Fire Pump Controller For Electric Driven Fire Pumps

Standard Equipment & Performance


• Single handle operator for easy operation of isolating switch & circuit breaker
• Door interlocked with switch to prevent unintended exposure to electrical hazard
• Automatic start with Pressure Control, Display & Logging
• Complies with latest edition of NFPA 20

System Pressure Display


• Ten inch pressure Chart Recording accessible through outer door
• Programmable Pressure Units (psi, kPa, bars)
• Pressure Adjustable in Increments of 1psi
• Failsafe Design (motor runs on loss of control power)
• Built-in Running Period Timer and LED
• Standard Sequential Start Timer and LED
• Deluge valve start from normally closed contact (open to start)
• Remote start from normally open contact (close to start)
• Emergency start, by simply lifting the mechanical start handle

Operator interface:
• 2 line liquid crystal display of all 3 phase to phase RMS voltage and
F current measurements simultaneously
• Real time clock
• RS485 communications
• LED “Power Available”: (Green) Illuminates when all three phase voltage are
greater than 83% of nominal. Extinguishes if one or more phases are below 83%
of nominal. LED will flash for 5 seconds if a brownout condition is detected
• LED “Phases Reversed”: (Red) Illuminates if phases are reversed.
• LED “Locked Rotor Impending Trip”: (Red) Flashes on impending breaker trip
• Test function for motor locked rotor protection. Software test through keypad
combination, will cause Motor Locked Rotor LED to flash. After appropriate time
delay, shunt trip relay of the Motor Protector will energize.
• Test function for Phases Reversed. Software test through keypad combination to
test the phase detection circuit for five seconds.
• Data logging at time of motor start (auto or manual), Motor Stop, Power On and
Power Off
• Tamper proof Membrane keypad for setting clock and recalling data logging

Microprocessor Motor Protector:


• Locked Rotor over-current protection: - Non-adjustable trip set to NFPA 20 7-4.4
requirements
• Detects phase loss by voltage level (one or more phases below 17% of nominal for
more than 30 cycles, phase angle and voltage imbalance greater than 6% for more
than three seconds)
• “Brown-out” detection: one or more phases below 83% of nominal to signal front panel.
Typical scan time: 1 per 1/4 to 1/2 second
• Phase reversal detection
• Provides Static Single Phase Protection: Permits motor to run under dynamic single
phase condition
• Accuracy: Voltage 1%, Current 3% at normal motor running conditions

Visit our Website www.joslynclark.com for detailed information

F2
General Information Fire Pump Control
Motor Starting Types Automatic Transfer Switch Modification
Across-The-Line Type D10630 Fire Pump Controllers with Automatic Transfer Switches
The most economical and most commonly used type of fire provide for power connections to the fire pump motor from
pump controller. Full voltage is applied to the motor for the primary power source or an alternate power source.
srarting, by use of a single motor contactor. Starting inrush If the primary power fails, the transfer switch automati-
is approximately 600% of rated motor full-load amperes. cally switches to the emergency source. Automatic
retransfer to primary power source occurs after restora-
Autotransformer Type D10640 tion of normal power.
The motor circuit voltage is reduced by autotransformer The alternate source may be an emergency generator or
action during the motor starting period. A line contactor by- second utility supply. Circuit requirements differ for each
passes the autotransformer after a time delay. type, therefore the alternate source must be specified.
Starting line current is 42% of across-the-line starting
The Automatic Transfer Switch is housed in a barriered
inrush approximately 250% rated motor full-load amperes
compartment of the Fire Pump Controller. This complete
with the autotransformer on the 65% tap as shipped from
assembly, consisting of Fire Pump Controller and Auto-
the factory. A 50% and 80% tap can be used.
matic Transfer Switch is factory assembled, wired, tested
and shipped as a single unit.
Primary Resistor Type D10650
A resistor, inserted in the motor line, results in soft starting
and smooth acceleration. A line contactor by passes the
resistor after a time delay. Starting line current is 65-74% of
across-the-line starting inrush approximately 390-444% of
rated motor full-load amperes.
F
Part Winding Type D10670
2-winding type motor required - the first winding is con-
nected to the line to start; the second connected in parallel
by a second contactor, after a time delay. Starting line
current is 65% of across-the-line starting inrush - approxi-
mately 390% of rated motor full-load amperes.

Wye-Delta Type D10680 and D10690


Under a normal automatic start mode, the start contactors
close connecting the motor to the line in a wye connection.
After approximately 3 second time delay the start contactors
open and the run contactor closes reconnecting the motor
in a Delta connection.
Starting line current is 33.3% of across-the-line starting
inrush - approximately 200% rated motor full-load amperes.
Closed transition type D10680 provides no power interrup-
tion to the motor during transition from Wye to Delta connec-
tion, This provides smooth acceleration.
Open transition type D10690 provides on brief interruption
of power to the motor during transition from start to run.

Solid State Reduced Voltage Type D10620


Solid State reduced voltage fire pump controllers provide
smooth, stepless transition from initial voltage to full run
voltage. This results in soft starting with smooth acceleration
4
1
and deceleration. Starting line current may be adjusted
5 down to 200% of rated full-load amperes.

Visit our Website www.joslynclark.com for detailed information

F3
Fire Pump Control General Information
General
Joslyn Clark Diesel Fire Pump Controllers are designed
and listed specifically for diesel engine driven fire pump
service. These controllers meet or exceed all require-
ments of the National Fire Protection Association Standard
NFPA 20, are listed by Underwriters Laboratories Inc., and
approved by the Factory Mutual System.
The diesel controller provides four (4) major functions:
Starts the diesel engine automatically from water
pressure control or nonautomatically from manual
electric control.
Monitors engine as well as system conditions.
Maintains charge on engine starting batteries.
Initiates a weekly test of the system.

