Description

Softstarters type PS S, PS D and PS DH


ABB’s solid state starter range is used when it is important to have a smooth start-up of various types of motor drives.
Instead of switching directly to full voltage the softstarter ensures a gradual voltage increase.
ABB’ s Softstarter is available in four versions, PS S 03…25, PS S 18/30…300/515, PS D 75…840 and PS DH 30…720.

PS S 03…PS S 25 is a compact solution for small motors. An optional ”Current limit” function is available. Two signal
Mounting is on 35 mm DIN-rail. This small softstarter has a relays are built in as standard. This softstarter has a service
built-in bypass contact. factor of 1.15, which means that the maximum operational
current is Ie (rated current) x1.15.
PS S 18/30…PS S 300/515 for normal duty applications
Example: the PS S 18/30 connected in-line has an Ie of 18 A.
and connection both ”In Line” and ”Inside Delta” (compare
The maximum operational current is then 1.15 x 18 A = 20.7 A.
the connection with a standard Y/D starter). The result of
”Inside Delta” connection is a 42 % reduction of the current PS D 75…PS D 840 and PS DH 30…PS DH 720 softstarters
exposed to the softstarter. It will then be possible, for have a robust design in metal housing for many types of
example, to start and run a 100 A motor using a 58 A applications, both normal duty and heavy duty. Flexible
softstarter. parameter settings with potentiometers and clear indication
with LEDs of status and faults on front of the unit. The optional
built in advanced electronic overload relay (always included as
standard for PS DH versions) provides much better motor
protection than a conventional bimetallic relay, for example in
intermittent duty.
1SFT 98899-003

In-line and inside-delta connection of PS S 18/30…300/515

PS S 03…12
3.5
2.0 5.0
0.5 6.5

4.0 40
PS S 18/30…300/515 PS D and PS DH
2.0 6.0
1SFT 98899-030

20 60
0.5 8.0 0 85

2 5
10
1
20
F1 F2 START
40
0,5 60 s
20
On R 5 50
STOP 100

PS S 25 T P 0,5
30
240 s
40

N Y UINI 50
5.0
2.5 7.5 PF
1 2 3 4
OFF

Kick 10 60 %
0.5 10 70
SC 50
TPF USD 90
10 norm slow
1SFT 98899-031

5 15 30 100 %
1SFT 98899-032

80 90 3 4
0.5 20
Ir ILIM

70 100 % 2 5 x Ir
25
15 35
1SFT 98899-043

5 50

The operator panels for PS S, PS D and PS DH have LED´s, potentiometers and switches for indication and settings.

ABB Building Technologies 3


1SFC 288001-en, ed5. June 2000
Ordering data Soft starter PS S 03…25, PS S18/30…300/515

PS S 03…25 For normal starts


Rated
Motor power motor Control
230 V 400 V 500 V 600 V current voltage
Pe Pe Pe Pe Ie Uc Type Order code Weight
kW kW kW kW A V kg
0.75 - - - 3.5 1) PS S 03-220B 1SFA 89 1001 R2209 0.27
- 1.1 - - 3.5 2) PS S 03-400B 1SFA 89 1001 R4009 0.27
- - 1.5 - 3.5 3) PS S 03-480B 1SFA 89 1001 R4809 0.27
3.0 - - - 12 1) PS S 12-220B 1SFA 89 1002 R2209 0.27
5.5 12 2) PS S 12-400B 1SFA 89 1002 R4009 0.27
- - 5.5 - 12 3) PS S 12-480B 1SFA 89 1002 R4809 0.27
- - - 7.5 12 3) PS S 12-600B 1SFA 89 1002 R6009 0.27
6.5 - - - 25 1) PS S 25-220B 1SFA 89 1003 R2209 0.60
11.0 25 2) PS S 25-400B 1SFA 89 1003 R4009 0.60
- - 15.0 - 25 3) PS S 25-480B 1SFA 89 1003 R4809 0.60
- - - 18.5 25 3) PS S 25-600B 1SFA 89 1003 R6009 0.60

1) Control Voltage 24-110 VAC/DC, 110-230 VAC


2) Control Voltage 24-110 VAC/DC, 110-400 VAC
3) Control Voltage 24-110 VAC/DC, 110-500 VAC

PS S 18/30…300/515 For normal starts

IN LINE INSIDE DELTA


Rated Rated
Motor power motor Motor power motor
230 V 400 V 500 V 690 V current 230 V 400 V 500 V 690 V currrent
Pe Pe Pe Pe Ie Pe Pe Pe Pe Ie Type Order code Weight
kW kW kW kW A kW kW kW kW A 1) 2) kg

