This manual does not contain all the information required to operate and maintain
the product. Refer to the following manuals for other required information.
iii
3500/92 Communication Gateway Module Operation Manual
Contents
iv
3.5.1 Module Switches.........................................................................................................................17
3.5.2 Channel Switches.......................................................................................................................17
4. I/O Module Description............................................................................... 19
4.1 Modbus RS-232/422 I/O Module Description .....................................................................19
4.1.1 General Response Time...........................................................................................................20
4.1.2 Connecting the I/O Module Port to the Host via RS-232 ..........................................20
4.1.3 Connecting the I/O Module to the Honeywell PLCG via RS-232............................20
4.1.4 Connecting the I/O Module Port to the Host via RS-422 ..........................................21
4.1.5 Daisy-Chaining the I/O Modules Ports via RS-422 ......................................................21
4.1.6 Connecting an I/O Module to a Host Computer in an Intrinsically Safe
Application....................................................................................................................................................22
4.2 Modbus RS-485 I/O Module Description...............................................................................23
4.2.1 General Response Time...........................................................................................................24
4.2.2 4-Wire Connections...................................................................................................................24
4.2.3 2-Wire Connections...................................................................................................................25
4.2.4 Termination...................................................................................................................................26
4.3 Ethernet/RS-232 I/O Module Description .............................................................................28
4.3.1 Ethernet – Port 1 .........................................................................................................................28
4.3.2 RS-232 – Port 2............................................................................................................................28
4.3.3 Ethernet/RS-485 I/O Module Description ........................................................................30
4.3.4 Ethernet – Port 1 .........................................................................................................................30
4.3.5 RS-485 – Port 2............................................................................................................................30
4.4 Cable Pinouts ....................................................................................................................................31
4.4.1 3500/92 to 3500/92 RS-422/485 Cable ...........................................................................31
4.4.2 Host Computer to RS-232/422 Converter Cable..........................................................32
4.4.3 Host Computer to 3500/92 RS-232 Cable.......................................................................33
4.4.4 Honeywell PLCG to 3500/92 RS-232 Cable ....................................................................34
4.4.5 RS-232/422 Converter to 3500/92 RS-422 Cable........................................................35
4.4.6 Rack to Rack RS-422 Cable....................................................................................................35
4.4.7 3500/95 RS-422 Extension Cable........................................................................................36
4.4.8 3500/92 RS-485 “Y” Cable ......................................................................................................37
5. Modbus Protocol .......................................................................................... 39
5.1 General Information.......................................................................................................................39
5.2 Supported Function Codes .........................................................................................................39
5.3 DCS and Modbus Addressing Notation .................................................................................40
5.4 General Register Layout...............................................................................................................41
5.5 Data Type Details ............................................................................................................................43
5.5.1 Primary Values.............................................................................................................................43
v
3500/92 Communication Gateway Module Operation Manual
5.5.2 Current Proportional Values..................................................................................................44
5.5.3 Last Read Proportional Time Stamp ..................................................................................46
5.5.4 Module Statuses (Input Status Format) ............................................................................47
5.5.5 Channel Statuses .......................................................................................................................51
5.5.6 Rack Status ...................................................................................................................................53
5.5.7 Setpoint Configuration.............................................................................................................54
5.5.8 Switch Settings ............................................................................................................................59
5.5.9 Configuration Lock ....................................................................................................................60
5.5.10 Alarm Event List .....................................................................................................................61
5.5.11 System Event List...................................................................................................................62
5.5.12 Rack Date and Time .............................................................................................................64
5.5.13 Rack Reset ................................................................................................................................65
5.5.14 Rack Group...............................................................................................................................65
5.5.15 Rack Trip Multiply (Software) ............................................................................................66
5.5.16 Rack Trip Multiply (Hardware)..........................................................................................66
5.5.17 Rack Alarm Inhibit (Software)...........................................................................................66
5.5.18 Rack Alarm Inhibit (Hardware).........................................................................................67
5.5.19 Last Command Success.....................................................................................................67
5.5.20 Full-Scale Range ....................................................................................................................68
5.5.21 Port Number ............................................................................................................................68
5.5.22 Data Ready...............................................................................................................................69
5.5.23 Group New Mode ..................................................................................................................69
5.6 Configurable Registers..................................................................................................................69
5.6.1 Channel Status ............................................................................................................................69
5.6.2 Module Status ..............................................................................................................................70
5.6.3 PPL Status......................................................................................................................................70
5.6.4 Proportional Values...................................................................................................................70
5.6.5 Setpoints ........................................................................................................................................70
5.7 Scaling the Data ..............................................................................................................................70
5.7.1 Proportional Value Example..................................................................................................70
5.7.2 Setpoint Example .......................................................................................................................71
5.8 Modbus Language Description.................................................................................................71
5.8.1 Message Definition ....................................................................................................................72
5.8.2 Byte Layout of Modbus Commands (RTU Framing)....................................................72
5.8.3 Description of Supported Commands ..............................................................................74
6. Maintenance............................................................................................... 105
6.1 Communication Gateway Port Test Utility........................................................................105
6.2 Performing Firmware Upgrades............................................................................................105
6.2.1 Installation Procedure...........................................................................................................106
vi
7. Troubleshooting......................................................................................... 109
7.1 Self-Test............................................................................................................................................109
7.2 LED Fault Conditions...................................................................................................................109
7.3 System Event List Messages ...................................................................................................110
7.4 Alarm Event List Messages ...................................................................................................... 119
8. Specifications ............................................................................................. 121
8.1 Inputs.................................................................................................................................................121
8.2 Outputs .............................................................................................................................................121
8.3 Environmental Limits ..................................................................................................................121
8.4 CE Mark Directives .......................................................................................................................122
8.4.1 EMC Directives ..........................................................................................................................122
8.4.2 Low Voltage Directives ......................................................................................................... 122
8.5 Hazardous Area Approvals ......................................................................................................123
8.6 Physical.............................................................................................................................................123
8.6.1 Main Board.................................................................................................................................123
8.6.2 Modbus RS-232/422 and Modbus RS-485 I/O Modules ........................................123
8.6.3 Rack Space Requirements ..................................................................................................123
9. Ordering Information................................................................................ 125
9.1 3500/92 Communication Gateway......................................................................................125
9.2 Cables................................................................................................................................................125
9.2.1 Ethernet RJ45 Cable...............................................................................................................125
9.2.2 Fiber Optic Cable .....................................................................................................................126
9.2.3 Host to 3500/92 RS-232 Cable..........................................................................................126
9.2.4 RS-232/422 Converter to 3500/92 PVC-Insulated RS-422 Cable ......................126
9.2.5 RS-232/422 Converter to 3500/92 Teflon-Insulated RS-422 Cable..................127
9.2.6 Honeywell PLCG to 350/92 RS-232 Cable....................................................................127
9.2.7 3500/92 to 3500/92 PVC-Insulated RS-422/RS-485 Cable ..................................127
9.2.8 3500/92 to 3500/92 Teflon-Insulated RS-422/RS-485 Cable..............................128
9.2.9 RS-422/RS-485 Extension Cable.......................................................................................128
9.3 Spares................................................................................................................................................128
9.3.1 Modules .......................................................................................................................................128
9.3.2 Cables...........................................................................................................................................129
vii
Section 1 - Receiving and Handling Instructions
Application Advisory
• Do not discharge static electricity onto the circuit board. Avoid tools or
procedures that would subject the circuit board to static damage. Some
possible causes include ungrounded soldering irons, nonconductive
plastics, and similar materials.
• Personnel must be grounded with a suitable grounding strap (such as 3M®
Velostat® No. 2060 strap) before handling or maintaining a printed circuit
board.
• Transport and store circuit boards in electrically conductive bags or foil.
• Use extra caution during dry weather. Relative humidity less than 30%
tends to multiply the accumulation of static charges on any surface.
• When performed properly, this module may be installed into or removed
from the rack while power is applied to the rack. Refer to the Rack
Installation and Maintenance Manual (part number 129766-01) for the
proper procedure.
1
Section 2 - General Information
2. General Information
The Communication Gateway Module provides serial communications between
the 3500 Monitor System and a plant information system such as a distributed
control system (DCS) or a programmable logic controller (PLC). The
Communication Gateway Module uses a high-speed internal network to collect
static data from the modules in the rack and sends this data to the information
system upon request.
The Communication Gateway can communicate with up to 6 hosts via Ethernet.
Hosts can be devices that use Modbus protocol or computers that run 3500 Rack
Configuration and Data Acquisition software. You can configure only 1
Communication Gateway module per 3500 rack to accept Rack Configuration or
Data Acquisition hosts.
1. Status LEDs
2. Communication Gateway module
3. RS-485 I/O module
4. RS-232/422 I/O module
5. Ethernet/RS-232 I/O module
6. Ethernet/RS-485 I/O module
2.1.2 Connect
This button selects the device listed in the “Network Device Name” field. When
you enter this screen, the software will specify the previous device. Simply click
on Connect to connect with this device. If you wish to connect to another device,
4
Section 2 - General Information
select Browse, highlight the desired device, and click on Connect. Alternatively,
select Browse and double-click on the desired device.
2.1.3 Browse
This button searches for 3500 racks within the same subnet on the local network.
2.1.4 Advanced
Advanced settings will assist you in establishing network communications. Set
these parameters with the help of a network administrator.
