Softstarter Range: ABB Building Technologies
Softstarter Range: ABB Building Technologies
Ordering data PS S 4
Accessories PS S 5
Ordering data PS D 6
Ordering data PS DH 7
Technical data 10
Dimensions 12
Circuit diagrams 14
PS S 03…PS S 25 is a compact solution for small motors. An optional ”Current limit” function is available. Two signal
Mounting is on 35 mm DIN-rail. This small softstarter has a relays are built in as standard. This softstarter has a service
built-in bypass contact. factor of 1.15, which means that the maximum operational
current is Ie (rated current) x1.15.
PS S 18/30…PS S 300/515 for normal duty applications
Example: the PS S 18/30 connected in-line has an Ie of 18 A.
and connection both ”In Line” and ”Inside Delta” (compare
The maximum operational current is then 1.15 x 18 A = 20.7 A.
the connection with a standard Y/D starter). The result of
”Inside Delta” connection is a 42 % reduction of the current PS D 75…PS D 840 and PS DH 30…PS DH 720 softstarters
exposed to the softstarter. It will then be possible, for have a robust design in metal housing for many types of
example, to start and run a 100 A motor using a 58 A applications, both normal duty and heavy duty. Flexible
softstarter. parameter settings with potentiometers and clear indication
with LEDs of status and faults on front of the unit. The optional
built in advanced electronic overload relay (always included as
standard for PS DH versions) provides much better motor
protection than a conventional bimetallic relay, for example in
intermittent duty.
1SFT 98899-003
PS S 03…12
3.5
2.0 5.0
0.5 6.5
4.0 40
PS S 18/30…300/515 PS D and PS DH
2.0 6.0
1SFT 98899-030
20 60
0.5 8.0 0 85
2 5
10
1
20
F1 F2 START
40
0,5 60 s
20
On R 5 50
STOP 100
PS S 25 T P 0,5
30
240 s
40
N Y UINI 50
5.0
2.5 7.5 PF
1 2 3 4
OFF
Kick 10 60 %
0.5 10 70
SC 50
TPF USD 90
10 norm slow
1SFT 98899-031
5 15 30 100 %
1SFT 98899-032
80 90 3 4
0.5 20
Ir ILIM
70 100 % 2 5 x Ir
25
15 35
1SFT 98899-043
5 50
The operator panels for PS S, PS D and PS DH have LED´s, potentiometers and switches for indication and settings.
1) Code letter for supply voltage * is F = 110-120V, 50/60Hz; L = 220-240V 50/60 Hz.
2) Code number for supply voltage x is 1 = 110-120V, 50/60Hz; 2 = 220-240V 50/60 Hz
4 ABB Building Technologies
1SFC 288001-en, ed5. June 2000
Ordering data Accessories PS S 18/30…300/515
Terminal enlargements
Type Order code For softstarter Weight
kg
Degree of protection
Main circuit IP 20 IP 20 IP 20 (PS S 18/30-500…44/76-500)
IP 10 (PS S 50/85-500…72/124-500)
IP 10 (PS S 18/30-690…72/124-690)
IP 00 (PS S 85/147…300/515)
Supply and control circuit IP 20 IP 20 IP 20
Settings
Ramp time during start s 0.5 – 6.5 -+15% 0.5 – 10 -+10% 1 – 30
Ramp time during stop s 0.5 – 8 -+25% 5 – 20 -+10% 0 – 30
Initial voltage during start % 0 – 85 -+15% 5 – 50 -+5% 30 – 70
Current limit function xIe No No 1.5 – 43)
Switch for
Inside delta connection ON/OFF No No Yes
Signal relay
By-pass signal No4) No4) Yes
Fault signal No No Yes
Rated operational voltage Ue V – – 250
Rated thermal current Ith A – – 5
Rated operational current Ie
at AC-15 (Ue=250 V) A – – 1.5
Signal indication LED
Ready to start/stand by ON Green Green Green
Ramping up/down Yellow Yellow (flashing) No
Completed start ramp T.O.R. Yellow Yellow Green
General fault F1 – Red Red
External fault F2 – – Red
1) Above 40 0C, up to max 600 C, reduce the rated current with 0.8 % per 0C.