4 7.5 11 - 18 7.5 15 18.5 - 30 PS S 18/30-500* 1SFA 89 2001 R100x 2.3


- 7.5 11 15 18 - 15 18.5 25 30 PS S 18/30-690* 1SFA 89 3001 R100x 2.3
7.5 15 18.5 - 30 12.5 25 30 - 52 PS S 30/52-500* 1SFA 89 2002 R100x 2.3
- 15 18.5 25 30 - 25 30 45 52 PS S 30/52-690* 1SFA 89 3002 R100x 2.3
9 18.5 22 - 37 15 30 37 - 64 PS S 37/64-500* 1SFA 89 2003 R100x 2.3
- 18.5 22 30 37 - 30 37 55 64 PS S 37/64-690* 1SFA 89 3003 R100x 2.3
11 22 25 - 44 22 37 45 - 76 PS S 44/76-500* 1SFA 89 2004 R100x 2.3
- 22 25 37 44 - 37 45 59 76 PS S 44/76-690* 1SFA 89 3004 R100x 2.3
12.5 25 30 - 50 25 45 55 - 85 PS S 50/85-500* 1SFA 89 2005 R100x 3.6
- 25 30 45 50 - 45 55 75 85 PS S 50/85-690* 1SFA 89 3005 R100x 3.6
15 30 37 - 60 30 55 75 - 105 PS S 60/105-500* 1SFA 89 2006 R100x 3.8
- 30 37 55 60 - 55 75 90 105 PS S 60/105-690* 1SFA 89 3006 R100x 3.8
18.5 37 45 - 72 37 59 80 - 124 PS S 72/124-500* 1SFA 89 2007 R100x 3.8
- 37 45 59 72 - 59 80 110 124 PS S 72/124-690* 1SFA 89 3007 R100x 3.8
22 45 55 - 85 40 75 90 - 147 PS S 85/147-500* 1SFA 89 2008 R100x 8.6
- 45 55 75 85 - 75 90 132 147 PS S 85/147-690* 1SFA 89 3008 R100x 8.6
30 55 75 - 105 55 90 110 - 181 PS S 105/181-500* 1SFA 89 2009 R100x 10.4
- 55 75 90 105 - 90 110 160 181 PS S 105/181-690* 1SFA 89 3009 R100x 10.4
37 75 90 - 142 75 132 160 - 245 PS S 142/245-500* 1SFA 89 2010 R100x 10.4
- 75 90 132 142 - 132 160 220 245 PS S 142/245-690* 1SFA 89 3010 R100x 10.4
45 90 110 - 175 90 160 200 _ 300 PS S 175/300-500* 1SFA 89 2011 R100x 20.5
- 90 110 160 175 - 160 200 257 300 PS S 175/300-690* 1SFA 89 3011 R100x 20.5
75 132 160 - 250 132 220 295 - 430 PS S 250/430-500* 1SFA 89 2013 R100x 22.0
- 132 160 220 250 - 220 295 400 430 PS S 250/430-690* 1SFA 89 3013 R100x 22.0
90 160 200 - 300 160 257 355 - 515 PS S 300/515-500* 1SFA 89 2014 R100x 22.0
- 160 200 257 300 - 257 355 500 515 PS S 300/515-690* 1SFA 89 2014 R100x 22.0

1) Code letter for supply voltage * is F = 110-120V, 50/60Hz; L = 220-240V 50/60 Hz.
2) Code number for supply voltage x is 1 = 110-120V, 50/60Hz; 2 = 220-240V 50/60 Hz
4 ABB Building Technologies
1SFC 288001-en, ed5. June 2000
Ordering data Accessories PS S 18/30…300/515

Current transformer for current limit function


To be connected to terminals 11 and 12 on the soft starter.
The setting range (1.5 – 4) corresponds to a multiple of the transformer ratio.
Technical data below shows transformer ratio and number of turns for the primary winding.

Type Order code Technical data For softstarter Weight


kg

PS CT-60 1SFA 89 9001 R1060 60/1 – 2 turns PS S 18/30 0.30


PS CT-40 1SFA 89 9001 R1040 40/1 – 1 turn PS S 30/52 0.30
PS CT-50 1SFA 89 9001 R1050 50/1 – 1 turn PS S 37/64 0.30
PS CT-60 1SFA 89 9001 R1060 60/1 – 1 turn PS S 44/76 0.30
PS CT-75 1SFA 89 9001 R1075 75/1 – 1 turn PS S 50/85 0.30
PS CT-75 1SFA 89 9001 R1075 75/1 – 1 turn PS S 60/105 0.30
PS CT-100 1SFA 89 9001 R1100 100/1 – 1 turn PS S 72/124 0.25
PS CT-125 1SFA 89 9001 R1125 125/1 – 1 turn PS S 85/147 0.25
PS CT-150 1SFA 89 9001 R1150 150/1 – 1 turn PS S 105/181 0.25
PS CT-200 1SFA 89 9001 R1200 200/1 – 1 turn PS S 142/245 0.25
PS CT-250 1SFA 89 9001 R1250 250/1 – 1 turn PS S 175/300 0.25
PS CT-400 1SFA 89 9001 R1400 400/1 – 1 turn PS S 250/430 0.25
PS CT-400 1SFA 89 9001 R1400 400/1 – 1 turn PS S 300/515 0.25

Cable connectors for Cu cables (set of 3)


Type Order code Wire range For softstarter Tightening torque Weight
max. Nm kg

– 1SDA 02 3354 R1 6-185 mm2 PS S 85/147…142/245 16 0.2


LZ 185-2C/120 1SFN 07 4709 R1000 2x(50-120) mm2 PS S 85/147…142/245 16 0.3
– 1SDA 02 3368 R1 16-240 mm2 PS S 175/300…300/515 25 0.4

Cable connectors for Al and Cu cables (set of 3)


