Dse 9130

You might also like

Download as pdf or txt
Download as pdf or txt
You are on page 1of 69

®

DSE

DSE9130, DSE9150, ENVIRONMENTAL TESTING STANDARDS

DSE9155 & DSE9255


ELECTRO-MAGNETIC COMPATIBILITY
BS EN 61000-6-2
EMC Generic Immunity Standard for
the Industrial Environment

COMPACT BATTERY CHARGERS


BS EN 61000-6-4
EMC Generic Emission Standard for
the Industrial Environment
2 AMP, 3 AMP & 5 AMP OPTIONS
TEMPERATURE
BS EN 60068-2-1
Ab/Ae Cold Test -30 oC
FEATURES BS EN 60068-2-2
Bb/Be Dry Heat +55 oC

VIBRATION
BS EN 60068-2-6
The 2 Amp, 3 Amp and 5 Amp The chargers will continue to Ten sweeps in each of three
Battery Chargers have been operate during cranking and major axes
5 Hz to 8 Hz @ +/-7.5 mm,
designed to be permanently running. All chargers can accept 8 Hz to 500 Hz @ 2 gn
connected to a battery, keeping it multiple AC voltage connections.
charged to maximum capacity. HUMIDITY
BS EN 60068-2-30
The DSE battery chargers are Db Damp Heat Cyclic 20/55 oC
The chargers can be either expertly designed using high-grade @ 95% RH 48 Hours
mounted via DIN rail or to the components and capacitors BS EN 60068-2-78
Cab Damp Heat Static 40 oC
chassis, using the fixing holes that allowing the units to function more @ 93% RH 48 Hours
are built into the case. The chargers efficiently, providing a longer and
SHOCK
stylish design includes an LED more reliable life-span than other BS EN 60068-2-27
indicator on the front that shows chargers in their class. Their in- Three shocks in each of three major axes
when the charger is in a normal or built robustness makes them ideal 15 gn in 11 mS
overload condition. for the rigours of a wide variety of
markets including heavy and light
industrial environments.

FEATURE LIST TO SUIT A WIDE VARIETY


OF APPLICATIONS

1ph
N

CHARGE OUTPUT AC POWER SUPPLY

COMPATIBLE WITH ALL DSE MODULES

DSE9000

CHARGE BOOST INPUT N/C VOLT FREE CHARGE FAIL OUTPUT


(Not available for DSE9150 & DSE9155) (Not available for DSE9150)

1 1

ISSUE 5
®

DSE

DSE9130, DSE9150, SPECIFICATION

DSE9155 & DSE9255


AC SUPPLY
FREQUENCY RANGE
48 Hz to 64 Hz

DSE9130 & DSE9255 VOLTAGE RANGE


COMPACT BATTERY CHARGERS 90 V to 305 V (L-N)

2 AMP, 3 AMP & 5 AMP OPTIONS DSE9150 VOLTAGE RANGE


90 V to 265 V (L-N)

DSE9155 VOLTAGE RANGE


85 V to 265 V (L-N)

FEATURES DC OUTPUT
DSE9130 OUTPUT
5 A DC 12 V DC at 13.7 V DC

DSE9150 OUTPUT
3 A DC 12 V DC at 13.7 V DC

DSE9155 OUTPUT
2 A DC 30 V DC at 34.3 V DC

DSE9255 OUTPUT
5 A DC 24 V DC at 27.4 V DV

RIPPLE AND NOISE


DSE9150 - 3 A 12 V <1%

EFFICIENCY
>80%

REGULATION
LINE
<0.001% Vo

LOAD
1% Vo

PROTECTIONS
Short Circuit
Over Voltage
Over Current
Reverse Polarity
DSE9130 - 5 A 12 V
DSE9155 - 2 A 30 V DIMENSIONS
DSE9255 - 5 A 24 V DSE9150 DIMENSIONS
108 mm x 101 mm x 49 mm
4.2” x 4” x 1.9”

WEIGHT
ADVANCED FEATURES KEY BENEFITS 0.16 kg
• Suitable for a wide range of
battery types DSE9130, DSE9155 & DSE9255
• Constant current- maximum • Boosts and equalises cell DIMENSIONS
current available during charge charge improving battery • No moving parts for longer 136 mm x 140 mm x 63 mm
recovery phase performance and life battery charger life 5.4” x 5.5” x 2.5”
• Constant voltage • Simple boost connection using • Switched mode design
WEIGHT
• Chargers automatically return to on-board terminals • Charge fail output 0.5 kg
float mode when charging is • Minimum 80% efficiency
throughout full operating range OPERATING TEMPERATURE RANGE
complete • Once the battery is fully -30 °C to +55 °C
-22 °F to +122 °F
charged the chargers switch to
• Makes the chargers ideal for all Eco-Power to save energy • Multiple modules can be linked STORAGE TEMPERATURE RANGE
battery types together to provide larger current -40 oC to +85 oC
output -40 °F to +185 °F

• Reverse polarity protection,


short circuit protection and
current limiting
• Automatic recovery after the
removal of fault conditions

RELATED MATERIALS
TITLE PART NO’S
DSE9000 Series Installation Instructions 053-049
DSE9000 Series Operator Manual 057-085

DEEP SEA ELECTRONICS PLC UK DEEP SEA ELECTRONICS INC USA


Highfield House, Hunmanby Industrial Estate, Hunmanby YO14 0PH 3230 Williams Avenue, Rockford, IL 61101-2668 USA
TELEPHONE +44 (0) 1723 890099 FACSIMILE +44 (0) 1723 893303 TELEPHONE +1 (815) 316 8706 FACSIMILE +1 (815) 316 8708
EMAIL sales@deepseaplc.com WEBSITE www.deepseaplc.com EMAIL sales@deepseausa.com WEBSITE www.deepseausa.com

Deep Sea Electronics Plc maintains a policy of continuous development and reserves the right to change Registered in England & Wales No.01319649 055-059/10/10 (7)
the details shown on this data sheet without prior notice. The contents are intended for guidance only. VAT No.316923457
DEEP SEA ELECTRONICS PLC
DSE9000 SERIES BATTERY CHARGER
OPERATOR MANUAL
Document Number: 057-085
Author: Ashley Senior

DSE9000 Series Battery Charger Operator Manual ISSUE 13


DSE9000 Series Battery Charger Operator Manual

Deep Sea Electronics Plc


Highfield House
Hunmanby
North Yorkshire
YO14 0PH
ENGLAND

Sales Tel: +44 (0) 1723 890099


Sales Fax: +44 (0) 1723 893303

E-mail: sales@deepseaplc.com
Website: www.deepseaplc.com

DSE9000 Series Battery Charger Operator Manual

© Deep Sea Electronics Plc


All rights reserved. No part of this publication may be reproduced in any material form (including
photocopying or storing in any medium by electronic means or other) without the written permission of
the copyright holder except in accordance with the provisions of the Copyright, Designs and Patents
Act 1988.
Applications for the copyright holder’s written permission to reproduce any part of this publication
should be addressed to Deep Sea Electronics Plc at the address above.

Any reference to trademarked product names used within this publication is owned by their respective
companies.

Deep Sea Electronics Plc reserves the right to change the contents of this document without prior
notice.

Amendments since last publication


Issue. No. Comments
1 Added Efficiency curve of 2A charger
2 Updated specs table of 3.7A charger
3 Added 5A DSE9255 charger and 9250-002 277V input charger
7 Added DSE9155 30V 2A charger
8 Added 10A charger
8.1 Added Indication (LED) for 10A chargers
8.2 Added detail regarding -002- chargers asnd cabinet/industrial chargers
9 Added 9400 series
9.1 Corrected specs for 9140
10 Removed all DSE9400 series chargers, added DSE9470
11 Added new DSE9400 series Chargers
12 Changes to add DSE9150 12V 3A
Updated DSE9470 and DSE9480 to -003 (MKII) and added DSE9472MKII and
13
DSE9481 MKII

Typeface : The typeface used in this document is Arial. Care should be taken not to mistake the upper
case letter I with the numeral 1. The numeral 1 has a top serif to avoid this confusion.

