Download as pdf or txt
Download as pdf or txt
You are on page 1of 17

Static and Dynamic Responses of Reinforced Concrete

Structures under Sudden Column Removal Scenario


Subjected to Distributed Loading
Anh Tuan Pham 1 and Kang Hai Tan 2

Abstract: In this paper, static and dynamic experiments on reinforced concrete beam-column frames under single-column-removal scenario
Downloaded from ascelibrary.org by Sergio Barreiro on 01/07/19. Copyright ASCE. For personal use only; all rights reserved.

applying a multipoint loading method were conducted. One of the objectives was to investigate structural behavior compared with the single-
point loading method, which has been popularly used in previous studies. By equally applying point loads at four locations of the double-span
beam structure, the test setup successfully simulated the uniformly distributed loading condition, which is generally applicable for gravity
loads in practice. Compared with the previously conducted static tests based on concentrated loading method, structural response from the
static tests under multipoint loading condition differed not only on load-bearing capacity but also on failure sequence and displacement
profile. On the basis of the test results, the analytical relationship between behaviors of the two loading methods was developed and verified.
Compared with the static tests, the dynamic tests highlighted dynamic effects created by the column loss event and confirmed the structural
behavior and failure modes observed in the static environment. The dynamic tests also verified the correctness and conservatism of the
dynamic assessment framework using a previously proposed energy-based approach. Most important, both the static and the dynamic tests
of structures under distributed loads showed less development of catenary action against progressive collapse compared with concentrated
loading tests. DOI: 10.1061/(ASCE)ST.1943-541X.0002214. © 2018 American Society of Civil Engineers.
Author keywords: Reinforced concrete; Progressive collapse; Catenary action; Compressive arch action; Concentrated loading; Uniformly
distributed loading.

Introduction blast-induced tests on existing multistory RC buildings (Sasani


et al. 2007; Sasani 2008; Sasani and Sagiroglu 2010) and observed
In a missing-column scenario, two different conditions of gravity the opposite trend of mechanism. In those tests, concrete strain
loading can be considered for the affected structure in a typical gauges were installed on the columns above the removed ground
floor above the removed column: (1) loads from above floors would column. All three studies showed a consistent phenomenon of rapid
transfer to below floors through the column (above the missing col- increase of tensile strains in the measured columns within a very
umn) in the form of concentrated loading (CL); and (2) every story short time, much faster than the flexure response (moving down-
above the missing column behaves identically under gravity action, ward) of the structure. That is, shortly after the column loss event,
and the loads transferred through the column are negligible. As a axial compressive forces in the above columns dropped signifi-
result, the main action is uniformly distributed loading (UDL) in cantly. In reality, depending on structural configuration, gravity ac-
the single story. Concerning structural response of planar RC beam- tion causing the double-span structure to move downwards can be a
column structures against progressive collapse under quasi-static combination of both CL (from the columns in the above floors) and
conditions, most of the experimental and analytical studies con- UDL (from the floor of the double-span structure that is being con-
ducted (Bao et al. 2008; Sasani and Kropelnicki 2008; Yi et al. sidered). Nonetheless, there is no study investigating the effect of
2008; Su et al. 2009; Choi and Kim 2011; Sadek et al. 2011; UDL condition on two-dimensional (2D) beam-column structures
Stinger and Orton 2013; Valipour et al. 2013; Yu and Tan so far, although UDL has already been considered when studying
2013a, b; Bao et al. 2014; Lew et al. 2014; Ren et al. 2016; Kang three-dimensional (3D) beam-slab systems under progressive col-
and Tan 2016; Lu et al. 2017; Yu and Tan 2017) applied CL con- lapse (Pham and Tan 2013, 2015; Qian et al. 2016).
figuration in which the middle joint of the beam-column structure The important question is whether catenary action (CA) in 2D
received a push-down displacement. In these studies, the point load frames can be fully mobilized under the UDL case. In terms of fail-
from the column above was considered the main action causing ure modes, experimental studies on RC subassemblages under the
the collapse. However, Sasani and colleagues conducted three CL case showed fracture of bottom rebars at the middle joint re-
gion, followed by a sudden drop of structural capacity (Yu and Tan
1
Researcher, Vietnam Institute for Building Science and Technology, 2013a, b). Subsequently, as the deformation was kept increasing,
81 Tran Cung St., Cau Giay District, Hanoi, Vietnam. Email: anhtuanpham structural resistance increased again under CA mobilization, and a
.vn@gmail.com complete collapse occurred when beam top rebars fractured at the
2
Professor, School of Civil and Environmental Engineering, Nanyang supports. Nevertheless, the change of loading method from CL to
Technological Univ., 50 Nanyang Ave., Singapore 639798, Singapore
UDL may change this sequence of failure and the deformation
(corresponding author). Email: ckhtan@ntu.edu.sg
Note. This manuscript was submitted on November 21, 2016; approved shape of the double-span beam.
on June 5, 2018; published online on November 9, 2018. Discussion period Although dynamic tests are closer to the nature of progressive
open until April 9, 2019; separate discussions must be submitted for indi- collapse than static tests, very few were conducted mainly due to
vidual papers. This paper is part of the Journal of Structural Engineering, complexity and safety concerns of the test setup. Moreover,
© ASCE, ISSN 0733-9445. dynamic tests are force controlled; that is, each test can only be

© ASCE 04018235-1 J. Struct. Eng.

J. Struct. Eng., 2019, 145(1): 04018235


conducted with a predefined value of applied load and can only 2.4 m. Thus, the double-span beam was 4.8 m. Side columns
provide one corresponding displacement profile of the frame and with a dimension of 180 × 180 mm2 and beam extensions were
beam. Despite laboratory constraints, some research works have provided at two ends of the double-span beam to simulate a sub-
been conducted on free-fall dynamic tests to compare with corre- structure from an RC multistory building, as shown in Fig. 1. Three
sponding static specimens that had the same structural design and deformed bars T10 with a diameter of 10 mm were arranged as top
boundary condition (Tian and Su 2011; Qian and Li 2012; reinforcement at each beam end. They were reduced to two T10 at
Sagiroglu 2012; Orton and Kirby 2014). However, such studies curtailment points 650 mm away from the beam-column interfaces.
often used different loading methods, that is, CL displacement- Only two T10 bars were used for beam bottom rebars and were
controlled method for the static tests but multipoint loading for continuous along the double-span beam. The respective lengths
the dynamic tests. As a result, it was difficult to directly compare of side columns and beam extensions were chosen at contra-
the structural responses of the two different loading arrangements flexural points, that is, half-length for columns and 0.21 span for
although the specimens had the same design and boundary beam extensions, so that only pin and horizontal supports were
conditions. needed at such locations. Mild steel bars of 6-mm diameter (R6)
To study the resistance of RC beam-column structures against were used as stirrups in the double-span beam and side columns.
a single-column-removal scenario under both types of loading To avoid shear failure, stirrup spacing near the joint interfaces was
Downloaded from ascelibrary.org by Sergio Barreiro on 01/07/19. Copyright ASCE. For personal use only; all rights reserved.