Type Order code Wire range For softstarter Tightening torque Weight
max. Nm kg

– 1SDA 02 3356 R1 35-95 mm2 PS S 85/147…142/245 13.5 0.1


– 1SDA 02 3357 R1 25-150 mm2 PS S 85/147…142/245 31 0.1
– 1SDA 02 3370 R1 120-240 mm2 PS S 175/300…300/515 43 0.1

Terminal shrouds (set of 2)


Type Order code For softstarter Weight
kg

LT 185-AC 1SFN 12 4701 R1000 For cable connectors PS S 85/147…142/245 0.1


LT 185-AL 1SFN 12 4703 R1000 For compression lugs PS S 85/147…142/245 0.1
LT 300-AC 1SFN 12 5101 R1000 For cable connectors PS S 175/300…300/515 0.2
LT 300-AL 1SFN 12 5103 R1000 For compression lugs PS S 175/300…300/515 0.2

Terminal nut washer (set of 2)


Type Order code For softstarter Weight
kg

LE 185 1SFN 07 4716 R1000 PS S 85/147…142/245 0.2


LE 300 1SFN 07 5116 R1000 PS S 175/300…300/515 0.3

Terminal enlargements
Type Order code For softstarter Weight
kg

LW 75 BK 529 002-A PS S 50/85…72/124 0.1


LW 185 1SFN 07 4707 R1000 PS S 85/147…142/245 0.25
LW 300 1SFN 07 5107 R1000 PS S 175/300…300/515 0.4

ABB Building Technologies 5


1SFC 288001-en, ed5. June 2000
Ordering data Softstarter PS D 75…840

PS D 75…840 For normal starts


Motor power Rated
220-230 V 380-400/415 V 500 V 690 V motor current Order code
Pe Pe Pe Pe Ie Type Supply voltage Us Supply voltage Us Weight
kW kW kW kW A PS D 110-127 V,50/60 Hz 220-240 V,50/60 Hz kg

22 37 – – 28–75 75 1SFA 88 4204- F 1SFA 88 4204- L 10


– – 45 – 28-75 75 1SFA 88 5204- F 1SFA 88 5204- L 10
30 55 – – 70–110 110 1SFA 88 4205- F 1SFA 88 4205- L 11
– – 75 – 70–110 110 1SFA 88 5205- F 1SFA 88 5205- L 11

37 75 – – 87.5–145 145 1SFA 88 4206- F 1SFA 88 4206- L 13


– – 90 – 87.5–145 145 1SFA 88 5206- F 1SFA 88 5206- L 13
45 90 – – 105–175 175 1SFA 88 4207- F 1SFA 88 4207- L 25
– – 110 – 105–175 175 1SFA 88 5207- F 1SFA 88 5207- L 25

55 110 – – 140–210 210 1SFA 88 4208- F 1SFA 88 4208- L 28


– – 132 – 140–210 210 1SFA 88 5208- F 1SFA 88 5208- L 28
75 132 – – 140–250 250 1SFA 88 4209- F 1SFA 88 4209- L 28
– – 160 – 140–250 250 1SFA 88 5209- F 1SFA 88 5209- L 28

90 160 – – 175–300 300 1SFA 88 4210- F 1SFA 88 4210- L 28


– – 200 – 175–300 300 1SFA 88 5210- F 1SFA 88 5210- L 28
110 200 – – 210–370 370 1SFA 88 4211- F 1SFA 88 4211- L 51
– – 250 – 210–370 370 1SFA 88 5211- F 1SFA 88 5211- L 51
– – – 355 100–370 370 1SFA 88 6211- A F 1SFA 88 6211- A L 51

132 250 – – 280–470 470 1SFA 88 4212- F 1SFA 88 4212- L 51


– – 315 – 280–470 470 1SFA 88 5212- F 1SFA 88 5212- L 51
– – – 450 250–470 470 1SFA 88 6212- A F 1SFA 88 6212- A L 51

160 315 – – 350–570 570 1SFA 88 4213- F 1SFA 88 4213- L 54


– – 400 – 350–570 570 1SFA 88 5213- F 1SFA 88 5213- L 54
– – – 560 300–570 570 1SFA 88 6213- A F 1SFA 88 6213- A L 54

200 400 – – 420–720 720 1SFA 88 4214- F 1SFA 88 4214- L 54


– – 500 – 420–720 720 1SFA 88 5214- F 1SFA 88 5214- L 54
– – – 710 375–720 720 1SFA 88 6214- A F 1SFA 88 6214- A L 64

250 450 – – 525–840 840 1SFA 88 4215- F 1SFA 88 4215- L 64


– – 560 – 525–840 840 1SFA 88 5215- F 1SFA 88 5215- L 64
– – – 800 500–840 840 1SFA 88 6215- A F 1SFA 88 6215- A L 64
replaced by “B” if overload relay is included, otherwise by “A”
replaced by code letter for current range according to table on page 7

6 ABB Building Technologies


1SFC 288001-en, ed5. June 2000
Ordering data Softstarter PS DH 30…720

PS DH 30...720 For heavy duty starts


Motor power Rated
220-230 V 380-400/415 V 500 V motor current Order code
Pe Pe Pe Ie Type Supply voltage Us Supply voltage Us Weight
kW kW kW A PS DH 110-127 V,50/60 Hz 220-240 V,50/60 Hz kg