2
DSE9000 Series Battery Charger Operator Manual

1 BIBLIOGRAPHY .................................................................................................. 5
1.1 INSTALLATION INSTRUCTIONS ....................................................................................... 5
1.2 MANUALS .......................................................................................................................... 5
3 SPECIFICATIONS ............................................................................................... 7
3.1 PART NUMBERING............................................................................................................ 7
3.1.1 DSE9100 CHASSIS MOUNT BATTERY CHARGERS .................................................. 7
3.1.2 DSE9200 CHASSIS MOUNT BATTERY CHARGERS .................................................. 8
3.1.3 DSE9400 MKII SERIES CHASSIS MOUNT BATTERY CHARGERS ............................ 9
3.1.4 DSE907 INDUSTRIAL / DSE908 CABINET MOUNTED BATTERY CHARGERS ........ 10
3.2 COMMON ELECTRICAL SPECIFICATIONS .................................................................... 11
3.3 COMMUNICATION PORT USAGE .................................................................................. 12
3.3.1 USB CONNECTION ................................................................................................... 12
3.3.2 RS485 ........................................................................................................................ 13
3.5 OUTPUT SPECIFICATIONS ............................................................................................. 15
3.5.1 DSE9130 12V 5A ....................................................................................................... 15
3.5.2 DSE9140 12V 10A ..................................................................................................... 16
3.5.3 DSE9150 12V 2A ....................................................................................................... 17
3.5.4 DSE9150 12V 3A ....................................................................................................... 18
3.5.5 DSE9155 30V 2A ....................................................................................................... 19
3.5.6 DSE9250 24V 3.7A .................................................................................................... 20
3.5.7 DSE9255 24V 5A ....................................................................................................... 21
3.5.8 DSE9260 24V 10A ..................................................................................................... 22
3.5.9 DSE9470 (MKII) 24V/12V 10A .................................................................................... 23
3.5.10 DSE9472 (MKII) 24V/12V 5A ...................................................................................... 25
3.5.11 DSE9480 (MKII) 12V 10A ........................................................................................... 26
3.5.12 DSE9481 (MKII) 12V 5A ............................................................................................. 28
3.6 DIMENSIONS AND MOUNTING ....................................................................................... 29
3.6.1 DSE907 12V 10A INDUSTRIAL BATTERY CHARGER .............................................. 29
3.6.2 DSE908 12V & 24V 10A CABINET MOUNTED BATTERY CHARGER ....................... 30
3.6.3 DSE9130 12V 5A ....................................................................................................... 31
3.6.4 DSE9150 12V 2A ....................................................................................................... 32
3.6.5 DSE9150 12V 3A ....................................................................................................... 33
3.6.6 DSE9140 12V 10A ..................................................................................................... 34
3.6.7 DSE9155 30V 2A ....................................................................................................... 35
3.6.8 DSE9250 24V 3.7A .................................................................................................... 36
3.6.9 DSE9255 24V 5A ....................................................................................................... 37
3.6.10 DSE9260 24V 10A ..................................................................................................... 38
3.6.11 DSE9470 (MKII) 24V/12V 10A .................................................................................... 39
3.6.12 DSE9472 (MKII) 24V/12V 5A ...................................................................................... 40
3.6.13 DSE9480 (MKII) 12V/24V 10A .................................................................................... 41
3.6.14 DSE9481 (MKII) 12V/24V 5A ...................................................................................... 42
3.7 APPLICABLE STANDARDS............................................................................................. 43
4 INSTALLATION ................................................................................................. 44
4.1 BATTERY SUITABILITY................................................................................................... 44
4.2 USER CONNECTIONS ..................................................................................................... 44
4.2.1 DSE9130, DSE9140, DSE9250, DSE9255 & DSE9260 .............................................. 45
4.2.2 DSE9150 .................................................................................................................... 45
4.2.3 DSE9155 .................................................................................................................... 46
4.2.4 DSE9470 MKII, DSE9472 MKII, DSE9480 MKII, DSE9481 MKII .............................. 47
4.3 TYPICAL WIRING DIAGRAM ........................................................................................... 49
4.3.1 DSE9150 .................................................................................................................... 49
4.3.2 DSE9155 & DSE9200 SERIES ................................................................................... 50
4.3.3 DSE9470 MKII, DSE9472 MKII, DSE9480 MKII, DSE9481 MKII ............................... 51
5 INDICATIONS .................................................................................................... 52
5.1 DSE907............................................................................................................................. 52
5.2 DSE908............................................................................................................................. 52
5.3 DSE9130, DSE9150, DSE9155, DSE9250 & DSE9255 ..................................................... 53
5.4 DSE9140 & DSE9260 ....................................................................................................... 54

3
DSE9000 Series Battery Charger Operator Manual

5.5 DSE9470 MKII, DSE9472 MKII, DSE9480 MKII, DSE9481 MKII ....................................... 55
5.5.1 STATUS ..................................................................................................................... 55
5.5.2 CHARGE MODE ........................................................................................................ 55
5.5.3 FAULT CONDITIONS ................................................................................................. 55
6 OPERATION ...................................................................................................... 56
6.1 OPERATION OF DSE9100 SERIES / DSE9200 SERIES .................................................. 56
6.1.1 PROTECTION ............................................................................................................ 56
6.1.2 PSU MODE ................................................................................................................ 56
6.1.3 CHARGE MODE ........................................................................................................ 56
6.1.4 BOOST MODE ........................................................................................................... 57
6.2 OPERATION OF DSE9400 MKII SERIES ......................................................................... 58
6.2.1 PROTECTION ............................................................................................................ 58
6.2.2 DIGITAL INPUT.......................................................................................................... 59
6.2.3 VOLTAGE ADJUSTMENT POTENTIOMETER ........................................................... 59
6.2.4 PSU MODE ................................................................................................................ 59
6.2.5 CHARGE MODE ........................................................................................................ 60
6.2.6 TEMPERATURE COMPENSATION ........................................................................... 61
7 FAULT DIAGNOSIS ........................................................................................... 62
8 MAINTENANCE, SPARES, REPAIR AND SERVICING ................................... 63
9 WARRANTY ...................................................................................................... 63
10 DISPOSAL ...................................................................................................... 63
10.1 WEEE (WASTE ELECTRICAL AND ELECTRONIC EQUIPMENT) ............................... 63
10.2 ROHS (RESTRICTION OF HAZARDOUS SUBSTANCES) ........................................... 63

4
Bibliography

1 BIBLIOGRAPHY
This document refers to and is referred to by the following DSE publications which can be obtained
from the DSE website www.deepseaplc.com

1.1 INSTALLATION INSTRUCTIONS


Installation instructions are supplied with the product in the box and are intended as a ‘quick start’
guide only.

DSE PART DESCRIPTION


053-049 DSE9200 / DSE9400 Series Battery Charger Installation Instructions
053-123 DSE9150 Battery Charger Installation Instructions

1.2 MANUALS
DSE PART DESCRIPTION
057-159 DSE9400 Series Battery Charger Configuration Suite Manual

5
Introduction

2 INTRODUCTION

NOTE: This document DOES NOT contain details of the ‘obsolete’ DSE9210 and DSE9240
battery chargers. For further details of these units, please contact Deep Sea Electronics.

This document details the installation requirements of the DSE9000 series range of battery chargers.
The manual forms part of the product and should be kept for the entire life of the product. If the
product is passed or supplied to another party, ensure that this document is passed to them for
reference purposes.
This is not a controlled document. You will not be automatically informed of updates. Any future
updates of this document will be added to the DSE website at www.deepseaplc.com.

The DSE9000 series modules are intended for mounting within a customer enclosure or panel (DIN
rail mounting or fastened by screws/bolts).

DSE also supply some of the battery chargers as completed units, factory mounted into enclosures for
wall or floor mounting.

The DSE9000 series chargers fulfill the most common functions required of a charger in the
generating set industry. Combining protected outputs, intelligent charging and power supply operation
with a robust enclosure.

6
Specifications

3 SPECIFICATIONS
3.1 PART NUMBERING
3.1.1 DSE9100 CHASSIS MOUNT BATTERY CHARGERS

9130 - 001 - 00

Variant
Product type
For lead acid batteries
12V charger set to 13.7V
00
DSE9130 12V 5A 9130 24V charger set to 27.4V

DSE9140 12V 10A 9140 For 9 or 18 cell NICAD batteries*


12V charger set to 13.0V
01
24V charger set to 26.0V
DSE9150 12V 2A 9150
For 10 or 20 cell NICAD batteries*
12V charger set to 14.5V
02
DSE9150 12V 3A 9150 24V charger set to 29.0V

DSE9155 30V 2A For other battery types*


9155 Specify required float voltage on ordering**
03

Hardware revisions

First version hardware 001

NOTE: For descriptions of other Hardware Revisions, please contact


support@deepseaplc.com

NOTE: The DSE9150 12V 2A is now obsolete, replaced with DSE9150 12V 3A.

NOTE: The DSE9150 12V 3A only available in Variant -00 (13.7V for lead acid batteries)

NOTE: For variant 03 (For other battery types), the float voltage can be adjusted between
12.5V and 15V for DSE9130 12V 5A chargers (25V - 30V for DSE9250 24V 3.7A chargers). This
change must be made at the DSE factory. Ensure the correct variant (and float voltage if
applicable) is specified on ordering. Consult your battery manufacturer for further details of
required float voltage.

7
Specifications

3.1.2 DSE9200 CHASSIS MOUNT BATTERY CHARGERS

9130 - 001 - 00

Variant
Product type
For lead acid batteries
12V charger set to 13.7V
00
DSE9250 24V 3.7A 9250 24V charger set to 27.4V

DSE9255 24V 5A For 9 or 18 cell NICAD batteries*


9255 12V charger set to 13.0V
01
24V charger set to 26.0V
DSE9260 24V 10A 9260
For 10 or 20 cell NICAD batteries*
12V charger set to 14.5V
02
24V charger set to 29.0V

For other battery types*


Specify required float voltage on ordering**
03

Hardware revisions

First version hardware 001

NOTE: For descriptions of other Hardware Revisions, please contact


support@deepseaplc.com

NOTE: - The DSE9250 battery charger is now obsolete, details provided for information
only.

NOTE: For variant 03 (For other battery types), the float voltage can be adjusted between
12.5V and 15V for DSE9130 12V 5A chargers (25V - 30V for DSE9250 24V 3.7A chargers). This
change must be made at the DSE factory. Ensure the correct variant (and float voltage if
applicable) is specified on ordering. Consult your battery manufacturer for further details of
required float voltage.

8
Specifications

3.1.3 DSE9400 MKII SERIES CHASSIS MOUNT BATTERY CHARGERS

9470 - 001 - 00

Variant
Product type
Standard
00
DSE9470 12/24V 10A 9470

DSE9472 24V/12V 5A 9472


Hardware revisions
DSE9480 24V/12V 10A 9480

DSE9481 24V/12V 5A 9481 First version hardware 001

NOTE: For descriptions of other Hardware Revisions, please contact


support@deepseaplc.com

NOTE: For hardware versions 003 and above, voltage and current levels can be user
configured via DSE Configuration Suite PC Software.
Part number 9470-001-00 is fixed at 24V 10A.
Part number 9480-001-00 is fixed at 12V 10A.

NOTE: DSE9400 series battery chargers are customer configurable via the DSE
Configuration Suite PC Software.
For further details, you are referred to DSE Publication: 057-159 DSE9400 Series Battery
Charger Configuration Suite Manual.

9
Specifications

3.1.4 DSE907 INDUSTRIAL / DSE908 CABINET MOUNTED BATTERY CHARGERS

NOTE: The DSE907 / DSE908 Industrial / Cabinet Mounted Battery Chargers are now
obsolete, replaced by DSE9460 / DSE9461 Enclosed Battery Chargers.

See the preceeding page for details of part numbering of chassis mounted battery chargers.

Industrial / Cabinet mounted battery chargers are 9000 series battery chargers factory fitted into wall
mounted enclosures. For details see the section entitled Dimensions and Mounting elsewhere in
this document.
0907-002-02 INDUSTRIAL BATTERY CHARGER 12V 5A 220-250V

0908-001-11 CABINET MOUNTED BATTERY CHARGER 12V 10A

0908-001-21 CABINET MOUNTED BATTERY CHARGER 24V 10A

0907 - 001 - 00

Variant

Product type Hardware revisions

When ordering Industrial / Cabinet mounted battery chargers, ensure you specify the type of batteries
that are to be charged. If you do not specify this, the chargers will be preset to charge Lead Acid type
batteries.