5
3500/92 Communication Gateway Module Operation Manual
2.3 Triple Modular Redundant (TMR) Description
The Communication Gateway is considered a "Consumer" of data because it
receives data from other modules, formats it, and sends it on to an external
device. Since the module does not produce data or provide data to other
modules in the 3500 rack, application do not require redundant Communication
Gateway Modules with voting options. For applications that require redundant
communication links, 2 or more Communication Gateway Modules can operate in
parallel in the same rack, provided that you configure only 1 module to allow the
"Bently Centurion Protocol" (refer to Section 3.2). You can use this configuration in
both standard and TMR rack types.
2.4.1 OK Status
This status indicates whether the Communication Gateway is functioning
correctly. A module returns a Not OK status under any of the following
conditions:
• Hardware Failure in the module
• Node Voltage Failure
• Configuration Failure
• Slot ID Failure
If the module OK status goes Not OK, the system OK Relay on the Rack Interface
I/O Module will be driven not OK.
6
Section 2 - General Information
2.4.2 Configuration Fault Status
This status indicates whether the Communication Gateway Module configuration
is invalid.
2.5.1 OK Status
This status indicates whether the associated Communication Gateway module
communication port has detected some internal fault. If the Communication
Gateway Module goes not OK, then all the channels are not OK.
1. OK LED. This LED indicates that the Communication Gateway Module and the I/O module are operating correctly.
2. TX/RX LED. This LED flashes at the rate that messages are received from other 3500 modules.
8
Section 3 - Configuration Information
3. Configuration Information
To configure a Communication Gateway module, use the 3500 Rack
Configuration Software to complete the following tasks:
• Set the communication parameters for the ports on the Communication
Gateway I/O Module.
• Assign data from rack modules to reserved addresses (Configurable
Modbus Registers) in the Communication Gateway Module.
• Set the software switches.
9
3500/92 Communication Gateway Module Operation Manual
3.2.1.1 Config ID
Config ID is a unique, 6-digit value that is entered when you download a
configuration to the 3500 rack.
3.2.1.2 Slot
This value specifies the location of the Communication Gateway Module in the
3500 rack.
3.2.2 Protocol
This value selects which I/O card your application uses. You order the I/O cards
as an option to the 3500/92.
10
Section 3 - Configuration Information
Table 3-1: Modbus I/O Card Protocols
Option Port 1 Port 2
-01 Modbus RS-232/422 Modbus RS-232/422
-02 Modbus RS-485 Modbus RS-485
-03 Ethernet TCP/IP Modbus RS-232
-04 Ethernet TCP/IP Modbus RS-485
The Ethernet TCP/IP option allows the module to use both Modbus®
communication and Bently Nevada™ 3500 software protocols. These protocols
can run simultaneously on the same port.
3.2.4.2 Address
This value specifies the address that the Communication Protocol uses to talk to
the Communication Port. If you daisy-chain the Communication Gateway Ports,
all the ports in the chain must have a unique address. The range of addresses is 1
to 255.
3.2.4.3 Connection
Direct is the only connection option that is available for the Modbus protocol.
11
3500/92 Communication Gateway Module Operation Manual
3.2.4.6 Full Scale Data Range
The Full Scale Data Range is a value between 1 and 65535 that is the maximum
value in the full-scale range. The module will scale the Current Proportional
Values and the Primary Values between 0 and the selected value.
Example:
If the Full Scale Data Range field is set to 4096, then the Current Proportional
Values and the Primary Values will be scaled between 0 and 4096.
3.2.5 Communication
3.2.5.1 Parity
The module uses this option for error checking.
3.2.5.1.1 None
This option specifies that the communication port uses no parity error checking.
3.2.5.1.2 Odd
When you select Odd parity, each word has an odd number of 1 bits.
3.2.5.1.3 Even
When you select Even parity, each word has an even number of 1 bits.
12
Section 3 - Configuration Information
3.3 Setting Network Parameters
The Communication Gateway Ethernet configuration screen, shown in Figure 3-2,
lets you set the network communication parameters for the Ethernet and Modbus
communication connectors on the Communication Gateway I/O Module. Note
that the Modbus serial communications parameters, shown in the lower half of
the screen, are identical to those discussed in Section 3.2, “Setting Serial
Communication Parameters”.
13
3500/92 Communication Gateway Module Operation Manual
3.3.1.4 Available Services
This parameter identifies different communication protocols that are available
with the 3500/92. Ethernet networks allow multiple protocols to run at the same
time.
3.4.1 Mode
3.4.1.1 Fixed
Fixed mode places the register or block of registers from the selected address and
below, and will overwrite existing registers.
3.4.1.2 Moveable
Moveable mode places the register or block of registers from the address selected
and will move the existing registers down. Registers moved beyond the end of the
500 addresses will be lost.
15
3500/92 Communication Gateway Module Operation Manual
3.4.3 Print
The printing features of the 3500/92 configuration screens offer 4 functions. You
select these functions by moving clicking the Print… button at the bottom to
activate the print pop-up menu. The print button within the pop up menu will
then execute the selected option.
3.4.3.1.1 To Screen
This option prints the Modbus Register Map to WordPad so that you can edit or
format the information. Saving this to a file after editing is completed within
WordPad.
3.4.3.1.2 To Printer
This option simply prints the Modbus Register Map to a printer.
16
Section 3 - Configuration Information
17
3500/92 Communication Gateway Module Operation Manual
Table 3-3: Communication Gateway Channel Switch Number
Channel Switch Number Switch Name
4 Configuration Mode
18
Section 4 - I/O Module Description
1. Host connector
2. Rack connector
19
3500/92 Communication Gateway Module Operation Manual
The rack connectors connect this RS-232/422 I/O module to the next RS-232/422
I/O module in the chain. This connection can use only RS-422. Refer to Section
4.1.5.
4.1.2 Connecting the I/O Module Port to the Host via RS-232
The baud rate you select for communications between the host (display or host
computer) and first RS-232/422 I/O module port will limit the communication rate.
1
1. Host to RS-232/422 I/O module port connection. Use cable 130419-AXXXX-BXX.
4.1.3 Connecting the I/O Module to the Honeywell PLCG via RS-232
The baud rate that you select for communications between the Honeywell PLCG
and the first RS-232/422 I/O module port will limit the communication rate.
1. Honeywell PLCG
2. Honeywell PLCG to RS-232/422 I/O module port connection. Use cable 130420-AXXXX-BXX.
20
Section 4 - I/O Module Description
4.1.4 Connecting the I/O Module Port to the Host via RS-422
The baud rate you select for communications between the host (display or host
computer) and first RS-232/422 I/O module port will limit the communication rate.
2 4
3
1
21
3500/92 Communication Gateway Module Operation Manual
22
Section 4 - I/O Module Description
rack isolated from earth ground. RS-485 uses an isolated ground and hence
requires no additional isolation.
3
1
1. Host computer
2. Host computer to serial data isolator connection. Use cable 130118-AXXXX-BXX.
3. Serial data isolator (part number 02200633)
23
3500/92 Communication Gateway Module Operation Manual
24
Section 4 - I/O Module Description
3 4 5
25
3500/92 Communication Gateway Module Operation Manual
Figure 4-9 shows the 2-wire connection between a host device and a Modbus RS-
485 I/O module.
TX/RXA TXA
TXB
RXA
TX/RXB RXB
GND GND
4.2.4 Termination
Proper termination is critical for reliable communications. Improper termination
can cause a loss of communication. In normal 4-wire applications you should
terminate the last device on each end of the chain. The transmitting pair should
use a standard termination and the receiving pair should use a bias termination
(also called a fail-safe termination or a power termination). Biasing prevents a
device from receiving a false bit when communications are idle. In normal 2-wire
applications the Modbus master should have a bias termination and the farthest
device should have a standard termination. If the Modbus master does not
provide a bias termination then another device in the chain must provide the bias.
For long distances or in noisy environments you may need to provide a bias at
additional devices regardless of termination. The I/O module provides 4-position
switches, shown in Figure 4-10, that allow you to configure a termination scheme.
26
Section 4 - I/O Module Description
1 2 3 4
1 2 3 4
1 2 3 4
1 2 3 4
27
3500/92 Communication Gateway Module Operation Manual
Older RS-485 I/O modules use a single "TERM/UNTERM" switch that provides a
normal 4-wire termination. For a 2-wire installation, use a discrete 120Ω resistor
between the RX+ and RX- lines to terminate these older I/O modules. Always
leave the switch in the "UNTERM" position.
1. Port 1 – Ethernet
2. Port 2 – RS-232
The I/O module provides additional pins for the Modbus Master devices with these
specifications:
Application Advisory
29
3500/92 Communication Gateway Module Operation Manual
4.3.3 Ethernet/RS-485 I/O Module Description
This I/O module provides Ethernet network communications and PLC/DCS
network communications.