7.5 15 – 14–30 30 1SFA 88 4301- B F 1SFA 88 4301- B L 10


– – 18.5 14–30 30 1SFA 88 5301- B F 1SFA 88 5301- B L 10
15 22 – 28–45 45 1SFA 88 4302- B F 1SFA 88 4302- B L 10
– – 30 28–45 45 1SFA 88 5302- B F 1SFA 88 5302- B L 10

18.5 30 – 35–60 60 1SFA 88 4303- B F 1SFA 88 4303- B L 10


– – 37 35–60 60 1SFA 88 5303- B F 1SFA 88 5303- B L 10
22 37 – 42–75 75 1SFA 88 4304- B F 1SFA 88 4304- B L 11
– – 45 42–75 75 1SFA 88 5304- B F 1SFA 88 5304- B L 11

30 55 – 70–110 110 1SFA 88 4305- B F 1SFA 88 4305- B L 13


– – 75 70–110 110 1SFA 88 5305- B F 1SFA 88 5305- B L 13
37 75 – 87.5–145 145 1SFA 88 4306- B F 1SFA 88 4306- B L 25
– – 90 87.5–145 145 1SFA 88 5306- B F 1SFA 88 5306- B L 25

45 90 – 105–175 175 1SFA 88 4307- B F 1SFA 88 4307- B L 28


– – 110 105–175 175 1SFA 88 5307- B F 1SFA 88 5307- B L 28
55 110 – 140–210 210 1SFA 88 4308- B F 1SFA 88 4308- B L 28
– – 132 140–210 210 1SFA 88 5308- B F 1SFA 88 5308- B L 28

75 132 – 140–250 250 1SFA 88 4309- B F 1SFA 88 4309- B L 28


– – 160 140–250 250 1SFA 88 5309- B F 1SFA 88 5309- B L 28
90 160 – 175–300 300 1SFA 88 4310- B F 1SFA 88 4310- B L 52
– – 200 175–300 300 1SFA 88 5310- B F 1SFA 88 5310- B L 52

110 200 – 210–370 370 1SFA 88 4311- B F 1SFA 88 4311- B L 52


– – 250 210–370 370 1SFA 88 5311- B F 1SFA 88 5311- B L 52
132 250 – 280–470 470 1SFA 88 4312- B F 1SFA 88 4312- B L 55
– – 315 280–470 470 1SFA 88 5312- B F 1SFA 88 5312- B L 55

160 315 – 350–570 570 1SFA 88 4313- B F 1SFA 88 4313- B L 55


– – 400 350–570 570 1SFA 88 5313- B F 1SFA 88 5313- B L 55
200 400 – 420–720 720 1SFA 88 4314- B F 1SFA 88 4314- B L 65
– – 500 420–720 720 1SFA 88 5314- B F 1SFA 88 5314- B L 65
replaced by code letter for current range according to table below

Code letter for current range


Current range PS D – – – – 75 110 145 175 210 250 300 370 470 570 720 840
A PS DH 30 45 60 75 – 110 145 175 210 250 300 370 470 570 720 –
PSD (690 V) – – – – – – – – – – – 370 470 570 720 840
220-500 V 690 V*
14 – 20 E
17,5 – 25 F
21 – 30 G
28 – 40 H H
35 – 50 J J J
42 – 60 K K K
52,5 – 75 L L
70 – 100 M
87,5 – 125 N N
105 – 150 P P
140 – 200 / 100 – 200 R R R R
175 – 250 S S S
210 – 300 / 150 – 300 T T/T
280 – 400 / 200 – 400 U/U U
350 – 500 / 250 – 500 V/V V
420 – 600 / 300 – 600 W/W W
525 – 750 / 375 – 750 X/X X
700 – 1000 / 500 – 1000 Y/Y
* For 690V red code letters are used.

ABB Building Technologies 7


1SFC 288001-en, ed5. June 2000
General technical data

PS S 03…PS S 25 and PS S 18/30…PS S 300/515

PS S 03…PS S 12 PS S 25 PS S 18/30…PS S 300/515

Rated insulation voltage Ui V 630 630 690


Rated operational voltage Ue V 220 – 230 220 – 230 200 – 690
400-415 400-415
480-500 480-500
600 600
Starting capacity at max.
Rated current Ie 5 x Ie for 5 sec 5 x Ie for 5 sec 4 x Ie for 10 sec
Number of starts per hour 62) 62) 305)
Overload capability Overload class A 10 10 10
Service factor % 100 100 115 (PS S 18/30…250/430)
110 (PS S 300/515)
Ambient temperature
During operation °C -20 – +50 -20 – +50 -25 – +601)
During storage °C -40 – +70 -40 – +70 -40 – +70