10
Specifications

3.2 COMMON ELECTRICAL SPECIFICATIONS


Parameter Min Nominal Max
AC Input Voltage (V)
DSE9130 12V 5A 90V 110V-277V 304V
DSE9150 12V 2A 90V 110V-240V 250V
DSE9150 12V 3A 90V 110V-240V 265V
DSE9140 12V 10A 90V 110V-240V 277V
DSE9155 30V 2A 85V 110V-240V 265V
DSE9250 24V 3.7A (9250-001-xx) 90V 110V-240V 265V
DSE9250 24V 3.7A (9250-002-xx) 90V 110V-277V 305V
DSE9255 24V 5A 90V 110V-277V 305V
DSE9260 24V 10A 90V 110V-277V 305V
DSE9470 24V/12V 10A 95V 110V-277V 305V
DSE9472 24V 5A 95V 110V-277V 305V
DSE9480 12V/24V 10A 95V 110V-277V 305V
DSE9481 12V 5A 95V 110V-277V 305V
DSE9100 Series -30°C 55°C
Operating
DSE9200 Series -30°C 55°C
Temperature
DSE9400 Series -30°C 85°C with de-ratings
Input Frequency (Hz) 48Hz 64Hz
DSE9100 Series 1% Vo
Output Ripple and
DSE9200 Series 2% Vo
Noise
DSE9400 Series 1% Vo
DSE9100 Series 1% Vo
Load Regulation DSE9200 Series 2% Vo
DSE9400 Series 1% Vo
Line Regulation <0.01% Vo
Output Voltage Overshoot % <5%Vo
Transient Response Peak Deviation (mV)
<4% Vo
(at 50% to 100% load step)
Warm Up Voltage (V) <1% Vo
DSE9100 Series <100ms
Output Voltage
DSE9200 Series <100ms
Rise Time (ms)
DSE9400 Series <200ms
Short Circuit Protection Hiccup
Switching Frequency (kHz)
9130-001-xx (replaced with 9130-002-xx) 100kHz
9250-001-xx (replaced with 9250-002-xx) 100kHz

9130-002-xx 67kHz
9250-002-xx 67kHz
94xx-xxx-xx 67kHz

All other chargers 100kHz


Efficiency % DSE9100 Series
>80%
(See section entitled DSE9200 Series
‘output specifications’
elsewhere in this DSE9400 Series >85%
manual)
Temperature Sensor
DSE9400 Series PT1000
Input

NOTE: Check the DSE9400 Series de-rating curves which can be found else where in this
manual for more information.

11
Specifications

3.3 COMMUNICATION PORT USAGE

Communication Specification
USB Port
USB2.0 Device for connection to PC running DSE Configuration Suite
(DSE9400 series
Max distance 6m (20 feet)
only)
Isolated
Data connection 2 wire + common
RS485 Serial Half Duplex
Port Data direction control for Transmit (by s/w protocol)
(DSE9400 series Max Baud Rate 19200
only) External termination required (120Ω)
Max common mode offset 70V (on board protection transorb)
Max distance 1.2km (¾ mile)

3.3.1 USB CONNECTION

The USB port is provided to give a simple means of connection between a PC and the DSE9400
series battery charger. Using the DSE Configuration Suite Software, the operator is then configure
and monitor the state of the battery charger.

To connect a DSE9400 series battery charger to a PC by USB, the following items are required:

• DSE9400 series battery charger

• DSE Configuration Suite Software


(Supplied on configuration suite software CD or available from
www.deepseaplc.com).

• USB cable Type A to Type B.


(This is the same cable as often used between a PC and a USB
printer)

DSE can supply this cable if required :


PC Configuration interface lead (USB type A – type B) DSE Part
No 016-125

NOTE: - Refer to DSE9400 Series Battery Charger PC Software Configuration Manual for
further details on configuring and monitoring.

12
Specifications

3.3.2 RS485

The RS485 port on the DSE9400 series battery chargers has two uses.
1) Supporting the DSE2541 remote battery charger display module (MKII only)
2) Support the Modbus RTU protocol for connection to a Modbus RTU Master device.

3.3.2.1 DSE2541 REMOTE BATTERY CHARGER DISPLAY MODULE

DSE2541 remote battery charger display modules


connects to the DSE9400 MKII Series battery
charger RS485 terminals.
This provides battery charger operating status, alarm
indication, instrumentation and control over the
DSE9400 MKII Series battery charger.

For further information please contact


sales@deepseaplc.com.

3.3.2.2 MODBUS RTU

RS485 is used for point-to-point cable connection of more than one device (maximum 32 devices)
and allows for connection to PCs, PLCs and Building Management Systems (to name just a few
devices).

Using the DSE Configuration Suite PC Software, Configurable Gencomm is used to map
instrumentation to modbus registers.

One advantage of the RS485 interface is the large distance specification (1.2km) when using Belden
9841 (or equivalent) cable. This allows for a large distance between the DSE9400 series battery
charger and a PC running the DSE Configuration Suite software. The operator is then able to view the
various operating parameters.

NOTE: - For distances up to 6m (8yds) the USB connection method is more suitable and
provides for a lower cost alternative to RS485 (which is more suited to longer distance
connections).

13
Specifications

3.3.2.3 OPTIONS FOR CONNECTION TO PCS

• Brainboxes PM154 PCMCIA RS485 card (for laptops PCs)


Set to ‘Half Duplex, Autogating” with ‘CTS True’ set to ‘enabled’

• Brainboxes VX-023 ExpressCard 1 Port RS422/485 (for laptops and


nettop PCs)

• Brainboxes UC320 PCI Velocity RS485 card (for desktop PCs)


Set to ‘Half Duplex, Autogating” with ‘CTS True’ set to ‘enabled’

• Brainboxes PX-324 PCI Express 1 Port RS422/485 (for desktop PCs)

Supplier:
Brainboxes
Tel: +44 (0)151 220 2500
Web: http://www.brainboxes.com
Email: Sales: sales@brainboxes.com

14
Specifications

3.5 OUTPUT SPECIFICATIONS


3.5.1 DSE9130 12V 5A

Parameter Min Nominal Max Comments


Output Voltage (12 V DC battery) 12.5V 13.7V 15.0V Specify float voltage on ordering.
Output Charging Current (A) 0A 5A 5.5A
Current limit threshold (A) 5A 5.3A 5.5A
Recovery from current limit (A) 5A
Full load AC input current (A) 1.5A With output at 13.7V DC
AC Input Inrush (10ms) current (A) 20A

DSE9130 Efficiency Curve at 5A


0.92

0.9

0.88
Efficiency (%)

0.86

0.84

0.82

0.8
85 110 230 260
Input Voltage (V)

15
Specifications

3.5.2 DSE9140 12V 10A

Parameter Min Nominal Max Comments


Output Voltage (12 V DC Battery) 12V 13.7V 15V
Output Charging Current (A) 10A 10A 11A
Current limit threshold (A) 10A 11A
Recovery from current limit (A) 10A 11A
Full load AC input current (A) 3.1A At Vin=85V, Vo=13.7V, Io=10Amp
Full load AC input current (A) 1.3A At Vin=230V, Vo=13.7V Io=10Amp
AC Input Inrush (10ms) current (A) 60A

DSE9140 Efficiency Curve at 10A


0.87
0.86
0.85
0.84
Efficiency (%)

0.83
0.82
0.81
0.8
0.79
0.78
85 110 230 260
Input Voltage (V)

16
Specifications

3.5.3 DSE9150 12V 2A

NOTE: This device is no longer available, replaced by DSE9150 12V 3A. See overleaf for
updated specifications.

Parameter Min Nominal Max Comments


Output Voltage (12 V DC Battery) 12.5V 13.7V 13.7V Float voltage not adjustable
Output Charging Current (A) 0A 2A 2.5A
Current limit threshold (A) 2A 2.3A 2.5A
Recovery from current limit (A) 2A
Full load AC input current (A) 0.7A With output at 13.7V DC
AC Input Inrush (10ms) current (A) 10A

DSE9150 Efficiency Curve at 2A


90

88

86
Efficiency (%)

84

82

80

78

76

74
85 110 230 250
Input Voltage (V)

17
Specifications

3.5.4 DSE9150 12V 3A

NOTE: This device has replaced DSE9150 12V 2A. See previous page for specifications of
the earlier model.

Parameter Min Nominal Max Comments


Output Voltage (12 V DC Battery) 12.5V 13.7V 13.7V Float voltage not adjustable
Output Charging Current (A) 0A 3A 3.5A
Current limit threshold (A) 3A 3.2A 3.5A
Recovery from current limit (A) 3A
Full load AC input current (A) 0.7A With output at 13.7V DC
AC Input Inrush (10ms) current (A) 10A

DSE9153 Efficiency Curve at 3A

0.87
0.86
Efficiency (%)

0.85
0.84
0.83
0.82
0.81
0.80
0.79
110 230 265

Input Voltage (V)

18
Specifications

3.5.5 DSE9155 30V 2A

Parameter Min Nominal Max Comments


Output Voltage (30 V DC Battery) 28.0V 34.3V 34.5
Output Charging Current (A) 0A 2.2A 3A
Current limit threshold (A) 2A 2.2A 3A
Recovery from current limit (A) 2A
Full load AC input current (A) 2A
AC Input Inrush (10ms) current (A) 30A

DSE9155 Efficiency Curve at 2A


0.94

0.92

0.9
Efficiency (%)

0.88

0.86

0.84

0.82

0.8

0.78
85 110 230 260
Input Voltage (V)

19
Specifications

3.5.6 DSE9250 24V 3.7A

NOTE: - This battery charger is now obsolete, details provided for information only.