1. Ethernet – Port 1
2. RS-485 – Port 2
30
Section 4 - I/O Module Description
Table 4-5: RS-485 Connector Pins
Signal Name Pin Number
GND Ground 5
TXB Transmit positive 3
TXA Transmit negative 9
RXB Receive positive 4
RXA Receive negative 6
1 2
T(+)/RXB 4 13 R(+)/RXB
T(-)/RXA 6 6 R(-)/RXA
R(+)/TXB 3 7 T(+)/TXB
R(-)/TXA 9 15 T(-)/TXA
COM/COM 5 8 COM/COM
NC NC
NC 3
31
3500/92 Communication Gateway Module Operation Manual
4.4.2 Host Computer to RS-232/422 Converter Cable
Cable 131119-01
1 2
3
TX 2 3 TX
4
COM 7 5 COM
5
RX 3 2 RX
4
NC NC
6 6
32
Section 4 - I/O Module Description
1 2
3
TxD 3 9 RxD
4
COMMON 5 5 COMMON
5
RxD 2 2 TxD
4
NC NC
6
RTS 7 3 CTS
4
CTS 8 10 RTS
7
DTR 4 12 DSR
4
DSR 6 4 DTR
DCD 1 11 DCD
8 8
1. Female host RS-232 connector, J1
2. Male 3500/92 host port connector, J2
3. Red wire
4. Black wire
5. Green wire
6. White wire
7. Blue wire
8. Shield to connector shell
33
3500/92 Communication Gateway Module Operation Manual
1 2
3
TxD 2 9 RxD
4
COMMON 7 5 COMMON
5
RxD 3 2 TxD
4
NC NC
6
DSR 6 4 DTR
4
DTR 20 12 DSR
DCD 8 11 DCD
RTS 4 3 CTS
CTS 5 10 RTS
7 7
1. Male PLCG host connector, J1
2. Male I/O module host connector, J2
3. Red wire
4. Black wire
5. White wire
6. Green wire
7. Shield to connector shell
34
Section 4 - I/O Module Description
1 2
T(+) 14 13 R(+)
T(-) 2 6 R(-)
R(+) 17 7 T(+)
R(-) 5 15 T(-)
COMMON 7 8 COMMON
NC NC
3 3
1 2
T(+) 4 4 R(+)
T(-) 6 6 R(-)
R(+) 3 3 T(+)
R(-) 9 9 T(-)
COMMON 5 5 COMMON
NC NC
3 3
1 2
R(+)/RXB 13 13 R(+)/RXB
R(-)/RXA 6 6 R(-)/RXA
T(+)/TXB 7 7 T(+)/TXB
T(-)/TXA 15 15 T(-)/TXA
COM/COM 8 8 COM/COM
NC NC
3 3
36
Section 4 - I/O Module Description
1 2
R(+)/RXB 4 4 R(+)/RXB
R(-)/RXA 6 6 R(-)/RXA
T(+)/TXB 3 3 T(+)/TXB
T(-)/TXA 9 9 T(-)/TXA
COM/COM 5 5 COM/COM
NC NC
3 3
4 R(+)/RXB
6 R(-)/RXA
3 T(+)/TXB
9 T(-)/TXA
5 COM/COM
NC
37
Section 5 - Modbus Protocol
5. Modbus Protocol
5.1 General Information
This section describes the Modbus Interface and shows how it relates to the
Communication Gateway Module. Before you begin programming, you should
refer to the AEG Modicon Modbus Protocol Reference Guide, Publication PI-MBUS-
300 Rev E - March 1993 to familiarize yourself with the basics of the Modbus
protocol.
This section does not tell you how to program your DCS computer to access the
Communication Gateway Module nor how to configure the interface database.
You must refer to the manuals for the DCS computer or controller for that
information.
39
3500/92 Communication Gateway Module Operation Manual
Code Meaning Communication Gateway Module Data
Current Proportional Values
04 Read Input Registers
Last Read Proportional Time Stamp
Setpoint Configuration
Switch Settings
Configuration Lock
Alarm Event List
System Event List
06 Preset Single Register
Rack Date and Time
Rack Reset
Rack Trip Multiply - Software,
Rack Alarm Inhibit – Software
Configurable Registers
0: Query Data
2: Diagnostic Register
10: Clear Counters
Loopback/Maintenance
08 11: Message Count
Diagnostic Codes
12: Communication Error Count
13: Exception Count
18: Character Overrun Count
Setpoint Configuration
Switch Settings
Configuration Lock
Alarm Event List
System Event List
16 Preset Multiple Registers
Rack Date and Time
Rack Reset
Rack Trip Multiply - Software,
Rack Alarm Inhibit – Software
Configurable Registers
Family ID and current revision number of the Communication
17 Report Slave ID
Gateway Module's firmware
40
Section 5 - Modbus Protocol
NOTE
This section uses 2 formats to list
addresses: the Modbus Programmable
Controller Register format (1-based) and the
query address format (0-based). Use the
format that is appropriated for your host.
41
3500/92 Communication Gateway Module Operation Manual
Address Ranges
Function Modbus Programmable
Data Type Query Address Format
Code Controller Format
(0-based)
(1-based)
The repeated data registers that are marked with an asterisk (*) in Table 5-3
contain duplicated data in different registers for some Modbus devices that only
support the 4XXXX series registers. Status data is bit-packed in the 4XXXX
registers so that the least significant bit (bit 0) of register 42001 corresponds to
42
Section 5 - Modbus Protocol
register 10001 and the most significant bit (bit 15) of register 42001 corresponds
to register 10016.
NOTE
These values are repeated in the 4XXXX
address range. Refer to Section 5.4 for
register layout.
44
Section 5 - Modbus Protocol
Full Height Module or
Lower Half-height Module
3500 Rack Upper Half-height Module
Slot Number Modbus PC Query Modbus PC Query
Format Format Format Format
9 30725 724 30741 740
10 30757 756 30773 772
11 30789 788 30805 804
12 30821 820 30837 836
13 30853 852 30869 868
14 30885 884 30901 900
15 30917 916 30933 932
Example:
For a 3500/40 Proximitor Monitor installed in slot 3 with channels 1 and 2
optioned as Thrust Position and channels 3 and 4 optioned as Radial
Vibration, you would set up the proportional values for this monitor as shown
in Table 5-6.
Modbus
Query Format
Proportional Proportional Value Programmable
(0-based)
Value Number Name Controller Format
Address
(1-based) Address
45
3500/92 Communication Gateway Module Operation Manual
14 Gap 545 50546
15 1X Amplitude 546 50547
16 1X Phase Lag 547 50548
17 2X Amplitude 548 30549
18 2X Phase Lag 549 30550
19 Not 1X Amplitude 550 30551
20 Smax Amplitude 551 30552
21 0 552 30553
22 0 553 30554
23 0 554 30555
24 0 555 30556
25 0 556 30557
26 0 557 30558
27 0 558 30559
28 0 559 30560
29 0 560 30561
30 0 561 30562
31 0 562 30563
32 0 563 30564
46
Section 5 - Modbus Protocol
NOTE
These values are repeated in the 4XXXX
address range. Refer to Section 5.4 for
register layout.
47
3500/92 Communication Gateway Module Operation Manual
the status for that power supply will be not OK ("1"). If the Rack Interface Module
is Not OK then the Not OK status will be set to "1".
If the state of the Module Status is unknown then the default value will be "0" for
false.
Use Function Code 2 (READ INPUT STATUS) to read the Module Statuses.
Equations to compute the starting address in 0-based format for any slot status
are:
Upper Slot Starting Address = 6 * slot number
Lower Slot Starting Address = (6 * slot number) + 3
NOTE
These values are repeated in the 4XXXX
address range. Refer to Section 5.4 for
register layout.
Query Modbus PC
Format Format
Slot Module Status
(0-based) (1-based)
Address Address
48
Section 5 - Modbus Protocol
Query Modbus PC
Format Format
Slot Module Status
(0-based) (1-based)
Address Address
49
3500/92 Communication Gateway Module Operation Manual
Query Modbus PC
Format Format
Slot Module Status
(0-based) (1-based)
Address Address
50
Section 5 - Modbus Protocol
Query Modbus PC
Format Format
Slot Module Status
(0-based) (1-based)
Address Address
51
3500/92 Communication Gateway Module Operation Manual
Bit Channel Statuses
2 Channel Danger/Alarm 2
3 Channel In Bypass Alarm
4 Channel Off
5 Channel Trip Multiply Mode
6 Channel Special Alarm Inhibit
Channel Not Monitoring (i.e., communication link between the
7
Communication Gateway module and the channel is broken)
8 Channel Keyphasor® Signal Not OK (M-boards only)
9 Channel Signal Path Not OK (M-boards only)
NOTE
These values are repeated in the 4XXXX
address range. Refer to Section 5.4 for
register layout.
52
Section 5 - Modbus Protocol
Full Height Module or
Lower Half-height Module
Upper Half-height Module
3500 Rack
Slot Number Modbus PC Query Modbus PC Query
Format Format Format Format
(1-based) (0-based) (1-based) (0-based)
15 13429 3428 13557 3556
NOTE
These values are repeated in the 4XXXX
address range. Refer to Section 5.4 for
register layout.
Take the following precautions when you use the Communication Gateway
Module to adjust setpoints:
• Adjust setpoints so that the over setpoint is greater than the under
setpoint. Refer to Section 5.5.7.2 for additional information about 1X and
2X phase setpoints.
54
Section 5 - Modbus Protocol
• Since you must adjust one setpoint at a time, turn on channel bypass
before you change setpoints for proportional values that have Over and
Under setpoints.
• Verify that the adjusted setpoints are within the linear range of the
transducer.
NOTE
You will not obtain the Configuration Lock and cannot
change the setpoint values if any other port has the
Configuration Lock. Also, if the Communication
Gateway configuration does allow it to change
configuration, then writing to the Configuration Lock
Register will generate an illegal address response. For
more details, refer to Section 5.5.9.
55
3500/92 Communication Gateway Module Operation Manual
3. Use Function Code 6 or Function Code 16 to write to the Slot Number Register
at Address 0 (Modicon PC Register 40001), the Channel Number Register at
Address 1 (Modicon PC Register 40002), the Setpoint Number Register at
Address 2 (Modicon PC Register 40003), and the Setpoint Value Register at
Address 3 (Modicon PC Register 40004) to specify which setpoint you wish to
change and the new setpoint value you wish to set.