2) When more than 6 starts per hour are required, contact your sales office.
3) Only if current transformer is connected (accessory).
4) The unit has built in by-pass contacts (AC-53b)
5) 50 % on time and 50 % off time. 3.5 x Ie for 7 sec.
Ambient temperature
During operation1) °C 0 – 50 0 – 50 0 – 50 0 – 50
During storage °C -40 – +70 -40 – +70 -40 – +70 -40 – +70
Degree of protection IP 00 IP 00 IP 00 IP 00
Settings
Ramp time during start sec 0.5 – 60 0.5 – 60 0.5 – 60 0.5 – 60
Initial voltage during start % 10 – 60 10 – 60 10 – 60 10 – 60
Ramp time during stop sec 0.5 – 240 0.5 – 240 0.5 – 240 0.5 – 240
Step down voltage special ramp % 100 – 30 100 – 30 100 – 30 100 – 30
Current limit function 2 – 5 x Ie 2 – 5 x Ie 2 – 5 x Ie 2 – 5 x Ie
Adjustable rated motor current Ie2) % 70 – 100 70 – 100 70 – 100 70 – 100
Switches for
Energy saving function ON/OFF (PF) Yes Yes Yes Yes
Kick start, YES/NO (KICK) Yes Yes Yes Yes
High current switch off, YES/NO (SC) Yes Yes Yes Yes
Reaction time for energy saving
normal/slow (TPF) Yes Yes Yes Yes
Signal relays
Fault signal K6 Yes Yes Yes Yes
By-pass signal, start ramp completed K5 Yes Yes Yes Yes
Run signal K4 Yes Yes Yes Yes
Overload signal Yes Yes Yes Yes
Rated operational voltage Ue V 250 250 250 250
Rated thermal current Ith A 5 5 5 5
Rated operational current Ie
at AC-15 (Ue=250V) A 1.5 1.5 1.5 1.5
1) Above 40 °C, up to max 50 °C, reduce the rated current with 0.8 % per °C.
2) For Ue = 690 V; setting 50 – 100 %
3) Optional for PSD types
PS S
03 TA 25 DU 2.2–3.1 – 16 A 170M1359 2
12 TA 25 DU 10–14 – 40 A 170M1363 2
25 TA 25 DU 18–25 – 50 A 170M1364 5
PS S
18/30 TA 25 DU 6–18 3) 50 A 170M1364 5) 63 A 6.6 URB 000 D08 V 0063 9
30/52 TA 25 DU 10–30 3) 80 A 170M1366 5) 100 A 6.6 URB 000 D08 V 0100 9
37/64 TA 42 DU 22–37 3) 125 A 170M1368 5) 160 A 6.6 URB 000 D08 V 0160 9
44/76 TA 75 DU 29–44 3) 160 A 170M1369 5) 200 A 6.6 URD 30 D08 A 0200 9
50/85 TA 75 DU 29–50 3) 160 A 170M1369 5) 200 A 6.6 URD 30 D08 A 0200 10
60/105 TA 75 DU 29–60 3) 200 A 170M1370 5) 250 A 6.6 URD 30 D08 A 0250 10
72/124 TA 75 DU 45–72 3) 250 A 170M1371 5) 315 A 6.6 URD 30 D08 A 0315 10
85/147 TA 110 DU 65–85 3) 315 A 170M1372 5) 400 A 6.6 URD 30 D08 A 0400 36
105/181 TA 110 DU 65–105 3) 400 A 170M3019 6) 400 A 6.6 URD 30 D08 A 0400 36
142/245 TA 200 DU 100–142 3) 450 A 170M3020 6) 500 A 6.6 URD 30 D08 A 0500 36
175/300 TA 200 DU 100-175 3) 500 A 170M3021 6) 530 A 6.6 URD 30 D08 A 0550 65
250/430 TA 450 DU 130-250 3) 700 A 170M4017 6) 630 A 6.6 URD 31 D08 A 0630 65
300/515 TA 450 DU 130-300 3) 900 A 170M5015 6) 900 A 6.6 URD 32 D11 A 0900 65
PS D
75 TA 75 DU 45–75 3) 250 A 170M1371 5) 315 A 6.6 URD 30 D08 A 0315 40
110 TA 110 DU 65–110 3) 315 A 170M1372 5) 400 A 6.6 URD 30 D08 A 0400 40
145 TA 200 DU 100–145 3) 400 A 170M3019 6) 400 A 6.6 URD 30 D08 A 0500 40