Parameter Min Nominal Max Comments


Output Voltage (24 V DC Battery) 25.0V 27.4V 30.0V Specify float voltage on ordering.
Output Charging Current (A) 0A 3.7A 4A
Current limit threshold (A) 3.6A 3.75A 4A
Recovery from current limit (A) 3.6A
Full load AC input current (A) 2A With output at 27.6V DC
AC Input Inrush (10ms) current (A) 30A

DSE9250 Efficiency Curve at 3.7A


0.92

0.9

0.88
Efficiency (%)

0.86

0.84

0.82

0.8
85 110 230 260
Input Voltage (V)

20
Specifications

3.5.7 DSE9255 24V 5A

Parameter Min Nominal Max Comments


Output Voltage (24 V DC Battery) 25.0V 27.4V 30.0V Specify float voltage on ordering.
Output Charging Current (A) 0A 5A
Current limit threshold (A) 5A 5.3A 6A
Recovery from current limit (A) 5A 5.2A
Full load AC input current (A) 0.65A 2.7A With output at 27.6V DC
AC Input Inrush (10ms) current (A) 30A

DSE9255 Efficiency Curve at 5A


0.94

0.92

0.9
Efficiency (%)

0.88

0.86

0.84

0.82

0.8
85 110 230 260
Input Voltage (V)

21
Specifications

3.5.8 DSE9260 24V 10A

Parameter Min Nominal Max Comments


Output Voltage (12V DC Battery) 26V 27.6V 29V
Output Charging Current (A) 10A 11A
Current limit threshold (A) 10A 11A
Recovery from current limit (A) 9.5A 10A 11A
Full load AC input current (A) 2.2A At Vin=230V, Vo=27.6V, Io=10Amp
Full load AC input current (A) 5.8A At Vin=85V, Vo=27.6V, Io=10Amp
AC Input Inrush (10ms) current (A) 60A For 10ms

DSE9260 Efficiency Curve at 10A


0.94

0.92

0.9
Efficiency (%)

0.88

0.86

0.84

0.82

0.8

0.78
85 110 230 265
Input Voltage (V)

22
Specifications

3.5.9 DSE9470 (MKII) 24V/12V 10A

NOTE: DSE9470 is factory configured to 24V 10A. If required, voltage and current levels
can be user configured via DSE Configuration Suite PC Software.
Part number 9470-001-00 is fixed at 24V 10A.

Parameter Min Nominal Max Comments


Output Voltage (24V DC Battery) 26.7V 27V 29V
Output Charging Current (A) 2A 10A 11A
Current limit threshold (A) 10A 11A
Recovery from current limit (A) 10A 11A
Full load AC input current (A) 2.3A At Vin=230V, Vo=28.8V, Io=10Amp
Full load AC input current (A) 4A At Vin=110V, Vo=28.8V, Io=10Amp
AC Input Inrush (10ms) current (A) 60A For 10ms

DSE9470 Efficiency Curve at 10A


0.925
0.92
0.915
Efficiency (%)

0.91
0.905
0.9
0.895
0.89
0.885
110 230 277
Input Voltage (V)

DSE9470 Smart Charger De-rating Curve


110V < Vin < 305V
12

10
Output Current (A)

0
-30 -20 -10 0 10 20 30 40 50 55 60 65 70 75 80 85
Ambient Temperature ºC

23
Specifications

DSE9470 Smart Charger De-rating Curve


95V < Vin < 110V

6.0

5.0
Output Current (A)

4.0

3.0

2.0

1.0

0.0
-30 -20 -10 0 10 20 30 40 50 60 70 80 90 100

Ambient Temperature (ºC)

24
Specifications

3.5.10 DSE9472 (MKII) 24V/12V 5A

Parameter Min Nominal Max Comments


Output Voltage (24V DC Battery) 26.7V 27V 29V
Output Charging Current (A) 2A 5A 5.5A
Current limit threshold (A) 5A 5.5A
Recovery from current limit (A) 5A 5.5A
Full load AC input current (A) 1.2A At Vin=230V, Vo=28.8V, Io=5Amp
Full load AC input current (A) 2.2A At Vin=110V, Vo=28.8V, Io=5Amp
AC Input Inrush (10ms) current (A) 60A For 10ms

DSE9472 Efficiency Curve at 5A


93%

92%

92%
Efficiency (%)

91%

91%

90%

90%

89%
110 230 277
Input Voltage (V)

DSE9472 Smart Charger De-rating Curve


90V < Vin < 305V
6

5
Output Current (A)

0
-30 -20 -10 0 10 20 30 40 50 55 60 65 70 75 80

Ambient Temperature (°°C)

25
Specifications

3.5.11 DSE9480 (MKII) 12V 10A

NOTE: DSE9480 is factory configured to 12V 10A. If required, voltage and currentl levels
can be user configured via DSE Configuration Suite PC Software.
Part number 9480-001-00 is fixed at 12V 10A.

Parameter Min Nominal Max Comments


Output Voltage (24V DC Battery) 13.4V 13.5V 14.5V
Output Charging Current (A) 2A 10A 11A
Current limit threshold (A) 10A 11A
Recovery from current limit (A) 10A 11A
Full load AC input current (A) 1.2A At Vin=230V, Vo=14.4V, Io=10Amp
Full load AC input current (A) 2.2A At Vin=110V, Vo=14.4V, Io=10Amp
AC Input Inrush (10ms) current (A) 60A For 10ms

DSE9480 Efficiency Curve at 10A


92%
91%
91%
90%
90%
Efficiency (%)

89%
89%
88%
88%
87%
87%
110 230 277
Input Voltage (V)

DSE9480 Smart Charger De-rating Curve


110V < Vin < 305V
12

10
Output Current (A)

0
-30 -20 -10 0 10 20 30 40 50 55 60 65 70 75 80 85
Ambient Temperature ºC

26
Specifications

DSE9470 Smart Charger De-rating Curve


95V < Vin < 110V

6.0

5.0
Output Current (A)

4.0

3.0

2.0

1.0

0.0
-30 -20 -10 0 10 20 30 40 50 60 70 80 90 100

Ambient Temperature (ºC)

27
Specifications

3.5.12 DSE9481 (MKII) 12V 5A

Parameter Min Nominal Max Comments


Output Voltage (24V DC Battery) 13.4V 13.5V 14.5V
Output Charging Current (A) 2A 5A 5.5A
Current limit threshold (A) 5A 5.5A
Recovery from current limit (A) 5A
Full load AC input current (A) 0.5A At Vin=230V, Vo=14.4V, Io=5Amp
Full load AC input current (A) 1.1A At Vin=110V, Vo=14.4V, Io=5Amp
AC Input Inrush (10ms) current (A) 60A For 10ms

DSE9481 Efficiency Curve at 5A


93%

92%

92%
Efficiency (%)

91%

91%

90%

90%

89%

89%
110 230 277
Input Voltage (V)

DSE9481 Smart Charger De-rating Curve


90V < Vin < 305V
6

5
Output Current (A)

0
-30 -20 -10 0 10 20 30 40 50 55 60 65 70 75 80

Ambient Temperature (°°C)

28
Specifications

3.6 DIMENSIONS AND MOUNTING


3.6.1 DSE907 12V 10A INDUSTRIAL BATTERY CHARGER

Parameter Comment
Cabinet type Custom cabinet
Overall size 200mm x 185mm x 170mm (7.9“ x 7.3“ x 6.7“)
(see below for diagram) Add 20mm (0.79”) to depth when using supplied mounting plate.
Material: Sheet steel enclosure of all-round solid construction
Surface finish: Powder-coated black
IP20
Protection category:
NEMA 1
Weight 5.6kg
Wall mounting using supplied wall bracket
Mounting type
Wall bracket add 20mm (0.79”) to the depth of the enclosure
Diameter 5mm (0.2”)
Mounting holes
130mm (5.1) centres
Input voltage (nominal) 110V-277V
Input voltage (absolute range) 90V-305V
3A DC resistive
Charge failure relay rating
30V maximum
-30°C to 55°C
Operating Temperature
(-22°F to 131°F)
Controls AC Power on/off
0A-10A DC ammeter
Indication
Power on Red neon indicator
Fuse holder mounted onto front panel.
AC Fuse
Accepts 2A anti-surge fuse (20mm x 5mm fuse)
Fuse holder mounted onto front panel.
DC Fuse
Accepts 5A anti-surge fuse (20mm x 5mm fuse)

165mm

185mm

130mm 170mm

170mm
130mm add 20mm when
fitting supplied wall
bracket 200mm

Mounting Plate (supplied) Enclosure

Dimensions in mm

29
Specifications

3.6.2 DSE908 12V & 24V 10A CABINET MOUNTED BATTERY CHARGER

Parameter Comment
AE1031.500 by Rittal –
Cabinet type
Rittal website www.rittal.de / www.rittal.co.uk
380mm x 300mm x 210mm
Overall size
(15.0.” x 11.8”x 8.3”)
Sheet steel enclosure of all-round solid construction
Single door, right hand hinge with one cam lock
Foamed-in door seal
Material:
1 foamed in gland plate in the enclosure base
(Gland plate supplied blank, ready for customer drilling as
required).
Dipcoat primed, powder-coated on the outside in textured RAL
Surface finish:
7035
Protection category: IP20
NEMA 1
Weight 15kg
Wall mounting. Can be mounted by customer drilled holes or by
using Rittal mounting brackets, suitable for Rittal cabinet type
Mounting type AE1030.500 – For example Rittal Part number 2508.010 (Pack of
4)
Rittal website www.rittal.de / www.rittal.co.uk
Input voltage (nominal) 110V-277V
Input voltage (absolute range) 90V-305V
3A DC resistive
Charge failure relay rating
30V maximum
-30°C to 55°C
Operating Temperature
(-22°F to 131°F)
AC Power on/off
Controls
Boost charge on/off
0A-15A DC ammeter
Indication
Power on Red neon indicator
Fuse holder mounted onto front panel.
AC Fuse
Accepts 2A anti-surge fuse (20mm x 5mm fuse)

300mm

380mm 210mm

Dimensions in mm

30
Specifications

3.6.3 DSE9130 12V 5A

NOTE: This battery charger is designed to be mounted with the base to a vertical surface
with the terminal strips at the bottom.

Parameter Comment
136.48mm x 140.41mm x 63.40mm
Overall size
(5.37” x 5.53” x 2.5”)
Weight 0.5kg
Mounting type DIN rail or chassis mounting
Din rail type EN 50022 35mm type only
Mounting holes Suitable for M4
119.36mm x 128.36mm
Mounting hole centres
(4.7” x 5.05”)

Dimensions in mm unless stated

31
Specifications

3.6.4 DSE9150 12V 2A

NOTE: This device is no longer available, replaced by DSE9150 12V 3A. See overleaf for
updated specifications.

NOTE: This battery charger is designed to be mounted with the base to a vertical surface
with the terminal strips at the bottom.