You may change multiple setpoints in the same slot by repeating this step.
NOTE
Setpoints are stored in flash memory,
which has a limited number of write
cycles. Therefore, do not excessively
write to these registers.
Application Advisory
0 3
50
1
120
2
1. Acceptance region
2. Over setpoint
3. Under setpoint
56
Section 5 - Modbus Protocol
0 2
50
120
3
1. Acceptance region
2. Over setpoint
3. Under setpoint
0 3
50
1
120
2
1. Acceptance region
2. Over setpoint
3. Under setpoint
0 2
50
120
3
1. Acceptance region
2. Over setpoint
3. Under setpoint
57
3500/92 Communication Gateway Module Operation Manual
NOTES
1. Phase acceptance regions define the areas for a non-alarm state.
The endpoints (setpoints) are included in the non-alarm state.
2. For 1X and 2X Phase Lag, the Over setpoint need not be greater
than the Under setpoint.
3. The acceptance region is always defined from the Under setpoint
to the Over setpoint in a counter-clockwise direction.
4. Setting the Under setpoint equal to the Over setpoint results in
full acceptance (no alarms).
4. If you did not receive an error code when you wrote the setpoint in step 3, you
can verify the new setpoint value by either
• following the steps in Section 5.5.7.1 to read back the setpoint value, or
• reading the Last Command Success registers (refer to Section 5.5.19).
Note that the value you read back may slightly differ from the value
you wrote due to scaling.
5. Use Function Code 6 or Function Code 16 to write a "0" to the Configuration
Lock Register and relinquish the Configuration Lock.
NOTE
These values are repeated in the 4XXXX
address range. Refer to Section 5.4 for
register layout.
58
Section 5 - Modbus Protocol
5.5.8 Switch Settings
Use the Switch Setting to read or write channel settings. Set up the Switch Setting
you desire by writing to the Slot Number, Upper/Lower, Channel Number, and
Switch Number registers. Refer to the switch section of the module’s operation
and maintenance manual for the switch numbers.
NOTE
You will not obtain the Configuration Lock and cannot
change the setpoint values if any other port has the
Configuration Lock. Also, if the Communication
Gateway configuration does allow it to change
configuration, then writing to the Configuration Lock
Register will generate an illegal address response. For
more details, refer to Section 5.5.9.
3. Use the Function Code 6 or Function Code 16 to write to the Slot Number,
Upper/Lower, Channel Number, Switch Number, and Switch Setting Registers
59
3500/92 Communication Gateway Module Operation Manual
to specify which Channel Setting you wish to change and the new value you
wish to set. If you wish to change the module switches, then specify Channel
0.
You may change Switch Settings on different channels in the same slot by
repeating step 3.
4. If you did not receive an error code when the switch was written, you can
verify the new switch value by either
• following the read Switch Setting steps to read back the switch value,
or
• reading the Last Command Success registers (refer to Section 5.5.19).
5. Use Function Code 6 or Function Code 16 to write a "0" to the Configuration
Lock Register and relinquish the Configuration Lock.
60
Section 5 - Modbus Protocol
The Communication Gateway module will not grant the Configuration Lock if the
following conditions are true:
• Another port in the rack has the lock.
• The Config Allowed box on the Modbus Protocol Setup screen of the 3500
Rack Configuration Software is cleared ( ).
Writing to the Configuration Lock Register when either of these conditions is true
will generate an illegal address response.
61
3500/92 Communication Gateway Module Operation Manual
Query Modicon PC
Alarm Event List Read or
Address Register Data Range (Decimal)
Description Write
(0-based) (1-based)
0 = UPPER
Upper/Lower 19 40020 Read Only
1 = LOWER
Channel 20 40021 0 - 32 Read Only
0 = Alert
1 = Danger
Alarm Type 21 40022 Read Only
2 = Not OK
3 = Relay Trip
0 = Entered Alarm
Alarm Direction 22 40023 Read Only
1 = Exit Alarm
00 – 99 (00 implies the
Year 23 40024 Read Only
year 2000)
Month 24 40025 1 –13 Read Only
Day 25 40026 1 – 31 Read Only
0 – 23 (00 = Midnight,
Hour 26 40027 Read Only
12 = Noon)
Minute 27 40028 0 – 59 Read Only
Second 28 40029 0 – 59 Read Only
1/100 Second 29 40030 0 - 99 Read Only
62
Section 5 - Modbus Protocol
Query Modicon PC
Alarm Event List Read or
Address Register Data Range (Decimal)
Description Write
(0-based) (1-based)
Requested System Event
30 – 31 40031 - 40032 0 – 4,294,967,245 Read/Write
Sequence Number
Last Posted System
32 – 33 40033 - 40034 0 – 4,294,967,245 Read Only
Event Sequence Number
System Event Sequence
34 - 35 40035 – 40036 0 – 4,294,967,245 Read Only
Number
0 = Severe/Fatal Event
1 = Potential Problem
Event
Event Classification 36 40037 Read Only
2 = Typical Logged
Event
3 = Reserved
System Event Number 37 40038 0 – 65535 Read Only
Source Slot 38 40039 0 - 15 Read Only
0 = UPPER
Upper/Lower 39 40040 Read Only
1 = LOWER
Destination Slot (refer to
40 40041 0 - 15 Read Only
note)
Upper/Lower (refer to 0 = UPPER
41 40042 Read Only
note) 1 = LOWER
00 – 99 (00 implies the
Year 23 40024 Read Only
year 2000)
Month 24 40025 1 –13 Read Only
Day 25 40026 1 – 31 Read Only
0 – 23 (00 = Midnight,
Hour 26 40027 Read Only
12 = Noon)
Minute 27 40028 0 – 59 Read Only
Second 28 40029 0 – 59 Read Only
1/100 Second 29 40030 0 - 99 Read Only
Note for Table 5-16: Refer to the operation and maintenance manual for the module installed in this slot (upper or
lower).
Refer to the module's operation and maintenance manual for the System Event
List messages. The Source Slot number is the slot number of the module that
caused the action. For example, if the Communication Gateway module changed
the module's setpoint, then the slot number for the Communication Gateway
module would be listed as the source slot.
63
3500/92 Communication Gateway Module Operation Manual
5.5.12 Rack Date and Time
You can either read or write the rack date and time. To read the actual rack date
and time, use Function Code 3 (READ HOLDING REGISTER) and the Actual Rack
Date and Time Registers shown in the table below.
To write a new rack date and time, use Function Code 6 (PRESET SINGLE
REGISTER) or Function Code 16 (PRESET MULTIPLE REGISTERS) to write the desired
time to the Write and Verify Rack Date and Time Registers shown in the table
below. You can read back the Write and Verify Rack Date and Time Registers to
verify the values you entered. You can preload the date and time except for the
1/100 second register. When you write to the 1/100 second register, the 3500
rack will store the new rack date and time.
To verify the new rack date and time, you can either
• use the Actual Rack Data and Time registers, or
• read the Last Command Success registers (refer to Section 5.5.19).
Table 5-18: Write and Verify Rack Date and Time Registers
Rack Modicon Code Read or
Date/Time PC Field Name Notes
Range Write
Address Register
87 40081 Year 00 - 99 00 implies the year 2000 Read Only
Months are in sequential order
88 40082 Month 1 – 12 Read Only
(e.g., 1 = Jan)
89 40083 Day 1 – 31 Read Only
64
Section 5 - Modbus Protocol
Rack Modicon Code Read or
Date/Time PC Field Name Notes
Range Write
Address Register
24- hour clock: 12 = Noon and
90 40084 Hour 0 – 23 Read Only
00 = Midnight
91 40085 Minute 0 – 59 Read Only
92 40086 Second 0 - 59 Read Only
Writing to this register will
write the time stored in the
93 40087 1/100 Second 0 - 99 Write and Verify Rack Date and Read Only
Time Registers to the Actual
Rack Date and Time Registers.
65
3500/92 Communication Gateway Module Operation Manual
5.5.15 Rack Trip Multiply (Software)
Before you use this command, use the 3500 Rack Configuration Software to verify
that the Config Allowed box on the Modbus Protocol Setup screen is checked (⌧).
If you attempt to write a "1" to the software Rack Trip Multiply software address
when the Config Allowed box is cleared ( ), the module will return an ILLEGAL
DATA ADDRESS response.
First, set the Rack Group register. To enable the software Rack Trip Multiply for
that group with the Modbus protocol, use Function Code 6 (PRESET SINGLE
REGISTER) or Function Code 16 (PRESET MULTIPLE REGISTER) to write a "1" to the
software Rack Trip Multiply address.
To disable the software Rack Trip Multiply with the Modbus protocol, use Function
Code 6 or Function Code 16 to write a "0" to the Rack Trip Multiply address.
To verify that you enabled or disabled the software Rack Trip Multiply, you can
use Function Code 3 (READ HOLDING REGISTERS) to read back the software Rack
Trip Multiply register or read the Last Command Success registers (refer to Section
5.5.19).
67
3500/92 Communication Gateway Module Operation Manual
• explains the error,
• states whether the command was successful or unsuccessful, or
• indicates whether or not the register is busy.
Data is scaled between zero and the number entered for the Full-scale Data
Range in the 3500 Rack Configuration Software. The Full-scale Data Range value
is equivalent to 100% of full-scale.
Refer to Section 5.7, “Scaling the Data” for examples.
68
Section 5 - Modbus Protocol
5.5.22 Data Ready
The Data Ready register indicates whether or not a request for any of the multiple
registers (setpoints, switch settings, events, or date/time) has completed fetching
the information from the RIM. You can set this register can be set manually if you
wish to see the transition from 0 to 1, or it will toggle automatically upon your
request for the information.