175 TA 200 DU 100–175 2) 450 A 170M3020 6) 500 A 6.6 URD 30 D08 A 0500 65
210 TA 450 DU 130–210 2) 500 A 170M3021 6) 530 A 6.6 URD 30 D08 A 0550 65
250 TA 450 DU 130–250 2) 630 A 170M4016 6) 550 A 6.6 URD 31 D08 A 0550 65
300 TA 450 DU 130–300 2) 700 A 170M4017 6) 630 A 6.6 URD 31 D08 A 0630 65
370 TA 900 DU 265–370 2) 900 A 170M5015 6) 900 A 6.6 URD 32 D11 A 0900 90
470 TA 900 DU 265–470 2) 1250 A 170M5018 6) 1250 A 6.6 URD 33 D11 A 1250 90
570 TA 900 DU 265–570 2) 1500 A 170M6018 6) 1250 A 6.6 URD 33 D11 A 1250 90
720 TA 900 DU 465–720 2) 1800 A 170M6020 6) 2000 A 6.6 URD 233 PLAF 2000 90
840 TA 900 DU 465–840 2) 1800 A 170M6020 6) 2000 A 6.6 URD 233 PLAF 2000 90
PS D(690V)
370 TA 450 DU 130–370 2) 900 A 170M5015 6) 900 A 6.6 URD 32 D11 A 0900 90
470 TA 900 DU 265–470 2) 1250 A 170M5018 6) 1250 A 6.6 URD 33 D11 A 1250 90
570 TA 900 DU 265–570 2) 1500 A 170M6018 6) 1250 A 6.6 URD 33 D11 A 1250 90
720 TA 900 DU 465–720 2) 1500 A 170M6018 6) 2000 A 6.6 URD 233 PLAF 2000 90
840 T 900 DU 465–840 2) 1500 A 170M6018 6) 2000 A 6.6 URD 233 PLAF 2000 90
PS DH
30 1) 3) 125 A 170M1368 5) 160 A 6.6 URD 30 D08 A 0160 40
45 1) 3) 200 A 170M1370 5) 200 A 6.6 URD 30 D08 A 0200 40
60 1) 3) 250 A 170M1371 5) 250 A 6.6 URD 30 D08 A 0250 40
75 1) 3) 315 A 170M1372 5) 315 A 6.6 URD 30 D08 A 0315 40
110 1) 3) 400 A 170M3019 6) 450 A 6.6 URD 30 D08 A 0450 40
145 1) 2) 450 A 170M3020 6) 500 A 6.6 URD 30 D08 A 0500 65
175 1) 2) 500 A 170M3021 6) 550 A 6.6 URD 30 D08 A 0550 65
210 1) 2) 630 A 170M4016 6) 630 A 6.6 URD 31 D08 A 0630 90
250 1) 2) 700 A 170M4017 6) 700 A 6.6 URD 32 D08 A 0700 90
300 1) 2) 900 A 170M5015 6) 900 A 6.6 URD 32 D08 A 0900 90
370 1) 2) 1000 A 170M5016 6) 1000 A 6.6 URD 33 D08 A 1000 90
470 1) 2) 1250 A 170M5018 6) 1250 A 6.6 URD 33 D08 A 1250 90
570 1) 2) 1500 A 170M6018 6) 1600 A 6.6 URD 33 TTF A 1600 90
720 1) 2) 1800 A 170M6020 6) 2000 A 6.6 URD 233 PLAF 2000 90
1) Electronic overload relay built in, optional for PS D types, standard for PS DH types 4) For the supply circuit: 6 A delayed
2) Total power loss: PLtot = [3 x Ie x 1.0] + 100 (W) Reduced to 100 W only when using by-pass 5) Fuse holder 170H 1007
3) Total power loss: PLtot = [3 x Ie x 1.0] + 50 (W) Reduced to 50 W only when using by-pass 6) Fuse holder 170H 3004
10 ABB Building Technologies
1SFC 288001-en, ed5. June 2000
Technical data
Main circuit
Connection clamp
Rigid solid/rigid stranded 1x mm2 2.5 10 2.5-16 6-50 See accessories See accessories
Rigid solid/rigid stranded 2x mm2 2.5 6 2.5-16 6-25 See accessories See accessories
Tightening torque (for guidance only) max.Nm 0.5 2 2.6 4.5 See accessories See accessories
Connection bar
Width and thickness mm – – – – 17.5x5 20x5
Hole diameter mm – – – – 8.5 10.2
Tightening torque (for guidance only) max. Nm – – – – 9 ?