Degree of protection
Main circuit IP 20 IP 20 IP 20 (PS S 18/30-500…44/76-500)
IP 10 (PS S 50/85-500…72/124-500)
IP 10 (PS S 18/30-690…72/124-690)
IP 00 (PS S 85/147…300/515)
Supply and control circuit IP 20 IP 20 IP 20
Settings
Ramp time during start s 0.5 – 6.5 -+15% 0.5 – 10 -+10% 1 – 30
Ramp time during stop s 0.5 – 8 -+25% 5 – 20 -+10% 0 – 30
Initial voltage during start % 0 – 85 -+15% 5 – 50 -+5% 30 – 70
Current limit function xIe No No 1.5 – 43)
Switch for
Inside delta connection ON/OFF No No Yes
Signal relay
By-pass signal No4) No4) Yes
Fault signal No No Yes
Rated operational voltage Ue V – – 250
Rated thermal current Ith A – – 5
Rated operational current Ie
at AC-15 (Ue=250 V) A – – 1.5
Signal indication LED
Ready to start/stand by ON Green Green Green
Ramping up/down Yellow Yellow (flashing) No
Completed start ramp T.O.R. Yellow Yellow Green
General fault F1 – Red Red
External fault F2 – – Red

1) Above 40 0C, up to max 600 C, reduce the rated current with 0.8 % per 0C.
2) When more than 6 starts per hour are required, contact your sales office.
3) Only if current transformer is connected (accessory).
4) The unit has built in by-pass contacts (AC-53b)
5) 50 % on time and 50 % off time. 3.5 x Ie for 7 sec.

8 ABB Building Technologies


1SFC 288001-en, ed5. June 2000
General technical data

General technical data PS D 75…840 and PS DH 30…720

PS D 75…145 PS D 175…840 PS DH 30…110 PS DH 145…720

Rated insulation voltage U i V 690 690 690 690


Rated operational voltage Ue V 220–690 220–690 220–500 220-500
Starting capacity at max
rated current Ie 4,5 x Ie for 14s 5 x Ie for 7s 5 x Ie for 25s 5 x Ie for 25s
Number of starts per hour 6 3 6 1
Overload capacity Overload class A 10 10 30 30
Service factor % 100 100 100 100

Ambient temperature
During operation1) °C 0 – 50 0 – 50 0 – 50 0 – 50
During storage °C -40 – +70 -40 – +70 -40 – +70 -40 – +70
Degree of protection IP 00 IP 00 IP 00 IP 00

Settings
Ramp time during start sec 0.5 – 60 0.5 – 60 0.5 – 60 0.5 – 60
Initial voltage during start % 10 – 60 10 – 60 10 – 60 10 – 60
Ramp time during stop sec 0.5 – 240 0.5 – 240 0.5 – 240 0.5 – 240
Step down voltage special ramp % 100 – 30 100 – 30 100 – 30 100 – 30
Current limit function 2 – 5 x Ie 2 – 5 x Ie 2 – 5 x Ie 2 – 5 x Ie
Adjustable rated motor current Ie2) % 70 – 100 70 – 100 70 – 100 70 – 100

Switches for
Energy saving function ON/OFF (PF) Yes Yes Yes Yes
Kick start, YES/NO (KICK) Yes Yes Yes Yes
High current switch off, YES/NO (SC) Yes Yes Yes Yes
Reaction time for energy saving
normal/slow (TPF) Yes Yes Yes Yes

Signal relays
Fault signal K6 Yes Yes Yes Yes
By-pass signal, start ramp completed K5 Yes Yes Yes Yes
Run signal K4 Yes Yes Yes Yes
Overload signal Yes Yes Yes Yes
Rated operational voltage Ue V 250 250 250 250
Rated thermal current Ith A 5 5 5 5
Rated operational current Ie
at AC-15 (Ue=250V) A 1.5 1.5 1.5 1.5

Signal indication (LED)


Fault (F1 and/or F2) red Yes Yes Yes Yes
Overload (OVL) yellow 3) Yes3) Yes3) Yes Yes
Ready to start/stand by (ON) green Yes Yes Yes Yes
Running (R) yellow Yes Yes Yes Yes
Completed start ramp (T) yellow Yes Yes Yes Yes
Energy saving function active (P) yellow Yes Yes Yes Yes

1) Above 40 °C, up to max 50 °C, reduce the rated current with 0.8 % per °C.
2) For Ue = 690 V; setting 50 – 100 %
3) Optional for PSD types

ABB Building Technologies 9


1SFC 288001-en, ed5. June 2000
Technical data

Size related data


Recommended ABB Power re-
Overload protection Max quirements
Current range power loss of supply
at max /e Max fuse rating main circuit4) circuit
Size Type A W Bussman fuses Ferraz fuses VA