69
3500/92 Communication Gateway Module Operation Manual
Bits 8-15 are specific to the monitor. You can review details from the printed
register map in the 3500 Rack Configuration Software.
5.6.5 Setpoints
You can use Function Code 3 to read setpoints or Function Codes 6 or 16 to write
setpoints. A Modbus command can set only one setpoint at a time.
Example:
Direct full-scale range = 0 to 10 mils
Measured value = 39231
Full-scale data range = 65535
70
Section 5 - Modbus Protocol
From the equation the scaled value is
Scaled Value = (39321/65535) x (10 mils – 0 mils) + 0 mils
= (0.60 x 10 mils) + 0 mils
= 6.0 mils + 0 mils
= 6.0 mils
Example:
Direct full-scale range = 25–0–25 mils
Desired setpoint value = 8.2 mils
Full-scale data range = 65535
From the equation the scale setpoint value is
Scaled Setpoint Value = [(8.2 mils – (-25 mils) x 65535]/(25 mils – (-25 mils))
= [33.2 mils x 65535]/(50 mils)
= 2,175,762 mils/50 mils
= 43515
If you successfully send 43515 to the Communication Gateway Module, the
data you read back may be off by a few counts because of scale differences.
71
3500/92 Communication Gateway Module Operation Manual
baud rate. You assign each responder a unique fixed device address in the range
of 1 to 255 by setting the address in the 3500 Rack Configuration Software.
For Communication Gateway I/O Module (Modbus) connections, the
Communication Gateway I/O Module (Modbus) will behave as a slave on the
communication link. A separate interfacing device, called a gateway, will serve as
the master on this connection and usually as a protocol converter between
Modbus protocol and a higher level Data Highway system. This section concerns
itself only with the Modbus communication link and does not discuss any special
features or requirements of the gateway or the data highway.
Each field is an integral multiple of 8-bit bytes. The slave address field is sent first
and the other fields follow in the order shown in Table 5-30.
72
Section 5 - Modbus Protocol
73
3500/92 Communication Gateway Module Operation Manual
1. Load the 16-bit CRC register with 0xFFFF (all 1s).
2. Exclusive-OR the first 8-bit byte of the message with the low-order byte
of the 16-bit CRC register and place the result in the CRC register.
3. Shift the CRC register 1 bit to the right (toward the least significant bit
(LSB)) and insert a 0 in the most significant bit (MSB).
4. Extract and examine the LSB:
a. If the LSB is 0, repeat Step 3
b. If the LSB is 1, exclusive-OR the CRC register with the polynomial
value 0xA001 (1010 0000 0000 0001).
5. Repeat steps 3 and 4 until the procedure has performed 8 shifts. When
this is done, the procedure will have processed a complete 8-bit byte.
6. Repeat steps 2 through 5 for the remaining 8-bit bytes of the message.
The final content of the CRC register is the CRC value. As the transmitter sends
each additional byte, it includes the byte in the register value in the same way.
The receiver also calculates the CRC value and compares it to the received CRC
value to verify the accuracy of the data received.
0x01 0x02 High Byte Low Byte High Byte Low Byte High Byte Low Byte
The following sections describe the data fields and their meanings. The slave
address and the CRC fields have the same format and meaning as described in
Sections 5.8.2.1 and 5.8.2.4, respectively.
74
Section 5 - Modbus Protocol
5.8.3.1.1 Start Address
The Start Address is the 16-bit Modbus address of the first input status in the
group that you wish to read. Note that each discrete input is allocated a Modbus
Status Address. The transmitter transmits the high byte first, followed by the low
byte. The allowed ranges are 0 to 3683 (0-referenced). Any address outside this
range will generate the exception response "ILLEGAL ADDRESS". Refer to Section
5.4 for the mapping of the Modicon PC Registers to the Communication Gateway
I/O Module (Modbus) data.
5.8.3.1.3 Example
Table 5-34 shows a Read Input Status Command (all byte values are in
hexadecimal) that retrieves 96 module statuses that start at address zero.
Queries that contain requests for data from addresses that are outside the valid
range of 0 to 3683 (0-referenced) will generate an "ILLEGAL ADDRESS" exception
response.
0x01 0x03 High Byte Low Byte High Byte Low Byte High Byte Low Byte
The following sections describe the data fields and their meanings. The slave
address and the CRC fields have the same format and meaning as described in
Sections 5.8.2.1 and 5.8.2.4, respectively.
76
Section 5 - Modbus Protocol
5.8.3.3.1 Start Address
The Start Address is the 16-bit Modbus address of the first holding register in the
group that you wish to read. The transmitter transmits the high byte first,
followed by the low byte. The allowed ranges are 0 to 6999 (0-referenced). Any
address outside this range will generate the exception response "ILLEGAL
ADDRESS". Refer to Section 5.4 for the mapping of the Modicon PC Registers to
the Communication Gateway I/O Module (Modbus) data.
5.8.3.3.3 Example
Table 5-37 shows a Read Holding Registers Command (all byte values are in
hexadecimal) that retrieves 5 values starting at address 6.
Data Data
Byte High Low
0x01 0x03 Register 1 … Register N
Count
High | Low High | Low
Byte Byte
77
3500/92 Communication Gateway Module Operation Manual
Queries that contain requests for data from addresses that are outside the valid
range of 0 to 6999 (0-referenced) will generate an "ILLEGAL ADDRESS" exception
response.
0x01 0x03 High Byte Low Byte High Byte Low Byte High Byte Low Byte
The following sections describe the data fields and their meanings. The slave
address and the CRC fields have the same format and meaning as described in
Sections 5.8.2.1 and 5.8.2.4, respectively.
78
Section 5 - Modbus Protocol
5.8.3.5.3 Example
Table 5-40 shows a Read Input Registers Command (all byte values are in
hexadecimal) that retrieves 6 values starting at address 513.
Data Data
Byte High Low
0x01 0x04 Register 1 … Register N
Count Byte Byte
High | Low High | Low
Queries that contain requests for data from addresses that are outside the valid
range of 0 to 956 (0-referenced) will generate an "ILLEGAL ADDRESS" exception
response.
79
3500/92 Communication Gateway Module Operation Manual
• Rack Date and Time
• Rack Reset
• Rack Trip Multiply – Software
• Rack Alarm Inhibit - Software.
The data for each register is a 16-bit word. Table 5-43 shows the query frame.
0x01 0x06 High Byte Low Byte High Byte Low Byte High Byte Low Byte
The following sections describe the data fields and their meanings. The slave
address and the CRC fields have the same format and meaning as described in
Sections 5.8.2.1 and 5.8.2.4, respectively.
5.8.3.7.1 Address
The Address is the 16-bit Modbus address that corresponds to the register. The
transmitter transmits the high byte first, followed by the low byte. The allowed
ranges are 0 to 3, 6 to 13, 30 to 31, 87 to 96, and 98 (all 0-referenced). Any
address outside this range will generate the exception response "ILLEGAL
ADDRESS". Refer to Section 5.4 for the mapping of the Modicon PC Registers to
the Communication Gateway I/O Module (Modbus) data.
5.8.3.7.2 Data
Data is the 16-bit word that you wish to write to the address.
5.8.3.7.3 Example
Table 5-43 shows a Preset Single Register Command (all byte values are in
hexadecimal) that sets the value in address 98 to 1.
80
Section 5 - Modbus Protocol
5.8.3.8 Preset Single Register Response
Table 5-41 shows the format of the response to the Preset Input Registers
command. The response includes the slave address, function code, the address,
the preset value, and the CRC check.
Queries that contain requests for data from addresses that are outside the valid
ranges of 0 to 3, 6 to 13, 30 to 31, 87 to 96, and 98 (all 0-referenced) will generate
an "ILLEGAL ADDRESS" exception response.
0x01 0x10 High Byte Low Byte High Byte Low Byte 8 bits
81
3500/92 Communication Gateway Module Operation Manual
Table 5-46: Preset Multiple Registers Command Query Frame (continued)
Data
Data Register 1 Data Register N CRC
Registers
High Byte Low Byte … High Byte Low Byte High Byte Low Byte
The following sections describe the data fields and their meanings. The slave
address and the CRC fields have the same format and meaning as described in
Sections 5.8.2.1 and 5.8.2.4, respectively.
5.8.3.9.3 Example
0x00 0x09 0x00 0x02 0x00 0x5e High Byte Low Byte
82
Section 5 - Modbus Protocol
Table 5-47 through Table 5-49 show a Preset Multiple Registers Command (all
byte values are in hexadecimal) that presets 7 values starting at address 87.
0x01 0x10 High Byte Low Byte High Byte Low Byte High Byte Low Byte
Queries that contain requests for data from addresses that are outside the valid
ranges of 4000 to 4003, 5000 to 5500, and 6000 to 6999 (all 0-referenced) will
generate an "ILLEGAL ADDRESS" exception response.
0x01 0x08 High Byte Low Byte 1 Byte 1 Byte High Byte Low Byte
0x01 0x08 Refer to Table 5-53 Refer to Table 5-53 High Byte Low Byte
83
3500/92 Communication Gateway Module Operation Manual
The response is the same as the query except that the Data fields depend on the
Diagnostic Code value.
Table 5-53 lists the decimal Diagnostic Code and corresponding Data field values.
Note that only power-up or Diagnostic Code 10 clears counter and diagnostic
registers. All counters count Modulo 65536.
