Multi-turn actuator
SAExC 07.1 – 16.1/SARExC 07.1 – 16.1
Intrusive
with actuator controls
AUMATIC ACExC 01.1
Control:
Parallel
Profibus DP
Profibus DP with FO
Modbus
Modbus with FO
DeviceNet
à Foundation Fieldbus
Reference documents:
.. Manual (Operation and setting) AUMATIC AC 01.0/ACExC 01.1 Foundation Fieldbus.
Manual (Fieldbus device integration) AUMATIC AC 01.0/ACExC 01.1 Foundation Fieldbus.
Can be downloaded from the Internet (www.auma.com) or ordered directly from AUMA (addresses from page 82).
1. Safety instructions . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5
1.1. General notes on safety 5
1.2. Range of application 6
1.3. Warnings and notes 7
1.4. Further references and symbols 7
2. Identification . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 8
2.1. Name plate 8
2.2. Short description 10
4. Assembly . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 12
4.1. Handwheel fitting 12
4.2. Multi-turn actuator mounting to valve/gearbox 13
4.2.1 Output drive types B1, B2, B3, B4, B, and E 13
4.2.2 Output drive type A 14
4.3. Accessories (option) 16
4.3.1 Protection tube for rising valve stem 16
4.4. Mounting positions of the local controls 17
5. Electrical connection . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 18
5.1. General notes 18
5.2. Connecting via plug/socket connector with screw-type terminals (KP, KPH) 20
5.3. Connecting via plug/socket connector with spring cage terminals (KES) 24
5.4. Accessories for electrical connection (option) 27
5.4.1 Controls mounted to wall bracket 27
5.4.2 Parking frame 28
5.4.3 Protection cover 28
5.4.4 Ground connection, external 28
6. Operation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 29
6.1. Manual operation 29
6.2. Motor operation 30
6.2.1 Local operation 30
6.2.2 Operation from REMOTE 30
6.3. Menu navigation via push buttons (for settings and indications) 31
6.3.1 Short overview: functions of the push buttons 31
6.3.2 Structural design and navigation 32
6.4. Language change in the display 33
2
Multi-turn actuator SAExC 07.1 – 16.1/SARExC 07.1 – 16.1 Intrusive
Operation instructions with actuator controls AUMATIC ACExC 01.1 Foundation Fieldbus
Page
7. Indications . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 35
7.1. Status indications in the display 35
7.1.1 Status indication S0/S6 - operation 35
7.2. Indication lights/LEDs 37
7.3. Mechanical position indicator/running indication (option) 37
8. Signals . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 38
8.1. Signals via fieldbus 38
8.2. Feedback via output contacts (binary) - (option) 38
8.3. Feedback signals (analogue) - (option) 38
9. Commissioning . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 39
9.1. Type of seating: check/edit for end positions 40
9.2. Switch compartment: open 43
9.3. Torque switching: set 44
9.4. Limit switching: set 45
9.4.1 End position CLOSED (black section): set 45
9.4.2 End position OPEN (white section): set 45
9.5. Intermediate positions (option): set 46
9.5.1 Running direction CLOSE (black section): set 46
9.5.2 Running direction OPEN (white section): set 46
9.6. Test run 47
9.6.1 Rotational direction check 47
9.6.2 Limit switching check 48
9.6.3 Perform reference operation 48
9.7. Potentiometer (option) setting 49
9.8. Electronic position transmitter RWG setting (option) 50
9.9. Mechanical position indicator setting (option) 51
9.10. Switch compartment: close 52
3
Multi-turn actuator SAExC 07.1 – 16.1/SARExC 07.1 – 16.1 Intrusive
with actuator controls AUMATIC ACExC 01.1 Foundation Fieldbus Operation instructions
Page
14. Certificates . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 77
14.1. Declaration of Conformity and Declaration of Incorporation 77
14.2. PTB certificate 78
Index . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 81
Addresses . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 82
4
Multi-turn actuator SAExC 07.1 – 16.1/SARExC 07.1 – 16.1 Intrusive
Operation instructions with actuator controls AUMATIC ACExC 01.1 Foundation Fieldbus
1. Safety instructions
1.1. General notes on safety
Standards/directives AUMA products are designed and manufactured in compliance with recog-
nised standards and directives. This is certified in a declaration of incorpora-
tion and a declaration of conformity.
The end user or the contractor must ensure that all requirements with
respect to assembly, electrical connection, and commissioning at the place
.
of installation are met. They include among others:
Standards and directives such as: EN 60079 “Electrical apparatus for
explosive gas atmospheres"
Part 14: Electrical installations in hazardous areas (other than mines).
Part 17: Inspection and maintenance of electrical installations in hazard-
Safety instructions/ All personnel working with this device must be familiar with the safety and
warnings warning instructions in this manual and observe the instructions given.
Safety instructions and warning signs on the device must be observed to
avoid personal injury or property damage.
Commissioning Prior to commissioning, it is important to check that all settings are in com-
pliance with the requirements of the application. Incorrect settings might
present a danger to the application, e.g. cause damage to the valve or the
installation.
The manufacturer will not be held liable for any consequential damage. Such
risk lies entirely with the user.
Operation
.
Prerequisites for safe and smooth operation:
Correct transport, proper storage, mounting and installation, as well as
. careful commissioning.
Only operate the device if it is in perfect condition while observing these
. instructions.
Immediately notify any faults and damage and allow for corrective mea-
.. sures.
Observe recognised rules for occupational health and safety.
Protective measures The end user or the contractor are responsible for implementing required
protective measures on site, such as enclosures, barriers, or personal
safety equipment for the staff.
5
Multi-turn actuator SAExC 07.1 – 16.1/SARExC 07.1 – 16.1 Intrusive
with actuator controls AUMATIC ACExC 01.1 Foundation Fieldbus Operation instructions
..
The following applications are not permitted, e.g.:
Industrial trucks according to EN ISO 3691
..
Lifting appliances according to EN 14502
Passenger lifts according to DIN 5306 and 15309
..
Service lifts according to EN 81-1/A1
Roller conveyors according to EN 14673 (draft)
..
Continuous operation
Buried service
.
Permanent submersion (observe enclosure protection)
Radiation exposed areas in nuclear power plants
Information These operation instructions are only valid for the “clockwise closing” stan-
dard version, i.e. driven shaft turns clockwise to close the valve. Separate
instructions are available for the “counterclockwise closing” special version.
6
Multi-turn actuator SAExC 07.1 – 16.1/SARExC 07.1 – 16.1 Intrusive
Operation instructions with actuator controls AUMATIC ACExC 01.1 Foundation Fieldbus
Information The term Information preceding the text indicates important notes and
information.
ò Step by step
Provides a detailed description of each step for setting/viewing the parame-
ter.