PS S
03 TA 25 DU 2.2–3.1 – 16 A 170M1359 2
12 TA 25 DU 10–14 – 40 A 170M1363 2
25 TA 25 DU 18–25 – 50 A 170M1364 5

PS S
18/30 TA 25 DU 6–18 3) 50 A 170M1364 5) 63 A 6.6 URB 000 D08 V 0063 9
30/52 TA 25 DU 10–30 3) 80 A 170M1366 5) 100 A 6.6 URB 000 D08 V 0100 9
37/64 TA 42 DU 22–37 3) 125 A 170M1368 5) 160 A 6.6 URB 000 D08 V 0160 9
44/76 TA 75 DU 29–44 3) 160 A 170M1369 5) 200 A 6.6 URD 30 D08 A 0200 9
50/85 TA 75 DU 29–50 3) 160 A 170M1369 5) 200 A 6.6 URD 30 D08 A 0200 10
60/105 TA 75 DU 29–60 3) 200 A 170M1370 5) 250 A 6.6 URD 30 D08 A 0250 10
72/124 TA 75 DU 45–72 3) 250 A 170M1371 5) 315 A 6.6 URD 30 D08 A 0315 10
85/147 TA 110 DU 65–85 3) 315 A 170M1372 5) 400 A 6.6 URD 30 D08 A 0400 36
105/181 TA 110 DU 65–105 3) 400 A 170M3019 6) 400 A 6.6 URD 30 D08 A 0400 36
142/245 TA 200 DU 100–142 3) 450 A 170M3020 6) 500 A 6.6 URD 30 D08 A 0500 36
175/300 TA 200 DU 100-175 3) 500 A 170M3021 6) 530 A 6.6 URD 30 D08 A 0550 65
250/430 TA 450 DU 130-250 3) 700 A 170M4017 6) 630 A 6.6 URD 31 D08 A 0630 65
300/515 TA 450 DU 130-300 3) 900 A 170M5015 6) 900 A 6.6 URD 32 D11 A 0900 65
PS D
75 TA 75 DU 45–75 3) 250 A 170M1371 5) 315 A 6.6 URD 30 D08 A 0315 40
110 TA 110 DU 65–110 3) 315 A 170M1372 5) 400 A 6.6 URD 30 D08 A 0400 40
145 TA 200 DU 100–145 3) 400 A 170M3019 6) 400 A 6.6 URD 30 D08 A 0500 40
175 TA 200 DU 100–175 2) 450 A 170M3020 6) 500 A 6.6 URD 30 D08 A 0500 65
210 TA 450 DU 130–210 2) 500 A 170M3021 6) 530 A 6.6 URD 30 D08 A 0550 65
250 TA 450 DU 130–250 2) 630 A 170M4016 6) 550 A 6.6 URD 31 D08 A 0550 65
300 TA 450 DU 130–300 2) 700 A 170M4017 6) 630 A 6.6 URD 31 D08 A 0630 65
370 TA 900 DU 265–370 2) 900 A 170M5015 6) 900 A 6.6 URD 32 D11 A 0900 90
470 TA 900 DU 265–470 2) 1250 A 170M5018 6) 1250 A 6.6 URD 33 D11 A 1250 90
570 TA 900 DU 265–570 2) 1500 A 170M6018 6) 1250 A 6.6 URD 33 D11 A 1250 90
720 TA 900 DU 465–720 2) 1800 A 170M6020 6) 2000 A 6.6 URD 233 PLAF 2000 90
840 TA 900 DU 465–840 2) 1800 A 170M6020 6) 2000 A 6.6 URD 233 PLAF 2000 90

PS D(690V)
370 TA 450 DU 130–370 2) 900 A 170M5015 6) 900 A 6.6 URD 32 D11 A 0900 90
470 TA 900 DU 265–470 2) 1250 A 170M5018 6) 1250 A 6.6 URD 33 D11 A 1250 90
570 TA 900 DU 265–570 2) 1500 A 170M6018 6) 1250 A 6.6 URD 33 D11 A 1250 90
720 TA 900 DU 465–720 2) 1500 A 170M6018 6) 2000 A 6.6 URD 233 PLAF 2000 90
840 T 900 DU 465–840 2) 1500 A 170M6018 6) 2000 A 6.6 URD 233 PLAF 2000 90

PS DH
30 1) 3) 125 A 170M1368 5) 160 A 6.6 URD 30 D08 A 0160 40
45 1) 3) 200 A 170M1370 5) 200 A 6.6 URD 30 D08 A 0200 40
60 1) 3) 250 A 170M1371 5) 250 A 6.6 URD 30 D08 A 0250 40
75 1) 3) 315 A 170M1372 5) 315 A 6.6 URD 30 D08 A 0315 40
110 1) 3) 400 A 170M3019 6) 450 A 6.6 URD 30 D08 A 0450 40
145 1) 2) 450 A 170M3020 6) 500 A 6.6 URD 30 D08 A 0500 65
175 1) 2) 500 A 170M3021 6) 550 A 6.6 URD 30 D08 A 0550 65
210 1) 2) 630 A 170M4016 6) 630 A 6.6 URD 31 D08 A 0630 90
250 1) 2) 700 A 170M4017 6) 700 A 6.6 URD 32 D08 A 0700 90
300 1) 2) 900 A 170M5015 6) 900 A 6.6 URD 32 D08 A 0900 90
370 1) 2) 1000 A 170M5016 6) 1000 A 6.6 URD 33 D08 A 1000 90
470 1) 2) 1250 A 170M5018 6) 1250 A 6.6 URD 33 D08 A 1250 90
570 1) 2) 1500 A 170M6018 6) 1600 A 6.6 URD 33 TTF A 1600 90
720 1) 2) 1800 A 170M6020 6) 2000 A 6.6 URD 233 PLAF 2000 90

1) Electronic overload relay built in, optional for PS D types, standard for PS DH types 4) For the supply circuit: 6 A delayed
2) Total power loss: PLtot = [3 x Ie x 1.0] + 100 (W) Reduced to 100 W only when using by-pass 5) Fuse holder 170H 1007
3) Total power loss: PLtot = [3 x Ie x 1.0] + 50 (W) Reduced to 50 W only when using by-pass 6) Fuse holder 170H 3004
10 ABB Building Technologies
1SFC 288001-en, ed5. June 2000
Technical data