High Low
0x01 0x08 0x00 0x02 0x00 7 6 5 4 3 2 1 0
Byte Byte
Bit 4: Configuration
Bit 1: ROM
Bit 0: RAM
A logic “1” in the Data 2 bit pattern indicates a failure for the indicated area.
84
Section 5 - Modbus Protocol
5.8.3.13 Exception Conditions
If the addressed Communication Gateway I/O Module (Modbus) receives a query
frame without a communications error and if some condition stops the
Communication Gateway I/O Module (Modbus) from responding, the interface
returns to the master an exception response that contains the appropriate error
code.
The interface sets the high-order bit (0x80) of the Function Code field to 0 in a
query or normal response frame, and to 1 in an exception response. Regardless
of the function code, the information field of all exception response frames is a
1-byte exception code. Refer to Table 5-55 for the exception conditions that
correspond to each code.
85
3500/92 Communication Gateway Module Operation Manual
5.8.3.15 Report Slave ID Response
Major Minor
Byte Family Family High Low
0x01 0x11 Revision Revision
Count ID MSB ID LSB
Number Number
Byte Byte
86
Section 5 - Modbus Protocol
The setpoint types are in an 8-bit (byte) format. Each bit in the byte has a specific
meaning. Table 5-58 shows the byte format. Table 5-59 through Table 5-61 show
the meaning of each value.
87
3500/92 Communication Gateway Module Operation Manual
YYYYY Bit Decimal YYYYY Bit Decimal
Meaning Meaning
Values Value Values Value
01001 9 Peak-to-Peak 11001 25 Bandpass
Shaft Absolute –
01010 10 Speed 11010 26
Direct
Num Reverse
01011 11 Prime Spike 11011 27
Rotations
01100 12 Power 11100 28 Zero Speed
01101 13 Peak Torque 11101 29 Speed Band
01110 14 Peak Speed 11110 30 Position
01111 15 Peak Power 11111 31 Differential
1 1 RPM
2 2 RPM
N/A 3 0
N/A 4 0
N/A 5 0
N/A 6 0
N/A 7 0
N/A 8 0
N/A 9 0
N/A 10 0
N/A 11 0
N/A 12 0
N/A 13 0
N/A 14 0
N/A 15 0
N/A 16 0
88
Section 5 - Modbus Protocol
Table 5-63: 3500/40 and 3500/40M Radial Vibration Channels
Channel Proportional Value Number Proportional Value Name
1 1 Direct
1 2 Gap
1 3 1X Amplitude
1 4 1X Phase
1 5 2X Amplitude
1 6 2X Phase
1 7 Not 1X Amplitude
1 8 Smax Amplitude
2 9 Direct
2 10 Gap
2 11 1X Amplitude
2 12 1X Phase
2 13 2X Amplitude
2 14 2X Phase
2 15 Not 1X Amplitude
2 16 Smax Amplitude
1 1 Peak-to-Peak
1 2 Gap
1 3 Direct Min
1 4 Direct Max
2 5 Peak-to-Peak
2 6 Gap
2 7 Direct Min
2 8 Direct Max
N/A 9 0
N/A 10 0
N/A 11 0
N/A 12 0
N/A 13 0
N/A 14 0
N/A 15 0
N/A 16 0
89
3500/92 Communication Gateway Module Operation Manual
Table 5-65: 3500/40 and 3500/40M Thrust Position Channels
Channel Proportional Value Number Proportional Value Name
1 1 Direct
1 2 Gap
2 3 Direct
2 4 Gap
N/A 5 0
N/A 6 0
N/A 7 0
N/A 8 0
N/A 9 0
N/A 10 0
N/A 11 0
N/A 12 0
N/A 13 0
N/A 14 0
N/A 15 0
N/A 16 0
1 1 Direct
1 2 Gap
2 3 Direct
2 4 Gap
N/A 5 0
N/A 6 0
N/A 7 0
N/A 8 0
N/A 9 0
N/A 10 0
N/A 11 0
N/A 12 0
N/A 13 0
N/A 14 0
N/A 15 0
N/A 16 0
90
Section 5 - Modbus Protocol
Table 5-67: 3500/42 Velocity Channels
Channel Proportional Value Number Proportional Value Name
1 1 Direct
2 2 Direct
N/A 3 0
N/A 4 0
N/A 5 0
N/A 6 0
N/A 7 0
N/A 8 0
N/A 9 0
N/A 10 0
N/A 11 0
N/A 12 0
N/A 13 0
N/A 14 0
N/A 15 0
N/A 16 0
1 1 Direct
1 2 Gap
1 3 1X Amplitude
1 4 1X Phase
1 5 2X Amplitude
1 6 2X Phase
1 7 Not 1X Amplitude
2 8 Direct
2 9 Gap
2 10 1X Amplitude
2 11 1X Phase
2 12 2X Amplitude
2 13 2X Phase
2 14 Not 1X Amplitude
N/A 15 0
N/A 16 0
91
3500/92 Communication Gateway Module Operation Manual
Table 5-69: 3500/42 and 3500/42M Eccentricity Channels
Channel Proportional Value Number Proportional Value Name
1 1 Peak-to-Peak
1 2 Gap
1 3 Direct Min
1 4 Direct Max
2 5 Peak-to-Peak
2 6 Gap
2 7 Direct Min
2 8 Direct Max
N/A 9 0
N/A 10 0
N/A 11 0
N/A 12 0
N/A 13 0
N/A 14 0
N/A 15 0
N/A 16 0
1 1 Direct
1 2 Gap
1 3 1X Amplitude
1 4 1X Phase
1 5 2X Amplitude
1 6 2X Phase
1 7 Not 1X Amplitude
1 8 Smax Amplitude
2 9 Direct
2 10 Gap
2 11 1X Amplitude
2 12 1X Phase
2 13 2X Amplitude
2 14 2X Phase
2 15 Not 1X Amplitude
2 16 Smax Amplitude
92
Section 5 - Modbus Protocol
Table 5-71: 3500/42 Acceleration Channels
Channel Proportional Value Number Proportional Value Name
1 1 Direct
2 2 Direct
N/A 3 0
N/A 4 0
N/A 5 0
N/A 6 0
N/A 7 0
N/A 8 0
N/A 9 0
N/A 10 0
N/A 11 0
N/A 12 0
N/A 13 0
N/A 14 0
N/A 15 0
N/A 16 0
1 1 Direct
1 2 Gap
1 3 1X Amplitude
1 4 1X Phase
1 5 2X Amplitude
1 6 2X Phase
1 7 Not 1X Amplitude
2 8 Direct
2 9 Gap
2 10 1X Amplitude
2 11 1X Phase
2 12 2X Amplitude
2 13 2X Phase
2 14 Not 1X Amplitude
N/A 15 0
N/A 16 0
93
3500/92 Communication Gateway Module Operation Manual
Table 5-73: 3500/42 and 3500/42M Thrust Position Channels
Channel Proportional Value Number Proportional Value Name
1 1 Direct
1 2 Gap
2 3 Direct
2 4 Gap
N/A 5 0
N/A 6 0
N/A 7 0
N/A 8 0
N/A 9 0
N/A 10 0
N/A 11 0
N/A 12 0
N/A 13 0
N/A 14 0
N/A 15 0
N/A 16 0
1 1 Direct
1 2 Gap
2 3 Direct
2 4 Gap
N/A 5 0
N/A 6 0
N/A 7 0
N/A 8 0
N/A 9 0
N/A 10 0
N/A 11 0
N/A 12 0
N/A 13 0
N/A 14 0
N/A 15 0
N/A 16 0
94
Section 5 - Modbus Protocol
Table 5-75: 3500/42M Shaft Absolute Radial Vibration Channels
Channel Proportional Value Number Proportional Value Name
1 1 RV Direct
1 2 RV Gap
1 3 RV 1X Amplitude
1 4 RV 1X Phase
2 5 RV Direct
2 6 RV Gap
2 7 RV 1X Amplitude
2 8 RV 1X Phase
N/A 9 0
N/A 10 0
N/A 11 0
N/A 12 0
N/A 13 0
N/A 14 0
N/A 15 0
N/A 16 0
3 4 Velocity Direct
3 5 Velocity 1X Amplitude
3 6 Velocity 1X Phase
4 10 Velocity Direct
4 11 Velocity 1X Amplitude
4 12 Velocity 1X Phase
N/A 13 0
N/A 14 0
N/A 15 0
N/A 16 0
95
3500/92 Communication Gateway Module Operation Manual
Table 5-77: 3500/44 and 3500/44M Aeroderivative Channels
Channel Proportional Value Number Proportional Value Name
1 1 Direct
1 2 1X Amplitude
1 3 Bandpass
2 4 Direct
2 5 1X Amplitude
2 6 Bandpass
N/A 7 0
N/A 8 0
N/A 9 0
N/A 10 0
N/A 11 0
N/A 12 0
N/A 13 0
N/A 14 0
N/A 15 0
N/A 16 0
1 1 Direct
1 2 Gap
2 3 Direct
2 4 Gap
N/A 5 0
N/A 6 0
N/A 7 0
N/A 8 0
N/A 9 0
N/A 10 0
N/A 11 0
N/A 12 0
N/A 13 0
N/A 14 0
N/A 15 0
N/A 16 0
96
Section 5 - Modbus Protocol
Table 5-79: 3500/45 Differential Expansion Channels
Channel Proportional Value Number Proportional Value Name
1 1 Direct
1 2 Gap
2 3 Direct
2 4 Gap
N/A 5 0
N/A 6 0
N/A 7 0
N/A 8 0
N/A 9 0
N/A 10 0
N/A 11 0
N/A 12 0
N/A 13 0
N/A 14 0
N/A 15 0
N/A 16 0
1 1 Composite
1 2 Direct
1 3 Gap
2 4 Composite
2 5 Direct
2 6 Gap
N/A 7 0
N/A 8 0
N/A 9 0
N/A 10 0
N/A 11 0
N/A 12 0
N/A 13 0
N/A 14 0
N/A 15 0
N/A 16 0
97
3500/92 Communication Gateway Module Operation Manual
Table 5-81: 3500/45 Complementary Input Channels
Channel Proportional Value Number Proportional Value Name
1 1 Composite
1 2 Direct
1 3 Gap
2 4 Composite
2 5 Direct
2 6 Gap
N/A 7 0
N/A 8 0
N/A 9 0
N/A 10 0
N/A 11 0
N/A 12 0
N/A 13 0
N/A 14 0
N/A 15 0
N/A 16 0
3 1 Direct
3 2 Composite
3 3 Position
4 4 Direct
4 5 Composite
4 6 Position
N/A 7 0
N/A 8 0
N/A 9 0
N/A 10 0
N/A 11 0
N/A 12 0
N/A 13 0
N/A 14 0
N/A 15 0
N/A 16 0
98
Section 5 - Modbus Protocol