7
Multi-turn actuator SAExC 07.1 – 16.1/SARExC 07.1 – 16.1 Intrusive
with actuator controls AUMATIC ACExC 01.1 Foundation Fieldbus Operation instructions
2. Identification
2.1. Name plate
1 SAExC 07.1-F10
2 Com No: 1309533
No : 3302MD 19302
No: 0902MA97286
KMS: TP180/001
3 ACP:E3FC-2P0--B000
3 ~ 400V IP67
Control: RS 485
8
Multi-turn actuator SAExC 07.1 – 16.1/SARExC 07.1 – 16.1 Intrusive
Operation instructions with actuator controls AUMATIC ACExC 01.1 Foundation Fieldbus
1 CC 0102
Riester GmbH & Co.KG
auma
D-79379 Muellheim
2 II2G EEx de IIC T4
3 PTB 01 ATEX 1087
4 2IIG c IIC T4
3 EC-type-examination certificate
4 Explosion protection classification –
non-electrical explosion protection
a b c
II 2 G c IIC T4
a) see above
b) Protection type (here constructional safety)
c) see above
Type and size These instructions apply to the following actuator controls combinations:
Type: SAExC = multi-turn actuator for open-close duty
Type: SARExC = multi-turn actuator for modulating duty
Size: 07.1 – 16.1
Version: Intrusive
Type: ACExC = AUMATIC actuator controls
Size: 01.1
Commission number An order-specific commission number is assigned to each device. You can
use this commission number to download inspection records and further
information for the device from the Internet (http://www.auma.com).
Wiring diagram/control Controlling the actuator controls is performed via a Foundation Fieldbus
interface , if the 11th position in the ACP wiring diagram contains the letters
B or C. Example: ACP 11F1-2P0—B000.
9
Multi-turn actuator SAExC 07.1 – 16.1/SARExC 07.1 – 16.1 Intrusive
with actuator controls AUMATIC ACExC 01.1 Foundation Fieldbus Operation instructions
Actuator controls The AUMATIC actuator controls is used to operate AUMA actuators and is
supplied ready for use.
The controls can be mounted directly to the actuator but also separately on
a wall bracket.
The functions of the AUMATIC controls include standard valve control in
OPEN - CLOSE duty, positioning, process control, logging of operating data,
diagnosis functions right through control via fieldbus.
Local controls/ Operation, setting, and display can be performed on site directly at the con-
COM-AC/fieldbus trols or alternatively from REMOTE via a fieldbus interface.
.
On site it is possible to
operate the actuator via the local controls (push buttons and display) and
Intrusive – Non-intrusive
.
Intrusive version:
Limit and torque setting is performed via switches in the actuator.
.
Non-Intrusive version:
Limit and torque setting is performed via the controls, actuator and con-
trols housings do not have to be opened.
For this purpose, the actuator is equipped with an MWG (magnetic limit
and torque transmitter), also supplying analogue torque feedback sig-
nals/torque indication.
10
Multi-turn actuator SAExC 07.1 – 16.1/SARExC 07.1 – 16.1 Intrusive
Operation instructions with actuator controls AUMATIC ACExC 01.1 Foundation Fieldbus
Long-term storage: If the device must be stored for a long period (more than 6 months) the fol-
lowing points must be observed in addition:
1. Prior to storage:
Ò Protect uncoated surfaces, in particular the output drive parts and
mounting surface, with long-term corrosion protection agent.
2. At an interval of approx. 6 months:
Ò Check for corrosion. If first signs of corrosion show, apply new corrosion
protection.
3.3. Packaging
Our products are protected by special packaging for the transport ex works.
The packaging consists of environmentally friendly materials which can eas-
ily be separated and recycled.
We use the following packaging materials: wood, cardboard, paper, and PE
foil. For the disposal of the packaging material, we recommend recycling
and collection centres.
11
Multi-turn actuator SAExC 07.1 – 16.1/SARExC 07.1 – 16.1 Intrusive
with actuator controls AUMATIC ACExC 01.1 Foundation Fieldbus Operation instructions
4. Assembly
4.1. Handwheel fitting
Information For transport purposes, handwheels from a diameter of 400 mm are sup-
plied separately.
1. Manually lift the red change-over lever while slightly turning the shaft
back and forth until manual operation engages.
The manual operation is correctly engaged if the change-over lever can
be lifted by approx. 85°.
85°
2. Attach handwheel over the red change-over lever then on to the shaft.
12
Multi-turn actuator SAExC 07.1 – 16.1/SARExC 07.1 – 16.1 Intrusive
Operation instructions with actuator controls AUMATIC ACExC 01.1 Foundation Fieldbus
13
Multi-turn actuator SAExC 07.1 – 16.1/SARExC 07.1 – 16.1 Intrusive
with actuator controls AUMATIC ACExC 01.1 Foundation Fieldbus Operation instructions
2 4
2 4
. The internal thread of the stem nut must match the thread of the valve
. stem.
If not ordered explicitly with thread, the stem nut is supplied unbored or
with a pilot bore.
Only required for stem nut if supplied unbored or with a pilot bore.
14
Multi-turn actuator SAExC 07.1 – 16.1/SARExC 07.1 – 16.1 Intrusive
Operation instructions with actuator controls AUMATIC ACExC 01.1 Foundation Fieldbus
Figure 7
1. Remove screws (3) and take off output drive type A (2) from multi-turn
actuator.
2. Check if the flange of output drive type A matches the valve flange (4).
3. Thoroughly degrease mounting faces of the mounting flanges.
4. Apply a small quantity of grease to the valve stem (1).
5. Place output drive type A on valve stem and fasten until it is seated sol-
idly on the valve flange.
6. Turn output drive type A until alignment of the fastening holes.
7. Screw in fastening screws (5), however do not completely fasten.
8. Fit multi-turn actuator on the valve stem so that the hollow shaft pinions
engage into the stem nut. The flanges are flush with each other if prop-
erly engaged.
9. Turn multi-turn actuator until alignment of the fastening holes.
10 Fasten multi-turn actuator with screws (3) according to table 1, page 13.
11. Fasten screws crosswise with a torque according to table 1.
12. Engage manual operation at multi-turn actuator and turn handwheel in
direction OPEN until valve flange and output drive type A are firmly
placed together.
13. Tighten fastening screws (5) between valve and output drive type A
crosswise with a torque according to table 1, page 13.
15
Multi-turn actuator SAExC 07.1 – 16.1/SARExC 07.1 – 16.1 Intrusive
with actuator controls AUMATIC ACExC 01.1 Foundation Fieldbus Operation instructions
16
Multi-turn actuator SAExC 07.1 – 16.1/SARExC 07.1 – 16.1 Intrusive
Operation instructions with actuator controls AUMATIC ACExC 01.1 Foundation Fieldbus
17
Multi-turn actuator SAExC 07.1 – 16.1/SARExC 07.1 – 16.1 Intrusive
with actuator controls AUMATIC ACExC 01.1 Foundation Fieldbus Operation instructions
5. Electrical connection
5.1. General notes
WARNING Danger due to incorrect electrical connection!
Failure to observe this warning can result in death, serious injury, or prop-
erty damage.
Ò The electrical connection must be carried out exclusively by suitably
qualified personnel.
Ò Prior to connection, observe general references contained in this clause.
Ò After connection but prior to applying the voltage, observe the Commis-
sioning and Test run clauses.
Wiring diagram/terminal plan The wiring diagram/terminal plan is attached to the device in a
weather-proof bag, together with these operation instructions. It can also be
obtained from AUMA (state commission no., refer to name plate) or down-
loaded directly from the Internet (www.auma.com).