configurations, that is, UDL and CL, an experimental program was reduced from 120 to 50 mm.
conducted at Nanyang Technological University. The first part To simulate distributed loads acting on the structure, a four-
of the program, which investigated dynamic structural responses point loading method was used in both the static and the dynamic
under CL condition, is reported in Pham and Tan (2017). The tests. Distances between the four applied loads were chosen to be
second part, which included two test series under UDL condition, equal along the double-span beam. An elastic analysis comparing
is presented in this paper. The first series included two specimens deformation shape and moment distribution of a structure subject to
under quasi-static condition, whereas the second series comprised UDL and four-point loading was carried out (Fig. 2). It showed that
three specimens under free-fall dynamic condition. Total loads ap- the equivalent loading system produced an almost similar displace-
plied on the specimens were equally distributed into four points ment profile to that by UDL, whereby both methods were in rea-
along the double-span beam. To have a direct comparison with the sonable agreement in terms of bending moments at the beam ends
CL condition, the specimen design and boundary condition of the and the middle joints, as well as locations of contra-flexural point
tests conducted in this study, as well as those in Pham and Tan along the double-span beam.
(2017), followed the corresponding 2D static test series conducted For the quasi-static tests, a steel-beam load-transfer system was
by Lim et al. (2015). Whereas Pham and Tan (2017) confirmed the fabricated as shown in Fig. 3(a) to equally divide the load from an
structural response and failures observed in quasi-static condition actuator above to four roller points on the specimen. Such a setup
under CL configuration, the UDL static experiments conducted in ensured that the steel beams could translate and rotate without
this paper showed differences in structural behavior between the affecting the deformation shape of the double-span beam. In the
two loading methods (CL and UDL), focusing on the degree of dynamic tests, steel plates with fixed equal weights were hung to
mobilization of CA. Thereafter, the UDL dynamic test series veri- the specimens at four locations in accordance with the static tests,
fied the responses and failure modes observed in the static tests as shown in Fig. 3(b). Two types of boundary conditions, that is,
and elucidated the dynamic effects between the two loading rates full-restraint and partial-restraint, were applied for both test series.
(quasi-static and free-fall dynamic). Finally, the results from the For the full-restraint specimens, beam extensions were arranged at
dynamic tests were compared with predictions using the Izzuddin two sides of the double-span beam and were horizontally restrained
method (Izzuddin et al. 2008) to verify this approach. by either an A-frame or a strong wall to simulate the loss of an
interior column in which horizontal restraints from adjacent struc-
tures were appropriately provided at both sides. Fig. 3(a) illustrates
Experimental Program the test setup for a typical static full-restraint specimen with a sym-
metric arrangement of load pins and horizontal load cells. With this
instrumentation, vertical and horizontal forces from the supporting
Specimen Design and Test Setup
system were well captured. On the other hand, for the partial-
Because experimental work on progressive collapse requires com- restraint specimens, the beam extension was only designed for the
binations of several structural members and their boundary condi- left side [Fig. 3(b)]. As a result, the right-side column was only
tions, a scaled model for testing is normally applied in most horizontally supported at its top and bottom ends. This type of
experimental studies. In the current research, a scale factor of 1=3 boundary condition represented the removal of a next-to-outermost
was used for the frame specimens. Because the expected domi- column in which the horizontal restraint from one side is remark-
nant failure modes involved flexure and CA, size effect would ably weaker than the other side. To simulate axial forces on the side
not have a significant effect on structural behavior. Although the columns arising from gravity loads from the above floors in a build-
contribution of floor slabs is important to resist progressive col- ing, preloaded compressive forces were applied onto these columns
lapse, especially through the mobilization of tensile membrane ac- before testing through a hydraulic jack placed on top. The value of
tion under large deformations, previous experimental studies on 3D this column axial load, which was similar to the tests by Lim et al.
beam-slab systems had encountered a difficulty in differentiating (2015), was 200 kN. In the free-fall dynamic tests, the middle joint
the contribution of CA (in beams) and tensile membrane action was suspended from a reaction frame by a quick-release device
(in slabs). Therefore, a study on 2D frame structures (conducted [Item (2) from Fig. 3(b)], which could be suddenly yanked free
in the current research) is important to quantify the enhancement to release the connection. This type of release mechanism has been
of CA in beams before any 3D beam-slab structural test is car- successfully applied in a previous progressive collapse study by Liu
ried out. et al. (2016).
The specimen design of the static and the dynamic tests con- For the UDL static test series, two tests named as FR-U (full
ducted in this study consisted of a double-span beam with a cross restraint) and PR-U (partial restraint) were conducted. They corre-
section of 100 × 180 mm2 and a center-to-center single span of sponded with two CL static tests of full restraint (FR) and partial

© ASCE 04018235-2 J. Struct. Eng.

J. Struct. Eng., 2019, 145(1): 04018235


PL 15x180x180 PL 15x180x180
PVC pipes

80
Four 30 mm dia.
FULL-RESTRAINT SPECIMEN
R6@50 7
4T10 6

100
4R6 6a 3
760

650 650
90 60
2 PL 15x180x180
PL 15x100x180

40
3T10 1 2T10 3T10 5 5 PL 15

125
2 1 1 1 3
1560
180

180

100
125
R6@50 5 4
R6@50 7

2T10

40
1 2 3 8T13
Right-side of
4 4 8 partial-restraint specimen
620

4 PVC pipes Ø30

330 360 840 360 330


R6@50 5 R6@90 5 R6@120 5 R6@90 5 R6@50 5

300
PL 15x180x180 PL 15x180x180
Downloaded from ascelibrary.org by Sergio Barreiro on 01/07/19. Copyright ASCE. For personal use only; all rights reserved.

400 180 2220 90 90 2220 180 400

2400 2400
6 4T10 4R6 6a 7 R6@50 R6@50 9
2 1 3T10 1 2T10 3 1 3T10 8 3T13
7 R6@50

180
180

180

180

180
5 R6@90 5 R6@120 5 R6@50 8 2T13
7a R6@100
4 2T10 4 2T10 4 2T10 8 3T13
180 180
100 100 100

Fig. 1. Specimen design.

(a) (b)

Fig. 2. Comparison between UDL and four-point loading methods: (a) uniformly distributed load; and (b) four-point load.

restraint (PR) from Lim et al. (2015). For the UDL dynamic test information on the two static tests conducted by Lim et al. (2015).
series, three specimens, named as FDU1 to FDU3, were cast In terms of concrete grade, the tests presented in this study had
and tested. FDU1 and FDU3 represented partial-restraint frames higher cylinder strengths compared with tests from Lim et al.
and were tested under two applied load levels of 42 and 61 kN. (2015). Regarding reinforcement, both the current (Table 2) and
On the other hand, FDU2 was designed as a full-restraint specimen the previous studies had similar material properties.
and was tested with a total load of 55 kN. FDU1 was tested twice
with two different loads, whereas FDU2 and FDU3 were only
tested once. After the first release of FDU1 with an applied load Instrumentation
of 42 kN (FDU1-P/42), the second release (FDU1-P/61) caused The instrumentation setup of the UDL static and the UDL dynamic
a complete collapse to this specimen. Hence, FDU3-P/61 was con- tests were similar to that of the previous CL static tests in Lim et al.
ducted with the same boundary condition (partial restraint) and ap- (2015) [and in Pham and Tan (2017)]. Reaction forces were mea-
plied load (61 kN) as FDU1-P/61 to observe the dynamic behavior sured by using load pins and horizontal load cells, as shown in
again under pristine condition of the specimen. Table 1 summarizes Fig. 3. Total horizontal reactions from one side of the specimen
the parameters of both the static and the dynamic tests, as well as were calculated by summing all the horizontal forces acting on that

© ASCE 04018235-3 J. Struct. Eng.

J. Struct. Eng., 2019, 145(1): 04018235


Downloaded from ascelibrary.org by Sergio Barreiro on 01/07/19. Copyright ASCE. For personal use only; all rights reserved.

Fig. 3. Test setup: (a) static test (full-restraint specimen); and (b) free-fall dynamic test (partial-restraint specimen).

Table 1. Specimen properties


Specimen Concrete cylinder strength (MPa) Restraint condition Dynamic test Total dynamic load (kN)
FR 32.0 Full restraint Static by Lim et al. (2015)
PR 32.0 Partial restraint Static by Lim et al. (2015)
FR-U 46.6 Full restraint Static test
PR-U 45.0 Partial restraint Static test
FDU1a 44.5 Partial restraint FDU1-P/42 42
Partial restraint FDU1-P/61 61
FDU2 44.5 Full restraint FDU2-F/55 55
FDU3 51.0 Partial restraint FDU3-P/61 61
a
Specimen FDU1 was tested twice with two different applied loads.

Table 2. Material properties for the static and the dynamic tests
Diameter Yield strength, Elastic modulus, Yield strain, Tensile strength, Ultimate strain,
Rebar (mm) fy (MPa) Es (GPa) εy (%) f u (MPa) εu (%)
R6 6 352 220 0.162 539 19.2
T10 10 554 196 0.288 653 11.5
T13 13 535 188 0.285 615 8.5

© ASCE 04018235-4 J. Struct. Eng.

J. Struct. Eng., 2019, 145(1): 04018235


Static test Dynamic test

351

A1

250
650 920 650

750
Lh4 L1
180 300

180 300
L2 L3
Lh2 L5

Lh1 L4
350

350
Lv5 Lv4 Lv3 Lv2 Lv1 90 90 300 350 300 310 310 350 300

880
Lh3
450 200 200 520 200 200 450 L1 to L5: displacement transducers
440

A1: accelerometer
markers for slow-motion camera
Lv1 to Lv5: vertical displacement transducers
Lh1 to Lh4: horizontal displacement transducers
Downloaded from ascelibrary.org by Sergio Barreiro on 01/07/19. Copyright ASCE. For personal use only; all rights reserved.