Cross section of connection cables PS S 03…25 and PS S 18/30…300/515

Type PS S 03… 12 25 18/30-500… 50/85-500… 85/147-500… 175/300…


44/76-500 72/124-500 142/245-500 300/515-500
18/30-690… 85/147-690… 175/300…
72/124-690 142/245-690 300/515-690

Main circuit
Connection clamp
Rigid solid/rigid stranded 1x mm2 2.5 10 2.5-16 6-50 See accessories See accessories
Rigid solid/rigid stranded 2x mm2 2.5 6 2.5-16 6-25 See accessories See accessories
Tightening torque (for guidance only) max.Nm 0.5 2 2.6 4.5 See accessories See accessories
Connection bar
Width and thickness mm – – – – 17.5x5 20x5
Hole diameter mm – – – – 8.5 10.2
Tightening torque (for guidance only) max. Nm – – – – 9 ?
Supply and control circuit
Connection clamp
Rigid solid/rigid stranded 1x mm2 2.5 2.5 2.5 2.5 2.5 2.5
Rigid solid/rigid stranded 2x mm2 2.5 - - - - -
Tightening torque (for guidance only) max. Nm 0.5 0.5 0.5 0.5 0.5 0.5

Cross section of connection cables PS D and PS DH

Type PS D 75 110...145 175...570 720 840


Type PS DH 30...60 75...110 145...470 570 720

Main circuit
Connection clamp
Cu-cable mm2 35 – – – –
Al-cable mm2 35 – – – –
Connection bar
Width x thickness mm – 15x4 25x6 40x6 50x6
Hole diameter mm – 7 11 11 11
Tightening torque min.Nm 2.5 2.4(M6) 12.0(M10) 12.0(M10) 12.0(M10)
(For guidance only) max.Nm 3.0 3.2(M6) 16.0(M10) 16.0(M10) 16.0(M10)
Supply and control circuit
Connection clamp mm2 2.5 2.5 2.5 2.5 2.5

ABB Building Technologies 11


1SFC 288001-en, ed5. June 2000
Dimensions

PS S 03, PS S12 PS S 25 PS S 18/30-500…44/76-500

1SFT 98899-007
163
104

104
1SFT 98899-005

1SFT 98899-009

10
120
Depth from DIN rail 101 mm Depth from DIN rail 101 mm
45 105 7,5
90
6,5(4x)
1SFT 98899-004

200
82

184
87
1SFT 98899-008

1SFT 98899-006
2

9
PS S 50/85-500…72/124-500 PS S 85/147-500…142/245-500 PS S 175/300-500…300/515-500
PS S 18/30-690…72/124-690 PS S 85/147-690…142/245-690 PS S 175/300-690…300/515-690
1SFT 98899-011
163

265

265
1SFT 98899-013

1SFT 98800-003
10

1,5

1.5

140 181 3,1 356 3.1

125 7,5 158 333

6,5(4x)
320

340
250
234

320

340
1SFT 98899-012
1SFT 98899-010

7(4x)
1SFT 98800-002
2

7(4x)
10
9

10

12 ABB Building Technologies


1SFC 288001-en, ed5. June 2000
Dimensions

PS D 75 PS D 110...145
PS DH 30...60 PS DH 75...110

1SFT 98899-017
1SFT 98899-015

4
218
218

125
280 280
265 7,5 265 7,5
45 45
L1 L2 L3
Ø 7 (4x) 15
20 21 22 23 24 25

OVERLOAD RESET

OVL

RESET

Ø 7 (4x)
20 21 22 23 24 25

OVERLOAD RESET

t
OVL

tar
fts
RESET

So
313
260
360

1SFT 98899-014

t
tar
fts
So

Max 400
2 5
10
1
20

260
313
F1 F2 START
40
0,5 60 s
20
On R 5 50
STOP

1SFT 98899-016
100

T P 0,5 240 s
30 40
N Y UINI 50
PF
Kick 10 60
70
SC 50
TPF
USD 90
norm slow
30 100
80 90 3 4
Ir I LIM

70 100 2 5 * Ir

2 5
10
1
20
F1 F2 START
40
0,5 60 s
20
On R 5 50
STOP 100

T P 0,5 240 s
220-240 V RUN TOR FAULT 30 40
50/60 Hz START/STOP N Y UINI 50
PF
Kick 10 60
70
SC 50
TPF
1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 norm slow
USD 90
30 100
80 90 3 4
Ir I LIM

T1 T2 T3 70 100 2 5 * Ir
26.5

220-240 V RUN TOR FAULT


50/60 Hz START/STOP

1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19

Ø7

26,5
PS D 175...300 PS D 370...840
PS DH 145...250 PS DH 300...720

F
6
6

1SFT 98899-021
310
1SFT 98899-019
310
235

205
183

540 66
210 210
6 hole 9x7
382
117 117
R3,5 25
20 21 22 23 24 25

OVERLOAD RESET

OVL

RESET
13

20 21 22 23 24 25

R5,5 OVERLOAD RESET

OVL

tart
fts
RESET

So

r t
572

600

sta
S oft F1

On
F2

R
START
1

0,5
5
2

20
5
10

40
60 s
50
20

STOP 100

T P 0,5 240 s
30 40
N Y UINI 50
PF
Kick 10 60
70
SC 50
TPF
USD 90
norm slow
380

402
444

30 100
80 90 3 4
Ir I LIM

70 100 2 5 * Ir

220-240 V RUN TOR FAULT


50/60 Hz START/STOP

2 5
10
1 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19
20
F1 F2 START
40
0,5 60 s
20
On R 5 50
STOP 100