Protection on site For short-circuit protection and for disconnecting the actuator from the
mains, fuses and disconnect switches have to be provided by the customer.
The current values for respective sizing can be derived from the current
consumption of the motor plus the current consumption of the controls.
Motor current consumption:
Refer to name plate on motor (nominal current).
Current consumption of the controls depending on the mains voltage:
100 to 120 V AC = max. 650 mA
208 to 240 V AC = max. 325 mA
380 to 500 V AC = max. 190 mA
24 V DC (+10 %/–15 %) = max. 500 mA, filter capacitor 2200 µF
Current consumption for actuator with 1-ph DC motor:
24 V DC (+10 %/–10 %) = max. 750 mA, filter capacitor 2200 µF
The maximum permissible fuse for controls with a rated power of 1.5 kW is
16 A (gL/gG); for controls with a rated power of 7.5 kW, the value amounts
to 32 A (gL/gG).
Cable installation in accordance Signal and bus cables are susceptible to interference.
with EMC
.
Motor cables are interference sources.
Lay cables being susceptible to interference or sources of interference at
Power supply Foundation Fieldbus requires an own power supply. Due to the special
Foundation Fieldbus requirements regarding this power supply, appropriate power supply units
must be provided within the control station.
The Foundation Fieldbus network design requires a power supply of 9 to 32 V DC
for each Foundation Fieldbus device.
The typical Foundation Fieldbus current consumption of the AUMATIC is 11
mA.
18
Multi-turn actuator SAExC 07.1 – 16.1/SARExC 07.1 – 16.1 Intrusive
Operation instructions with actuator controls AUMATIC ACExC 01.1 Foundation Fieldbus
Bus cables Various types of fieldbus cables can be applied for Foundation Fieldbus. The
following table lists the cable types specified by the IEC/ISA 61158-2, Physi-
cal Layer Standard.
The preferred fieldbus cable is type A cable. This cable should be used in
new installations. However, other cable types may be used for the fieldbus
wiring (e.g type B, C, and D).
Their disadvantage is the reduced cable length; for this reason their use is
not recommended.
Table 3
Type A
(Refer- Type B Type C Type D
ence)
One or multiple Multiple
Twisted Multiple
twisted non-twisted
Cable design conductor twisted pairs,
conductor pairs, pairs, not
pair not shielded
overall shield shielded
Conductor cross-section 0.8 mm² 0.32 mm² 0.13 mm² 1.25 mm²
(nominal) (AWG 18) (AWG 22) (AWG 26) (AWG 16)
Loop impedance
44 Ω/km 112 Ω/km 264 Ω/km 40 Ω/km
(DC current)
Wave resistance at 100 Ω 100 Ω
not specified not specified
31.25 kHz ± 20 % ± 30 %
Wave attenuation
3 dB/km 5 dB/km 8 dB/km 8 dB/km
at 39 kHz
Capacitve asymmetry 2 nF/km 2 nF/km not specified not specified
Group delay distortion
1.7 µs/km not specified not specified not specified
(7.9 – 39 kHz)
Degree of shield
90 % not specified not specified not specified
coverage
Recommended network
1,900 m 1,200 m 400 m 200 m
expansion (incl. spur line)
. cables.
If possible, bus cables should be laid in a separate, conductive, and
19
Multi-turn actuator SAExC 07.1 – 16.1/SARExC 07.1 – 16.1 Intrusive
with actuator controls AUMATIC ACExC 01.1 Foundation Fieldbus Operation instructions
5.2. Connecting via plug/socket connector with screw-type terminals (KP, KPH)
VD00 63-4/45
Art Nr: Z006.413
a CC
3 ~ 400 V 50 Hz
0.090 kW
Y 0.60 A
Figure 11
IP 67 1680 1/min
Temp.Schutz: Th
Isol.Kl: F
3. Seal cable entries which are not used with suitable plugs.
4. Insert the wires into the cable glands.
20
Multi-turn actuator SAExC 07.1 – 16.1/SARExC 07.1 – 16.1 Intrusive
Operation instructions with actuator controls AUMATIC ACExC 01.1 Foundation Fieldbus
1 PE connection 2 PE connection
Control cables Motor wire
21
Multi-turn actuator SAExC 07.1 – 16.1/SARExC 07.1 – 16.1 Intrusive
with actuator controls AUMATIC ACExC 01.1 Foundation Fieldbus Operation instructions
Information The cable shield of Foundation Fieldbus cables may only be connected to
the ground potential at one single point.
31 32 39 31 32 39 31 32 39
FF+ FF+
FF –
FF –
£ further devices will follow ↑ from the previous device, channel 1
¢ final device ↓ to the next device, channel 1
A external termination ⊥ SHIELD (cable shield)
Information Although the AUMATIC is equipped with an automatic polarity detection and
correction, it is recommended to connect the fieldbus cables according to
their polarity to generate a consistent wiring for all fieldbus devices.
22
Multi-turn actuator SAExC 07.1 – 16.1/SARExC 07.1 – 16.1 Intrusive
Operation instructions with actuator controls AUMATIC ACExC 01.1 Foundation Fieldbus
23
Multi-turn actuator SAExC 07.1 – 16.1/SARExC 07.1 – 16.1 Intrusive
with actuator controls AUMATIC ACExC 01.1 Foundation Fieldbus Operation instructions
5.3. Connecting via plug/socket connector with spring cage terminals (KES)
VD00 63-4/45
Art No: Z006.413
a CC
3 ~ 400 V 50 Hz
0.090 kW
Y 0.60 A
Figure 15
IP 67 1680 rpm
Temp.Protection: Th
Insulation Class: F
3. Seal cable entries which are not used with suitable plugs.
4. Insert the wires into the cable glands.
24
Multi-turn actuator SAExC 07.1 – 16.1/SARExC 07.1 – 16.1 Intrusive
Operation instructions with actuator controls AUMATIC ACExC 01.1 Foundation Fieldbus
Information The cable shield of Foundation Fieldbus cables may only be connected to
the ground potential at one single point.
31 32 39 31 32 39 31 32 39
FF+ FF+ A
FF – FF –
25
Multi-turn actuator SAExC 07.1 – 16.1/SARExC 07.1 – 16.1 Intrusive
with actuator controls AUMATIC ACExC 01.1 Foundation Fieldbus Operation instructions
4 EEx e
EEx d
26
Multi-turn actuator SAExC 07.1 – 16.1/SARExC 07.1 – 16.1 Intrusive
Operation instructions with actuator controls AUMATIC ACExC 01.1 Foundation Fieldbus
Design
Figure 18
27
Multi-turn actuator SAExC 07.1 – 16.1/SARExC 07.1 – 16.1 Intrusive
with actuator controls AUMATIC ACExC 01.1 Foundation Fieldbus Operation instructions
28
Multi-turn actuator SAExC 07.1 – 16.1/SARExC 07.1 – 16.1 Intrusive
Operation instructions with actuator controls AUMATIC ACExC 01.1 Foundation Fieldbus
6. Operation
6.1. Manual operation
In case of motor failure or power failure, the actuator may be operated man-
ually for purposes of setting and commissioning.
Manual operation is engaged by an internal change-over mechanism.