Standard Equipment
Type 2 Drip-Proof, Moisture Resistant, lockable
enclosure with break glass panel, is suitable for wall
or floor mounting. Painted with a UL Recognized
F Corrosion Resistant red baked enamel offers
superior resistance to the damp corrosive environ-
ment of pump rooms.
Voltage surge arrester for incoming 120 Volt AC
supply is connected to a line disconnect switch.
Provides an added degree of component pro-
tection against lightning strikes for greater reliability.
Visual indicators and audible alarms are provided to
indicate the following:
Automatic ON Charger Loss
Low Oil Pressure #1 Battery Overcharge
Engine Over Temp #1 Battery Failure
Safety Shut Down #2 Battery Overcharge
Fail To Start #2 Battery Failure
Engine Overspeed

2 SETS OF SPDT contacts for remote alarm of :


Engine Running, Engine Failure and Controller
Switch Off.
Battery chargers are solid state, 12 amps
current limiting for 225 ampere hour batteries.
Pressure recorder 7 day spring wound type is
located with the pressure switch below and away Safety shut down circuit will shut down engine on "Low
from electric components. Oil Pressure" and "Engine Over Temperature" if engine
is running due to "Weekly Test" or "AC Power failure".
Programable Weekly Timer to automatically start An alarm will signal this condition.
and run the engine for 30 minutes once a week.
Two "Manual Start" pushbuttons are provided to crank
Solid State crank cycle controller is a plug-in tamper from either battery or both at the same time for hard 3
resistant module. start conditions. 0
5
Internal plumbing and solenoid valve is rated for LED's (light emitting diodes) provide easy diognotics
500 PSI service. of engine and controller interaction as well as charger
and battery conditions.

Visit our Website www.joslynclark.com for detailed information

F4
General Information Fire Pump Control
Alarm Panel
General
Joslyn Clark alarm panels provide visual signals and
audible alarms to monitor the status and operation of the
pump controller. A separate, "reliable" source of 115V
supervisory power must be provided to the alarm panel.
Each abnormal condition lights the appropriate light and
sounds the audible alarm. The audible alarm can be push
button silenced, but the light remains lit until the abnormal-
ity is cleared. Signals are independent of each other and
the panel operation will repeat for each new abnormal
condition, regardless of the previous status.

Standard Equipment & Performance


Type 1 wall mounting enclosure
Key lockable enclosure
Alarm test button
Individual audible alarm silence button
Basic Type 10665-1 alarm panel includes both visual
and audible alarms for:
Supervisory power failure
Pump Running
Phase Reversal
Phase Loss and-or Controller power loss
F
Field Connection Diagram A10-357165
Schematic Diagram A10-357160

Listed Modifications
Fire Pump Start - This is commonly called "Remote
Start" for starting the main fire pump controller.
Up to three additional alarm lights and silence buttons
may be ordered. Specify name plate markings. Signal
contacts must close for alarm.

1 Thru 8 is a combination Pushbutton &Light.

1. Supervisory Power Failure


2. Pump Running
3. Phase Reversal
4. Phase Loss and/or Control Power Loss
5. Option 1 "Fire Pump Start" Button (Remote Start)
6. Option 4
7. Option 5
8. Option 2

3
0
5

Visit our Website www.joslynclark.com for detailed information

Ordering Information
See Price Sheet PS-10600-1

F5
General Information Fire Pump Control
Medium Voltage Type
General
Medium voltage fire pump controllers are primarily used to start large
horsepower motors. These starters are designed for automatic starting of
squirrel cage motors when starting current must be reduced.

Motors starting current at 2300 volts or 4160 volts is considerably below that
at 460 volts. This eliminates many problems that exists when starting large
horsepower motors at lower voltages.

Approvals and Standards


Joslyn Clark Controllers are UL listed and FM approved for applications up to
7200 volts. They are built to meet or exceed the following standards:

NEMA ICS2-329 class E2


UL 347 High Voltage Industrial Control Equipment
NFPA 20 The Installation of Electric Fire Pumps
NFPA 70 National Electrical Code

F Construction Details
Enclosures - Free standing, single high, non withdrawable starter
mounted in a NEMA 2 enclosure. NEMA 3R and 12 enclosures
are also available. NEMA 4 design includes an outer shell. The
enclosure is painted, all other parts are plated with corrosion
resistant materials. Type 4X outer enclosure is constructed with
#304 stainless steel.

Grounding - The control enclosure can be grounded through the


conduit connections and by ground wire to grounding pad.

Isolating Means - The isolating means is Fault Making, Load


Breaking, visible break disconnect switch externally operable.
The 3 blades are grounded in the open position. It has an
auxiliary contact that disconnects the control supply when
opened. It has a mechanical interlock so that the switch had to
be open before the high voltage door can be opened, and the
door has to be closed before the isolating switch can be closed.
The contactor is interlocked so that the isolating switch can not
be opened with contactor closed.

Power Fuse - Three medium voltage power fuses R-rated are


provided for short circuit protection.

Fuses - For Control Transformers - Three medium voltage control


transformers primary E-rated fuses are provided for short circuit
protection of control transformers.

Motor Starting - Manual electric starting may be obtained when


control circuit power is available by push button or by an
externally operable handle through a lever which actuates interlock
contacts. Manual electric starting causes the starting contactor coils
to be energized.

If control circuit power is not available, manual mechanical starting


may be obtained by the externally operable handle through a lever
which mechanically closes the motor run contact.