(a)
Static test Dynamic test
middle middle Hs1 Hs2
joint joint
end end
joint joint
To Ti T1 T1a T2 Tm T3 T4a T4 T4 T3 Tm T2 T1 Ti To

Bo Bi B1 B1a B2 Bm B3 B4a B4 B4 B3 Bm B2 B1 Bi Bo
Section m

Section m
Section 1

Section 2

Section 3

Section 4

Section 4

Section 3

Section 2

Section 1
180 470 460 460 470 180 650 460 460 650

(b)

Fig. 4. Setup of instrumentation: (a) displacement measurement; and (b) strain measurement.

side. Each test showed that the total horizontal forces from the larger and significantly enhanced the capacity, the structure
left and right sides were similar even for the partial-restraint cases. reached the first peak at a MJD of about 0.4dbeam .
Displacement transducers were arranged along the double-span • Stage II: After attaining the peak of CAA, concrete crushing
beam and at the end-joint regions to measure vertical and horizontal started occurring at compressive zones of the end joints, causing
deformations of the structure [Fig. 4(a)]. Strain gauges were placed structural capacity to gradually reduce. This stage finished at a
along the beam longitudinal bars at five critical sections [Fig. 4(b)]: MJD of one dbeam when structural response started increasing
end-joint interface (Section 1), rebar curtailment point near the again (for both FR-U and PR-U), indicating a transformation
end joint (Section 2), rebar curtailment point near the middle joint from CAA to CA. In both stages, there were little discernible
(Section 3), middle-joint interface (Section 4), and mid-single-span differences between full- and partial-restraint specimens.
section (Section m). Dynamic data acquisitions at a sampling rate • Stage III: In this stage, horizontal reaction changed from com-
of 1,000 Hz were used in the dynamic tests. To measure the release pression to tension, and the structural capacity kept increasing
time of the device, two strain gauges (HS1 and HS2) were attached under the mobilization of CA. The first failure mode took place
to the hooks on top of the middle joint. when the first top rebar from one end joint fractured, hereafter
called “first top rebar fracture,” causing a sudden drop in struc-
tural capacity. This failure occurred earlier in PR-U (at 275-mm
Static Test Results of FR-U and PR-U MJD) than in FR-U (318 mm). From this point on, structural
responses of FR-U and PR-U differed significantly. Under in-
creasing displacement, the load-carrying capacity of FR-U in-
Overall Behavior creased but that of PR-U decreased until all the top rebars at
Total applied loads and total horizontal reactions measured from the end joint from one side fractured completely, hereafter called
the two UDL static tests are presented in Fig. 5 together with those “one-side top rebar fracture.” The increase of MJD after this
from the relevant CL tests of FR and PR (Lim et al. 2015) for com- point led to no further noticeable increase of structural capacity.
parison. Focusing on the static tests FR-U and PR-U, the general All the critical points of response from the UDL static tests are
frame behavior subjected to UDL can be summarized into three listed in Table 3, together with the relevant values from the CL
stages: static tests. It was clearly observed that vertical applied loads of
• Stage I: From the beginning of loading when the structure was the UDL tests under both boundary conditions were similar to
elastic under flexure until it gained its first peak due to compres- each other until rebar fracture took place, and were slightly more
sive arch action (CAA). In this stage, the structure was about to than twice those of the CL tests [Fig. 5(a)]. In addition, MJDs
attain yield at a middle-joint displacement (MJD) of 0.25dbeam , corresponding to different stages of response (yielding point,
marked by the yielding of tensile rebars at both Sections 1 and 4 end of Stage I, and end of Stage II) were comparable between
[Fig. 4(b)]. When the compression force in the beam became the two loading methods, as shown in Fig. 5(a) and Table 3.

© ASCE 04018235-5 J. Struct. Eng.

J. Struct. Eng., 2019, 145(1): 04018235


Downloaded from ascelibrary.org by Sergio Barreiro on 01/07/19. Copyright ASCE. For personal use only; all rights reserved.

Fig. 5. General responses of static tests: (a) vertical applied load; and (b) total horizontal reaction.

Table 3. Summary of static test results


Bottom rebar One-side top rebar
Yielding point Maximum CAA fracture First top rebar fracture fracture Horizontal force (kN)
Beam-end
MJD Applied MJD Applied MJD Applied MJD Applied rotation MJD Applied Maximum Maximum
Test (mm) load (kN) (mm) load (kN) (mm) load (kN) (mm) load (kN) (degree) (mm) load (kN) compression tension
FR-U 44 53.9 74 56.45 N/A N/A 318 77.9 9.1 368.0 100.3 −28.3 81.9
PR-U 42 55.4 76 59.20 N/A N/A 275 67.8 9.1 286.3 44.6 −25.8 49.5
FR 44 24.7 70 27.40 230 26.4 549 70.9 8.6 a a
−28.5 148.8
PR 56 25.4 80 26.90 329 33.9 N/A N/A N/A N/A N/A −20.0 54.3
Note: N/A = top/bottom rebar fracture did not occur in the test.
a
All top rebars fractured together.

However, bottom rebar fracture at the middle joint, which occurred cracks at the end joint (Section 1) did not propagate significantly
in the CL static tests of Lim et al. (2015) and in all reported CL tests toward the curtailment points (Sections 2 and 3) in the UDL tests.
in the literature, did not occur in the UDL static tests. Hence, it can In the CL tests, this top-surface crack propagation was obvious.
be considered as the key difference between the two loading sce- However, bottom-surface cracks from the CL tests only occurred
narios. In terms of horizontal reaction, the UDL and the CL static near the middle joint (Section 4), much fewer than those at the
tests had relatively similar values [Fig. 5(b)], and maximum com- middle joint of the UDL tests. To further study the development
pression forces during the CAA stage between the two loading of tensile zones in the structure in the flexure/CAA stage, compres-
methods agreed well with each other (Table 3). However, the maxi- sion and tension zones of FR-U and FR were plotted according to
mum MJD from FR-U was noticeably smaller than that from FR. strain gauge readings from beam longitudinal bars (Fig. 7). It was
As a result, the maximum tension force of the horizontal reaction in assumed that, at this stage, the beam sections still remained plane
FR-U was 45% smaller than that in FR. Regarding partial-restraint and strain distribution along each section was linear. During the
specimens, the MJD and the horizontal reaction of PR-U at the elastic range (0.1dbeam ), tension zones from the two loading cases
maximum capacity was 16% and 9% smaller than those of PR, were relatively similar. As MJD increased to 0.25 and 0.4dbeam , the
respectively. However, after attaining the stage of bottom rebar tension zone near the end joint in FR quickly expanded toward the
fracture in the PR test, the partially restrained side column started middle joint. However, in FR-U, the trend was opposite, with
moving inward under CA. Because the structural capacity had no the tension zone near the middle joint quickly propagating toward
sign of increase, the test was stopped to prevent excessive column the end joint. This difference in the development of tensile region
lateral movement. As a consequence of this early termination, accounted for the difference of crack distribution between the two
the maximum applied load and horizontal reaction of PR were ap- loading methods during flexure/CAA.
proximately 48% and 37% of the corresponding values from FR. At a beam section with a distance Li from the side-column cent-
In contrast, the difference between PR-U and FR-U was less (68% roid, bending moment M i was calculated according to recorded
and 60% for applied load and horizontal reaction, respectively). reaction forces and corresponding vertical deformation δ i at this
section, as shown in Fig. 8(a). As a result, M i at the end-joint inter-
face and at the locations of displacement transducers [Lv1 to Lv5
Damage Patterns and Failure Modes
in Fig. 4(a)] was calculated to obtain the bending moment distri-
Fig. 6 describes the final damage patterns and failure modes of the bution along the beam. Fig. 8(b) shows this distribution at an MJD
UDL static tests together with the corresponding CL static tests. of 0.25dbeam (yielding state) for both FR-U and FR tests. It agrees
During Stages I and II, it was observed that top-surface flexural well with the development of concrete tension zone presented in

© ASCE 04018235-6 J. Struct. Eng.

J. Struct. Eng., 2019, 145(1): 04018235


1
2
m
4 3
(a)

1
2
m
4 3
(b)
Downloaded from ascelibrary.org by Sergio Barreiro on 01/07/19. Copyright ASCE. For personal use only; all rights reserved.

1
2
m
3

4
(c)

1
2
m
3
4
(d)

Fig. 6. Final failure modes of static tests: (a) FR-U; (b) PR-U; (c) FR; and (d) PR.

(a) (b)

Fig. 7. Tensile zone development in static tests: (a) FR-U (UDL); and (b) FR (CL).

Fig. 7. The bending moment distribution in FR-U followed a para- After the MJD had exceeded one beam depth, the horizontal
bolic shape, whereas that of FR was linear with a steep curvature reaction gradually changed to tension, and there were only few
at midspan. Compared with FR, FR-U shows a more uniform new cracks occurring in the UDL tests. Instead, opening of existing
distribution of bending moment at the middle-joint region. This cracks was more dominant. When the top rebars started fracturing
explains why flexural cracks were more equally spaced out in at one end joint, bottom-surface cracks near the middle joint propa-
FR-U [Fig. 6(a)]. gated toward Section 2. This crack propagation can be explained by

© ASCE 04018235-7 J. Struct. Eng.

J. Struct. Eng., 2019, 145(1): 04018235


LH3 LH3

LH2 LH2

LH1 LH1

LV LV
Downloaded from ascelibrary.org by Sergio Barreiro on 01/07/19. Copyright ASCE. For personal use only; all rights reserved.

(a)
Section m

Section m
Section 2

Section 3

Section 4

Section 4

Section 3

Section 2
Section 1

Section 1
450 400 520 400 450 450 400 520 400 450

Lv5 Lv4 Lv3 Lv2 Lv1 Lv1 Lv2 Lv3 Lv4 Lv5

middle
end end
joint joint joint

(b)

middle
end end
joint joint joint

(c)

Fig. 8. Moment distribution of the specimens under CL and UDL conditions: (a) bending moment at typical sections of RC frames; (b) moment
distribution at MJD ¼ 0.25dbeam (kN m); and (c) moment distribution at MJD ¼ 2dbeam (kN m).

the moment distribution of the beam at an MJD of 2dbeam , that is, displacement profiles, whereas the CL tests showed a rigid-link
at a large deformation stage [Fig. 8(c)]. After the first top rebar type of deformation, the UDL tests exhibited the usual parabolic
fracture of FR-U at 318 mm (1.8dbeam ), bending moment at the end shape.
joint reduced, shifting contra-flexural point toward the end joint, When examining the two UDL static tests [Figs. 6(a and b)],
which caused propagation of bottom-surface cracks. On the other there were fewer flexural cracks at the end joint in PR-U compared
hand, for FR, the bottom rebars had completely fractured at this with FR-U, suggesting greater strain concentration at the beam-
stage of deformation causing nearly zero bending moment at the column interface of PR-U. Therefore, the top rebars started fractur-
middle joint and negative bending moment along the entire beam. ing earlier in PR-U at 275 mm (1.5dbeam ) than in FR-U at 318 mm
As a result, top-surface cracks extensively developed in FR during (1.8dbeam ). Moreover, because the collapse of PR-U came from the
Stage III. There was no major failure (concrete crushing or rebar fracture of top rebars at one end joint, its partially restrained column
fracturing) at the middle-joint regions of the UDL tests. On the underwent little inward movement. This inward column movement
other hand, in the CL tests (FR and PR), top-surface cracks propa- was more significant in PR.
gated throughout curtailment regions after the bottom rebars had Structural responses of UDL and CL static tests were also com-
fractured. Full-depth tension cracks also occurred in these tests, pared at the cross-sectional level by studying the top and bottom
illustrating that some beam sections were already under pure reinforcement strains along the double-span beam (Fig. 9). In FR,
tension. In contrast, there were no full-depth cracks for FR-U and top rebars in curtailment points (T2, Tm, and T3) yielded quickly
PR-U, indicating lower development of tensile force. Regarding after the fracture of bottom rebars at an MJD of 230 mm [Fig. 9(a)],

© ASCE 04018235-8 J. Struct. Eng.

J. Struct. Eng., 2019, 145(1): 04018235


MJD (mm) MJD (mm)
5000 5000
4000
4000 yield strain

Strain of reinforcement (µ)

Strain of reinforcement (µ)


3000
yield strain 2000
3000
1000
2000 0
T1
T2 -1000 0 100 200 300 400 500 600
1000 Tm
T3 -2000 B1
T4 B2
-3000 yield strain Bm
0
0 100 200 300 400 500 600 -4000 B3
B4
-1000 -5000
(a) (b)
Downloaded from ascelibrary.org by Sergio Barreiro on 01/07/19. Copyright ASCE. For personal use only; all rights reserved.

MJD (mm) Deflection (mm)


5000 5000
T1 4000
T2 yield strain
Strain of reinforcement (µ)

4000

Strain of reinforcement (µ)


T3 3000
yield strain T4 2000
3000
1000
2000 0
-1000 0 100 200 300 400
1000 -2000
B1
B2
-3000 Bm
0 yield strain B3
0 100 200 300 400 -4000
B4
-1000 -5000
(c) (d)

Fig. 9. Comparison of rebar strains between CL and UDL static tests: (a) top rebars of FR; (b) bottom rebars of FR; (c) top rebars of FR-U; and
(d) bottom rebars of FR-U.

accounting for the occurrence of top-surface cracks at this region PR-U, and FR. Because top rebars did not fracture in PR, the
[Fig. 6(c)]. On the other hand, in FR-U, these rebars remained elas- rotation result of this test was not considered. It is shown that the
tic until the end of the test [Fig. 9(c)]. As a result, negative-moment beam-end rotations at the first top rebar fracture, denoted as θmax ,
plastic hinges did not form at the curtailment points in the UDL were relatively similar among all the three tests [approximately 9°
tests [Figs. 6(a and b)]. Thus, curtailment of top rebars at the middle (Table 3)], although the failure occurred at different MJDs when
zone of the single span (Fig. 1), which had a significant effect comparing the UDL and the CL tests. The horizontal reactions of
on deflected shape under CL condition, had almost no effect the two loading cases at this state are described in Fig. 11 and de-
under the UDL case. Concerning the beam bottom reinforcement pend on the resultant forces from top (Fatop ) and bottom (Fabot )
[Figs. 9(b and d)] in FR and FR-U, the development of rebar tensile rebars at Section 1 of Fig. 4(b). From Fig. 9(b and d), Fabot (rep-
strain at Section 3 (B3) during Stages I and II was limited in FR resented by Strain gauge B1) was in tension in FR and in compres-
than in FR-U. It agreed well with the bending moment in Fig. 8(a), sion in FR-U at this state. As a result, horizontal reactions of
which shows a more uniform distribution of negative moment near FR (H CL ) and FR-U (HUDL ) are calculated using Eqs. (1) and (2),
the middle joint in FR-U. Before the top rebar fracture in FR (MJD respectively, as follows:
of 549 mm), the bottom rebar at Section 1 (B1) already changed
from compression to tension, showing that the entire beam section H CL ¼ cosðθmax ÞðFatop þ Fabot Þ ð1Þ
at the end joint was in tension at this stage. However, in FR-U, B1
was still in compression until the end of the test (MJD of 368 mm),
indicating that tensile force was not yet fully developed throughout HUDL ¼ cosðθmax ÞðFatop − Fabot − Fc Þ ð2Þ
the end-joint section.
where Fc = resultant force of concrete region in compression at
beam bottom surface.
Beam-End Rotation and Horizontal Reaction at Top
At the state of top rebar fracture, it is assumed that Fatop had
Rebar Fracture
reached the ultimate tensile capacity of reinforcement for both load-
The behaviors of the UDL and the CL static tests at the state of final ing cases. As a consequence, if the maximum beam-end rotation
collapse(i.e., top rebar fracture) were investigated via relative rota- θmax was assumed to be equal in both cases, HCL would be obvi-
tion θ between the beam end and the end joint; θ was measured in ously larger than HUDL . In the static tests when the specimens
the tests by two displacement transducers Lm1 and Lm2 arranged failed, HCL and HUDL were 148.8 and 81.9 kN, respectively. There-
at this location, as shown in Fig. 10(a). The development of this fore, although having the same beam-end rotation at the final stage
rotation with respect to MJD is presented in Fig. 10(b) for FR-U, of top rebar fracture, CA could not be fully utilized in the UDL tests

© ASCE 04018235-9 J. Struct. Eng.

J. Struct. Eng., 2019, 145(1): 04018235


end
joint

Lm2

Lm1
Downloaded from ascelibrary.org by Sergio Barreiro on 01/07/19. Copyright ASCE. For personal use only; all rights reserved.

(a) (b)

Fig. 10. Comparison of beam-end rotations at first top rebar fracture: (a) measurement method; and (b) rotation responses.

end end
joint joint

(a) (b)

Fig. 11. Total horizontal reaction and rebar forces at the end joint at state of first top rebar fracture: (a) CL case; and (b) UDL case.

unlike in the CL tests because part of the end-joint section was still where M mid and M end = plastic bending moment capacities at the
under compression. middle and the end joints, respectively. They can be simply calcu-
lated on the basis of the equation proposed by Paulay and Priestley
Analytical Relationship of Structural Behaviors (1992) as follows:
between UDL and CL Conditions
M ¼ As f y ðd − d 0 Þ ð5Þ
On the basis of the results of the beam-column tests under the
UDL (section “Static Test Results of FR-U and PR-U”) and CL where As and fy = area and yield strength of tension rebars, respec-
(Lim et al. 2015) cases, the relationship between behaviors from tively; and d and d 0 = distances from tension and compression
these two loading configurations was developed. The structural re- rebars to the extreme compressive fibre of concrete, respectively.
sponses at the initial yielding stage, large-deformation stage, and Based on Eqs. (3)–(5), the PCL and PUDL at yielding state of the
final failure stage were compared. The structural capacity of a specimens used in this study (Fig. 1) were equal to 28.5 and
double-span beam at the yielding point under both UDL and CL 57.0 kN, respectively, which are relatively similar to test results
conditions can be simply calculated by assuming the formation (24.7 and 53.9 kN in Table 3).
of plastic hinges at both the middle and the end joints, as shown When the MJD is relatively large and the beam axial force starts
in Fig. 12(a). Hence, neglecting the effect of axial compression to significantly affect structural response, that is, during CAA and
force and basing on analytical relationships between applied loads CA stages, on the basis of the equilibrium of moment from half of
and moment distributions of the two cases, Eqs. (3) and (4) show the structure as illustrated in Fig. 12(b), the relationships between
that the total applied load from the UDL case (PUDL ) is twice that of total applied loads and horizontal reactions can be described as
the CL case (PCL ) follows:

PCL ð2LÞ 2ðM mid þ M end þ HCL δ CL Þ


¼ M mid þ M end ð3Þ PCL ¼ ð6Þ
4 L

qð2LÞ2 PUDL ð2LÞ 4ðM mid þ M end þ HUDL δ UDL Þ


¼ ¼ M mid þ M end ð4Þ PUDL ¼ ð7Þ
8 8 L

© ASCE 04018235-10 J. Struct. Eng.

J. Struct. Eng., 2019, 145(1): 04018235


(a)
Downloaded from ascelibrary.org by Sergio Barreiro on 01/07/19. Copyright ASCE. For personal use only; all rights reserved.

(b)

Fig. 12. Relationship between CL and UDL responses: (a) moment distribution at yielding point; and (b) force equilibrium at large deformation.

where H CL and HUDL = horizontal reactions for the CL and UDL Measuring Location (m)
cases, respectively; and δ CL and δUDL = MJDs from the CL and 0 0.5 1 1.5 2 2.5
UDL cases, respectively. 0
From the static tests results [Fig. 5(b)], HCL and H UDL were -50
relatively similar for the same MJD (i.e., δCL ¼ δ UDL ) before
Vertical deflection (mm)

any rebar fracture occurred. Applying this observation, from -100


Eqs. (6) and (7), PUDL is equal to 2PCL , which was also observed -150
in the static test results for large MJDs, that is, Stages II and III
-200
[Fig. 5(a)].
Regarding maximum MJD of the static tests at the failure state -250
of top rebar fracture (θ ¼ θmax ), if the displacement profile of
-300
the CL case follows a linear function defined in Eq. (8), then the FR-U (test)
corresponding MJD of this loading case at θmax can be calculated -350 FR-U (analytical)
according to Eq. (9) as follows: -400
δ
y ¼ CL ðx − LÞ ð8Þ Fig. 13. Displacement profiles under UDL.
L

maxðδ CL Þ ¼ tanðθmax Þ · L ð9Þ


horizontal reaction is similar between the two loading conditions.
To analytically predict the displacement profile of UDL tests, This relationship is valid not only at the yielding stage but also at
a second-order function presented in Eq. (10) is used, which agrees the CAA and the CA stages, until fracture starts occurring at either
reasonably well with actual displacement profiles (Fig. 13). The top rebars (UDL) or bottom rebars (CL). At the final stage of
corresponding MJD at θmax applying the second-order function catenary action (top rebar fracture), maximum deformation of the
is presented in Eq. (11). Hence, if it is assumed that θmax is similar UDL case can be conservatively equal to half of that from the CL
for both loading cases at the stage of first top rebar fracture, case. The relationship on structural behavior between the two load-
maxðδ UDL Þ is equal to 0.5 of maxðδ CL Þ. The test results from ing cases is important for studying frame responses under UDL
FR-U and FR indicated that this ratio was 0.58 (Table 3), which because no static experimental study has been previously con-
shows that the proposed method to predict the maximum displace- ducted for this loading method.
ment under UDL based on that under CL is conservative
δ UDL 2
y¼ ðx − L2 Þ ð10Þ Dynamic Test Results of FDU1 to FDU3
L2

L Overall Responses
maxðδ UDL Þ ¼ tanðθmax Þ · ð11Þ
2
Before conducting the dynamic tests, axial loads were applied to
In summary, at the same MJD, the vertical load–carrying ca- the side columns via a hydraulic jack installed on each side column.
pacity of the UDL case is twice that of the CL case, whereas total At the same time, temporary supports for the steel-plate systems

© ASCE 04018235-11 J. Struct. Eng.

J. Struct. Eng., 2019, 145(1): 04018235


Table 4. Summary of dynamic test results
Initial total Damping Maximum Maximum
Applied vertical Release Vibration ratio of vertical horizontal
load reaction time, period, vibration Maximum Residual reaction reaction
Test (kN) (kN) tr (ms) T d (ms) tr =T d phase (%) MJD (mm) MJD (mm) (kN) DLIF (kN)
FDU1-P/42 42 20.5 70 285 0.25 3.5 36 30.4 54.4 1.30 −0.3a
FDU1-P/61b 61 25.6 70 Collapse 74.9
FDU2-F/55 55 27.8 22 305 0.07 3.5 250 248.0 61.1 1.11 21.2
FDU3-P/61c 61 29.0 65 305 0.21 3.5 485 480.0 76.7 1.26 75.1
a
Only compression force was mobilized.
b
Second release of specimen FDU1.
c
Axial force of side column lost after the test.
Downloaded from ascelibrary.org by Sergio Barreiro on 01/07/19. Copyright ASCE. For personal use only; all rights reserved.