Supply and control circuit
Connection clamp
Rigid solid/rigid stranded 1x mm2 2.5 2.5 2.5 2.5 2.5 2.5
Rigid solid/rigid stranded 2x mm2 2.5 - - - - -
Tightening torque (for guidance only) max. Nm 0.5 0.5 0.5 0.5 0.5 0.5
Main circuit
Connection clamp
Cu-cable mm2 35 – – – –
Al-cable mm2 35 – – – –
Connection bar
Width x thickness mm – 15x4 25x6 40x6 50x6
Hole diameter mm – 7 11 11 11
Tightening torque min.Nm 2.5 2.4(M6) 12.0(M10) 12.0(M10) 12.0(M10)
(For guidance only) max.Nm 3.0 3.2(M6) 16.0(M10) 16.0(M10) 16.0(M10)
Supply and control circuit
Connection clamp mm2 2.5 2.5 2.5 2.5 2.5
1SFT 98899-007
163
104
104
1SFT 98899-005
1SFT 98899-009
10
120
Depth from DIN rail 101 mm Depth from DIN rail 101 mm
45 105 7,5
90
6,5(4x)
1SFT 98899-004
200
82
184
87
1SFT 98899-008
1SFT 98899-006
2
9
PS S 50/85-500…72/124-500 PS S 85/147-500…142/245-500 PS S 175/300-500…300/515-500
PS S 18/30-690…72/124-690 PS S 85/147-690…142/245-690 PS S 175/300-690…300/515-690
1SFT 98899-011
163
265
265
1SFT 98899-013
1SFT 98800-003
10
1,5
1.5
6,5(4x)
320
340
250
234
320
340
1SFT 98899-012
1SFT 98899-010
7(4x)
1SFT 98800-002
2
7(4x)
10
9
10
PS D 75 PS D 110...145
PS DH 30...60 PS DH 75...110
1SFT 98899-017
1SFT 98899-015
4
218
218
125
280 280
265 7,5 265 7,5
45 45
L1 L2 L3
Ø 7 (4x) 15
20 21 22 23 24 25
OVERLOAD RESET
OVL
RESET
Ø 7 (4x)
20 21 22 23 24 25
OVERLOAD RESET
t
OVL
tar
fts
RESET
So
313
260
360
1SFT 98899-014
t
tar
fts
So
Max 400
2 5
10
1
20
260
313
F1 F2 START
40
0,5 60 s
20
On R 5 50
STOP
1SFT 98899-016
100
T P 0,5 240 s
30 40
N Y UINI 50
PF
Kick 10 60
70
SC 50
TPF
USD 90
norm slow
30 100
80 90 3 4
Ir I LIM
70 100 2 5 * Ir
2 5
10
1
20
F1 F2 START
40
0,5 60 s
20
On R 5 50
STOP 100
T P 0,5 240 s
220-240 V RUN TOR FAULT 30 40
50/60 Hz START/STOP N Y UINI 50
PF
Kick 10 60
70
SC 50
TPF
1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 norm slow
USD 90
30 100
80 90 3 4
Ir I LIM
T1 T2 T3 70 100 2 5 * Ir
26.5
1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19
Ø7
26,5
PS D 175...300 PS D 370...840
PS DH 145...250 PS DH 300...720
F
6
6
1SFT 98899-021
310
1SFT 98899-019
310
235
205
183
540 66
210 210
6 hole 9x7
382
117 117
R3,5 25
20 21 22 23 24 25
OVERLOAD RESET
OVL
RESET
13
20 21 22 23 24 25