Parameter Comment
108.03mm x 101.10mm x 48.6mm
Overall size
(4.25” x 3.98” x 1.91”)
Weight 0.16kg
Mounting type DIN rail or chassis mounting
Din rail type EN 50022 35mm type only
Mounting holes Suitable for M4
91mm x 89mm
Mounting hole centres
(4.25” x 3.51”)

Dimensions in mm unless stated

32
Specifications

3.6.5 DSE9150 12V 3A

NOTE: This device has replaced DSE9150 12V 2A. See previous page for specifications of
the earlier model.

NOTE: This battery charger is designed to be mounted with the base to a vertical surface
with the terminal strips at the bottom.

Parameter Comment
108.03mm x 101.10mm x 48.6mm
Overall size
(4.25” x 3.98” x 1.91”)
Weight 0.16kg
Mounting type DIN rail or chassis mounting
Din rail type EN 50022 35mm type only
Mounting holes Suitable for M4
91mm x 89mm
Mounting hole centres
(4.25” x 3.51”)

Dimensions in mm unless stated

33
Specifications

3.6.6 DSE9140 12V 10A

NOTE: This battery charger is designed to be mounted with the base to a vertical surface
with the terminal strips at the bottom.

Parameter Comment
152mm x 188mm x 2.44mm
Overall size
(6” x 7.4”x 2.44”)
Weight 0.75kg
Mounting type DIN rail or chassis mounting
Din rail type EN 50022 35mm type only
Mounting holes Suitable for M4
142mm x 128mm
(5.59” x 5.0”)
Mounting hole centres
30mm (1.18”) from top and bottom edges
5mm (1.97”) from left and right edges.
Input voltage (nominal) 110V-277V
Input voltage (absolute range) 90V-305V
3A DC resistive
Charge failure relay rating
30V maximum
-30°C to 55°C
Operating Temperature
(-22°F to 131°F)

6 in 2.44 in
7.4 in

Dimensions in mm unless stated

34
Specifications

3.6.7 DSE9155 30V 2A

NOTE: This battery charger is designed to be mounted with the base to a vertical surface
with the terminal strips at the bottom.

Parameter Comment
136.48mm x 140.41mm x 63.40mm
Overall size
(5.37” x 5.53” x 2.5”)
Weight 0.5kg
Mounting type DIN rail or chassis mounting
Din rail type EN 50022 35mm type only
Mounting holes Suitable for M4
119.36mm x 128.36mm
Mounting hole centres
4.7” x 5.05”

Dimensions in mm unless stated

35
Specifications

3.6.8 DSE9250 24V 3.7A

NOTE: - This battery charger is now obsolete, details provided for information only.

NOTE: This battery charger is designed to be mounted with the base to a vertical surface
with the terminal strips at the bottom.

Parameter Comment
136.48mm x 140.41mm x 63.40mm
Overall size
(5.37” x 5.53” x 2.5”)
Weight 0.5kg
Mounting type DIN rail or chassis mounting
Din rail type EN 50022 35mm type only
Mounting holes Suitable for M4
119.36mm x 128.36mm
Mounting hole centres
(4.7” x 5.05”)

Dimensions in mm unless stated

36
Specifications

3.6.9 DSE9255 24V 5A

NOTE: This battery charger is designed to be mounted with the base to a vertical surface
with the terminal strips at the bottom.

Parameter Comment
Overall size 136.48mm x 140.41mm x 63.40mm
(5.37” x 5.53” x 2.5”)
Weight 0.5kg
Mounting type DIN rail or chassis mounting
Din rail type EN 50022 35mm type only
Mounting holes Suitable for M4
Mounting hole centres 119.36mm x 128.36mm
(4.7” x 5.05”)

Dimensions in mm unless stated

37
Specifications

3.6.10 DSE9260 24V 10A

NOTE: This battery charger is designed to be mounted with the base to a vertical surface
with the terminal strips at the bottom.

Parameter Comment
152mm x 188mm x 2.44mm
Overall size
(6.0” x 7.4”x 2.44”)
Weight 0.85kg
Mounting type DIN rail or chassis mounting
Din rail type EN 50022 35mm type only
Mounting holes Suitable for M4
142mm x 128mm
Mounting hole centres
(5.59” x 5.0”)
Input voltage (nominal) 110V-277V
Input voltage (absolute range) 90V-305V
3A DC resistive
Charge failure relay rating
30V maximum
-30°C to 55°C
Operating Temperature
(-22°F to 131°F)

6 in 2.44 in
7.4 in

Dimensions in mm unless stated

38
Specifications

3.6.11 DSE9470 (MKII) 24V/12V 10A

NOTE: This battery charger is designed to be mounted with the base to a vertical surface
with the terminal strips at the bottom.

Parameter Comment
205mm x 135mm x 80mm
Overall size(mm)
(8.0” x 5.3” x 3.1”)
Weight 0.78kg
Mounting type DIN rail or chassis mounting
Din rail type EN 50022 35mm type only
Mounting holes Suitable for M4
190mm x 120mm
Mounting hole centres
(7.5” x 4.7”)
Input voltage (nominal) 110V-277V
Input voltage (absolute range) 95V-305V
3A DC resistive
Charge failure relay rating
30V maximum
-30°C to 85°C with de rating
Operating Temperature
(-22°F to 185°F with de rating)

39
Specifications

3.6.12 DSE9472 (MKII) 24V/12V 5A

NOTE: This battery charger is designed to be mounted with the base to a vertical surface
with the terminal strips at the bottom.

Parameter Comment
205mm x 135mm x 80mm
Overall size(mm)
(8.0” x 5.3” x 3.1”)
Weight 0.7kg
Mounting type DIN rail or chassis mounting
Din rail type EN 50022 35mm type only
Mounting holes Suitable for M4
190mm x 120mm
Mounting hole centres
(7.5” x 4.7”)
Input voltage (nominal) 110V-277V
Input voltage (absolute range) 95V-305V
3A DC resistive
Charge failure relay rating
30V maximum
-30°C to 85°C with de rating
Operating Temperature
(-22°F to 185°F with de rating)

40
Specifications

3.6.13 DSE9480 (MKII) 12V/24V 10A

NOTE: This battery charger is designed to be mounted with the base to a vertical surface
with the terminal strips at the bottom.

Parameter Comment
205mm x 135mm x 80mm
Overall size(mm)
(8.0” x 5.3” x 3.1”)
Weight 0.7kg
Mounting type DIN rail or chassis mounting
Din rail type EN 50022 35mm type only
Mounting holes Suitable for M4
190mm x 120mm
Mounting hole centres
(7.5” x 4.7”)
Input voltage (nominal) 110V-277V
Input voltage (absolute range) 95V-305V
3A DC resistive
Charge failure relay rating
30V maximum
-30°C to 85°C with de rating
Operating Temperature
(-22°F to 185°F with de rating)

41
Specifications

3.6.14 DSE9481 (MKII) 12V/24V 5A

NOTE: This battery charger is designed to be mounted with the base to a vertical surface
with the terminal strips at the bottom.

Parameter Comment
205mm x 135mm x 80mm
Overall size(mm)
(8.0” x 5.3” x 3.1”)
Weight 0.7kg
Mounting type DIN rail or chassis mounting
Din rail type EN 50022 35mm type only
Mounting holes Suitable for M4
190mm x 120mm
Mounting hole centres
(7.5” x 4.7”)
Input voltage (nominal) 110V-277V
Input voltage (absolute range) 95V-305V
3A DC resistive
Charge failure relay rating
30V maximum
-30°C to 85°C with de rating
Operating Temperature
(-22°F to 185°F with de rating)

42
Specifications

3.7 APPLICABLE STANDARDS

This document conforms to BS4884-1 1992 Specification for


BS 4884-1
presentation of essential information.

BS 4884-2 This document conforms to BS4884-2 1993 Guide to content.

BS 4884-3 This document conforms to BS4884-3 1993 Guide to presentation.

BS EN 60068-2-1
-30°C (-22°F)
(Minimum temperature)

BS EN 60068-2-2
+55°C (131°F)
(Maximum temperature)

Safety of information technology equipment, including electrical


BS EN 60950
business equipment.

BS EN 61000-6-2 EMC Generic Immunity Standard (Industrial).

BS EN 61000-6-4 EMC Generic Emission Standard (Industrial).

IP20
BS EN 60529
Protected against penetration by solid objects with a diameter of more
(Degrees of protection
than 12 mm. Fingers or similar objects prevented from approach.
provided by enclosures)
No protection against water

Enclosure type 1
UL508
NEMA rating Provides a degree of protection against contact with the enclosure
equipment and against a limited amount of falling dirt

UK WEEE
Producer Registration Number WEE/BE0052TQ
REGULATIONS

In line with our policy of continual development, Deep Sea Electronics, reserve the right to change specification without notice.

43
Installation

4 INSTALLATION

NOTE: The DSE9000 series battery charger should only be used to charge one battery
bank at a time. It is not recommended to parallel batteries as the tolerance of the batteries
leads to imbalance in their charging.

The DSE9000 battery charger is designed to be mounted within a control panel, on the panel DIN rail
utilising the integral mounts or on a chassis utilising the mounting holes. For dimension and mounting
details, see the section entitled Specification, Dimensions elsewhere in this document.

The DSE9000 battery charger is fit-and-forget. It can be permanently connected to the supply and the
load, with no requirement to disable the charger during times of heavy load (such as engine cranking)
or when the generator is running (even when a DC charging alternator is fitted).

4.1 BATTERY SUITABILITY


The standard charger is factory set by DSE to suit Lead Acid batteries but can be adjusted at the time
of ordering to suit other battery types. Care should be taken to ensure the batteries connected to the
charger are of the correct ‘technology’ to suit the setting of the charger.
For details of other supported battery types and float voltages see the section entitled Specifications,
Part Numbering elsewhere in this document.

4.2 USER CONNECTIONS


Parameter Comment
Connection type Screw terminal, rising clamp, no internal spring
Min cable size 0.5mm² (AWG 20)
Max cable size 2.5mm² (AWG 14)
Recommended AC fuse 230V AC Input 110V AC Input
DSE9130 12V 5A charger 1.0A anti-surge 2.0A anti-surge
DSE9140 12V 10A charger 2.0A anti-surge 3.5A anti-surge
DSE9150 12V 2A charger 1.0A anti-surge 1.5A anti-surge
DSE9150 12V 3A charger 1.5A anti-surge 2.0A anti-surge
DSE9155 30V 2A charger 1.0A anti-surge 2.5A anti-surge
DSE9250 24V 3.7A charger 1.0A anti-surge 2.5A anti-surge
DSE9260 24V 10A charger 3.5A anti-surge 6.3A anti-surge
DSE9255 24V 5A charger 2.0A anti-surge 3.5A anti-surge
DSE9470 24V/12V 10A charger 3.5A anti-surge 6.3A anti-surge
DSE9480 12V/24V 10A charger 2.0A anti-surge 3.5A anti-surge
DSE9481 12V 5A charger 1.0A antisurge 2.5A anti-surge
DSE9472 24V 5A charger 2.0A antisurge 3.5A anti-surge

NOTE: Where DSE9470 / DSE9480 current rating has been user configured below 10A, an
appropriate fuse size must be selected to match the lower maximum output current.