1. Pivot change-over lever manually to approx. 85° while slightly turning the
handwheel back and forth until manual operation engages.
29
Multi-turn actuator SAExC 07.1 – 16.1/SARExC 07.1 – 16.1 Intrusive
with actuator controls AUMATIC ACExC 01.1 Foundation Fieldbus Operation instructions
6 1
2 STOP
4 Reset
The actuator can now be operated using the push buttons (1 – 3).
Information Use the MODE input (refer to wiring diagram) to select between REMOTE
MODE (open-close duty) and SETPOINT MODE (modulating duty).
30
Multi-turn actuator SAExC 07.1 – 16.1/SARExC 07.1 – 16.1 Intrusive
Operation instructions with actuator controls AUMATIC ACExC 01.1 Foundation Fieldbus
6.3. Menu navigation via push buttons (for settings and indications)
The push buttons of the local controls (figure 23) are used to view, edit, and
show various indications on the display.
Figure 23
1 p
6 2 q
3 8
4 C
5
Now, settings and indications can be performed via the push buttons (1 – 4).
Table 4
Push
Functions
buttons
Cancel process
31
Multi-turn actuator SAExC 07.1 – 16.1/SARExC 07.1 – 16.1 Intrusive
with actuator controls AUMATIC ACExC 01.1 Foundation Fieldbus Operation instructions
..
The indications on the display are divided into 3 groups:
Group S = status indications
M0
M0
OFF S0
E2 100%
OPEN POSITION
OFF S0
E2 100%
OPEN POSITION
Enter the password In the menu (group M), the settings are protected by a password.
To change the parameters, a password must first be entered.
The following default password is set in the factory: 0000.
ENTER PASSWORD
0 * * *
Information If no input is received over a longer period of time (approx. 10 min), the con-
trols automatically returns to the status indication S0.
32
Multi-turn actuator SAExC 07.1 – 16.1/SARExC 07.1 – 16.1 Intrusive
Operation instructions with actuator controls AUMATIC ACExC 01.1 Foundation Fieldbus
ò Step by step:
1. Set the selector switch to position 0 (OFF).
0
I
I
MAIN MENU M0
LANGUAGE/CONTRAST
SETTINGS
OPERATIONAL DATA
3. Press 8 .
Display indicates:
LANGUAGE/CONTRAS M00
VIEW
EDIT
4. Press q.
Display indicates:
LANGUAGE/CONTRAS M01
VIEW
EDIT
5. Press 8 .
Display indicates:
ENTER PASSWORD
0 * * *
6. Enter password:
Press 8 4 times = 0000 (default factory password).
33
Multi-turn actuator SAExC 07.1 – 16.1/SARExC 07.1 – 16.1 Intrusive
with actuator controls AUMATIC ACExC 01.1 Foundation Fieldbus Operation instructions
Display indicates:
EDIT M010
LANGUAGE
LCD CONTRAST
7. Press 8 .
Display shows the set value.
EDIT M010
LANGUAGE
ENGLISH
↵:EDIT C:ESC
EDIT M010
LANGUAGE
ENGLISH
:EDIT ↵:OK C:ESC
34
Multi-turn actuator SAExC 07.1 – 16.1/SARExC 07.1 – 16.1 Intrusive
Operation instructions with actuator controls AUMATIC ACExC 01.1 Foundation Fieldbus
7. Indications
7.1. Status indications in the display
Information For actuators equipped with process controllers, status indication S6 is dis-
played instead of status indication S0. The description below applies to both
indications (S0 und S6).
Operation mode display Line 1 indicates the current operation mode (LOCAL MODE, OFF,
SETPOINT MODE, …)
LOCAL MODE S0
OPEN
E2 100 %
RUNNING OPEN
Operation command/setpoint dis- Line 2 indicates currently incoming operation commands (OPEN, STOP,
play CLOSE) or the setpoints E1 or E7 (for actuators equipped with
positioner/process controller) in % of the total travel.
LOCAL MODE S0
OPEN
E2 100 %
RUNNING OPEN
Valve position display Line 3 indicates the valve position in % of the travel.
This indication is only available if the actuator is equipped with a position
transmitter.
LOCAL MODE S0
OPEN
E2 100%
RUNNING OPEN
LOCAL MODE S0
OPEN
E2 100%
RUNNING OPEN
RUNNING CLOSE
Actuator runs logically CLOSE (remains set during operation pauses).
OPEN POSITION
End position OPEN reached.
35
Multi-turn actuator SAExC 07.1 – 16.1/SARExC 07.1 – 16.1 Intrusive
with actuator controls AUMATIC ACExC 01.1 Foundation Fieldbus Operation instructions
CLOSED POSITION
End position CLOSED reached.
SETPOINT POSITION
Setpoint (modulating actuators only).
36
Multi-turn actuator SAExC 07.1 – 16.1/SARExC 07.1 – 16.1 Intrusive
Operation instructions with actuator controls AUMATIC ACExC 01.1 Foundation Fieldbus
Information The behaviour (blinking/illuminated) can be changed via the BLINKER parameter.
.
Mechanical position indicator
continuously indicates the valve position
(Indicator disc rotates approximately 180° to 230° at full travel from
auma
4
1
37
Multi-turn actuator SAExC 07.1 – 16.1/SARExC 07.1 – 16.1 Intrusive
with actuator controls AUMATIC ACExC 01.1 Foundation Fieldbus Operation instructions
8. Signals
8.1. Signals via fieldbus
Feedback signals via output contacts are only available if a parallel interface
is provided in addition to the fieldbus interface
The output contacts can be used to indicate operation modes of the actuator
or the controls as binary signals. The signals can be freely assigned. Exam-
ple:
Output contact open = no thermal fault
Output closes = thermal fault in actuator
Fault signals can be issued via the ALARM CONTACT parameter, other sig-
nals via the OUTPUT CONTACTS 1 to 5.
For further information on this topic refer to “Manual (Operation and setting)
AUMATIC AC 01.1/ACExC 01.1”.
Analogue feedback signals are only available if the following conditions are
.
met:
In addition to the fieldbus interface, the AUMATIC is equipped with a par-
. allel interface.
The actuator is equipped with a position transmitter (potentiometer or
RWG).
For further information on this topic refer to “Manual (Operation and setting)
AUMATIC AC 01.1/ACExC 01.1”
38
Multi-turn actuator SAExC 07.1 – 16.1/SARExC 07.1 – 16.1 Intrusive
Operation instructions with actuator controls AUMATIC ACExC 01.1 Foundation Fieldbus
9. Commissioning
Prior to any electrical operation (motor operation), ensure that all commis-
sioning settings described in this clause have been performed.
I
I
Information The selector switch is not a mains switch. The actuator control is disabled in
0 (OFF) position. The controls’ power supply is maintained.
Low temperature version Please note that for low temperature versions, the controls require a heat-up
time.
Heat-up time This heat-up time is applicable in case the actuator and the controls are not
live and have cooled down to ambient temperature. Under these conditions,
the following heat-up times have been met prior to commissioning after con-
nection to the voltage supply:
60
50
30
0
0 – 10 – 20 – 30 – 40 – 50 – 60 ϑ[°C]
39
Multi-turn actuator SAExC 07.1 – 16.1/SARExC 07.1 – 16.1 Intrusive
with actuator controls AUMATIC ACExC 01.1 Foundation Fieldbus Operation instructions
Limit seating The limit switching is set in such a way that the actuator switches off at the
desired switching points. The torque switching acts as an overload protec-
tion for the valve.