T P 0,5 240 s
30 40
N Y UINI 50
PF
Kick 10 60
70
SC 50
1SFT 98899-020

TPF
USD 90
norm slow
1SFT 98899-018

30 100
80 90 3 4
Ir I LIM

70 100 2 5 * Ir

220-240 V RUN TOR FAULT


50/60 Hz START/STOP

1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19
27
K
14

125 125 125


12

Ø11 7 Ø11
41 300 173,5 173,5 E

Dimension
Type E F K
PS D370…570
PS DH300…470 34 25 65
PS D720
PS DH570 41.5 40 62.5
PS D840
PS DH720 46.5 50 62.5

ABB Building Technologies 13


1SFC 288001-en, ed5. June 2000
Circuit diagrams

PS S 03…25
1L1 3L2 5L3

A3

Start K5: 1 K5: 2


A2
V1 V2
Uc=24-110V K5 Integral By-pass
AC DC V1, V2 Semiconductor
Start A1

2T1 4T2 6T3

W
U
V

A3

Uc=110-480V

1SFT 98899-022
AC Start A2

A1

PS S 18/30…300/515
T2

11 12 1L1 3L2 5L3

Stop Start
L N X21
TH
X22
6 F6 Temperature monitor
5 K5 K5 Relay, actuated at full
Ue=
4 100% voltage (Ue = 100%)
K6
K6 Relay, fault signal
T1 Control transformer
6 Common
X17
5 X14 T2 Current transformer
Start V5
X15
V6
4 Stop
X14 V1-V6 Tyristor
Stop Start

T1
Uc=220-240V X13
X19 X18 X12
10V V3
Uc=110 120V Uc=110 120V X11
X27 X28 X27 X28 X20 V4
X10
X27X28 X23 X24 X25 X26

Fan Fan Fan Fan Fan Fan Fan Fan

Fan X9
X8 V1
PS S175/300...300/515 PS S175/300...300/515
X7
X6 V2
PS S18/30-500...
44/76-500
X27 X28 Uc=110 120V X27 X28 Uc=220-240V

Fan Fan Fan Fan

2T1 4T2 6T3


T1
PS S85/147...142/245 PS S85/147...142/245
X19 X18

X20

X23 X24 X25 X26 Uc=110-120V


1SFT 98800-001

Fan Fan

PS S50/85-500...72/124-500
PS S18/30-690...72/124-690

14 ABB Building Technologies


1SFC 288001-en, ed5. June 2000
Circuit diagrams

PS D without electronic overload relay

E1 Circuit board
E3–E5 Fan
F6 Temperature
monitor
J1–J3 Contact blocks
K4 Relay, actuated
in operational
position
K5 Relay, actuated
at full voltage
(Ue = 100 %)
K6 Relay, fault
signal
T2 Current
transformer
T5 Control
transformer
V1–V6 Thyristor
X1–X3 Terminal block

1SFT 98899-024

PS D and PS DH with electronic overload relay


E1 Circuit board
E2 Circuit board
OVL
E3–E5 Fan
F6 Temperature
monitor
J1–J3 Contact blocks
K3 Relay, overload
K4 Relay, actuated
in operational
position
K5 Relay, actuated
at full voltage
(Ue = 100 %)
K6 Relay, fault
signal
T2 Current
transformer
T3 Current
transformer
T5 Control
transformer
V1–V6 Thyristor
X1–X3 Terminal block
1SFT 98899-025

ABB Building Technologies 15


1SFC 288001-en, ed5. June 2000
Minimum distance to wall/front
Dimensions
Type No. E F G H
PS S 18/30-500…44/76-500 120 200 - 163
PS S 50/85-500…72/124-500 140 250 - 163
A PS S 18/30-690…72/124-690 140 250 - 163
A
PS S 85/147-500…142/245-500 181 340 - 265
PS S 85/147-690…142/245-690 181 340 - 265
PS S 175/300-500…300/515-500 356 340 - 265
1SFT98899-027

H PS S 175/300-690…300/515-690 356 340 - 265

1SFT98899-029
H
PS D75
PS DH30…60 280 360 313 218
PS D110…145
PS DH75…110 280 400 313 218
PS D175…300
PS DH145…250 382 444 402 310
PS D370…840
PS DH300…720 540 600 600 310

PS D(H) PS S 18/30…300/515

D E E
Minimum distance to wall/front
C
A = 20 mm
B = 10 mm
C = 100 mm Both top and bottom

Catalogue 1SFC 288001-en, ed5. June 2000. Prod. ABB Control/XM Printed in Sweden Västerås 2000-06
F G D = 150 mm Both top and bottom
F
1SFT98899-028
1SFT98899-026

B B

B B

ABB Control, SE-721 61 Västerås, Sweden, Tel. +46 21 32 07 00, Fax +46 21 12 60 01