44
Installation

4.2.1 DSE9130, DSE9140, DSE9250, DSE9255 & DSE9260

Connector A
Terminal Function Recommended Size Comments
-OP Load negative 1mm² (AWG 16) Battery negative terminal
+OP Load Positive 1mm² (AWG 16) Battery positive terminal
BOOST Boost mode 0.5 mm² (AWG 22)
Connect together for boost operation
BOOST Boost mode 0.5 mm² (AWG 22)
CF Charge failure relay 0.5 mm² (AWG 22)
Closes under charge fail conditions
CF Charge failure relay 0.5 mm² (AWG 22)

Connector B
Terminal Function Recommended Size
Earth 1mm² (AWG 16)
N AC Neutral 1mm² (AWG 16)
L AC Live 1mm² (AWG 16)

CAUTION: Ensure Earth Terminal is connected to Battery negative (for negative earth
systems) or Battery positive (for positive earth systems)
Where no system earth exists, Earth Terminal must be connected to battery negative

4.2.2 DSE9150

Connector A
Terminal Function Recommended Size Comments
NC Not Connected Do not connect
-OP Load negative 1mm² (AWG 16) Battery negative terminal
+OP Load Positive 1mm² (AWG 16) Battery positive terminal

Connector B
Terminal Function Recommended Size
Earth 1mm² (AWG 18)
N AC Neutral 1mm² (AWG 18)
L AC Live 1mm² (AWG 18)

CAUTION: Ensure Earth Terminal is connected to Battery negative (for negative earth
systems) or Battery positive (for positive earth systems)
Where no system earth exists, Earth Terminal must be connected to battery negative

45
Installation

4.2.3 DSE9155

Connector A
Terminal Function Recommended size Comments
-OP Load negative 1mm² (AWG 16) Battery negative terminal
+OP Load Positive 1mm² (AWG 16) Battery positive terminal
BOOST N/A 0.5 mm² (AWG 22)
Boost not avaialble on DSE9155
BOOST N/A 0.5 mm² (AWG 22)
CF Charge failure relay 0.5 mm² (AWG 22)
Closes under charge fail conditions
CF Charge failure relay 0.5 mm² (AWG 22)

Connector B
Terminal Function Recommended Size
Earth 1mm² (AWG 16)
N AC Neutral 1mm² (AWG 16)
L AC Live 1mm² (AWG 16)

CAUTION: Ensure Earth Terminal is connected to Battery negative (for negative earth
systems) or Battery positive (for positive earth systems).
Where no system earth exists, Earth Terminal must be connected to battery negative.

46
Installation

4.2.4 DSE9470 MKII, DSE9472 MKII, DSE9480 MKII, DSE9481 MKII

NOTE: For obsolete parts 9470-001-00 and 9480-001-00 contact DSE Technical Support for
connection details.

Connector A
Terminal Function Recommended size Comments
-OP Load negative 1mm² (AWG 16) Battery negative terminal
+OP Load Positive 1mm² (AWG 16) Battery positive terminal

Connector B
Terminal Function Recommended size Comments
Connect the terminals together
to activate the input.
LK1 Configurable Input 1mm² (AWG 16) The Factory Setting for the
digital input provides a
selection of 12V / 24V
operation.
Customer configurable using
DSE Configuration Suite PC
Software.
LK1
Configurable Input (0V) 1mm² (AWG 16)
NOTE: Digital Input Not
Fitted to 9470-001-00 and
9480-001-00.

Normally Closed Contact


NC 0.5 mm² (AWG 22)
of the Charge failure relay
Charge failure relay Changes State Under Charge
COM 0.5 mm² (AWG 22)
Contact Common Fail Conditions
Normally Open Contact of
NO 0.5 mm² (AWG 22)
the Charge failure relay

NOTE: For further details of PC Configuration, you are referred to DSE Publication: 057-
159 DSE9400 Series Battery Charger Configuration Suite Manual.

47
Installation

Connector B
Terminal Function Recommended size Comments
SCR RS485 screen 0.5mm² (AWG20) Use only 120Ω RS485 approved cable
A RS485 -ve 0.5mm² (AWG20) Use only 120Ω RS485 approved cable
B RS485 +ve 0.5mm² (AWG20) Use only 120Ω RS485 approved cable
NTC PT1000 connection 0.5mm² (AWG20)
Use only PT1000
NTC terminals 0.5mm² (AWG20)

Connector C
Terminal Function Recommended Size
Earth 1mm² (AWG 16)
N AC Neutral 1mm² (AWG 16)
L AC Live 1mm² (AWG 16)

CAUTION: Ensure Earth Terminal is connected to Battery negative (for negative earth
systems) or Battery positive (for positive earth systems)
Where no system earth exists, Earth Terminal must be connected to battery negative

48
Installation

4.3 TYPICAL WIRING DIAGRAM


4.3.1 DSE9150

DSE9150

Recommended AC fuse 230V AC Input 110V AC Input


DSE9150 12V 2A charger (see Note below) 1.0A anti-surge 1.5A anti-surge
DSE9150 12V 3A charger 1.5A anti-surge 2.0A anti-surge

NOTE: DSE9150 12V 2A is no longer available and is included for legacy support only.

49
Installation

4.3.2 DSE9155 & DSE9200 SERIES

Recommended AC fuse 230V AC Input 110V AC Input


DSE9130 12V 5A charger 1.0A anti-surge 2.0A anti-surge
DSE9140 12V 10A charger 2.0A anti-surge 3.5A anti-surge
DSE9155 30V 2A charger 1.0A anti-surge 2.5A anti-surge
DSE9250 24V 3.7A charger 1.0A anti-surge 2.5A anti-surge
DSE9260 24V 10A charger 3.5 A anti-surge 6.3A anti-surge
DSE9255 24V 5A charger 2.0A anti-surge 3.5A anti-surge

50
Installation

4.3.3 DSE9470 MKII, DSE9472 MKII, DSE9480 MKII, DSE9481 MKII

NOTE: For obsolete parts 9470-001-00 and 9480-001-00 contact DSE Technical Support for
connection details.

Recommended AC fuse 230V AC Input 110V AC Input


DSE9470 24V/12V 10A 3.5A antisurge 6.3A antisurge
DSE9480 12V/24V 10A 3.5A antisurge 6.3A antisurge
DSE9481 12V/24V 5A 1.0A antisurge 2.5A antisurge
DSE9472 24V/12V 5A 2.0A antisurge 3.5A antisurge

51
Operation

5 INDICATIONS

DANGER OF DEATH : LIVE PARTS exist within the DSE9000 enclosure. The enclosure
cover must not be removed when connected to an AC supply.

5.1 DSE907

Charge Ammeter

Power Indication

Function Action
Illuminated RED when AC power is connected and the POWER switch is in the
Power indication
‘1’ position
Charge Ammeter Scaled 0A to 10A to show charge current (Max 5A charge)

5.2 DSE908

Power Indication

Charge Ammeter

Function Action
Illuminated RED when AC power is connected and the POWER switch is in the
Power indication
ON position
Charge Ammeter Scaled 0A to 15A to show charge current (Max 5A charge)

52
Operation

5.3 DSE9130, DSE9150, DSE9155, DSE9250 & DSE9255


DSE9130 12V 5A
DSE9155 30V 2A DSE9150 12V 2A
DSE9250 24V 3.7A DSE9150 12V 3A
DSE9255 24V 5A

Charger Status Charger Status

LED Indications
Function Colour Action
• Off when AC supply is not present or output volts are too low.
• Steady during normal operation with AC supply above minimum
Charger Status Red operating voltage.
• Flashing when connected to an operating charging alternator.
• Pulsing during overload conditions.

53
Operation

5.4 DSE9140 & DSE9260


DSE9140 12V 10A
DSE9260 24V 10A

Charger Status

Short Circuit

LED Indications
Function LED Action
• Off when AC supply is not present or output voltage is too low
• Steady during normal operation with AC supply above
Charger Status Red
minimum operating voltage
• Flashing when connected to an operating charging alternator
• Off when AC supply is not present or output voltage is too low
Short circuit and
• Steady during normal operation with AC supply above
reverse polarity Green
minimum operating voltage
indication
• Flashing during short circuit or reverse polarity conditions

54
Operation

5.5 DSE9470 MKII, DSE9472 MKII, DSE9480 MKII, DSE9481 MKII

NOTE: For obsolete parts 9470-001-00 and 9480-001-00 contact DSE Technical Support for
LED descriptions.

Boost Voltage
potentiometer
access hole

Charger Status
(OPE)

Fault LEDs

5.5.1 STATUS

LED DESIGNATION
Condition
OPE FAULT 1 FAULT 2
Charger Off Off Off Off
Green Red Red
Battery not Detected (Battery Detection Mode)
Constant Constant Flashing
Green Red Red
Battery Connected (Battery Detection Mode)
Constant Constant Constant
Not Charging
Red Red
(Charger is operating correctly but the ouput has Off
Constant Constant
been disconnected from the battery)

5.5.2 CHARGE MODE

LED DESIGNATION
Mode
OPE
Bulk Charge in progress Yellow Constant
Absorption Charge in progress Yellow Flashing
Float Charge in Progress Green Constant
Storage Charge in Progress Green Flashing

5.5.3 FAULT CONDITIONS

LED DESIGNATION
Condition
FAULT 1 FAULT 2
Red
High Output Voltage (DC) Off
Constant
Red
High / Low Input Voltage (AC) or High Output Current (DC) Off
Flashing
High Ambient / Charger Temperature, High Battery Red
Off
Temperature (if enabled) Constant
Red
Short Circuit/ Reverse Polarity (DC Output Connection) Off
Flashing

55
Operation

6 OPERATION
6.1 OPERATION OF DSE9100 SERIES / DSE9200 SERIES
DSE9100 SERIES DSE9200 SERIES
DSE9130 12V 5A DSE9250 24V 3.7A
DSE9140 12V 10A DSE9255 24V 5A
DSE9150 12V 2A DSE9260 24V 10A
DSE9150 12V 3A
DSE9155 30V 2A

The DSE9100 & DSE9200 series of battery chargers can be used as a battery charger, DC power
supply, or both at the same time. For instance, the units can be used to power the generator control
panels and charge the panel batteries or starter batteries at the same time.