Torque seating The torque switching is set to the desired tripping torque. After reaching the
tripping torque the actuator is turned off.
The limit seating is used for signalling that the limit switching is tripped
shortly before reaching the set tripping torque. If this is not the case, one of
the following fault signals is displayed: TSO FAULTS or TSC FAULTS
(menu S1).
ò Step by step:
1. Set the selector switch to position 0 (OFF).
0
I
I
MAIN MENU M0
LANGUAGE/CONTRAST
SETTINGS
OPERATIONAL DATA
3. Press q.
Display indicates:
MAIN MENU M1
LANGUAGE/CONTRAST
SETTINGS
OPERATIONAL DATA
4. Press 8 .
40
Multi-turn actuator SAExC 07.1 – 16.1/SARExC 07.1 – 16.1 Intrusive
Operation instructions with actuator controls AUMATIC ACExC 01.1 Foundation Fieldbus
Display indicates:
SETTINGS M11
SEATING MODE
TORQUE
LOCAL CONTROLS
5. Press 8 .
Display indicates:
VIEW VIEW
OPEN POSITION CLOSED POSITION
LIMIT LIMIT
C:ESC C:ESC
Change setting
Display indicates:
10. Press q.
Display indicates:
11. Press 8 .
41
Multi-turn actuator SAExC 07.1 – 16.1/SARExC 07.1 – 16.1 Intrusive
with actuator controls AUMATIC ACExC 01.1 Foundation Fieldbus Operation instructions
Display indicates:
ENTER PASSWORD
0 * * *
p q are also used here to change between the OPEN POSITION (left
figure) and CLOSED POSITION (right figure) displays.
42
Multi-turn actuator SAExC 07.1 – 16.1/SARExC 07.1 – 16.1 Intrusive
Operation instructions with actuator controls AUMATIC ACExC 01.1 Foundation Fieldbus
1. Loosen screws (2) and remove cover (1) from the switch compartment.
43
Multi-turn actuator SAExC 07.1 – 16.1/SARExC 07.1 – 16.1 Intrusive
with actuator controls AUMATIC ACExC 01.1 Foundation Fieldbus Operation instructions
Figure 27
1. Loosen both lock screws (3) at the indicator disc (figure 27).
2. Turn torque dial (4) for setting the required torque (1 da Nm = 10 Nm).
Example:
Figure 27 shows the following setting:
3.5 da Nm = 35 Nm for direction CLOSE
4.5 da Nm = 45 Nm for direction OPEN
3. Fasten lock screws (3) again.
The torque switches setting is complete.
44
Multi-turn actuator SAExC 07.1 – 16.1/SARExC 07.1 – 16.1 Intrusive
Operation instructions with actuator controls AUMATIC ACExC 01.1 Foundation Fieldbus
45
Multi-turn actuator SAExC 07.1 – 16.1/SARExC 07.1 – 16.1 Intrusive
with actuator controls AUMATIC ACExC 01.1 Foundation Fieldbus Operation instructions
Actuators equipped with DUO limit switching contain two intermediate posi-
tion switches. One intermediate position may be set for each running direc-
tion.
Figure 29
46
Multi-turn actuator SAExC 07.1 – 16.1/SARExC 07.1 – 16.1 Intrusive
Operation instructions with actuator controls AUMATIC ACExC 01.1 Foundation Fieldbus
Perform test run only once all settings previously described in the Commis-
sioning clause have been performed.
I
I
auma
47
Multi-turn actuator SAExC 07.1 – 16.1/SARExC 07.1 – 16.1 Intrusive
with actuator controls AUMATIC ACExC 01.1 Foundation Fieldbus Operation instructions
5
1
2 6
3
.
ation has to be performed after the setting has been changed:
Operate actuator electrically (via the push buttons OPEN and CLOSE of
the local controls) once to the end position OPEN and once to the end
. position CLOSED.
If no reference operation is performed after changing the limit switching,
the feedback signal via the bus is not correct. The bus signals the miss-
ing reference operation as a warning.
48
Multi-turn actuator SAExC 07.1 – 16.1/SARExC 07.1 – 16.1 Intrusive
Operation instructions with actuator controls AUMATIC ACExC 01.1 Foundation Fieldbus
This setting is only required if the potentiometer is directly wired to the cus-
tomer connection XK (refer to wiring diagram).
Figure 31
1 Potentiometer
Information Due to the ratio of the reduction gearing the complete resistance
range/stroke is not always passed. Therefore, external adjustment (setting
potentiometer) must be provided.
49
Multi-turn actuator SAExC 07.1 – 16.1/SARExC 07.1 – 16.1 Intrusive
with actuator controls AUMATIC ACExC 01.1 Foundation Fieldbus Operation instructions
The electronic position transmitter RWG records the valve position. On the
basis of the nominal position value measured by the potentiometer (travel
monitoring), it generates a current signal between 0 – 20 mA or 4 – 20 mA
Figure 32
Information If the maximum value cannot be reached, check whether the appropriate
reduction gearing has been selected. (The max. possible turns/stroke are
indicated on the order-related technical data sheet for the actuator).
50
Multi-turn actuator SAExC 07.1 – 16.1/SARExC 07.1 – 16.1 Intrusive
Operation instructions with actuator controls AUMATIC ACExC 01.1 Foundation Fieldbus
51
Multi-turn actuator SAExC 07.1 – 16.1/SARExC 07.1 – 16.1 Intrusive
with actuator controls AUMATIC ACExC 01.1 Foundation Fieldbus Operation instructions
52
Multi-turn actuator SAExC 07.1 – 16.1/SARExC 07.1 – 16.1 Intrusive
Operation instructions with actuator controls AUMATIC ACExC 01.1 Foundation Fieldbus
The red test buttons (1) and (2) are used for manual operation of the limit
switches:
Ò Turn test button (1) in direction of the TSC arrow:
Torque switch CLOSED trips.
The indication light torque fault OPEN on the local controls is illumi-
nated.
Ò Press push button OPEN to reset the fault (red indication light) by oper-
ating the device in the opposite direction.
Ò Turn test button (2) in direction of the TSO arrow:
Torque switch OPEN trips.
The indication light torque fault CLOSE on the local controls is illumi-
nated.
Ò Press push button CLOSE to reset the fault (red indication light) by oper-
ating the device in the opposite direction.
Information If the actuator is equipped with a DUO limit switching (option), the intermedi-
ate position switches will be operated at the same time.
Ò Turn test button (1) in direction of the LSC arrow:
Limit switch CLOSED trips.
Ò Turn test button (2) in direction of the LSO arrow:
Limit switch OPEN trips.
53
Multi-turn actuator SAExC 07.1 – 16.1/SARExC 07.1 – 16.1 Intrusive
with actuator controls AUMATIC ACExC 01.1 Foundation Fieldbus Operation instructions
Fault description Actuator runs to end stop although the limit switches work properly.
Possible cause The overrun was not considered when setting the limit switching.