underneath the specimen [Item (9) in Fig. 3(b)] were slowly re- reactions from the other tests changed from negative to positive,
moved. As a result, self-weights from the steel plates were first car- illustrating the onset of CA. For FDU1-P/61, which was the second
ried by the single span, causing initial readings in the pin supports, test of specimen FDU1 and was the only one that totally collapsed,
as shown in Table 4, which summarizes important results of the both the vertical and the horizontal reactions dropped significantly
dynamic tests. After readings from all data channels were stable, at 0.67 s, denoting a complete failure of the specimen. Thereafter,
the rope from the quick-release device was suddenly yanked free, the specimen hit the strong floor at 1.035 s. For specimens that
releasing the specimen in a free-fall movement. If there was no fail- survived the free fall, their maximum vertical reactions were di-
ure, the specimen vibrated freely in its final deformation position vided by their applied loads to calculate the dynamic load increase
and slowly came to rest under damping effect. Otherwise, the struc- factor (DLIF), which measured the inertial effect of applied weights
ture lost its bearing capacity and dropped to the floor with a loud on the structures. This factor ranged from 1.11 to 1.30, as shown
thud. Overall deformations of all the dynamic tests are shown in in Table 4.
Fig. 14(a). Among the four dynamic tests, only FDU1-P/42 with
42 kN of loads sustained a small deformation. The others were
under higher loads of 55 and 61 kN and attained maximum MJDs Structural Damages and Failure Modes
larger than one beam depth, indicating that the structures already Structural damages, failure modes, and deflected shapes of all the
entered into Stage III of response. The release duration tr of the UDL dynamic tests had good resemblance with the corresponding
quick-release device, measured by strain gauges attached on the UDL static tests, as shown in Fig. 16. The first release of the partial-
middle-joint hooks, was compared with fundamental period T d restraint specimen FDU1 under 42 kN of applied load only caused
of the specimens during the vibration stage (Table 4). It was found minor flexural cracks to the structure. There was no sign of concrete
that tr =T d did not exceed 0.25 for all the surviving specimens, crushing, indicating that the specimen had not yet reached its maxi-
indicating that the release duration was significantly smaller than mum capacity under CAA. After the first test, FDU1 was pulled
the natural period of vibration (Biggs 1964). The damping ratio of back up to its original position. The second release of this specimen
the oscillating phase was defined on the basis of the logarithmic was under 61 kN, which led to a complete collapse. The specimen
decrement method and was approximately equal to 3.5% for all experienced multiple severe damages including the fracture of
specimens [Table 4 and Fig. 14(b)]. top rebars at the left-side end joint and the fracture of all sectional
On the basis of the load-pin and load-cell readings, the total rebars at the right-side end joint. However, its partially restrained
vertical reactions and total horizontal reactions from the left side column experienced less inward movement effect, similar to the
of all dynamic tests were defined and plotted in Fig. 15. Whereas corresponding static test PR-U. For FDU2-F/55, multiple cracks
the horizontal reaction of FDU1-P/42 was purely negative showing occurred at the end joints and in the two sides of the middle joint,
that the specimen was still under flexure/CAA stage, the horizontal together with concrete crushing at bottom surfaces of the end joints.

Time (s) Time (s)


0 1 2 3 4 0 1 2 3 4
0 0

FDU1 -P/42 -5
-100
-10
-200 FDU2 -F/55 -15
MJD (mm)

MJD (mm)

-300 -20
-25
FDU1 -P/61

-400
FDU3 -P/61 -30
-500
specimen collapsed -35
-600 -40
(a) (b)

Fig. 14. General responses of dynamic tests: (a) MJD time history; and (b) damping ratio (FDU1-P/42).

© ASCE 04018235-12 J. Struct. Eng.

J. Struct. Eng., 2019, 145(1): 04018235


Time (s) Time (s)
90 100
FDU1-P/42 FDU1-P/42
80 FDU1-P/61 FDU1-P/61
FDU2-F/55
80 FDU2-F/55

Horizontal reaction (kN)


70 FDU3-P/61

Vertical reaction (kN)


FDU3-P/61
60
60
50 40
40 20
30
0
20 0 1 2 3 4
10 -20
specimen hit the floor specimen hit the floor
0 -40
0 1 2 3 4
Downloaded from ascelibrary.org by Sergio Barreiro on 01/07/19. Copyright ASCE. For personal use only; all rights reserved.

(a) (b)

Fig. 15. Structural reactions from dynamic tests: (a) total vertical reaction; and (b) total horizontal reaction (left side).

(a)

(b)

(c)

(d)

Fig. 16. Damage patterns and failure modes of dynamic tests: (a) FDU1-P/42; (b) FDU1-P/61; (c) FDU2-F/55; and (d) FDU3-P/61.

However, no rebar fracture was observed. For FDU3-P/61 which column was not observed in the corresponding UDL static test
had identical boundary condition and applied load with FDU1- for PR-U [Fig. 6(b)], but occurred in the CL static test for PR
P/61, excessive vertical deflection (up to 485 mm) was captured, [Fig. 6(d)]. Nonetheless, after completing FDU3-P/61, the axial
together with severe concrete cracking and crushing. Top rebars at force on the partially-restrained side column was only 35% of its
the left-side end joint also fractured after the test. Under large original value, owing to a widening gap between the hydraulic jack
pulling-in effect from the double-span beam, the partially restrained and the steel plate on top of the column. This gap was created by
side column underwent an excessive deformation (up to 47 mm) excessive inward movement of the end joint, which caused mis-
and experienced severe concrete crushing at its outer face. How- alignment with the vertical axis. As a result, it was questionable if
ever, the specimen sustained the applied load, and no collapse took FDU3 had indeed survived the free fall since the column load had
place. Such behavior of large inward deformation for the side dropped significantly.

© ASCE 04018235-13 J. Struct. Eng.

J. Struct. Eng., 2019, 145(1): 04018235


Table 5. Summary of strain rates and DIF for rebars
Tensile rebars at Section 1 (end joint) Tensile rebars at Section 4 (middle joint)
DIF DIF
Maximum strain rate Yield Ultimate Maximum strain rate Yield Ultimate
Test (1=s) up to yielding strength strength (1=s) up to yielding strength strength
FDU1-P/42 0.224 1.175 1.056 0.06 1.143 1.046
FDU1-P/62 0.404 1.189 1.060 0.079 1.149 1.048
FDU2-F/55 0.490 1.194 1.062 0.097 1.154 1.050
FDU3-P/61 0.670 1.202 1.064 0.067 1.145 1.047

Strain Rate Effect on Material Strength Comparisons of Structural Responses between UDL
Static and UDL Dynamic Tests
Downloaded from ascelibrary.org by Sergio Barreiro on 01/07/19. Copyright ASCE. For personal use only; all rights reserved.

The material dynamic increase factors (DIFs) for rebar yield


strength due to strain rate effect was calculated on the basis of em- In the static tests, all data were collected corresponding to MJD; in
pirical equations proposed by Malvar (1998) [Eqs. (12) and (13)]. dynamic tests, they were recorded with respect to time. Therefore,
Strain rates were defined for beam reinforcement at Sections 1 to compare the behavior of the UDL static tests with the corre-
and 4 [Fig. 4(b)] up to the yield strain value. If the maximum strain sponding UDL dynamic tests at the structural level, data from dy-
rates used for yield strength were also applied to calculate rebar namic tests such as vertical and horizontal reactions were plotted
ultimate strength, the corresponding DIF was computed following with reference to MJD instead of time. Fig. 17 shows the compar-
Eq. (14). The results for maximum strain rates and DIFs are pre- isons between the dynamic tests under the applied loads of 42 and
sented in Table 5. Basically, the strain rates of tensile rebars at 55 kN with the static tests of FR-U and PR-U. Due to the initial
Section 1 (end joint) were greater than those at Section 4 (middle effect of applied weights distributing on the single span before the
joint). The maximum DIFs for rebar yield strength of Sections 1 release, which was mentioned in Fig. 15(a) and Table 4, vertical
and 4 were 1.20 and 1.15, respectively, because, under UDL con- reactions from the dynamic tests had initial nonzero values at zero
dition, bending moment was developed at a faster rate at the end MJD compared with vertical applied loads from the static tests.
joint than at the middle joint. Regarding rebar ultimate strength, the Other than that, responses of the vertical and horizontal reactions
enhancement was negligible, as the largest DIF was only 1.06. from both test series had reasonably good agreement. For the dy-
In other words, strain rate effect on reinforcement had some effect namic tests under 61 kN (Fig. 18), they also displayed a similar
on the flexure/CAA capacity of the structure via increasing rebar trend of response to the relevant static test for PR-U. The peaks
yield strength, but only marginal influence on CA capacity, which of CAA from the dynamic tests were larger than those from the
relies on rebar ultimate strength static tests by 8% and 14% for the full- and the partial-restraint
specimens, respectively. This could be due to the enhancement in
 α
ε̇ rebar yield strength, which led to an increase of plastic bending
DIF ¼ ð12Þ
10−4 moment resistances M mid and Mend , as explained in the section
“Strain Rate Effect on Material Strength.”
FDU1-P/61 and FDU3-P/61 had a sudden drop in structural
capacity (for both vertical and horizontal reactions) at an MJD of
fy
For yield strength∶ α ¼ αfy ¼ 0.074 − 0.040 ð13Þ 320 and 324 mm, respectively. It was assumed to be the state when
414 top rebars at the end joints started fracturing during these two
dynamic tests, which were comparable with PR-U and FR-U. The
beam-end rotations at this state were calculated as 9.4° and 9.6° for
fy FDU1 and FDU3, respectively. It is noteworthy that such rotations
For ultimate strength∶ α ¼ αfu ¼ 0.019 − 0.009 ð14Þ
414 had good agreement with those from the UDL and the CL static

MJD (mm) MJD (mm)


120 120
PR-U (vertical) FR-U (vertical)
100 100 FDU2-F/55 (vertical)
Applied load/Reaction (kN)

FDU1-P/42 (vertical)
Applied load/reaction (kN)

PR-U (horizontal) FR-U (horizontal)


80 FDU1-P/42 (horizontal) 80 FDU2-F/55 (horizontal)
60 60
40 40
20 20
0 0
0 50 100 150 200 0 100 200 300 400
-20 -20
-40 -40
(a) (b)

Fig. 17. Structural responses of dynamic tests with load levels of 42 and 55 kN: (a) full-restraint specimens; and (b) partial-restraint specimens.