With no AC input to the charger, the Charge fail relay will be closed. This can be used to provide
indication of charger failure which operates upon mains supply AC supply failure or upon one of the
protections being activated.

6.1.1 PROTECTION

• Current limit to charger specification (2A or 3A depending upon charger model)


• Short circuit protection. Charger automatically restarts operation after the fault is removed.
• Reverse battery polarity protection. Charger automatically restarts operation after the fault is
removed.

6.1.2 PSU MODE

If no battery is connected to the output terminals, the DSE9100 & DSE9200 series battery charger will
operate as a DC power supply only, current limit is factory set. See the section entitled Specification
elsewhere in this manual for output specifications.

6.1.3 CHARGE MODE

Constant Voltage
The DSE9100 & DSE9200 series battery charger operates in Constant voltage current limited mode.
The charger output voltage is maintained at a constant level to allow the battery to charge while the
load does not exceed the maximum rating of the charger.
Once the battery is fully charged, the DSE9100 & DSE9200 series battery charger will switch to ECO-
POWER mode. This is a low power use standby mode.

Current Limit
If the load on the battery charger (battery charge demand+standing load) exceeds the maximum
current rating of the charger, the charging current is limited to the maximum rating of the charger and
the voltage is reduced.
The voltage will rise to the rated voltage again once the load drops below the maximum rating of the
charger.

56
Operation

Charging time
Charge time is often of little consequence when the battery is used in a standby operation. An
example of this is when the battery is used to supply the starting system of a diesel generator. During
normal operation, the battery is at full capacity and the battery charger is used to maintain the float
voltage of the battery. The battery is only drained when the generator is called to start. As the
generator has a DC charging alternator fitted, the battery is quickly recharged when the generator is
running. Should the generator stop before the battery is fully recharged, the DSE9100 & DSE9200
series will continue to recharge the battery until it is fully charged.

Typically a battery will charge from flat to 80% capacity in 16hrs when when charged at C/10.
For example charging a 50Ah battery for 16hrs at 5A will charge the battery to 80% of its full capacity.
Remember to take into account any other standing load such as control panel requirements when
calculating how much power is ‘left’ to charge the battery.

6.1.4 BOOST MODE

(Not applicable to DSE9150 12V 2A, DSE9150 12V 3A or DSE9155 30V 2A)

CAUTION: Boost mode is intended for equalisation of the cells in lead acid batteries and
should not be operated when the battery charger is connected to other battery types or when
the charger is used as a power supply only. If in doubt, consult your battery manufacturer.

Boost mode is operated by connecting the BOOST terminals together (for instance with an external
switch or timer circuit). This will raise the battery charger floating voltage by 0.8V DC.

57
Operation

6.2 OPERATION OF DSE9400 MKII SERIES

DSE9400 SERIES
DSE9470 MKII 24V/12V 10A
DSE9472 MKII 24V/12V 5A
DSE9480 MKII 12V/24V 10A
DSE9481 MKII 12V/24V 5A

The DSE9400 MKII Series battery charger can be used as a battery charger, DC power supply, or
both at the same time. For instance, the unit can be used to power the generator control panels and
charge the panel batteries or starter batteries at the same time.

With no AC input to the charger, the Fault relay is in it’s inactive state. This volts-free change over
relay can be used to provide indication of alarms as detailed in the Protection section below.
When a suitable AC supply is connected, operation of the unit will depend upon the load connected to
the unit’s output terminals :

NOTE: For details of Battery Charger Configuration, you are referred to DSE Publication:
057-159 DSE9400 Series Battery Charger Configuration Suite Manual.

6.2.1 PROTECTION

Alarms fall into two categories :


• Factory Configured, non-ajustable alarms.
• User Configurable Alarms, adjustable by DSE Configuration Suite PC Software.

6.2.1.1 FACTORY CONFIGURED ALARMS

Under the following conditions, the Fault Relay de-energises and charging is stopped (DC output is
disabled) :

• Mains voltage > 310V (rms)


• Mains voltage < 85V (rms)
• Battery temperature > 60 ºC (if temperature compensation is enabled)
• Battery Charger ambient temperature> 85 ºC
• DC output voltage > 110% of Boost Voltage
• Short circuit / reverse polarity of the DC output.

6.2.1.2 USER CONFIGURABLE ALARMS

NOTE: For details of Battery Charger Configuration, you are referred to DSE Publication:
057-159 DSE9400 Series Battery Charger Configuration Suite Manual.

The following alarms are user configurable using DSE Configuration Suite PC Software. In each case,
the Fault relay de-energises.

• DC Overcurrent alarm
• DC Overvoltage alarm
• Battery Temperature alarm. Activation of this alarm places the charger into Float mode.
• Mains Over Voltage alarm. Activation of this alarm places the charger into Float mode.
• Mains Under Voltage alarm. Activation of this alarm places the charger into Float mode.

58
Operation

6.2.2 DIGITAL INPUT

The DSE9400 series is fitted with a configurable digital input. Configuration is made using the DSE
Configuration Suite PC Software.

The Factory Setting for the digital input provides a 12V / 24V selection function.

6.2.3 VOLTAGE ADJUSTMENT POTENTIOMETER

A manually operated potentiometer is provided to make small adjustments to the Boost Voltage
without the requirement for the DSE Configuration Suite PC Software.
This is primarily intended to increase charger output to cater for voltage drop in long connection
cables.

The potentiometer adjusts the boost voltage byup to ±1.7V. This is subject to an absolute maximum
of 29.5V.

The table below shows the effect of the potentiometer on the boost voltage in the various charging
modes.

Charge Mode Effect on boost voltage


Bulk 100% of potentiometer setting
Absorption 50% of potentiometer setting
Float Potentiometer has no effect on Float Voltage
Storage Potentiometer has no effect on Storage Voltage

6.2.4 PSU MODE

If no battery is connected to the output terminals, the battery charger will operate as a DC power
supply only, current limit is factory set to 10A and is adjustable (2A – 10A) using the DSE
Configuration Suite PC Software. See the section entitled Specification elsewhere in this manual for
further output specifications.

59
Operation

6.2.5 CHARGE MODE

NOTE: For details of Battery Charger Configuration, you are referred to DSE Publication:
057-159 DSE9400 Series Battery Charger Configuration Suite Manual.

NOTE: Should a 2-Stage charging profile be required, select a 3-Stage profile and
configure Boost Voltage and Float Voltage to the same value.

Using DSE Conifiguration Suite PC Software, the battery charger is configured to use either a 3-
Stage Charge or 4-Stage Charge profile as shown below. The description of each charge mode is
given in the following sections.

Bulk Absorption Float Storage

Bulk Absorption Float

3-Stage Charge Profile Configuration 4-Stage Charge Profile Configuration

6.2.5.1 BULK CHARGE

The battery charger operates in Constant voltage current limited mode.


The charger output voltage is maintained at a constant level (boost voltage) to allow the battery to
charge while the load does not exceed the maximum rating of the charger.
If the load on the battery charger (battery charge demand+standing load) exceeds the maximum
current rating of the charger, the charging current is limited to the maximum rating of the charger and
the voltage is reduced.
The voltage will rise to the rated voltage again once the load drops below the maximum rating of the
charger. This may occur naturally as the battery charges.
As the battery charges and the charge current drops below 75% of the current rating, Absorption
mode is entered.

6.2.5.2 ABSORPTION

This mode is active for the duration of the Absorption Timer. This is adjustable using the DSE
Configuration Suite PC Software.
Absorption mode is used to complete the charging process, bringing the battery to 100% charged
status.
After the Absorption timer, float charge mode is entered.

60
Operation

6.2.5.3 FLOAT CHARGE

The battery charger DC voltage is lowered to the configured float voltage.


Float Charge is used to provide a small amount of current to the battery, to overcome internal losses
and keep the battery at it’s 100% charged state. The battery can be left in this mode indefinitely.

6.2.5.4 STORAGE

When configured to use a four stage charging profile, a time limited storage charge is periodically
entered (storage timer) to maintain the battery charge at optimum levels. This occurs at the level of
the storage voltage. This is adjustable using the DSE Configuration Suite PC Software.
When the storage timer expires, the charger re-enters the Absorption mode.

Additionally, this is used as an ‘Automatic Boost’ facility, to periodically attempt to remove sulfation
from the battery plates.

6.2.5.5 CHARGING TIME

Charge time is often of little consequence when the battery is used in a standby operation. An
example of this is when the battery is used to supply the starting system of a diesel generator. During
normal operation, the battery is at full capacity and the battery charger is used to maintain the float
voltage of the battery. The battery is only drained when the generator is called to start. As the
generator has a DC charging alternator fitted, the battery is quickly recharged when the generator is
running. Should the generator stop before the battery is fully recharged, the DSE9400 MKII Series
battery charger will continue to recharge the battery until it is fully charged.

Typically a battery will charge from flat to 80% capacity in 16hrs when when charged at C/10.
For example charging a 50Ah battery for 16hrs at 5A will charge the battery to 80% of its full capacity.
Remember to take into account any other standing load such as control panel requirements when
calculating how much power is ‘left’ to charge the battery.

6.2.5.6 MANUAL BOOST

NOTE: The Digital Input must be configured to Manual Boost to provide this function.
For further details, you are referred to DSE Publication: 057-159 DSE9400 Series Battery
Charger Configuration Suite Manual.

Manual boost will place the charger into Bulk Charge mode, charging at the level of the boost voltage.
A typical use of manual boost is with Lead Acid type batteries. When the battery is fully charged,
placing the charger into boost mode will raise the output voltage. This has the effect of gassing the
battery, helping to remove sulfation from the battery plates and helping the cells to equalise in
voltage.

6.2.6 TEMPERATURE COMPENSATION

NOTE: For details of Battery Charger Configuration, you are referred to DSE Publication:
057-159 DSE9400 Series Battery Charger Configuration Suite Manual.

