Prererion] 0.9000 9971000~200:7100.0%) 10 | o | o | 456 +" Pr-contolintegraton| ~ ~ ole os] Treanor (100~99 99/1000 ~2809/1000,0%) 1000 485 Hos1|2cPreamaleTovaior| 9 99~ 98 991000~ 990.7000) woo | o | © | ase P-contrl proportion ~ ole Hos2 UP conto o01~10.00 100 458 2° contol proportion ~ ole H252 eon Sa 0.01~10.00 100 456 N300 INSTRUCTION MANUAL, Chapter 4 Explanation of function Function Made Setting] re" Code | Function name Setting range Initial data | SENS] moce | Page nnn 080] FeSO tte 0~ 100%) wo. | o | o | 7 z 2"OHeSLV ter ~ & | Ho0|2204 0~100(%) to. | o | o | a7 : Ho70| beseepepeon (0.00~90 967100. ~999.97000.%) soo | o | o | «56 3 | nor Pocoatineaton 0.00~90.90710000~990.91000(%) woo | © | o | as vore| Ponte popation cco-000 ra | © | | ase ‘Option operation > 001 | lection on error O(TRPYO1(RUN) 00 x 467 jon 2 operation Poo | Often 2 operat (0(TRPYO1(RUN) 00 x | o | 467 oto | Feed back onion 0(rwvakgyOX(vakd) 00 x | x. |Notet) Port eameae SE MUTERT | 729, ~o000,1000~6500(10000~e8000) (ous) | 102 | Xx | Xx [Nott O12 | Control made selection (00(ASRmode)01(APRmode) oo | x | x [ron Pot | fee tan input mode (Mode 102 Mode 2v03{Mode 3) 00 x |x _|Noter) Orientation sy ota | Onerraton stp 0.~4096, °. x | 0 |Noter) ots | penton seed 0.00 ~99.89/100.0~120.0¢%2) 00 | x | © |Notet) Pore | Oreraton drecton (00(Forwardy01(Reverse) 00 x |x. |Notet) [Orentation completion ~ ° 017 | Orentaien 0.~999911000 (puise) 5 x Niet) é Pots | eae 0.00~9.068) oo | x | © {Noten Electronic O19) postion selection 00 (Feed-back}/0 (Reference) oo | x | © [Noten 7020 cy om fx |e feo Elseronie gear 021 |denominato of rao 0.~9900. 1 x | 0 [Noten setting Postion cond 022 | poston ca in seting| 0.00~99.98/100.0~655.3 oo | x | o [note Postion controlToop ~ o 023 | Son 0.00~99.99/100.0 oso | x Note) P08 scion 00(hnvayOX (valid) oo | x | o |Notet) ozs | Ory sees avert (0.00~99.99/100.0~1500%) 150 | x | © [Now] ‘Spood-eror over ~ Too on O27 | See Te ean 0.00~99.99/100.0~ 120.0¢%2) 70 | x | © |Nott) Digialnpat pion 03: | input made selection (04operatryO1 (option 1)'02(0pion 2) oo | x | x | Note (AcatDec) N300 INSTRUCTION MANUAL. Chapter 4 Explanation of function Function Mode [change Code} Function name Setting range Initial data |SetthSl mode | Page onan a2 Spain| opro01 (pon 1y0AopOn 2) co | x | o /werl [evceNtunangovrat | Pevensie gre 0.00~99.998 100 | x | x. (Notes) [ang acon atonal | —O0(TapyOT(Conroned STOP TrpVOdTi=noe) 8 | Pots sonnzen Renee | ot | x | x [uae JOuassntie rane O46 | number sting 20,21, 100 a | x | x: [Not [reutassanboinstanan o47 [roitasurio 70,71, 101 m1 | x | x: [Not [aed fkdmaiebrmcin | O0(Tap OT(Conroled STOP TrpVO2Tinore) Poss ee thcosttosepyouconrciaseey™” | ot | 2 | x (Nas) ods presage 0~38 (Seting only an even number) o | x | x Nota) 001 [User selection nold001-PO4 wo | x | o | 466 W002 |User2 selection noldO0-PO4 ro | x | 0 | 466 [W008 [User selection neldo0-PO4G m | x | o | 46 W004 User 4 selection noldD01-PO4G=-POG> mo | x |e | 466 § | U00S fuser section nold001-PO4G-POR> ro | x | o | 46s Unobeooos ———— Toe 3 | 007 fuser? selection nold001-PO4O ro | x | 0 | 460 008 [User 8 selection nold001-PD4G mo | x | o | 466 008 ser 8 satocton nold001-PO49 ro | x | 0 | 468 00 User 10 selection nold001-PD4G-POR> mo | x | o | 46 dt fuser 11 salotion nold001-PO4S ro | x | o | 466 Uot2 [ser 12 selection nold001-PO4O ro | x | o | 460 Note 1) Refer to the instruction manual of N-FB Note 2) Refer to the instruction manual of N-DG Note 3) Indicate the setting range of 5.5 ~55kW N300 INSTRUCTION MANUAL Chapter 4 Explanation of function 4.3 Explanation of fun 4.3.1 Monitor mode Output frequency monitor /-— Relation code Indication code d001 displays the frequency the inverter outputs. The data is displayed as follows. When 4001 is displayed, the monitor lamp "Hz" is illuminated, (Display) 0.00 - 99.99 : Display is in 0.01Hz unit. 100.0 - 400.00 : Display is in 0.1Hz unit. 4001 : Output frequency monitor Output current monitor Relation code Indication code d002 displays the output current value. The data is displayed as follows. 