© ASCE 04018235-14 J. Struct. Eng.

J. Struct. Eng., 2019, 145(1): 04018235


MJD (mm) MJD (mm)
90 100
80 80 PR-U

Vertical load/reaction (kN)

Horizontal reaction (kN)


70 FDU1-P/61
60 FDU3-P/61
60
50 40
40 20
30
PR-U 0
20 0 100 200 300 400 500
FDU1-P/61
-20
10 FDU3-P/61
0 -40
0 100 200 300 400 500
(a) (b)
Downloaded from ascelibrary.org by Sergio Barreiro on 01/07/19. Copyright ASCE. For personal use only; all rights reserved.

Fig. 18. Structural responses of dynamic tests with 61 kN: (a) vertical load/reaction; and (b) horizontal reaction.

tests (Table 3). After this failure, the structural responses of MJD (mm)
FDU1-P/61 dropped to zero, probably due to initial damages 70
FDU1-P/61 (collapsed)
caused by the first release. On the other hand, the structural 60
response of FDU3-P/61 did not drop to zero at the end of the FDU3-P/61

Applied load (kN)


50 FDU1-P/42
test, denoting that a complete collapse did not occur, although FDU2-F/55
the column axial load dropped to one-third of its original value. 40
30
Comparison between UDL Dynamic Tests Conducted
20
in This Study and CL Dynamic Tests in Pham and Tan
10
The load levels used in the dynamic tests in this study and in Pham
and Tan (2017) were different. Whereas the load levels in Pham and 0
Tan (2017) were 20, 25, and 30.5 kN for partial restraint and 20, 29, 0 200 400 600
and 34 kN for full restraint, those used in the UDL dynamic tests Pseudo-static (FR-U) Pseudo-static (PR-U)
were 40 and 61 kN for partial restraint and 55 kN for full restraint. Pseudo-static (FR) Pseudo-static (PR)
The reason for this difference is the difference in the load-carrying Dynamic tests
capacities between the CL and UDL cases observed for quasi-static
tests. In the free-fall dynamic tests, the loading levels were chosen Fig. 19. Comparison between pseudostatic predictions and actual
to maximize the behavior observed, from small deformation (com- dynamic tests.
pressive arch action) to large deformation (catenary action). There-
fore, the results from the CL dynamic tests could not be directly
compared with those from the UDL dynamic tests. In terms of boundary condition on UDL tests because the maximum MJD
damage patterns and rebar fracturing sequence, the CL dynamic from the UDL tests was significantly smaller than that from the
tests in Pham and Tan (2017) closely followed the CL static tests CL tests. When comparing the maximum dynamic capacities
in Lim et al. (2015), which were quite different from the UDL between the UDL and the CL tests predicted from the Izzuddin
dynamic tests. method, FR-U was 1.8 times larger than FR, and PR-U was 2.1
times larger than PR.
The maximum MJD versus applied load results from all the dy-
Comparison of Load-Carrying Capacity between namic tests were compared with the dynamic responses predicted
Actual Dynamic Tests and Simplified Energy-Based by the Izzuddin method, as shown in Fig. 19. Among the three load
Method levels applied in the dynamic tests, 42 kN was close to the predicted
dynamic capacity at the first peak of CAA (MJD of 0.4dbeam ),
The energy-based method proposed by Izzuddin et al. (2008) was 55 kN was almost equal to the ultimate dynamic capacity of both
applied to predict the pseudostatic behavior on the basis of the FR-U and PR-U, and 61 kN was slightly larger than these load
static responses of the UDL and the CL static tests, and the results limits (Fig. 19). The simplified method provided reasonable and
are illustrated in Fig. 19. It is shown that FR-U and PR-U had rel- conservative results compared with the actual dynamic capacities
atively identical dynamic responses with comparable maximum at load levels of 42 and 55 kN. For the applied load of 61 kN,
dynamic capacities. For FR-U, although the static peak of the one- whereas FDU1-P/61 showed a complete collapse, FDU3-P/61 sus-
side top rebar fracture was 29% larger than that of the first top rebar tained this load and possessed a higher MJD capacity than the pre-
fracture (Table 3), the difference for the corresponding dynamic diction from Izzuddin method. However, due to the loss of column
peaks was only 5%. Therefore, the state of first top rebar fracture axial force during the test, FDU3-P/61 could also be considered as
can be conservatively considered as the final failure mode for both having collapsed, making the load level of 61 kN exceed the actual
FR-U and PR-U. When comparing the difference of maximum dynamic capacity of the specimen. Therefore, for safety, predic-
dynamic capacity between the partial- and the full-restraint condi- tions from the Izzuddin energy-based method in the CA stage
tions, FR-U was only 7.5% larger than PR-U, whereas FR was 28% should be considered as the ultimate capacity that a structure can
larger than PR. Again, this emphasizes the weaker influence of reach under a sudden column removal scenario.

© ASCE 04018235-15 J. Struct. Eng.

J. Struct. Eng., 2019, 145(1): 04018235


Conclusions 140 (1): 04013026. https://doi.org/10.1061/(ASCE)ST.1943-541X
.0000773.
In this paper, a quasi-static and a free-fall dynamic test series were Biggs, J. M. 1964. Introduction to structural dynamics. New York:
conducted by applying equivalent UDL conditions. The results McGraw-Hill College.
from the UDL static tests were compared with previous CL static Choi, H., and J. Kim. 2011. “Progressive collapse-resisting capacity of RC
tests on similar specimens. In addition, dynamic response caused beam–column sub-assemblage.” Mag. Concr. Res. 63 (4): 297–310.
by the actual sudden removal of a supporting column was also in- https://doi.org/10.1680/macr.9.00170.
vestigated in the UDL dynamic tests. The following conclusions Izzuddin, B., A. Vlassis, A. Elghazouli, and D. Nethercot. 2008.
“Progressive collapse of multi-storey buildings due to sudden column
are highlighted:
loss. Part I: Simplified assessment framework.” Eng. Struct. 30 (5):
1. Using four-point loading method for RC frames reasonably 1308–1318. https://doi.org/10.1016/j.engstruct.2007.07.011.
simulated the UDL condition in actual structures. Kang, S. B., and K. H. Tan. 2016. “Analytical model for compressive
2. Differences between behaviors in CL and UDL methods in- arch action in horizontally restrained beam-column subassemblages.”
cluded load-carrying capacity, sequence of failure (no bottom ACI Struct. J. 113 (4): 813–826. https://doi.org/10.14359/51688629.
rebar fracture in UDL tests), deformation profile (linear in CL Lew, H., Y. Bao, S. Pujol, and M. A. Sozen. 2014. “Experimental study
but parabolic in UDL), and maximum deflection. The analytical of reinforced concrete assemblies under column removal scenario.”
Downloaded from ascelibrary.org by Sergio Barreiro on 01/07/19. Copyright ASCE. For personal use only; all rights reserved.