The overrun is generated by the inertia of both the actuator and the valve
and the delay time of the controls.
Display indicates::
LOCAL RESTRICTED S0
E2 100%
OPEN POSITION
EMERGENCY STOP S0
E2 100%
OPEN POSITION
Possible cause . RESTRICTED means that the local controls of the AUMATIC have not
54
Multi-turn actuator SAExC 07.1 – 16.1/SARExC 07.1 – 16.1 Intrusive
Operation instructions with actuator controls AUMATIC ACExC 01.1 Foundation Fieldbus
LOCAL MODE S0
OPEN
E2 100%
FAULT IND.
WARNING IND.
A warning has occurred
Ò For further information, press qp and go to status indication S2.
FAULT + WARNING
Faults as well as warnings have occurred.
Ò For further information, press qp and go to status indications S1
(faults) or S2 (warnings).
FLT + NR
Faults and the NOT READY IND. signal have occurred.
Ò For further information, press qp and go to status indications S1 or S3.
WRN + NR
Faults and the NOT READY IND. signal have occurred.
Ò For further information, press qp and go to status indications S2 or S3.
FLT + WRN + NR
Faults, warnings, and the NOT READY IND. signal have occurred.
Ò For further information, press qp and go to status indications S1 to S3.
55
Multi-turn actuator SAExC 07.1 – 16.1/SARExC 07.1 – 16.1 Intrusive
with actuator controls AUMATIC ACExC 01.1 Foundation Fieldbus Operation instructions
FAULT IND. S1
NO FAULT
INTERNAL FAULT
Internal fault has occurred.
For further information:
1. Go to group D0: Press C and hold it down until diagnostic indication D0
is displayed.
2. Go to diagnostic indication D2: Press q twice.
LOSS OF PHASE
One phase is missing.
Ò Test/connect phases.
THERMAL FAULT
Motor protection tripped.
Ò Wait for cooling off.
– If the fault indication display persists after cooling off:
Set selector switch to position Local control (LOCAL) and reset fault
indication via Reset push button, or
– Issue reset command via fieldbus.
Ò Check fuse F4.
CONFIGURATION FAULT
The controls configuration is incorrect.
For further information:
1. Go to group D0: Press C and hold it down until diagnostic indication D0
is displayed.
2. Go to diagnostic indication D4: Press q four times.
56
Multi-turn actuator SAExC 07.1 – 16.1/SARExC 07.1 – 16.1 Intrusive
Operation instructions with actuator controls AUMATIC ACExC 01.1 Foundation Fieldbus
WARNING IND. S2
NO WARNING
WARNING OPER.TIME
The preset running time for a travel between end position OPEN and end
position CLOSED has been exceeded.
Ò Set the running time (MONITOR TRIGGERS parameter) in accordance
with the actual running time.
Ò Check tripping behaviour of end position switches.
Ò Check actuator mechanics.
WARNING STARTS/RUN
The preset values for max. starts/h or max. running time/h have been
exceeded.
Ò Check modulating behaviour.
Ò Increase dead time.
Ò Reduce number of nominal value changes.
INTERNAL FEEDBACK
Position transmitter is not standardised.
Ò Operate actuator into both end positions (OPEN and CLOSED).
INTERNAL WARNING
Internal warnings have occurred.
For further information:
1. Go to group D0: Press C and hold it down until diagnostic indication D0
is displayed.
2. Go to diagnostic indication D3: Press q three times.
FEEDBACK E2 LOSS
Signal loss of position transmitter.
Ò Check position transmitter signal.
1. Go to group D0: Press C and hold it down until diagnostic indication D0
is displayed.
2. Go to diagnostic indication D7, D8, or D9: Press q either seven, eight,
or nine times.
Ò Check position transmitter wiring.
Ò Check POSITION E2. The setting must correspond to the wiring dia-
gram.
SETPOINT E1 LOSS
Signal loss of the set point.
Ò Check wiring.
TORQUE E6 LOSS
Signal loss of torque source.
Ò Check wiring.
57
Multi-turn actuator SAExC 07.1 – 16.1/SARExC 07.1 – 16.1 Intrusive
with actuator controls AUMATIC ACExC 01.1 Foundation Fieldbus Operation instructions
Ò Check wiring.
P-FEEDBACK E4 LOSS
Signal loss of the actual process value E4 (only if PID controller is available
and active).
Ò Check wiring.
58
Multi-turn actuator SAExC 07.1 – 16.1/SARExC 07.1 – 16.1 Intrusive
Operation instructions with actuator controls AUMATIC ACExC 01.1 Foundation Fieldbus
NOT REMOTE
Actuator cannot be operated from REMOTE as the selector switch is in
position LOCAL or OFF (0).
WRONG COMMAND
Indicates that inadmissible operation commands have been received via
Foundation Fieldbus.
EMERGENCY MODE
The EMERGENCY operation mode is active.
EXTERNAL CONTROLS
For combination fieldbus/standard interface function:
Operation via parallel interface.
ACTUATOR LOCKED
Actuator locked (only set for special applications e.g. for by-pass function).
59
Multi-turn actuator SAExC 07.1 – 16.1/SARExC 07.1 – 16.1 Intrusive
with actuator controls AUMATIC ACExC 01.1 Foundation Fieldbus Operation instructions
10.3. Fuses
DANGER Flameproof enclosure, danger of explosion!
Risk of death or serious injury.
Ò Before opening, ensure that there is no explosive gas and no voltage.
Ò Handle cover and housing parts with care.
Ò Joint surfaces must not be damaged or soiled in any way.
Ò Do not jam cover during fitting.
F3 Internal 24 V DC supply
F4
..
Internal 24 V AC supply (115 V AC) for:
Heater, switch compartment, reversing contactors control,
60
Multi-turn actuator SAExC 07.1 – 16.1/SARExC 07.1 – 16.1 Intrusive
Operation instructions with actuator controls AUMATIC ACExC 01.1 Foundation Fieldbus
..
The actuator is switched off and the following signals are given:
LED 3 (thermal fault) on the local controls is illuminated.
The motor has to cool down before the operation can be resumed.
Depending on the parameter setting, the fault signal is either automatically
reset or the fault signal has to be acknowledged.
..
The acknowledgement can either be made:
via the Reset push button in selector switch position LOCAL.
or with the reset command via the fieldbus.
For further information on this topic refer to “Manual (Operation and setting)
AUMATIC AC 01.1/ACExC 01.1 Foundation Fieldbus”.
61
Multi-turn actuator SAExC 07.1 – 16.1/SARExC 07.1 – 16.1 Intrusive
with actuator controls AUMATIC ACExC 01.1 Foundation Fieldbus Operation instructions
Service AUMA offers extensive service such as maintenance and inspection as well
as customer product training. For the relevant contact addresses, please
refer to page 82 et seqq. and on the Internet (www.auma.com).
.
Every 6 months after commissioning
Carry out visual inspection:
– For electrical devices: cable entries, cable glands, screw plugs, etc.
have to be checked for correct tightness and sealing.
..
After submersion:
Check multi-turn actuator.
In case of ingress of water, dry device correctly and check for proper
function.