4002 : Output current In case of displaying d002, the monitor lamp "A" is illuminated. monitor (Display) 0.0 - 9999 : Display is in 0.1 A unit Operation direction monitor Indication code 4003 displays the direction that the Inverter output is rotating. Forward, reverse or stop. (On operating the inverter (in case of forward or reverse), the RUN lamp will illuminate. (Cisplay) Relation code F : Forward 4003 : Operation direction 0: Stop monitor ©: Reverse PID feedback monitor When you select PID function (01) in A071, the inverter displays the feedback value changed by A075 (PID scale) “Display of monitor part" = " Feedback quantity" x "PID scale” (Frequency command value) (A075) (Setting) A071 : 0.1 (PID is effective) A075 : 0.01 - 99.99 (Display is 0.01 - 99.99 (Set with the 0.01 unit) /—— Relation code (Display) 0.00 - 99.99 : Display is in 0.01 unit. 100.0 - 999.9 : Display is in 0.1 unit. 1000 - 9999 : Display is in 1 unit. 100 - 999: Display is in 100 unit. d004 : PID feedback monitor A071 : PID selection A075 : PID scale 4-13 N300 INSTRUCTION MANUAL Chapter 4 Explanation of function Intelligent input monitor The LED display will monitor the state of the intelligent inputs. Relation code (Example) 005 : Intelligent input FW : Input inteligent terminal 7, 2, 1: ON Input intelligent terminal 8, 6, 5, 4, 3 : OFF monitor Display pwON ee FI on (e200 ats | |) oFF 0 (White) : Lights out or tt tt tt t Input inteligent 8 7 6 5 4 3.2 1 terminal Intelligent output monitor Relation code The LED display will monitor the state of the intelligent outputs. 4006 : Intelligent output monitor (Example) Output intelligent terminal 12, 11 : ON Output alarm AL, Output intelligent terminal 15, 14, 13 : OFF Display oh ih § (Black) : Lights up imi oO 0 (White) : Lights out tt ttt 1514 1312 11 OFFOFF OFFON ON AL Output intelligent (OFF) terminal N300 INSTRUCTION MANUAL Chapter 4 Explanation of function Frequency conversion monitor This inverter displays the value changed by the Inverter output ferquency and the valye set in 086 on the monitor part "Monitor part of display" = "output frequency9d001)" x “output frequency factor(b086)" (Display) Display of d007 0.00 - 99.99 : Display is in 0.01 unit 100.0 - 999.9 : Display is in 0.1 unit 100. - 9999. : Display is in 1 unit 1000 - 3996 : Display is in 10 unit Relation code Frequency conversion monitor : Frequency conversion factor (Range of setting) The setting range of b086 0.1 - 99.9 : Set it with the 0.1 unit. (Example) Output frequency (4001) :50.00Hz When the frequency conversion factor (b086) is 1.1, the frequency conversion monitor (4007) displays "55.00" as "50 x 1.1 = 55.00" (Note) Output frequency of FW terminal becomes same as b007 at the time of setting up the digital output frequency to the FW terminal. Output torque monitor This inverter displays the output torque estimation value. Relation code The monitor lamp "2%" should illuminate while the contents of d012 are displayed. 4012 : Output torque monitor Display substitutes only at the time of the sensorless vector control, Hz domain sensorless vector control and vector control. (Display) ~300.0 - 300.0: Display is in 1% unit Output voltage monitor This inverter displays the output voltage of the inverter converted Relation code into the alternating voltage. . The monitor lamp "V" should ilurinate while the contents of do13 | 4013: Output volage are displayed. (Display) 0.0 - 600.0 : Display is in 0.1V unit. Input electric power monitor Display input electric power from inverter. The monitor lamp "kW" ("V" and "A") should illuminate while the contents of d014 is displayed, Relation code (Cisplay) 2014: put lect 0.0 - 999.9 : Display is in 0.1kW unit. Pow 4-15 N300 INSTRUCTION MANUAL Chapter 4 Explanation of function Accumulated time monitor on RUN The operation time of inverter is accumulated and the value is displayed. (Display) 0. - 9999. : Display is in 1 hour units. 1000 - 9999 : Display is in 10 hour unit 100. - 999... : Display is in 1000 hour unit. Power ON time monitor Relation code. —— d016 : Accumulated time monitor on RUN This accumulates the time running to the inverter and displays the value. (Display) 0. - 9999. : Display is in 1 hour unit. 1000 - 9999 : Display is in 10 hour unit 100. - 999. : Display is in 1000 hour unit. Trip time monitor This displays the number of inverter trips. (Display) 0. - 9999. : Display is in 1 hour units. 1000 - 6553 : Display is in 10 hour unit ‘Trip monitor 1 - 6 This displays the details for the last six protective trips. The trip monitor 1 displayed the details of the last trip. (Display contents) [1] Trip code (Display anything from E01 to £79) (Note1) [2] Output frequency on tripping (Hz) [3] Output current on tripping (A) [4] The direct voltage (between P and N) on tripping (V) Relation code. ——~ 4017 : Power ON time monitor Relation code. —— 080 : Trip time monitor Relation code rip monitor 1 rip monitor 2 4083 : Trip monitor 3 d084 : Trip monitor 4 4085 : Trip monitor d086 : Trip monitor 6 [5] The accumulated time inverter was operating unt tripping (h) [6] The accumulated time inverter was run until tripping (h) (Note 1) Please refer to the pages 4.4 protection function list (2) Trip monitor display. The methods of trip monitor _ Otip factor @Teptemency OQ Tipeurent @Tip voltage @ Accumulated _@ Power ON sme @ woes Av 27 EN ay i _ Ay Avy dO8i|e>[E012 |« [60.00 |« >| 4.00 |< 3980|+>| .Je>| Ble (Note 2) In case of no tipping [~~~] is displayed. 4-16

You might also like