Professional Documents
Culture Documents
B3 212 2014
B3 212 2014
B3 212 2014
http : //www.cigre.org
SUMMARY
Capacitor banks are critical substation assets that play a vital role in providing reactive power support,
thereby increasing the power system capacity. Capacitor banks are constructed as single-wye, double-
wye, or H-bridge configurations and can be grounded or ungrounded. Capacitor banks consist of a
number of single-phase capacitor units connected in series and parallel to achieve the desired voltage
and VAR rating. Similarly, each capacitor unit consists of a number of individual capacitor elements
connected in series and parallel. The capacitor units can be externally or internally fused, fuseless, or
unfused. Although modern capacitor units are more reliable than earlier units, faults within the units
and elements still occur. When the element overvoltages resulting from these unit or element failures
become too high, the capacitor bank needs to be taken out of service and the faulty units must be
replaced.
It is important that capacitor bank outage time be as short as possible. Normally, the majority of the
outage time is spent locating the faulty unit. Identifying the faulty unit in a capacitor bank helps return
the bank to service in a minimum amount of time. If the bank is externally fused, then the unit with the
blown fuse is usually the faulty unit, making identification obvious. If the bank is internally fused,
fuseless, or unfused, then fault location is very difficult because there is no visual indication of the
faulted unit. This results in an extended outage of the capacitor bank. Although it is not possible to
identify the faulty unit in an internally fused, fuseless, or unfused bank, identifying the faulted phase
and section helps minimize the outage time.
This paper analyzes various capacitor bank configurations and proposes a method to help locate the
faulty units for each configuration. The paper also provides results that verify the proposed methods
using a power system simulator.
KEYWORDS
Capacitor Bank Protection, Fault Location, Capacitor Unit
satish_samineni@selinc.com
1. INTRODUCTION
Capacitor banks are critical substation assets that play a vital role in providing reactive power support,
thereby increasing the power system capacity [1]. Capacitor banks consist of a number of series- and
parallel-connected single-phase capacitor units. The number of capacitor units in a bank depends on
the voltage and VAR ratings of both the bank and the capacitor units. Each capacitor unit consists of a
number of series- and parallel-connected capacitor elements. The capacitor units can be fused (external
or internal) or fuseless. Capacitor unit or element failures result in an overvoltage condition for the
remaining elements, and if the overvoltage is beyond the long-term withstand value of the element, a
protective relay operates to take the bank out of service. For an externally fused bank, the faulty unit is
the one with the blown fuse, but for internally fused or fuseless banks, there is no visual indication of
the faulty unit. So the majority of the bank outage time is spent in locating the faulty units. Although
identifying the faulty unit is not possible for internally fused or fuseless banks, identifying the phase
and section of the capacitor bank with the faulty unit or element reduces the fault location time
significantly, allowing the bank to be returned to service quickly.
2. FAULT LOCATION TECHNIQUE
Unbalance protection provides primary protection against unit or element failures in capacitor banks.
Phase voltage unbalance, neutral voltage unbalance, phase current unbalance, and neutral current
unbalance are the four commonly used unbalance protection schemes [2]. The choice of protection
scheme depends on various factors such as bank configuration, availability of instrument transformers,
sensitivity requirements, and so on. The unbalance protection scheme uses one or more of the
measured quantities from the instrument transformers to calculate the unbalance quantity. The
unbalance quantity magnitude is then compared to an alarm and trip threshold for unbalance protection.
The unbalance quantity magnitude indicates the number of failed elements or units within the bank.
The proposed fault location technique uses the phase angle of the unbalance quantity and compares it
with a reference phase angle to identify the phase and section of the bank that has the faulty unit [3]
[4]. The fault location technique is supervised with an alarm or trip condition from unbalance
protection for security. If the bank is protected with the phase voltage or phase current unbalance
protection scheme, then phase voltage (bus) or phase current (bank) is used as the reference phasor. If
the bank is protected with the neutral voltage or neutral current unbalance protection scheme, then
positive-sequence bus voltage or positive-sequence bank current is used as the reference phasor. The
unbalance phase angle is referenced to the reference phase angle. The referenced unbalance phase
angle is then checked to determine if it is in Sector 1 (0° ± 15°), Sector 2 (180° ± 15°), Sector 3
(–120° ± 15°), Sector 4 (60° ± 15°), Sector 5 (120° ± 15°), or Sector 6 (–60° ± 15°), as shown in
Fig. 1. The sectors are formed by a ±15-degree blinder that is applied for security to exclude
unbalances not resulting from capacitor failures, such as instrument transformer errors. Depending on
the type of unbalance protection scheme, the unbalance phasor can be in any of the six sectors and
gives unique fault location information. The fault location information can be included as part of the
relay event report and can be used by the utility crew. The fault location technique is embedded as part
of the unbalance protection, and hence, it is an economical solution.