Table 5-83: 3500/45 Case Expansion – Single Channels
Channel Proportional Value Number Proportional Value Name
3 1 Direct
3 2 Position
4 3 Direct
4 4 Position
N/A 5 0
N/A 6 0
N/A 7 0
N/A 8 0
N/A 9 0
N/A 10 0
N/A 11 0
N/A 12 0
N/A 13 0
N/A 14 0
N/A 15 0
N/A 16 0
1 1 Direct
1 2 Position
2 3 Direct
2 4 Position
3 5 Direct
3 6 Position
4 7 Direct
4 8 Position
N/A 9 0
N/A 10 0
N/A 11 0
N/A 12 0
N/A 13 0
N/A 14 0
N/A 15 0
N/A 16 0
99
3500/92 Communication Gateway Module Operation Manual
Table 5-85: 3500/50 Rotor Acceleration Channels
Channel Proportional Value Number Proportional Value Name
1 1 Rotor Acceleration
1 2 Speed
1 3 Peak Speed
N/A 4 0
N/A 5 0
N/A 6 0
N/A 7 0
N/A 8 0
N/A 9 0
N/A 10 0
N/A 11 0
N/A 12 0
N/A 13 0
N/A 14 0
N/A 15 0
N/A 16 0
1 1 Zero Speed
1 2 Speed
1 3 Peak Speed
N/A 4 0
N/A 5 0
N/A 6 0
N/A 7 0
N/A 8 0
N/A 9 0
N/A 10 0
N/A 11 0
N/A 12 0
N/A 13 0
N/A 14 0
N/A 15 0
N/A 16 0
100
Section 5 - Modbus Protocol
Table 5-87: 3500/50 Rotor Speed Channels
Channel Proportional Value Number Proportional Value Name
1 1 Speed
1 2 Speed Band
1 3 Peak Band
N/A 4 0
N/A 5 0
N/A 6 0
N/A 7 0
N/A 8 0
N/A 9 0
N/A 10 0
N/A 11 0
N/A 12 0
N/A 13 0
N/A 14 0
N/A 15 0
N/A 16 0
1 1 Speed
1 2 Peak Speed
N/A 3 0
N/A 4 0
N/A 5 0
N/A 6 0
N/A 7 0
N/A 8 0
N/A 9 0
N/A 10 0
N/A 11 0
N/A 12 0
N/A 13 0
N/A 14 0
N/A 15 0
N/A 16 0
101
3500/92 Communication Gateway Module Operation Manual
Table 5-89: 3500/60 Temperature Speed Channels
Channel Proportional Value Number Proportional Value Name
1 1 Direct
2 2 Direct
3 3 Direct
4 4 Direct
5 5 Direct
6 6 Direct
N/A 7 0
N/A 8 0
N/A 9 0
N/A 10 0
N/A 11 0
N/A 12 0
N/A 13 0
N/A 14 0
N/A 15 0
N/A 16 0
1 1 Direct
1 2 Composite
1 3 Differential
N/A 4 0
N/A 5 0
N/A 6 0
N/A 7 0
N/A 8 0
N/A 9 0
N/A 10 0
N/A 11 0
N/A 12 0
N/A 13 0
N/A 14 0
N/A 15 0
N/A 16 0
102
Section 5 - Modbus Protocol
Table 5-91: 3500/61 Temperature Channels
Channel Proportional Value Number Proportional Value Name
1 1 Direct
2 2 Direct
3 3 Direct
4 4 Direct
5 5 Direct
6 6 Direct
N/A 7 0
N/A 8 0
N/A 9 0
N/A 10 0
N/A 11 0
N/A 12 0
N/A 13 0
N/A 14 0
N/A 15 0
N/A 16 0
1 1 Direct
1 2 Composite
1 3 Differential
N/A 4 0
N/A 5 0
N/A 6 0
N/A 7 0
N/A 8 0
N/A 9 0
N/A 10 0
N/A 11 0
N/A 12 0
N/A 13 0
N/A 14 0
N/A 15 0
N/A 16 0
103
3500/92 Communication Gateway Module Operation Manual
Table 5-93: 3500/62 Process Variable Channels
Channel Proportional Value Number Proportional Value Name
1 1 Direct
2 2 Direct
3 3 Direct
4 4 Direct
5 5 Direct
6 6 Direct
N/A 7 0
N/A 8 0
N/A 9 0
N/A 10 0
N/A 11 0
N/A 12 0
N/A 13 0
N/A 14 0
N/A 15 0
N/A 16 0
1 1 Direct
1 2 Direct
N/A 3 0
N/A 4 0
N/A 5 0
N/A 6 0
N/A 7 0
N/A 8 0
N/A 9 0
N/A 10 0
N/A 11 0
N/A 12 0
N/A 13 0
N/A 14 0
N/A 15 0
N/A 16 0
104
Section 6 - Maintenance
6. Maintenance
You cannot repair the boards and components inside 3500 modules in the field.
3500 rack maintenance consists of testing module channels to verify that they
are operating correctly. You should replace modules that are not operating
correctly with a spare.
When performed properly, you may remove this module from or install this
module into the rack while power is applied to the rack. Refer to the Rack
Installation and Maintenance Manual (part number 129766-01) for the proper
procedure.
This section shows how to verify that the Communication Gateway Module is
operating correctly.
105
3500/92 Communication Gateway Module Operation Manual
Refer to Section 9.3.1 for the firmware upgrade IC part numbers. You may also
order a grounding wrist strap from this section or use your own grounding wrist
strap if you already have one.
106
Section 6 - Maintenance
1. Top shield
2. Standoff
3. Large flathead screwdriver
107
3500/92 Communication Gateway Module Operation Manual
2. Slightly lift the one end of the chip by gently prying with the screwdriver. Move
to the other end of the chip and repeat. Continue this process until the chip
comes loose from the socket.
3. Repeat the steps 1 and 2 for U6 (or the EVEN word IC), which is situated below
the other firmware IC.
108
Section 7 - Troubleshooting
7. Troubleshooting
This section describes how to use the information that the self-test, LEDs, System
Event List, and Alarm Event provide to troubleshoot a problem with the
Communication Gateway Module or the I/O module.
7.1 Self-Test
Application Advisory
109
3500/92 Communication Gateway Module Operation Manual
Table 7-1: Summary of LED Fault Conditions
OK LED TX/RX Condition Solution
Communication Gateway module Reconfigure the Communication
1 Hz 1 Hz
is not configured. Gateway module.
Not Communication Gateway Module is
5 Hz Check the System Event List.
relevant Not OK.
Communication Gateway Module is
ON Flashing No action required.
operating correctly.
Not Communication Gateway Module is
OFF Check the System Event List.
relevant not operating correctly.
Communication Gateway Module is
Not Not
not communicating correctly or Check the System Event List.
relevant Flashing
there are no monitors in the rack.
EEPROM Memory
0000000123 13 1 02/01/90 12:24:31:99 5
Failure
Sequence Number: This is the number of the event in the System Event List (for
example 123).
Event Information: This provides the name of the event (for example EEPROM
Memory Failure).
Event Number: This identifies the specific event that occurred.
Class: This indicates the severity of the event. The following
classes are available:
Table 7-3: System Event List Classes
Class Value Classification
0 Severe/fatal event
1 Potential problem event
2 Typical logged event
3 Reserved
110
Section 7 - Troubleshooting
Event Date: This specifies the date that the event occurred.
Event Time: This specifies the time that the event occurred.
Event Specific: Provides additional information for the events that use this
field.
Slot: This identifies the module with which the event is
associated. If the module is a half-height module in the
upper slot or a full-height module, this field will be 0 to 15. If
the module is a half-height module in the lower slot then
this field will be 0L to 15L. For example, this field would
identify a half-height module in the lower position of slot 5
as 5L.
The Communication Gateway module may place following messages, which are
listed in numerical order, into the System Event List. Events marked with a star (*)
will stop communications on both ports on the Communication Gateway I/O
module. If you are unable to solve any problems contact your nearest Bently
Nevada LLC office.
111
3500/92 Communication Gateway Module Operation Manual
Device Is Communicating
Event Number: 33
Event Classification: Potential Problem
Action: Determine whether one of the following components is faulty:
• the Communication Gateway Module
• the rack backplane
Fail Main Board +5V-A (Fail Main Board +5V - Upper Power Supply)
Event Number: 100
Event Classification: Potential Problem
Action: Verify that noise from the power source is not causing the problem.
If the problem is not caused by noise, then determine whether one
of the following components is faulty:
• the Communication Gateway Module
• the Power Supply installed in the upper slot
Pass Main Board +5V-A (Pass Main Board +5V - Upper Power Supply)
Event Number: 101
Event Classification: Potential Problem
Action: Verify that noise from the power source is not causing the problem.
If the problem is not caused by noise, determine whether one of the
following components is faulty:
112
Section 7 - Troubleshooting
• the Communication Gateway Module
• the Power Supply installed in the upper slot
Fail Main Board +5V-B (Fail Main Board +5V - Lower Power Supply)
Event Number: 102
Event Classification: Potential Problem
Action: Verify that noise from the power source is not causing the problem.
If the problem is not caused by noise, determine whether one of the
following components is faulty:
• the Communication Gateway Module
• the Power Supply installed in the lower slot
Pass Main Board +5V-B (Pass Main Board +5V - Lower Power Supply)
Event Number: 103
Event Classification: Potential Problem
Action: Verify that noise from the power source is not causing the problem.
If the problem is not caused by noise, determine whether one of the
following components is faulty:
• the Communication Gateway Module
• the Power Supply installed in the lower slot
* Fail Main Board +5V-AB (Fail Main Board +5V - Upper and Lower Power
Supplies)
Event Number: 104
Event Classification: Severe / Fatal Event
Action: Verify that noise from the power source is not causing the problem.
If the problem is not caused by noise, determine whether one of the
following components is faulty:
• the Communication Gateway Module
• the Power Supply installed in the lower slot
• the Power Supply installed in the upper slot
113
3500/92 Communication Gateway Module Operation Manual
Pass Main Board +5V-AB (Pass Main Board +5V - Upper and Lower Power
Supplies)
Event Number: 105
Event Classification: Severe / Fatal Event
Action Verify that noise from the power source is not causing the problem.
If the problem is not caused by noise, determine whether one of the
following components is faulty:
• the Communication Gateway Module
• the Power Supply installed in the lower slot
• the Power Supply installed in the upper slot
Fail Main Board +15V-A (Fail Main Board +15V - Upper Power Supply)
Event Number: 106
Event Classification: Potential Problem
Action: Verify that noise from the power source is not causing the problem.
If the problem is not caused by noise, determine whether one of the
following components is faulty:
• the Communication Gateway Module
• the Power Supply installed in the upper slot
Pass Main Board +15V-A (Pass Main Board +15V - Upper Power Supply)
Event Number: 107
Event Classification: Potential Problem
Action: Verify that noise from the power source is not causing the problem.
If the problem is not caused by noise, determine whether one of the
following components is faulty:
• the Communication Gateway Module
• the Power Supply installed in the upper slot
114
Section 7 - Troubleshooting
Fail Main Board +15V-B (Fail Main Board +15V - Lower Power Supply)
Event Number: 108
Event Classification: Potential Problem
Action: Verify that noise from the power source is not causing the problem.
If the problem is not caused by noise, determine whether one of the
following components is faulty:
• the Communication Gateway Module
• the Power Supply installed in the lower slot
Pass Main Board +15V-B (Pass Main Board +15V - Lower Power Supply)
Event Number: 109
Event Classification: Potential Problem
Action: Verify that noise from the power source is not causing the problem.
If the problem is not caused by noise, determine whether one of the
following components is faulty:
• the Communication Gateway Module
• the Power Supply installed in the lower slot
Fail Main Board +15V-AB (Fail Main Board +15V - Upper and Lower Power
Supplies)
Event Number: 110
Event Classification: Severe / Fatal Event
Action: Verify that noise from the power source is not causing the problem.
If the problem is not caused by noise, determine whether one of the
following components is faulty:
• the Communication Gateway Module
• the Power Supply installed in the lower slot
• the Power Supply installed in the upper slot
Pass Main Board +15V-AB (Pass Main Board +15V - Upper and Lower Power
Supplies)
Event Number: 111
115
3500/92 Communication Gateway Module Operation Manual
Event Classification: Severe / Fatal Event
Action: Verify that noise from the power source is not causing the problem.
If the problem is not caused by noise, determine whether one of the
following components is faulty:
• the Communication Gateway Module
• the Power Supply installed in the lower slot
• the Power Supply installed in the upper slot
Device Configured
Event Number: 300
Event Classification: Typical Logged Event
Action: No action required.
Configuration Failure
Event Number: 301
Event Classification: Severe/Fatal Event
Action: Disable “Bently Centurion Protocol” and download a new
configuration to the Communication Gateway module. If the
problem still exists, replace the Communication Gateway module
immediately.
116
Section 7 - Troubleshooting
Action: Download the software switches to the Communication Gateway
module. If the software switches are not correct, replace the
Communication Gateway module.
Module Reboot
Event Number: 320
Event Classification: Typical Logged Event
Action: No action required.
117
3500/92 Communication Gateway Module Operation Manual
I/O Module Detect Fault
Event Number: 399
Event Classification: Severe/Fatal Event
Action: Verify that the Communication Gateway Module and the
Communication Gateway I/O Module are plugged into the 3500
rack correctly. If that does not solve the problem, then determine
whether one of the following components is faulty:
• Communication Gateway Module
• Communication Gateway I/O Module
118
Section 7 - Troubleshooting
Event Classification: Severe/Fatal Event
Action: Verify that the Communication Gateway Module is fully inserted in
the rack. If the Communication Gateway Module is installed
correctly, determine whether one of the following components is
faulty:
• the Communication Gateway Module
• the rack backplane
119
Section 8 - Specifications
8. Specifications
8.1 Inputs
Power Consumption
5 watts typical.
Data
Collects data, such as current values and current
alarm statuses, via a high-speed internal network.
8.2 Outputs
Front Panel LEDs
OK LED
Indicates when the 3500/92 is operating properly.
TX/RX LED
Indicates when the 3500/92 is communicating with
other modules in the 3500 rack.
Protocols
Modbus
Based on AEG PI-MBUS-300 Rev. E Reference Manual.
3500 Software
Bently Nevada LLC proprietary protocol for 3500
Monitoring System configuration and data
acquisition.
121
3500/92 Communication Gateway Module Operation Manual
8.4 CE Mark Directives
8.4.1 EMC Directives
EN50081-2
Radiated Emissions
EN 55011, Class A
Conducted
Emissions
EN55011, Class A
EN50082-2
Electrostatic
Discharge
EN 61000-4-2, Criteria B
Radiated
Susceptibility
EN 50140, Criteria A
Conducted
Susceptibility
EN 50141, Criteria A
Electrical Fast
Transient
EN 61000-4-4, Criteria B
Surge Capability
EN 61000-4-5, Criteria B
Magnetic Field
EN 61000-4-8, Criteria A
Power Supply Dip
EN 61000-4-11, Criteria B
Radio Telephone
ENV 50204, Criteria B
122
Section 8 - Specifications
8.5 Hazardous Area Approvals
CSA-NRTL/C
Class I, Division 2, Groups A, B, C, D
8.6 Physical
8.6.1 Main Board
Dimensions (Height x
Width x Depth)
241 x 24.4 x 242 mm (9.50 x 0.96 x 9.50 in)
Weight
0.82 kg (1.8 lbm)
123
Section 9 - Ordering Information
9. Ordering Information
9.1 3500/92 Communication Gateway
Application Advisory
3500/92-AXX-BXX-CXX
A: I/O Module Type
01 Modbus RS-232/422 I/O module
02 Modbus RS-485 I/O module
03 Ethernet/Modbus RS-232 I/O module
04 Ethernet/Modbus RS-485 I/O module
B: Memory Option
01 Low memory
C: Agency Approval Option
00 None
01 CSA-NTRL/C
9.2 Cables
9.2.1 Ethernet RJ45 Cable
138131-AXXX
A: Cable Length
006 6 feet (1.8 metres)
125
3500/92 Communication Gateway Module Operation Manual
010 10 feet (3.1 metres)
025 25 feet (7.6 metres)
040 40 feet (12.2 metres)
050 50 feet (15.3 metres)
075 75 feet (22.8 metres)
085 85 feet (25.9 metres)
100 100 feet (30.5 metres)
120 120 feet (36.6 metres)
150 150 feet (45.7 metres)
200 200 feet (61.0 metres)
250 250 feet (76.2 metres)
320 320 feet (97.5 metres)
127
3500/92 Communication Gateway Module Operation Manual
02 Assembled
9.3 Spares
9.3.1 Modules
136180-01
3500/92 Communication Gateway Module.
125736-01
Modbus RS-232/422 I/O Module.
133323-01
Modbus RS-485 I/O Module.
136188-01
Ethernet/Modbus RS-232 I/O Module.
128
Section 9 - Ordering Information
136188-02
Ethernet Modbus RS-485 I/O Module.
138629-01
3500/92 Communication Gateway Module
Operation Manual.
04425545
Grounding Wrist Strap. For single use only.
137494-01
EVEN Firmware IC. You must order this as a pair
with part number 137495-01 when upgrading
firmware.
137495-01
ODD Firmware IC. You must order this as a pair with
part number 137494-01 when upgrading firmware.
9.3.2 Cables
130119-01
Host Computer to RS-232/422 Converter RS-232
Cable.
022300411
RS-232 to RS-422 Converter 110 Vac Cable.
02230412
RS-232 to RS-422 Converter 220 Vac Cable.
139036-01
RS-485 “Y” Cable.