62
Multi-turn actuator SAExC 07.1 – 16.1/SARExC 07.1 – 16.1 Intrusive
Operation instructions with actuator controls AUMATIC ACExC 01.1 Foundation Fieldbus
If the device must be demounted, e.g. for service purposes, it can be sepa-
rated from the mains without having to remove the wiring.
Figure 36
63
Multi-turn actuator SAExC 07.1 – 16.1/SARExC 07.1 – 16.1 Intrusive
with actuator controls AUMATIC ACExC 01.1 Foundation Fieldbus Operation instructions
11.3. Maintenance
Lubricant change .. In the factory, the gear housing is filled with grease.
Grease change is performed during maintenance:
– Generally after 4 to 6 years for modulating duty.
– Generally after 6 to 8 years if operated frequently (open-close duty).
. – Generally after 10 to 12 years if operated rarely (open-close duty).
No additional lubrication is required during operation.
Notes regarding the maintenance . Check actuator visually. Ensure that no outside damage or changes are
. visible.
The electric connecting cables must be without damage and wired cor-
. rectly.
Do a thorough touch-up of possible damage to paint finish to prevent cor-
. water immediately.
Check the flame path gaps of flameproof enclosures for dirt and corro-
. sion.
Since the dimensions of all flameproof joints are strictly defined and
inspected, no mechanical work (such as grinding) shall be performed on
them. The joint surfaces have to be cleaned chemically (e. g. with
. Esso-Varsol).
Before fitting, the joint surfaces have to be preserved with an acid-free
.. are checked.
All cable and motor protection components have to be checked.
If defects which affect the safety are detected during maintenance, repair
64
Multi-turn actuator SAExC 07.1 – 16.1/SARExC 07.1 – 16.1 Intrusive
Operation instructions with actuator controls AUMATIC ACExC 01.1 Foundation Fieldbus
.. electronic scrap
.. various metals
plastics
greases and oils
. ronment.
Arrange for controlled waste disposal of the disassembled material or for
65
Multi-turn actuator SAExC 07.1 – 16.1/SARExC 07.1 – 16.1 Intrusive
with actuator controls AUMATIC ACExC 01.1 Foundation Fieldbus Operation instructions
66
Multi-turn actuator SAExC 07.1 – 16.1/SARExC 07.1 – 16.1 Intrusive
Operation instructions with actuator controls AUMATIC ACExC 01.1 Foundation Fieldbus
Note:
Please state type and commission no. of the device (see name plate) when ordering spare parts. Only original AUMA
spare parts should be used. Failure to use original spare parts voids the warranty and exempts AUMA from any lia-
bility. Delivered spare parts may slightly vary from the representation.
67
Multi-turn actuator SAExC 07.1 – 16.1/SARExC 07.1 – 16.1 Intrusive
with actuator controls AUMATIC ACExC 01.1 Foundation Fieldbus Operation instructions
12.2. Controls ACExC 01.1 with ex-plug/socket connector with terminal board (KP, KPH)
68
Multi-turn actuator SAExC 07.1 – 16.1/SARExC 07.1 – 16.1 Intrusive
Operation instructions with actuator controls AUMATIC ACExC 01.1 Foundation Fieldbus
Note:
Please state type and commission no. of the device (see name plate) when ordering spare parts. Only original AUMA
spare parts should be used. Failure to use original spare parts voids the warranty and exempts AUMA from any lia-
bility. Delivered spare parts may slightly vary from the representation.
69
Multi-turn actuator SAExC 07.1 – 16.1/SARExC 07.1 – 16.1 Intrusive
with actuator controls AUMATIC ACExC 01.1 Foundation Fieldbus Operation instructions
70
Multi-turn actuator SAExC 07.1 – 16.1/SARExC 07.1 – 16.1 Intrusive
Operation instructions with actuator controls AUMATIC ACExC 01.1 Foundation Fieldbus
Note:
Please state type and commission no. of the device (see name plate) when ordering spare parts. Only original AUMA
spare parts should be used. Failure to use original spare parts voids the warranty and exempts AUMA from any lia-
bility. Delivered spare parts may slightly vary from the representation.
71
Multi-turn actuator SAExC 07.1 – 16.1/SARExC 07.1 – 16.1 Intrusive
with actuator controls AUMATIC ACExC 01.1 Foundation Fieldbus Operation instructions
1) Based on 20 °C ambient temperature and at an average load with running torque or modulating torque according to Technical data SA or SAR
72
Multi-turn actuator SAExC 07.1 – 16.1/SARExC 07.1 – 16.1 Intrusive
Operation instructions with actuator controls AUMATIC ACExC 01.1 Foundation Fieldbus
73
Multi-turn actuator SAExC 07.1 – 16.1/SARExC 07.1 – 16.1 Intrusive
with actuator controls AUMATIC ACExC 01.1 Foundation Fieldbus Operation instructions
Functions Standard:
Switch-off mode adjustable
limit or torque seating for end position OPEN and end position CLOSED
Torque monitoring over the whole travel
Torque by-pass, adjustable up to 5 seconds
(no torque monitoring during running time)
Phase loss monitoring6) with automatic phase correction
Programmable behaviour in case of bus failure
Running indication via indication lights
Positioner7):
Actual position value via Foundation Fieldbus interface
Programmable behaviour on loss of signal
Automatic adaptation of the dead band (adaptive behaviour selectable)
Change-over between OPEN - CLOSE duty and modulating duty
via use of different Foundation Fieldbus function blocks.
Monitoring functions Programmable monitoring of the max. number of starts, generates warning signal
Reaction monitoring for operation command (programmable from 1 to 15 seconds),
generates fault signal and results in switching off
Operating time monitoring (programmable from 4 to 1,800 seconds), generates warning
signal
Electronic name plate Order data: AUMATIC commission number, actuator commission number,
KKS number (definition system for power plants), valve number,
plant number
Product data: Product name, actuator works number, AUMATIC works number,
logic software version, logic hardware version, date of final test,
wiring diagram, terminal plan
Project data: Project name, 2 freely definable customer fields with a max. of 19 digits each
Service data: Service telephone, Internet address, service text 1, service text 2
Logging of operating data A resettable counter and a lifetime counter for:
Motor running time, number of starts, torque switch trippings in end position CLOSED, limit
switch trippings in end position CLOSED, torque switch trippings in end position OPEN, limit
switch trippings in end position OPEN, torque faults CLOSE, torque faults OPEN, motor
protection trippings
Motor protection evaluation Standard: Monitoring of the motor temperature in combination with thermoswitches
in the motor
Options: Additional thermal overload relay in the controls in combination with
thermoswitches within the motor
Electrical connection Standard: Plug/socket connector with screw type connection (KP, KPH)
Protection type: increased safety EEx de
Options: Plug/socket connector with spring cage terminals (KES)
Protection type: increased safety EEx de
Threads for cable entries
Plug/socket connector with spring cage terminals (KES)
Protection type: flameproof enclosure EEx d
Special threads, other than standard mentioned above, possible
Parking frame for wall mounting of the disconnected plug
Protection cover for plug compartment (when plus is removed)
Overvoltage protection (option) Protection of the actuator and control electronics against overvoltages on the fieldbus
cables of up to 4 kV8)
Wiring diagram (basic version) ACP E3FC-2M0—B000 KMS TP202/001
Further options for version with potentiometer or RWG in the actuator
Electronic timer Start and end of stepping mode as well as ON and OFF time (1 up to 300 seconds) can be
programmed individually for the directions OPEN and CLOSE.