Fig. 1. Fault Location Technique Based on Phase Angle Between Unbalance Phasor and Reference Phasor
1
The fault location technique is affected by the fusing method of the bank (i.e., whether it is fused or
fuseless). The fault location technique is not affected by the inherent bank unbalance as long as the
unbalance protection compensates for it [2]. The bank operators are advised to save the fault location
information before resetting the unbalance alarm, or the relay compensating for the inherent unbalance
will forget the preexisting failure and its location.
A power system was modeled using a power system simulator and was used to validate the fault
location techniques for various capacitor bank configurations.
3. PHASE VOLTAGE UNBALANCE PROTECTION APPLIED TO SINGLE-WYE
BANKS
Fig. 2 shows a single-wye-connected grounded capacitor bank with a potential transformer (PT) at the
tap point. This configuration uses a phase voltage unbalance protection scheme. The tap point can be
at the midpoint or at a low voltage capacitor just above the wye connection. The faulty unit can be in
any of the six locations in this bank, as shown in Fig. 2.
2
Fig. 3. Fault Location in Bank Using Phase Voltage Unbalance Protection (Top Section, Phase A)
3
Fig. 5. Fault Location in Bank Using Neutral Voltage Unbalance Protection (Phase C)
4
Fig. 7. Fault Location in H-Bridge Bank Using Phase Current Unbalance Protection (Top Left or
Bottom Right Section, Phase A)
Fig. 8. Fault Location in H-Bridge Bank Using Phase Voltage and Phase Current Unbalance Protection
(Top Left Section, Phase A)
5
7. PHASE CURRENT UNBALANCE PROTECTION APPLIED TO SINGLE- OR
DOUBLE-WYE BANKS
Fig. 9 shows a single-wye grounded bank with a CT in each phase. The unbalance protection and fault
location technique are the same as for the H-bridge bank, but there are no top or bottom sections. The
faulty element or unit can be in any of six locations with respect to the phase CT, as shown in Fig. 9.
This fault location technique reduces investigation time by up to 83.3 percent (one out of six possible
fault locations).
6
Fig. 11. Fault Location in Bank Using Neutral Current Unbalance Protection (Left Section, Phase B)
9. CONCLUSION
The phase angle of the unbalance quantity from the unbalance protection provides important
information about the location of failed units in the bank. This paper proposes a fault location
technique that can be applied to various capacitor bank configurations using different unbalance
protection schemes and fusing methods. The fault location technique can reduce the investigation time
between 66 and 92 percent, depending on the bank configuration. The fault location technique is
embedded as part of the unbalance protection, making it an economical solution. The fault location
technique is not affected by the inherent bank unbalance as long as the unbalance protection
compensates for it. The fault location technique helps in providing advance alarms for planned
maintenance. It can be used to detect element failures in an externally fused bank before the fuse
operates and therefore provide fuse savings and safety from possible case rupture. Using multiple
unbalance protection schemes helps to improve the reliability of protection and fault location.
BIBLIOGRAPHY
[1] R. Natarajan, Power System Capacitors. CRC Press, Boca Raton, FL, 2005.
[2] IEEE Standard C37.99-2012, IEEE Guide for the Protection of Shunt Capacitor Banks.
[3] S. Samineni, C. Labuschagne, and J. Pope, “Principles of Shunt Capacitor Bank Application and
Protection,” proceedings of the 36th Annual Western Protective Relay Conference, Spokane,
WA, October 2009.
[4] S. Samineni and C. Labuschagne, “Apparatus and Method for Identifying a Faulted Phase in a
Shunt Capacitor Bank,” U.S. Patent 8 575 941, Nov. 5, 2013.
[5] J. Schaefer, S. Samineni, C. Labuschagne, S. Chase, and D. Hawaz, “Minimizing Capacitor
Bank Outage Time Through Fault Location,” proceedings of the 40th Annual Western
Protective Relay Conference,
Spokane, WA, October 2013.