If temperature compensation is enabled through configuration, and remote temperature sensor is


connected, the output voltage automatically varies by a configureable voltage per cell for each 1°C
deviation from 20°C, within the range of -20°C to 60°C. Increasing temperature gives decreasing
output voltage and increasing temperatures gives increasing output voltage..
The battery temperature is measured by a 2 wire PT1000 sensor placed on the battery itself.

61
Fault Diagnosis

7 FAULT DIAGNOSIS
Nature of problem Suggestion
Check that the incoming AC supply is correctly connected and within
limits and check the integrity of any external fuse that may be fitted.

Ensure the charger is not being operated above the maximum


The charger is not operating
temperature specification.

Check the LED indications against the LED descriptions listed


elsewhere in this document.
Charge fail relay Check the connected load of the charger is not reverse connected or
continuously operated short circuit.
Check the batteries using the battery manufacturers
Batteries fail to charge
recommendations.
Typically a battery will charge from flat to 80% capacity in 16hrs when
when charged at C/10.
For example charging a 50Ah battery for 16hrs at 5A will charge the
Charge time is too long battery to 80% of its full capacity.
Remember to take into account any other standing load such as
control panel requirements when calculating how much power is ‘left’
to charge the battery.

62
This page is intentionally left blank.

8 MAINTENANCE, SPARES, REPAIR AND SERVICING


The DSE battery chargers are designed to be Fit and Forget. As such, there are no user serviceable
parts. In the case of malfunction you should contact your original equipment supplier (OEM).

9 WARRANTY
DSE provides limited warranty to the equipment purchaser at the point of sale. For full details of any
applicable warranty, you are referred to your original equipment supplier (OEM).

10 DISPOSAL
10.1 WEEE (WASTE ELECTRICAL AND ELECTRONIC EQUIPMENT)
Directive 2002/96/EC
If you use electrical and electronic equipment you must store, collect, treat,
recycle and dispose of WEEE separately from your other waste.

10.2 ROHS (RESTRICTION OF HAZARDOUS SUBSTANCES)


Directive 2002/95/EC:2006
To remove specified hazardous substances (Lead, Mercury, Hexavalent Chromium, Cadmium, PBB &
PBDE´s)

Exemption Note: Category 9. (Monitoring & Control Instruments) as defined in Annex 1B of the WEEE
directive will be exempt from the RoHS legislation. This was confirmed in the August 2005 UK´s
Department of Trade and Industry RoHS REGULATIONS Guide (Para 11).

Despite this exemption DSE has been carefully removing all non RoHS compliant components from
our supply chain and products.
When this is completed a Lead Free & RoHS compatible manufacturing process will be phased into
DSE production.

This is a process that is almost complete and is being phased through different product groups.

63
This page is intentionally left blank.
®

DSEPower

DSE9130, 9150, 9155 & 9255


COMPACT BATTERY CHARGERS
2 AMP & 5 AMP OPTIONS

1ph
N

CHARGE OUTPUT AC POWER SUPPLY

COMPATIBLE WITH ALL DSE MODULES

DSE9000
7

OTHER

CHARGE BOOST N/C VOLT FREE CHARGE


INPUT FAIL OUTPUT

1 1

ISSUE 5
Dimensions and Mounting 053-049
ISSUE 13 DEEP SEA ELECTRONICS
DSE9150 12V 3A
Overall size 108mm x 101mm x 49mm
(4.25” x 3.98” x 1.91”)
DSE9xxx Battery Charger Installation Instructions
Weight 0.16kg
Mounting type DIN rail or chassis mounting
Din rail type EN 50022 35mm type only DANGER OF DEATH : LIVE PARTS exist within the DSE9xxx enclosures. The enclosure cover must not
Mounting holes Suitable for M4 be removed.
Mounting hole centres 91mm x 89mm
(4.25” x 3.51”) Installation
Input voltage (nominal) 110V-240V The DSE9xxx battery chargers are designed to be mounted within a control panel, on the panel DIN rail utilising the integral mounts
Input voltage (absolute 90V-250V or on a chassis utilising the mounting holes. For dimension and mounting details, see overleaf.
range) The DSE9xxx battery chargers are fit-and-forget. It can be permanently connected to the supply and the load, with no requirement to
Charge failure relay 3A DC resistive, 30V maximum disable the charger during times of heavy load (such as engine cranking) or when in parallel with a charging alternator.
rating
Operating Temperature -30°C to 55°C
Battery suitability
The charger is factory set by DSE to suit Lead Acid batteries. The DSE91xx & DSE92xx battery chargers can be adjusted at the time
(-22°F to 131°F)
of ordering to suit other battery types. The DSE947x MKII & DSE948x MKII battery chargers are configured using the DSE
Configuraiton Suite to suit other battery types.
Care should be taken to ensure the batteries connected to the charger are of the correct ‘technology’ to suit the setting of the
charger.

Indications
The DSE9xxx Battery Chargers feature an LED indicator(s) to show the battery charger Status.
(Refer to DSE publication: 057-085 DSE9xxx Series Operator Manual for further information)

Boost Mode
(Not applicable to DSE9150 12V 2A or DSE9155 30V 2A)
(DSE947x & DSE948x MKII Series Only. Boost feature is controlled automatically, no external connection needed.)
Boost mode is operated by connecting the BOOST terminals together (for instance with an external switch or timer circuit. This will
raise the battery charger floating voltage by 0.8V DC.
Caution:- Boost mode is intended for equalisation of cells in lead acid batteries.
Dimensions in mm unless stated Typical Wiring Diagrams
Connection type Screw terminal, rising clamp, no
DSE 91xx & 92xx Series
internal spring Battery Chargers
Min cable size 0.5mm² (AWG 20) DSE 947x & 948x MKII Battery Chargers
Max cable size 2.5mm² (AWG 14)
Recommended AC fuse 230V AC Input 110V AC Input
DSE9130 12V 5A charger 1.0A anti-surge 2.0A anti-surge
DSE9140 12V 10A charger 2.0A anti-surge 3.5A anti-surge
DSE9150 12V 3A charger 1.0A anti-surge 1.5A anti-surge
DSE9155 30V 2A charger 1.0A anti-surge 2.5A anti-surge
DSE9250 24V 3.7A charger 1.0A anti-surge 2.5A anti-surge CF not available on
DSE9255 24V 5A charger 2.0A anti-surge 3.5A anti-surge DSE9150 12V 2A
DSE9260 24V 10A charger 3.5A anti-surge 6.3A anti-surge Boost not available on
DSE9470 MKII 24V 10A charger 3.5A anti-surge 6.3A anti-surge DSE9150 12V 3A
DSE9472 MKII 24V 5A charger 2.0A antisurge 3.5A anti-surge DSE9155 30V 2A
DSE9480 MKII 12V 10A charger 2.0A anti-surge 3.5A anti-surge
DSE9481 MKII 12V 5A charger 1.0A antisurge 2.5A anti-surge
Dimensions and Mounting Dimensions and Mounting Dimensions and Mounting
DSE9130 12V 5A DSE9250 24V 3.7A * DSE9140 12V 10A Intelligent Battery Chargers
DSE9155 30V 2A DSE9255 24V 5A DSE9260 24V 10A
DSE9481 MKII 12V 5A DSE9480 MKII 12V 10A
* This model is no longer available Overall size 152mm x 188mm x 62mm DSE9472 MKII 24V 5A DSE9470 MKII 24V 10A
(6” x 7.4”x 2.44”)
Overall size 136mm x 140mm x 63mm Overall size 205mm x 135mm x 80mm
Weight
(5.37” x 5.53” x 2.5”) (8.1” x 5.3” x 3.1”)
DSE9140 12V 10A 0.75kg
Weight 0.5kg DSE9260 24V 10A 0.85kg Weight
Mounting type DIN rail or chassis mounting DSE9470 MKII 0.78kg
Mounting type DIN rail or chassis mounting
Din rail type EN 50022 35mm type only DSE9472/80/81 MKII 0.7kg
Din rail type EN 50022 35mm type only
Mounting holes Suitable for M4 Mounting type DIN rail or chassis mounting
Mounting holes Suitable for M4
Mounting hole 119.36mm x 128.36mm Din rail type EN 50022 35mm type only
Mounting hole centres 142mm x 128mm
centres (4.7” x 5.05”) Mounting holes Suitable for M4
(5.59” x 5.0”)
Input voltage DSE9250-001 24V 3.7A 110V-240V Mounting hole centres 190mm x 120mm
Input voltage (nominal) 110V-277V
(nominal) DSE9250-002 24V 3.7A 110V-277V (7.5” x 4.7”)
Input voltage 90V-305V
DSE9130 12V 5A 110V-277V Input voltage (nominal) 110V-277V
(absolute range)
DSE9255 24V 5A 110V-277V Input voltage 95V-305V
Charge failure relay rating 3A DC resistive 30V Maximum
Input voltage DSE9250-001 24V 3.7A 90V-265V (absolute range)
Operating Temperature -30°C to 55°C
(absolute range) DSE9250-002 24V 3.7A 90V-305V Charge failure relay rating 3A DC resistive
(-22°F to 131°F) 30V maximum
DSE9130 12V 5A 90V-305V
DSE9255 24V 5A 90V-305V Operating Temperature -30°C to 85°C with de-rating
Charge failure 3A DC resistive, 30V maximum 6in 2.44in (-22°F to 185°F)
relay rating Optional Temperature NTC connections for PT1000
Operating -30°C to 55°C Sensor sensor only
Temperature (-22°F to 131°F) Communications RS485
PC connection (USB) To enable PC Configuration

7.4 in
Dimensions in mm unless stated Dimensions in mm unless stated

Dimensions in mm unless stated

NOTE : DSE9000 series chargers are designed to be mounted with the base to a vertical surface with
Deep Sea Electronics Inc.
the terminal strips at the bottom.
Deep Sea Electronics Plc.
Tel:+44 (0)1723 890099 Phone: +1 (815) 316-8706
Fax: +44 (0)1723 893303 Fax: +1 (815) 316- 8708
Email: sales@deepseaplc.com Email: sales@deepseausa.com NOTE : This document is intended as a ‘quick start’ guide only. For full operating instructions and
Web: www.deepseaplc.com Web: www.deepseausa.com specifications, refer to DSE publication: 057-085 DSE9xxx Series Operator Manual

You might also like