Intermediate positions Any 8 intermediate positions between 0 and 100 %
Reaction and signal behaviour programmable
Setting/programming the Foundation Fieldbus interface
Setting the Foundation Fieldbus Address setting is made via Foundation Fieldbus using the provided System Management
address Services and a configuration software for Foundation Fieldbus (e.g. NI-FBUS)
Configurable feedback signals The discrete feedback signals of the three discrete input (DI) function blocks within the
AUMATIC may be configured in accordance with the requirements.
The configuration is made via Foundation Fieldbus using the AUMATIC device description
and a configuration software for Foundation Fieldbus (e.g. NI-FBUS).
Configuration of AUMATIC user Configuration of AUMATIC user functions (e.g. stepping mode, intermediate positions, ...)
functions can be made either via the display or via the Foundation Fieldbus using the AUMATIC
device description and a configuration software for Foundation Fieldbus (e.g. NI-FBUS)
6) During an adjustable period (factory setting 10 seconds) faults in the supply voltage (e.g. voltage drops) will not lead to a fault signal.
7) Requires position transmitter in the actuator
8) Only in combination with standard electrical connection plug/socket connector with screw-type terminals (KP, KPH).
74
Multi-turn actuator SAExC 07.1 – 16.1/SARExC 07.1 – 16.1 Intrusive
Operation instructions with actuator controls AUMATIC ACExC 01.1 Foundation Fieldbus
75
Multi-turn actuator SAExC 07.1 – 16.1/SARExC 07.1 – 16.1 Intrusive
with actuator controls AUMATIC ACExC 01.1 Foundation Fieldbus Operation instructions
11) The enclosure protection according to the name plate applies. For enclosure protection IP 68, higher corrosion protection KS or KX is strongly recommended.
12) With special sizing of the actuator up to max. 70°C possible
13) The lifetime depends on the load and the number of starts. A high starting frequency will rarely improve the modulating accuracy. To reach the longest possible
maintenance and fault-free operating time, the number of starts per hour chosen should be as low as possible for the process.
14) Cable length between actuator and AUMATIC max. 100 m. Requires separate data cable for MWG. If actuator and AUMATIC are separated at a later date, the
max. cable length is 10 m.
76
Multi-turn actuator SAExC 07.1 – 16.1/SARExC 07.1 – 16.1 Intrusive
Operation instructions with actuator controls AUMATIC ACExC 01.1 Foundation Fieldbus
14. Certificates
14.1. Declaration of Conformity and Declaration of Incorporation
77
Multi-turn actuator SAExC 07.1 – 16.1/SARExC 07.1 – 16.1 Intrusive
with actuator controls AUMATIC ACExC 01.1 Foundation Fieldbus Operation instructions
78
Multi-turn actuator SAExC 07.1 – 16.1/SARExC 07.1 – 16.1 Intrusive
Operation instructions with actuator controls AUMATIC ACExC 01.1 Foundation Fieldbus
79
Multi-turn actuator SAExC 07.1 – 16.1/SARExC 07.1 – 16.1 Intrusive
with actuator controls AUMATIC ACExC 01.1 Foundation Fieldbus Operation instructions
80
Multi-turn actuator SAExC 07.1 – 16.1/SARExC 07.1 – 16.1 Intrusive
Operation instructions with actuator controls AUMATIC ACExC 01.1 Foundation Fieldbus
Index
A I R
Accessories for mounting 16 Indications 35 Rated power 10,72
Assembly 12 Indicator disc 51 Reference documents 2
Indicator disk 43 Running indication 37
B
Intermediate positions 46
Bus cables 19 S
Internet 9
Safety instructions 5
C Intrusive 10
Self-retaining mode 30
Cable installation 18 L Service 62
Cable installation in accordance
Language change in the display 33 Short-circuit protection 18
with EMC 18
Limit switching 45 Signals 38
Classification 9
Local controls 17 Size 9
Commission number 8
Long-term storage 11 Spare parts list 66
Commissioning 39
Low temperature version 39 Controls 68,70
Connecting cables 27
Lubricant change 64 Multi-turn actuator 66
Control 9
Status indication 35
Corrective action 53 M
Stem nut 14
Corrosion protection 11 Maintenance intervals 64
Storage 11
Cross sections 21,25 Manual operation 29
Current consumption 18 Mechanical position indicator 51 T
Motor heater 21,25 Technical data 72
D
Motor operation 30 Terminal plan 18
Declaration of Conformity 77
Motor protection 61 Test run 47
Declaration of Incorporation 77
Mounting 13 Thermoswitches 61
Disconnect switches 18
Mounting positions of the local Torque switching setting 44
Disposal and recycling 65
controls 17 Transport 11
DUO limit switching 46
Tripping torque 44
O
E Type 9
Operation 29
Electrical connection 18 V
Output drive type A 14
Electronic position transmitter RWG
Output drive types B1, B2, B3, B4, Valve position 35
50
B, and E 13
W
F Overrun 54
Wall bracket 27
Faults 55 P Warnings 55
Faults during commissioning 53
Packaging 11 Wiring diagram (name plate) 9
Fuses 60
Parking frame 28 Wiring diagram locating 18
Fuses on site 18
Password entry 32
G PE connection 25
Ground connection, external 28 Position indicator 51
Position transmitter RWG 50
H
Potentiometer 49
Handwheel 29 Protection cover 28
Handwheel fitting 12 Protection on site 18
Heater 21,25 Protection tube 16
Heat-up time 39 PTB certificate 78
PTC thermistors 61
Push-to-run operation 30
81
AUMA wordwide
82
AUMA ACTUATORS (Singapore) Pte Ltd. Sunny Valves and Intertrade Corp. Ltd.
SG-569551 Singapore TH-10120 Yannawa Bangkok
Tel +65 6 4818750 Tel +66 2 2400656
Fax +65 6 4818269 Fax +66 2 2401095
sales@auma.com.sg sunnyvalves@inet.co.th
www.auma.com.sg www.sunnyvalves.co.th/
AUMA Actuators Middle East W.L.L. Top Advance Enterprises Ltd.
AE- 15268 Salmabad 704 TW- Jhonghe City Taipei Hsien (235)
Tel +971 17877377 Tel +886 2 2225 1718
Fax +971 17877355 Fax +886 2 8228 1975
Naveen.Shetty@auma.com support@auma-taiwan.com.tw
www.auma-taiwan.com.tw
PERFECT CONTROLS Ltd.
HK- Tsuen Wan, Kowloon
Tel +852 2493 7726
Australia
Fax +852 2416 3763 BARRON GJM Pty. Ltd.
joeip@perfectcontrols.com.hk AU-NSW 1570 Artarmon
Tel +61 294361088
DW Controls Co., Ltd. Fax +61 294393413
KR-153-803 Seoul Korea info@barron.com.au
Tel +82 2 2113 1100 www.barron.com.au
Fax +82 2 2113 1088/1089
sichoi@actuatorbank.com
www.actuatorbank.com
2009-10-19
83