calculation in the UDL case confirms a 100% increase for ver- ACI Struct. J. 111 (1–6): 881–892.
tical applied load but a 50% reduction in maximum deflection Lim, N. S., C. K. Lee, and K. H. Tan. 2015. “Experimental studies on 2-D
compared with the CL case. However, the two loading methods RC frame with middle column removed under progressive collapse.”
provided similar horizontal reactions for the same displacement. In Proc., FIB Symp. 2015. Lausanne, Switzerland: International
Moreover, at the state of top rebar fracture, the UDL and CL Federation for Structural Concrete.
methods had the same beam-end rotation. This can be used as Liu, C., T. C. Fung, and K. H. Tan. 2016. “Dynamic performance of
the failure criterion for predictions. flush end-plate beam-column connections and design applications in
progressive collapse.” J. Struct. Eng. 142 (1): 04015074. https://doi
3. Catenary action, which was observed to significantly affect the
.org/10.1061/(ASCE)ST.1943-541X.0001329.
structural response under CL condition, showed a lesser degree
Lu, X., K. Lin, Y. Li, H. Guan, P. Ren, and Y. Zhou. 2017. “Experimental
of mobilization under UDL condition, leading to a weaker in- investigation of RC beam-slab substructures against progressive col-
fluence of boundary condition on structural response. lapse subject to an edge-column-removal scenario.” Eng. Struct. 149:
4. The release device used in the dynamic tests could simulate well 91–103. https://doi.org/10.1016/j.engstruct.2016.07.039.
the sudden loss of a supporting column. Dynamic effects of Malvar, L. J. 1998. “Review of static and dynamic properties of steel
applied loads were observed when comparing with the corre- reinforcing bars.” ACI Mater. J. 95 (5): 609–616.
sponding UDL static. Material DIFs due to strain rate effect Orton, S. L., and J. E. Kirby. 2014. “Dynamic response of a RC frame under
showed some increase for flexure/CAA capacity but little effect column removal.” J. Perform. Constr. Facil. 28 (4): 04014010. https://
on CA capacity. doi.org/10.1061/(ASCE)CF.1943-5509.0000464.
5. The dynamic tests displayed similar structural response, failure Paulay, T., and M. Priestley. 1992. Seismic design of reinforced concrete
modes, and displacement profile to those of corresponding UDL and masonry buildings. New York: Wiley.
static tests, showing that the increase of loading rate from a Pham, A. T., and K. H. Tan. 2017. “Experimental study on dynamic
quasi-static (10−4 =s) to a free-fall environment (up to 0.67=s) responses of reinforced concrete frames under sudden column removal
applying concentrated loading.” Eng. Struct. 139: 31–45. https://doi.org
did not change the mechanism or failure mode. The dynamic
/10.1016/j.engstruct.2017.02.002.
tests, although following a force-controlled manner, had a
Pham, X. D., and K. H. Tan. 2013. “Experimental study of beam–slab sub-
relatively similar trend of reaction responses to those of the structures subjected to a penultimate-internal column loss.” Eng. Struct.
static tests. 55: 2–15. https://doi.org/10.1016/j.engstruct.2013.03.026.
6. Dynamic capacities predicted by using the Izzuddin method Pham, X. D., and K. H. Tan. 2015. “Experimental response of beam-
provided accurate and conservative predictions compared with slab substructures subject to penultimate-external column removal.”
actual dynamic responses. Nonetheless, in engineering practice, J. Struct. Eng. 141 (7): 04014170. https://doi.org/10.1061/(ASCE)ST
the maximum load during CA stage calculated by this method .1943-541X.0001123.
should be considered as the ultimate capacity of a structure Qian, K., and B. Li. 2012. “Dynamic performance of RC beam-column
under sudden column loss scenarios. substructures under the scenario of the loss of a corner column—
Experimental results.” Eng. Struct. 42: 154–167. https://doi.org/10
.1016/j.engstruct.2012.04.016.
Acknowledgments Qian, K., B. Li, and Z. Zhang. 2016. “Influence of multicolumn removal on
the behavior of RC floors.” J. Struct. Eng. 142 (5): 04016006. https://
This study was financially supported by the research grant GPC: doi.org/10.1061/(ASCE)ST.1943-541X.0001461.
MHA 191/9/1/345 provided by Ministry of Home Affairs, Singa- Ren, P., Y. Li, X. Lu, H. Guan, and Y. Zhou. 2016. “Experimental
pore, as well as from the Grant 107.01-2018.01 provided by investigation of progressive collapse resistance of one-way reinforced
National Foundation For Science and Technology Development concrete beam–slab substructures under a middle-column-removal
(NAFOSTED), Vietnam. The authors greatly appreciate the finan- scenario.” Eng. Struct. 118: 28–40. https://doi.org/10.1016/j.engstruct
cial supports by both organizations. .2016.03.051.
Sadek, F., J. A. Main, H. S. Lew, and Y. Bao. 2011. “Testing and analysis of
steel and concrete beam-column assemblies under a column removal
References scenario.” J. Struct. Eng. 137 (9): 881–892. https://doi.org/10.1061
/(ASCE)ST.1943-541X.0000422.
Bao, Y., S. Kunnath, S. El-Tawil, and H. Lew. 2008. “Macromodel-based Sagiroglu, S. 2012. “Analytical and experimental evaluation of progressive
simulation of progressive collapse: RC frame structures.” J. Struct. Eng. collapse resistance of reinforced concrete structures.” Ph.D. disserta-
134 (7): 1079–1091. https://doi.org/10.1061/(ASCE)0733-9445(2008) tion, Dept. of Civil and Environmental Engineering, Northeastern Univ.
134:7(1079). Sasani, M. 2008. “Response of a reinforced concrete infilled-frame
Bao, Y., H. S. Lew, and S. K. Kunnath. 2014. “Modeling of reinforced structure to removal of two adjacent columns.” Eng. Struct. 30 (9):
concrete assemblies under column-removal scenario.” J. Struct. Eng. 2478–2491. https://doi.org/10.1016/j.engstruct.2008.01.019.

© ASCE 04018235-16 J. Struct. Eng.

J. Struct. Eng., 2019, 145(1): 04018235


Sasani, M., M. Bazan, and S. Sagiroglu. 2007. “Experimental and analyti- Valipour, H., N. FarhangVesali, and S. Foster. 2013. “A generic model for
cal progressive collapse evaluation of actual reinforced concrete struc- investigation of arching action in reinforced concrete members.” Constr.
ture.” ACI Struct. J. 104 (6): 731–739. Build. Mater. 38: 742–750. https://doi.org/10.1016/j.conbuildmat
Sasani, M., and J. Kropelnicki. 2008. “Progressive collapse analysis of .2012.09.046.
an RC structure.” Struct. Des. Tall Special Build. 17 (4): 757–771. Yi, W. J., Q. F. He, Y. Xiao, and S. K. Kunnath. 2008. “Experimental
https://doi.org/10.1002/tal.v17:4. study on progressive collapse-resistant behavior of reinforced concrete
Sasani, M., and S. Sagiroglu. 2010. “Gravity load redistribution and frame structures.” ACI Struct. J. 105 (4): 433–439..
progressive collapse resistance of 20-story reinforced concrete structure Yu, J., and K. H. Tan. 2013a. “Experimental and numerical investigation
following loss of interior column.” ACI Struct. J. 107 (6): 636–644. on progressive collapse resistance of reinforced concrete beam column
Stinger, S. M., and S. L. Orton. 2013. “Experimental evaluation of dispro- sub-assemblages.” Eng. Struct. 55: 90–106. https://doi.org/10.1016/j
portionate collapse resistance in reinforced concrete frames.” ACI .engstruct.2011.08.040.
Struct. J. 110 (3): 521. Yu, J., and K. H. Tan. 2013b. “Structural behavior of rc beam-column
Su, Y., Y. Tian, and X. Song. 2009. “Progressive collapse resistance of subassemblages under a middle column removal scenario.” J. Struct.
axially-restrained frame beams.” ACI Struct. J. 106 (5): 600–607. Eng. 139 (2): 233–250. https://doi.org/10.1061/(ASCE)ST.1943-541X
Tian, Y., and Y. Su. 2011. “Dynamic response of reinforced concrete beams .0000658.
following instantaneous removal of a bearing column.” Int. J. Concr. Yu, J., and K. H. Tan. 2017. “Structural behavior of reinforced concrete
Downloaded from ascelibrary.org by Sergio Barreiro on 01/07/19. Copyright ASCE. For personal use only; all rights reserved.

Struct. Mater. 5 (1): 19–28. https://doi.org/10.4334/IJCSM.2011.5 frames subjected to progressive collapse.” ACI Struct. J. 114 (1):
.1.019. 63–74. https://doi.org/10.14359/51689424.

© ASCE 04018235-17 J. Struct. Eng.

J. Struct. Eng., 2019, 145(1): 04018235

You might also like