OVL
tart
fts
RESET
So
r t
572
600
sta
S oft F1
On
F2
R
START
1
0,5
5
2
20
5
10
40
60 s
50
20
STOP 100
T P 0,5 240 s
30 40
N Y UINI 50
PF
Kick 10 60
70
SC 50
TPF
USD 90
norm slow
380
402
444
30 100
80 90 3 4
Ir I LIM
70 100 2 5 * Ir
2 5
10
1 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19
20
F1 F2 START
40
0,5 60 s
20
On R 5 50
STOP 100
T P 0,5 240 s
30 40
N Y UINI 50
PF
Kick 10 60
70
SC 50
1SFT 98899-020
TPF
USD 90
norm slow
1SFT 98899-018
30 100
80 90 3 4
Ir I LIM
70 100 2 5 * Ir
1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19
27
K
14
Ø11 7 Ø11
41 300 173,5 173,5 E
Dimension
Type E F K
PS D370…570
PS DH300…470 34 25 65
PS D720
PS DH570 41.5 40 62.5
PS D840
PS DH720 46.5 50 62.5
PS S 03…25
1L1 3L2 5L3
A3
W
U
V
A3
Uc=110-480V
1SFT 98899-022
AC Start A2
A1
PS S 18/30…300/515
T2
Stop Start
L N X21
TH
X22
6 F6 Temperature monitor
5 K5 K5 Relay, actuated at full
Ue=
4 100% voltage (Ue = 100%)
K6
K6 Relay, fault signal
T1 Control transformer
6 Common
X17
5 X14 T2 Current transformer
Start V5
X15
V6
4 Stop
X14 V1-V6 Tyristor
Stop Start
T1
Uc=220-240V X13
X19 X18 X12
10V V3
Uc=110 120V Uc=110 120V X11
X27 X28 X27 X28 X20 V4
X10
X27X28 X23 X24 X25 X26
Fan X9
X8 V1
PS S175/300...300/515 PS S175/300...300/515
X7
X6 V2
PS S18/30-500...
44/76-500
X27 X28 Uc=110 120V X27 X28 Uc=220-240V
X20
Fan Fan
PS S50/85-500...72/124-500
PS S18/30-690...72/124-690
E1 Circuit board
E3–E5 Fan
F6 Temperature
monitor
J1–J3 Contact blocks
K4 Relay, actuated
in operational
position
K5 Relay, actuated
at full voltage
(Ue = 100 %)
K6 Relay, fault
signal
T2 Current
transformer
T5 Control
transformer
V1–V6 Thyristor
X1–X3 Terminal block
1SFT 98899-024
1SFT98899-029
H
PS D75
PS DH30…60 280 360 313 218
PS D110…145
PS DH75…110 280 400 313 218
PS D175…300
PS DH145…250 382 444 402 310
PS D370…840
PS DH300…720 540 600 600 310
PS D(H) PS S 18/30…300/515
D E E
Minimum distance to wall/front
C
A = 20 mm
B = 10 mm
C = 100 mm Both top and bottom
Catalogue 1SFC 288001-en, ed5. June 2000. Prod. ABB Control/XM Printed in Sweden Västerås 2000-06
F G D = 150 mm Both top and bottom
F
1SFT98899-028
1SFT98899-026
B B
B B
ABB Control, SE-721 61 Västerås, Sweden, Tel. +46 21 32 07 00, Fax +46 21 12 60 01