UPS Maintenance Report (3phase - 3phase) - Latest
UPS Maintenance Report (3phase - 3phase) - Latest
Customer:
Address:
Site Environment:
(Prior to commencing maintenance record site environmental conditions. Make comments in the fields provided)
UPS location Computer Room Plant Room Other / Comment
Environment Clean Appropriate Contaminated / Comment
Air environment Air conditioned Force Ventilation Natural Ventilation
Ambient temperature surrounding UPS equipment deg. C Measured Approximated
Battery location Computer Room Plant Room Other / Comment
Accommodation Battery Cabinet Battery Rack Internal / batt pack
Environment Clean Appropriate Contaminated / Comment
Air environment Air conditioned Force Ventilation Natural Ventilation
Ambient temperature surrounding UPS batteries deg. C Measured Approximated
Comments:
UPS Mechanical:
(Transfer load to maintenance bypass and perform mechanical checks. Make comments in the fields provided)
Loose Electrical connections None Found / Comment
Bad Insulation None Found / Comment
Overheating None Found / Comment
Damage or displacement None Found / Comment
Fuses (type, value, condition) Good Deteriorated / Comment
Fans Good Deteriorated / Comment
PCB plugs & connectors Good Deteriorated / Comment
Clean UPS internally Complete
Clean UPS externally Complete
Check Battery Bank Complete Deteriorated / Comment
Comments:
UPS Parameters
(Record parameters from UPS display and/or metering, N/A where not applicable)
Input Frequency: (valid range: + / - 1 Hz of nominal)
UPS Display Measured value Parameters normal
Hertz Hertz Abnormal / Comment
Input Voltage: (valid range: + / - 10% of nominal UPS voltage)
UPS Display Measured value Parameters normal
R phase Vrms R phase Vrms Abnormal / Comment
S phase Vrms S phase Vrms
T phase Vrms T phase Vrms
Earth -- Neutral
Input Current: (valid range: 0% to 100% of UPS input current, refer UPS manual)
UPS Display Measured value Parameters normal
R phase Arms R phase Arms Abnormal / Comment
S phase Arms S phase Arms
T phase Arms T phase Arms
Comments:
Check UPS LED (light emitting diode) indicators Functional Abnormal / Comment Not applicable
Check UPS LCD (liquid crystal display) panel Functional Abnormal / Comment Not applicable
Check UPS control switches / buttons Functional Abnormal / Comment Not applicable
Check UPS transfer to / from bypass Functional Abnormal / Comment Not applicable
Check UPS external bypass interlock Functional Abnormal / Comment Not applicable
Check UPS remote alarm & communication options Relay Card Functional Web/SNMP Card Functional
Comments:
Conclusion: