Professional Documents
Culture Documents
PTC 30 1991
PTC 30 1991
~ ~~~
Dimensions
Symbol Definjtion U.S. Customary Units SI Units
LMTD Log mean temperature difference "F "C
r Radius ft rn
10017
PERFORMANCE
M E C H A N I C AE LN G I N E E R S
AN AMERICAN NATIONAL STANDARD
N.Y.
New York,
TEST
~
Air Cooled
Heat Exchangers
The 1991 edition of this document is being issued with an automatic addenda
subscription service. The use of an addenda allows revisions made in re-
sponse to public review comments or committee actions to be published as
necessary; revisions published in addenda will become effective 1 year after
the Date of Issuance of the document. This document will be revised when
the Society approves the issuance of the next edition, scheduled for 1996.
This code or standard was developed under prccedures accredited as meeting the criteria for
American National Standards. The Consensus Committee that approved the code or standard
was balanced to assure that individuals from competent and concerned interests have had an
opportunity to participate. .The proposed code or standard was made available for public review
and comment which provides an opportunity for additional public input from industry, academia,
regulatory agencies, and the public-at-large.
ASME does not "approve," "rate," or "endorse" any item, construction, proprietary device, or
activity.
ASME does not take any position with respect to the validity of any patent rights asserted in
connection with any items mentioned in this document, and does not undertake to insure anyone
utilizing a standard against liability for infringement of any applicable Letters Patent, nor assume
any such liability. Users of a code or standard are expressly advised that determination of the
validity of any suchpatent rights, and the risk of infringement of such rights, is entirely their own
responsibility.
Participation by federal agency representative(s) or person(s) affiliated with industry is not to
be interpreted as government or industry'endorsement of this code or standard.
ASME acepts responsibility for only those interpretations issued in accordance with governing
ASME procedures and policies which preclude the issuance of interpretations by individual vol-
unteers.
Copyright 0 1991 by
THE AMERICAN SOCIETY OF MECHANICAL ENGINEERS
All Rights Reserved
Printed in U.S.A. ,
Copyrighted material licensed to Stanford University by Thomson Scientific (www.techstreet.com), downloaded on Oct-05-2010 by Stanford University User. No further reproduction or distribution is permitted. Uncontrolled w
FOREWORD
iii
Copyrighted material licensed to Stanford University by Thomson Scientific (www.techstreet.com), downloaded on Oct-05-2010 by Stanford University User. No further reproduction or distribution is permitted. Uncontrolled w
All ASME codes are copyrighted, with all rights reserved to the Society. Reproduction of
this or any other ASME code is a violation of Federal Law. Legalities aside, the user should
appreciate that the publishingof the high quality codes that have typified ASME documents
requires a substantialcommitment by the Society. Thousands of volunteers work diligently
to develop these codes. They participate on their own or with a sponsor’s assistance and
produce documentsthat meet the requirementsof an ASME consensus standard. The codes
are very valuable pieces of literature to industry and commerce, and the effort to improve
these “living documents” and develop additional needed codes must be continued. The
monies spent for research and further code development, administrativestaff support and
publication are essential and constitute a substantial drainon ASME. The purchase price of
these documents helps offset these costs. User reproduction undermines this system and
representsan added financial drain on ASME. Whenextracopiesareneeded,youare
requested to call or write the ASME Order Department, 22 Law Drive, Box 2300, Fairfield,
New Jersey 07007-2300, and ASME will expedite delivery of such copies to you by return
mail. Please instruct your people to buy.required test codes rather than copy them. Your
cooperation in this matter is greatly appreciated.
iv
Copyrighted material licensed to Stanford University by Thomson Scientific (www.techstreet.com), downloaded on Oct-05-2010 by Stanford University User. No further reproduction or distribution is permitted. Uncontrolled w
PERSONNEL OF ASME PERFORMANCE TEST CODE COMMITTEE NO. 30
ON AIR COOLED HEAT EXCHANGERS
(The following is the roster of the Committee at the time of approval of this Standard.)
OFFICERS
J. C. Campbell, Chairman
R. B. Miller, Vice Chairman
J. Karian, Secretary
COMMllTEE PERSONNEL
J. A. Bartz, Edison Power Research Institute
K. J. Bell, Oklahoma State University
J. M. Burns, Stone and Webster Engineering Corp.
J. C. Campbell, Lilie-Hoffman Cooling Towers, Inc. (retired)
R. R. Carpenter, Duke Power Co.
M. C. Hu, United Engineers and Constructors, Inc.
B. M. Johnson, Battelle Northwest
G. E. Kluppel, Hudson Products Corp.
P. A. Lindahl, The Marley Cooling Tower Co.
P. M. McHale, Ebasco Plant Services Inc.
R. B. Miller, Stone and Webster Engineering Corp.
D. S. Parris, Jr., American Energy
J. G. Yost, Environmental Systems Corp.
V
Copyrighted material licensed to Stanford University by Thomson Scientific (www.techstreet.com), downloaded on Oct-05-2010 by Stanford University User. No further reproduction or distribution is permitted. Uncontrolled w
{-
vi
Copyrighted material licensed to Stanford University by Thomson Scientific (www.techstreet.com), downloaded on Oct-05-2010 by Stanford University User. No further reproduction or distribution is permitted. Uncontrolled w
CONTENTS
Introduction .................................................................... 1
Object and Scope .............................................................. 3
1.1 Object ...................................................................... 3
1.2 Scope ...................................................................... 3
1.3 Uncertainty .................................................................. 3
Definitions and Description of Terms ........................................ 5
2.1 Terms ...................................................................... 5
2.2 Letter Symbols ............................................................. 8
Guiding Principles ............................................................. 11
General .....................................................................
.
3.1 11
3.2 Agreements Prior to Test .................................................. 11
3.3 Selection of Personnel ..................................................... 11
3.4 Pre-Test Uncertainty Analysis ............................................. 11
3.5 Arrangement of Test Apparatus ........................................... 11
3.6 Methods of Operation During Testing .................................... 12
3.7 Provisions for Equipment Inspection ...................................... 12
3.8 Calibration of Instruments ................................................. 12
3.9 Preliminary Testing ........................................................ 12
3.1 0 Conduct of Test ............................................................ 13
3.1 1 Permissible and Nonpermissible Adjustmentsto Test
Procedures .............................................................. 13
3.1 2 Duration of Test ........................................................... 13
3.1 3 Number of Test Readings ................................................. 13
3.1 4 Permissible Limitsof Test Parameters ..................................... 13
3.1 5 Degree of Constancy of Test Conditions ................................. 14
3.1 6 Causes for Rejection of Test Readings or Results ......................... 14
3.1 7 Post-Test Uncertainty Analysis ............................................ 14
InstrumentsandMethods of Measurement .................................. 15
4.1 General ...................................................................... 15
4.2 Measurement of PhysicalDimensions .................................... 15
4.3 Fan
Measurements ........................................................ 15
4.4 Measurement of Air Flow ................................................. 15
4.5 Measurement of Air-SidePressure Differential ........................... 17
4.6 Measurement of Fan Driver Power ....................................... 18
vii
Copyrighted material licensed to Stanford University by Thomson Scientific (www.techstreet.com), downloaded on Oct-05-2010 by Stanford University User. No further reproduction or distribution is permitted. Uncontrolled wh
4.7 Measurement ofSoundLevel ............................................. 19
4.8 Measurement of AtmosphericPressure ................................... 19
4.9 Measurement of EnvironmentalEffects ................................... 19
4.1 0 Measurement of Wind Velocity ........................................... 19
4.1 1 Measurement of Air Temperatures ........................................ 19
4.1 2 Measurement ofAmbientandEntering Air Temperatures ............... 20
4.1 3 Measurement ofExit Air Temperature .................................... 20
4.1 4 Measurement of Process Fluid Temperatures ............................ 20
4.1 5 Measurement of Process Fluid Pressures ................................. 20
4.1 6 Measurement ofProcess Fluid FlowRate ................................. 21
4.1 7 Measurement of Composition of Process Fluid .......................... 21
5 Computation of Results ........................................................ 23
5.1 General ..................................................................... 23
5.2 ReviewofTestDataandTestConditions ................................. 23
5.3 ReductionofTestData .................................................... 23
5.4 Determination ofMaterialandHeatBalances ............................ 24
5.5 Computation of Effective
MeanTemperature
Difference ............................................................... 25
5.6 Computation ofOverallHeatTransferCoefficient ....................... 25
5.7 Determination ofAir-SidePressureLosses ............................... 26
5.8 Determination of Process Fluid PressureLosses .......................... 26
5.9 Adjustments ofTestData to DesignConditions .......................... 28
6 Report of Results ............................................................... 47
6.1 Composition Report
of .................................................... 47
6.2 Report
Data ................................................................ 48
Figures
4.1 Locationof Air VelocityandTemperatureMeasurement
Points Across Fan Ring .......................................................
16
4.2 TypicalVelocityDistributionAcrossFanStack ................................ 18
5.1 MeanTemperatureDifferenceRelationships - Crossflow
Unit - 1 TubeRow,Unmixed .............................................. 33
5.2 MeanTemperatureDifferenceRelationships - Crossflow
Unit - 2 TubeRows. 1 Pass.Unmixed ..................................... 34
5.3 MeanTemperatureDifferenceRelationships - Crossflow
Unit . 3 TubeRows, 1 Pass.Unmixed .....................................
35
5.4 MeanTemperatureDifferenceRelationships - Crossflow
Unit - 4 TubeRows. 1 Pass. Unmixed ..................................... 36
5.5 MeanTemperatureDifferenceRelationships . Crossflow
Unit - 2 Tube Rows. 2 Passes. Unmixed Between Passes .................
37
5.6 MeanTemperatureDifferenceRelationships - Crossflow
Unit . 3 Tube Rows. 3 Passes. Unmixed Between Passes .................
38
5.7 MeanTemperatureDifferenceRelationships - Crossflow
Unit - 4 Tube Rows. 4 Passes. Unmixed Between Passes ................. 39
5.8 MeanTemperatureDifferenceRelationships . Crossflow
Unit - 4 Tube Rows in 2 Passes. 2 Tube Rows per Pass.
Mixed at the Header ......................................................... 40
5.9 Schematic of Process Fluid Piping ............................................. 41
5.10 Fin Efficiency of Several Types of Straight Fins ................................ 42
5.1 1 Efficiency Curves for Four Types of Spine Fins ................................ 43
5.12 Efficiency of Annular Fins of Constant Thickness .............................. 44
5.1 3 Efficiency of Annular Fins With Constant Metal Area for
HeatFlow .................................................................... 45
viii
Copyrighted material licensed to Stanford University by Thomson Scientific (www.techstreet.com), downloaded on Oct-05-2010 by Stanford University User. No further reproduction or distribution is permitted. Uncontrolled w
Tables
4.1Recommended Minimum Number of AirVelocity
MeasurementPoints for FanRingTraverse ................................. 17
5.1Values of Ft, for Equation5.38 ................................................. 31
Appendices
A Testing
Guidelines .............................................................. 49
B Example ......................................................................... 51
C Example UncertaintyAnalysis .................................................. 57
D SpecialConsiderations for ComputationandAdjustment of
Results ........................................................................ 65
E Fouling .......................................................................... 77
F Recirculation of Air ............................................................. 79
G References ....................................................................... 81
Figures
D.l Moody-Darcy Friction Factor Chart for Flow Through Plain
Tubes ......................................................................... 66
D.2a 'Chart for Calculating In-Tube Heat Transfer Coefficients for
Water ......................................................................... 69
.
D.2b Correction Factor to Fig D.2a for Other Tube Diameters .................... 70
D.3Two-Phase FlowFriction Pressure Drop Correction Factor ................... 72
D.4 p as aFunction for JI for the Chaddock Method ............................ 73
D.5 Colburn Correlation for Condensation on a Vertical Surface
- No VaporShear ........................................................... 74
Tables
C.laSensitivityFactors for UncertaintyAnalysis .................................... 60
C.l b SensitivityFactors for Uncertainty Analysis .................................... 61
C.2ErrorEstimateValues for Capability ........................................... 62
C.3ErrorEstimateValues for Capability ........................................... 63
C.4
Two-Tailed STUDENT4 Table for the 95Percent
Confidence Level ............................................................. 64
ix
Copyrighted material licensed to Stanford University by Thomson Scientific (www.techstreet.com), downloaded on Oct-05-2010 by Stanford University User. No further reproduction or distribution is permitted. Uncontrolled w
ASME PTC 30-1991
SECTION 0 - INTRODUCTION
1
Copyrighted material licensed to Stanford University by Thomson Scientific (www.techstreet.com), downloaded on Oct-05-2010 by Stanford University User. No further reproduction or distribution is permitted. Uncontrolled wh
AIR COOLED HEAT EXCHANGERS ASME PTC 30-1991
cases, modifications must be made to the procedures Code test for the specified equipment being tested
3
Copyrighted material licensed to Stanford University by Thomson Scientific (www.techstreet.com), downloaded on Oct-05-2010 by Stanford University User. No further reproduction or distribution is permitted. Uncontrolled wh
ASME PTC 30-1991 AIR COOLED HEAT EXCHANGERS
4
Copyrighted material licensed to Stanford University by Thomson Scientific (www.techstreet.com), downloaded on Oct-05-2010 by Stanford University User. No further reproduction or distribution is permitted. Uncontrolled w
AIR COOLED HEAT EXCHANGERS ASME PTC 30-1991
SECTION 2 - DEFINITIONSAND
DESCRIPTION OF TERMS
2.1 TERMS
In this Section only those terms are defined which
are characteristic of air cooled heat exchangers and
the requirements for testing them. For the definition
of all other physical terms, or the description of in-
struments used in this Code, reference is madeto the
literature and to PTC 19 SeriesonInstruments and
Apparatus.
Term Description
Air Mixture of gases and associated water vapor around the earth; dry air plus its
associated water vapor. This term is used synonymously with atmosphere or
moist air.
Air Cooled Heat A heat exchanger utilizing air as the heat sink to absorb heat from a closed circuit
Exchanger process fluid. This term is used synonymously with dry cooling tower in the
(ACHE) power industry.
Air Flow Rate The mass per unit time of air flowing through the ACHE.
Air, Standard Dry air at standard temperature (70"F) and pressure (14.696 psia) which has a
density of approximately 0.075 Ibm/ft3.
Alternate Process A fluid selected for use in performance testing when use of the actual design fluid
Fluid is impractical for testing purposes due to proprietary or other reasons.
Ambient Air The temperature of the air measured upwind of the ACHE within its air supply
Temperature stream.
Ambient Wind The speed and direction of the wind measured upwind of the ACHE within its air
Velocity supply stream.
Approach The minimum temperature difference between the process stream and air stream
Temperature at an exiting condition:
Difference '(a) T,-t, (counterflow)
or, (b) T, -t, (counterflow)
or, (c) T2- r, (cocurrent flow or cross flow)
5
Copyrighted material licensed to Stanford University by Thomson Scientific (www.techstreet.com), downloaded on Oct-05-2010 by Stanford University User. No further reproduction or distribution is permitted. Uncontrolled wh
ASME PTC 30-1991 AIR COOLED HEAT EXCHANGERS
Term Description
Aspect Ratio The ratio of certainkey dimensions that establishes similarity of shape or
proportionality
Bare Surface The surface area of the bare conduit excluding extended surface. Thisterm is
used synonymously with prime surface.
One or more tube bundlesserved by one or more fans complete with structure,
plenum, and other attendant equipment. This term
is used synonymously with
cell.
Capability Thermal performance capabilityexpressed in terms of test capacity, that is, the
actual quantity of processfluid the ACHE will handle atdesign conditions of fluid
inlet and outlet temperatures, fluid inlet pressure, fluid composition, air inlet
temperature and fan power.
Face Area The gross air flow area through theACHE heat transfer surface in a plane normal
to the air flow.
Fan Assisted A type of ACHE utilizing a combination of chimney effect and fan(s)to provide
Natural Draft the required air flow.
Fan Input Power The power which is actually transmittedto the fan.
Fan Pitch The angle from the fan plane atthe designated pitch measurement location to
which the blades of a fan are set.
Fin Efficiency The ratio of the total heat dissipatedby the fin to that which would be dissipated
if the entirefin surface were atthe temperature of the fin root.
Finned Surface, The contact surface exposed to the process fluid. This term is used synonymously
Inside with inside extended surface.
Finned Surface, The contact surface exposed to the air flow. This term is used synonymously with
Outside outside extendedsurface.
Flow Regime A fluid mechanics definition of flow characteristics, e.& /afr?iflar or tUrbUht flow.
6
Copyrighted material licensed to Stanford University by Thomson Scientific (www.techstreet.com), downloaded on Oct-05-2010 by Stanford University User. No further reproduction or distribution is permitted. Uncontrolled wh
AIR COOLED HEAT EXCHANGERS ASME PTC 30-1991
Term Description
Forced Draft A type of mechanical draft ACHE in which the fan is located in the air current
upstream from the heat exchanger surface.
Fouling Accumulated foreign material such as corrosion products or any other deposits on
the heat transfer surface.
Free Flow Area The minimum air flow area through the ACHE heat transfer surface in a plane
normal to the air flow.
Induced Draft A type of mechanical draft ACHE in which the fan is located in the air current
downstream from the heat excha’nger surface.
Initial Temperature difference between entering process temperature and entering air
Temperature temperature, T, 4,.
Difference
Mechanical Draft A type of ACHE in which the air flow is maintained by mechanical air moving
devices such as fans or blowers.
Motor Output The net power delivered by the motor output shaft.
Power
Natural Draft A type of ACHE in which the air flow is maintained by the difference in the
densities of the ambient air and the exiting air streams.
Prime Surface The surface areaof the bare conduit excluding extended surface. This term is
used synonymously with bare surface.
Process Fluid The fluid circulated within the closed conduit of an ACHE.
Process Fluid Generally, an average bulk temperature of the process fluid defined at some
Temperature location entering, leaving, or within the ACHE.
Process Fluid The difference between inlet and outlet temperatures of the process fluid.
Temperature
Range
Process Fluid The total hydraulic loss, including dynamic and static (if applicable) losses,
Pressure Drop between defined locations as the process fluid enters and leaves the ACHE.
Process Fluid The mass per unit time ofprocess fluid flowing through the ACHE.
Flow Rate
Recirculation The flow ofexit air into the ACHE air inlet.
Test Run A complete set of data that will allow analysis of capability per this Code. In some
cases multiple test runs are taken and averagedto yield the capability.
Test Uncertainty The overall uncertainty in results due to the combined effects of instrument
inaccurcy, unsteady state conditions, and reading and methodological error.
Test Value A value measured during a test with its calibration correction applied.
Tube Row All of thetubes or conduits within an ACHE which have axial centerlines falling
within a plane normal to the air flow. This term is synonymous to tube layer.
Unit One or more tube bundles in one or more bays for an individual service.
7
Copyrighted material licensed to Stanford University by Thomson Scientific (www.techstreet.com), downloaded on Oct-05-2010 by Stanford University User. No further reproduction or distribution is permitted. Uncontrolled wh
ASME PTC 30-1991 AIR COOLED HEAT EXCHANGERS
Dimensions
Symbol Definition US.
Customary Units SI Units
d Wall thickness ft m
0 Diameter ft m
t; Fin thickness ft
8, Proportionality factorin
'Newton's 2nd Law
-
32.18 Ibmft
Ibfvsecl
I Fin height ft
L Length ft
8
Copyrighted material licensed to Stanford University by Thomson Scientific (www.techstreet.com), downloaded on Oct-05-2010 by Stanford University User. No further reproduction or distribution is permitted. Uncontrolled w
AIR COOLED HEAT EXCHANGERS ASME PTC 30-1991
r
Dimensions
~~~~
r Radius ft rn
RH Hydraulic radius ft m
Nu
st Stanton number, h/c,C =- Dimensionless Dimensionless
RePr
T, Torque Ibf-ft
V Speed Wmin
9
Copyrighted material licensed to Stanford University by Thomson Scientific (www.techstreet.com), downloaded on Oct-05-2010 by Stanford University User. No further reproduction or distribution is permitted. Uncontrolled wh
ASME PTC 30-1991 AIR COOLED HEAT EXCHANGERS
Dimensions
Symbol Definition U.S. Customary Units SI Units
Process fluid flowrate Ibmihr kg/s
Subscript Description
a Air
af film Air
b Bond
d Dirt
d Dry
e Electrical
f Fouling
fn Fin
H Hydraulic
i Inside
I Liquid
rn Mechanical
rn Moist
0 Outside
P Prime tube
P Process
R Absolute
temperature
R wall Fin root
r surface Reference
s Static
T Total
V Vapor
V Velocity
W Wall
2 Zone
1 Inlet
2 Outlet
Superscript Description
t Design value
0
Test value
+ Adjusted value
10
Copyrighted material licensed to Stanford University by Thomson Scientific (www.techstreet.com), downloaded on Oct-05-2010 by Stanford University User. No further reproduction or distribution is permitted. Uncontrolled w
AIR COOLED HEAT EXCHANGERS ASME PTC 30-1991
3.1 GENERAL (h) the procedures and frequency for cleaning the
air- and/or tube-side surfaces;
Theperformance of atmospheric cooling equip-
(i) the scope of the test beyond. thisCode, includ-
ment is influenced by the conditions of the atmos-
ing partial testing or any other departures from this
phere in which it operates.ThisCoderequires
Code;
recognition of the fact that changes in the ambient
and other operating conditionswill affect the equip-
0) the fouling factors to be assumedfor analysis of
results (see Appendix E).
ment performance. Extraneous sources of heat and
those variables which affect the airflow must be re-
corded and evaluated. It is extremely important that
performance tests be conducted under stable oper-
ating conditions. 3.3 SELECTION OF PERSONNEL
The test shall be conducted by, or under the su-
pervision of, personnel fully experienced in plant and
3.2 AGREEMENTSPRIOR TO TEST equipment operating procedures. The test procedure
The parties to any test under this Code shall reach shall conform to the latest requirements of all appli-
definite agreement on the specific objective of the cable industry, local, state, and Federal regulations.
test and the method of operation. This shall reflect Testing an air cooled heat exchanger presents poten-
the intent of any applicable contract or specification. tially hazardous conditions which may include rotat-
Contractualtermsshallbeagreed to concerning ing equipment, high temperatures, hazardous fluids,
treatment of uncertaintyrelative to acceptance of noise, and danger of falling.
equipment based on reported capability. Any speci-
fied or contractoperatingconditions,and/orany
specified performance conditions that are pertinent
to the objectivesof the test, shall be ascertained. Any 3.4 PRE-TESTUNCERTAINTYANALYSIS
omissions or ambiguities as to any of the conditions Prior to the test an uncertainty analysis shall be
are to be eliminated or their values or intent agreed
performed. An example of uncertainty analysis is in-
upon before thetest is started.
cluded in Appendix C. Theanalysis is beneficial in
The parties to the test shall reach agreement, prior
that it will highlight those parameters that are major
to the start of test, regarding the following items:
contributors to test uncertainty.
(a) the specific methods and scope of inspection
Parties to the test shall add or improve instrumen-
prior to and during thetest;
tation or increase the frequency of readings if such
(b) the number of test runs and reading intervals;
actions will materially improve testaccuracy.
(c) the method for starting thetest;
(d) the method of operation of the equipment;
(e) the fan blade settings;
(0 the type, quantity, calibration, and location of
3.5 ARRANGEMENT OF TESTAPPARATUS
all instruments;
@ the allowable biasin instrumentationand mea- The performance test shall be conducted with all
surements, and the maximum permissible overall un- components of the ACHE oriented as specified for
certainty in the test results (see Appendix Cfor normal operation. Any changes from normal opera-
discussion); tion or orientation shall be agreed prior to the test.
11
Copyrighted material licensed to Stanford University by Thomson Scientific (www.techstreet.com), downloaded on Oct-05-2010 by Stanford University User. No further reproduction or distribution is permitted. Uncontrolled w
ASME PTC 30-1991 AIR COOLED HEAT EXCHANGERS
3.6 METHODS OF OPERATION DURING Prior to the test, the parties to the test shall reach
TESTING agreement on the calibration procedures to be fol-
lowed. Supplements on Instruments and Apparatus
Although it is preferable to evaluate the perform- (PTC 19 Series) may be used as a guide for the se-
ance of air cooled heat exchangers under complete lection,use,andcalibration of instruments. Instru-
design and steady-state conditions, this is normally mentcalibrationsandcorrectioncurvesshouldbe
not practicable for an on-site evaluation of this equip- prepared in advance.
ment. Therefore, prior agreement shall be established Removal and replacement of any instrument during
for procedures to adjust the test results to the design the testmay require calibration of the new instrument
conditions as in para. 5.9. priortocontinuingthetest. All calibrationcurves
shall be retainedas part of the permanent test record.
13
Copyrighted material licensed to Stanford University by Thomson Scientific (www.techstreet.com), downloaded on Oct-05-2010 by Stanford University User. No further reproduction or distribution is permitted. Uncontrolled wh
ASME PTC 30-1991 AIR COOLED HEAT EXCHANGERS
14
Copyrighted material licensed to Stanford University by Thomson Scientific (www.techstreet.com), downloaded on Oct-05-2010 by Stanford University User. No further reproduction or distribution is permitted. Uncontrolled w
AIR COOLED HEAT EXCHANGERS ASME PTC 30-1991
Ib Area
1
2
3
4
5
6
7
8
9
10
Id
FIG* 4.1 LOCATION OF AIRVELOCITY AND TEMPERATUREMEASUREMENT POINTS
ACROSS FANRING
the plane of the area surveyed, it may be necessary 4.4.3 For induced draft units, air flow should be de-
to correct thereadings for yaw. The anemometer shall termined by traversing the streams emitting from the
be held parallelto the traverse plane, and the actual fans. The recommended minimum number of mea-
direction of air flow during the timed interval esti- surement points and the locationsof these points are
mated. If the angle between the observed direction given in Table 4.1. Measurements along additional
of air flow and the anemometer axisis 5 deg. or more, diameters may be necessary to avoid error due to the
the reading shall be corrected. Specific corrections effects of structural members.For additional infor-
for yaw shall be determined by calibration prior to mation on traversing methods, instrumentation, and
the test. ’ evaluation of data, refer to PTC 18 and PTC 19.5.
To illustrate, a20-point traverse (five measurement
points per quadrant) is made as follows.
4.4.2 The selection of the most suitablearea for the The plane bounded by the inner periphery at the
anemometer traverse shall be guided by the general top of the fan ring is divided into ten equal concentric
physical
arrangement,
accessibility,
obstructions, areas numbered consecutivelyfrom 1 to 10 as shown
wind conditions, and air temperature rise. Because in Fig. 4.1.
of the decreased effect of ambient wind, accuracy is The ring is also divided into four quadrants as
usually better when the traverse is made in a high shown.The air velocity is thenmeasuredateach
velocity stream. In the case where these constraints point of intersection of the radii a,b,c, and d with
require that a velocitytraverse be done at the inlet, the inner peripheries of areas, 1, 3, 5, 7, and 9, at
a velocitytraverse is also required at the exit
in order the center. The average velocitiesin combined areas
to allow weighting the exit temperatures. 1+2,3+4,5+6,7+8,and9+lOarethenobtained
16
Copyrighted material licensed to Stanford University by Thomson Scientific (www.techstreet.com), downloaded on Oct-05-2010 by Stanford University User. No further reproduction or distribution is permitted. Uncontrolled w
AIR COOLED HEAT EXCHANGERS ASME PTC 30-1991
L TABLE 4.1
RECOMMENDED MINIMUM NUMBER OF AIR VELOCITY MEASUREMENT POINTS
FORFANRING TRAVERSE
Recommended Number Corresponding Corresponding
Fan Ring of Concentric
Areas Measurements Total Number
Diameter, ft for Traverse Per Quadrant of Measurements
4 12 6 3
6 8 4 16
8 10 5 20
12 10 5 20
16 10 5 20
20 12 6 24
24 14 7 28
Measurement
Location of Measurement
Points,
Distance
From
Inner Wall of Ring
Fan
Points Per
Quadrant
Point 1 Point 2 Point 3 Point 4 Point 5 Point 6 Point 7
0.0436D 3 465D ' 0.2959D ... ... ... ...
47D0.0323D 4 938D 0.3232D ... ... ...
5 0.0810.0257D D
7D 0.2261
0.1465D 0.3419D ... ...
0.021 6 3D 0.1 0.1181D
0.0670D 773D 0.2500D 0.3557D ...
7 0.0182D D 0.0991
0.0568D 0.1464D 0.2012D 0.3664D
0.2685D
GENERAL NOTE: D is I.D. of fan ring at plane of traverse. Figure
4.1 illustrates the locationsfor the case in which five measurement points
per quadrant are used.
by averaging the five measurements taken along the For forced draft units an exit traverse is normally
inner peripheries of areas 1, 3, 5, 7, and 9, respec- required, in conjunction with temperature measure-
tively. These velocities are plotted against the total ments, so that the weighted exit temperature can be
areas bounded by the corresponding circles as shown determined (see para. 4.1 3).
in Fig. 4.2. If the traverse measurements are made in a plane
The net area below the resulting curve, between upstream from the tube bundle face (typical for in-
the limits Soand ST, represents the actual volume of duced draft units), the plane shall be located at least
air delivered by the fan perunit oftime. five prime tube diameters from the extremitiesof the
If mutually agreed upon by the partiesto the test, fins to prevent error due to the restriction effect of
the foregoing procedure for determining the air flow the tubes; for downstreamtraverses (typical for
rate may be simplified by averaging directly the 20 forced draft units) the requiredminimum distance is
air velocities (the reading at the centerof the fan is 15 prime tube diameters. To minimize error due to
not used in this method) and multiplyingthe resulting wind effect a suitable shieldis necessary in most in-
number by,the total fan ring area ST. stances (Ref. 111).
17
Copyrighted material licensed to Stanford University by Thomson Scientific (www.techstreet.com), downloaded on Oct-05-2010 by Stanford University User. No further reproduction or distribution is permitted. Uncontrolled wh
ASME PTC 30-1991 AIR COOLED HEAT EXCHANGERS
4o
ST will be sensed by the probe located at the heat ex-
va = VdS
changer outlet. The low pressure area should exhibit
fairly constant pressure; once constancy is verified,
ST
the probe should be left in position for duration of
differentialpressuremeasurements.Thehighpres-
where Va i s the average velocity. sure side to be probed will be at the fan discharge,
and the probe should be positioned at the fan dis-
charge area at a location sufficiently downstream of
FIG. 4.2 TYPICALVELOCITY DISTRIBUTION fan to minimize severe turbulence.
ACROSS FAN STACK
4.7MEASUREMENT OF SOUND LEVEL tion should bexhosen for the measurement that is
unobstructed upwind andatanelevationapproxi-
This subject is treated in PTC 36-1985. mately midway between the average air inlet plane
elevation and the average air exit plane elevation. If
such a locationis impracticable, an alternatelocation
may be agreed upon by the partiesto the test.
4.8 MEASUREMENT OF ATMOSPHERIC PRESSURE
Atmospheric pressure shall be measured by means
of a mercury barometer.
If mutually agreed by the parties to the test, the 4.1 1 MEASUREMENT OF AIR TEMPERATURES
barometric pressure may be obtainedfrom a nearby 4.1 1.1 FTC 19.3 shall be used to stipulate satisfac-
weather bureau station. If this method is used, it is tory instrumentation anddetails of construction of *
necessary to establish whetherthe readings given are sensor wells,the readingof the instruments, andtheir
for station or sea level pressure.Thereadings ob- calibration and corrections.
tained shall be corrected for the difference in eleva- The uncertainty of temperaturemeasurements
tion of the barometerand the unit beingtested. shall not exceed the larger of the following values:
Resultsshallbebased on atmospheric pressure at (SZ, 0.2"F,or
station level. Readings may be correctedto sea level (b) two percent of the smallest of the following
if desired. Details of the procedurefor correction are three key temperature differences:
given in PTC 19.2. (7) the temperature range of the process fluid
(unless isothermal)
(2) the temperature range of the air
(3) the minimum approach temperature differ-
4.9MEASUREMENT OF ENVIRONMENTAL ence.
EFFECTS Satisfactoryinstrumentsincludesuitable ASTM
Prior to the test, a survey of the area surrounding mercury-in-glass thermometers, thermocouples, cal-
the unit shall be conducted jointly by the parties to ibrated sensors with signal conditioner such as re-
the test. All conditions that may contribute to varia- sistance temperaturedevices or thermistors, or
tions in performance, such as heat sources affecting equivalent.
inlet air temperature, and nearby buildings or struc- The sensing elements shall be exposed to the at-
tures which maycause aircurrentsthatresult in mosphere, but shielded from direct sunlightor other
warm air recirculation, or .in reduced fan perform- radiation source by meansof an opaque shield.
ance, shall be investigated. Measurements necessary
to map these effects during the test shall be deter- 4.1 1.2 The wet-bulb temperature measuring instru-
mined by mutual agreement, and substantiating test ments should be mechanically aspirated and incor-
data shall be obtained asnecessary. Ambient tem- porate the following features:
perature measurements shallbe taken in accordance (4A calibrated temperaturesensor whose uncer-
with paras. 4.11 and 4.12 of this Code.Measure- tainty is less than kO.1 O F in the range of the expected
mentsshouldbemade in all locations,simultane- test temperatures.
ously if possible, or in rapid succession. If such (b) Sensing elements shielded from direct sunlight
locations are not accessible or the area surrounding or other radiationsource. Theinner side of the shield
the ACHE contains elements (see above) which can shall be essentially at the dry-bulbtemperature.
affect the ambient temperature, a suitable location (c) Wicking covering thesensor shall be clean and
for thesemeasurementsshallbe mutually agreed continuously suppliedfrom a reservoir of distilled or
upon. demineralized water. Thewick shall be a snug fit and
extend at least 1 in. over the active portion of the
sensor.
(d)The temperature of the water used to wet the
4.10 MEASUREMENT OF WIND VELOCITY wick shall be at approximately the wet-bulb temper-
The instrument recommendedis either the rotating ature.
cup or rotating vane anemometer with preferably a (e) The air velocity over the wick shall be contin-
continuous readout or recording capability. A loca- uous at approximately1000 Wmin.
19
Copyrighted material licensed to Stanford University by Thomson Scientific (www.techstreet.com), downloaded on Oct-05-2010 by Stanford University User. No further reproduction or distribution is permitted. Uncontrolled w
ASME PTC 30-1991 AIR COOLED HEAT EXCHANGERS
4.12 MEASUREMENT OF AMBIENT AND rectangular areas (at least 20 or one per 12 square
ENTERING AIR TEMPERATURES feet, whichever is greater) with the same aspectratio
as the plane being measured, if practical. Shields shall
This survey shall consist of two ambient wet- and be providedfor the temperature sensing elements to
dry-bulb temperature measurements and a suitable prevent error due to dilution by outside air, or due
number of entering dry-bulb temperature measure- to radiation from the sun or other sources. The tem-
ments. perature measurement devices shall be located a suf-
The ambient wet- and dry-bulb temperature mea- ficient distance from the ACHE to minimize the effect
surements shall be taken at approximately 5 ft above of the tube wakes (usually 15 prime tube diameters
the ground elevation not less than 50 or more than
is sufficient).
100 ft upwind of the equipment.Theseshall be
spread along aline which brackets that flow. If these
.locations are inaccessibleor contain elements which
can affect the reading of wet-bulb temperature, al-
ternate locations shall be mutuallyagreed upon. 4.14 MEASUREMENT OF PROCESS FLUID
Entering dry-bulb temperature measuring stations TEMPERATURES
shall be selectedon an equal-area basis, and shallbe 4.14.1 The uncertainty of temperaturemeasure-
located in a plane6 in. below the fan ring for forced ments shallnot exceed the larger of the two following
draft, and 12 in. below the finned tubes for induced values:
draft units. The sensing elements of the thermome- (a) 0.2"F, or
ters, or thermocouples, shall be properly located and (b) two percent of the smallest of three key tem-
shielded to prevent appreciable error due to radia- perature differences;
tion. The recommended number of stations is given (7) the temperature range of the process fluid
in para. 4.4. If the maximum and minimum temper- (unless isothermal)
atures differ by 5°F or more due to warm ,air recir- (2) the temperature rangeof the air, or
culation, or environmental effects, additional stations (3) the minimum approach temperature differ-
shall be selected, the number and location of these ence. See para. 4.1 1 for satisfactory instruments.
stations shall be determinedby mutual agreement of
the parties to the test.
4.14.2 The measuring stations shall be located close
enough to the unit to prevent appreciable error due
to temperature change occurring between the sta-
4.1 3 MEASUREMENT OF EXIT AIR TEMPERATURE
is a possibility,
tions and the unit. Where stratification
Unless otherwise agreedby the partiesto the test, preliminary tests shall be conductedto determine the
coincident temperatures and velocities shall be mea- magnitude of possible resultant error. These shall be
sured. atall selected stationsso that the weighted exit made a part of the test report.
air temperature can be calculated. The instruments
to be used shall be as specified in para. 4.1 1.
4.13.1 Induced Draft Units. Measurement stations 4.15 MEASUREMENT OF PROCESS FLUID
shall be locatedprior to the testperiod in accordance PRESSURES
with para. 4.4.3 so that the measurements will best
The requireduncertainty limit of fluid pressure
represent the true bulk temperature. Formultiple-fan measurement devices shall betwo percent of the ab-
units, fewer stations may be used if agreed upon by solute fluid pressure. Instrument selection and details
the parties to the test. The temperature profile of one of measurement techniques shallbe made in accord-
fan shall be investigated thoroughlyprior to the test ance with PTC 19.2. Satisfactory instruments include
period to ensure sufficient accuracy; the data shall pressuregages,manometers,pressuretransducers,
be made apart of the test report. or other equivalentdevices.
Measuring stations shall be located as close to the
4.13.2 Forced Draft Units. Measuring stations shall unit as practicable. Corrections shall be made for line
belocateddownstream of thetube bundles.The losses, fitting losses, etc., that result in pressure dif-
measurement plane shall be divided into imaginary ference betweenthe measuring stations and the unit.
\
20
Copyrighted material licensed to Stanford University by Thomson Scientific (www.techstreet.com), downloaded on Oct-05-2010 by Stanford University User. No further reproduction or distribution is permitted. Uncontrolled w
AIR COOLED HEAT EXCHANGERS ASME PTC 30-1991
21
Copyrighted material licensed to Stanford University by Thomson Scientific (www.techstreet.com), downloaded on Oct-05-2010 by Stanford University User. No further reproduction or distribution is permitted. Uncontrolled w
AIR COOLED HEAT EXCHANGERS ASME PTC 30-1991
23
Copyrighted material licensed to Stanford University by Thomson Scientific (www.techstreet.com), downloaded on Oct-05-2010 by Stanford University User. No further reproduction or distribution is permitted. Uncontrolled w
ASME PTC 30-1991 COOLED AIR HEAT EXCHANGERS
5.3.1 Air-Side
Data
Reduction
density
The calculated
be
can
air
dry
from
of
(a) AirVelocity.Individualairvelocitymeasure- pa = 1.325 BftR (Note (5.3)
ments shall be corrected for instrument calibration
and then averaged as discussed in para. 4.4
(b) Computation of Heat Load:
(b) Air Temperature. Air temperature data readings
shall be averaged for each set of test data. Exit air
temperaturesshallbeaveraged by the massflow
weighted average method shown in Eq. (5.1); how-
ever, variations in inlet air temperature are normally
5.4.2 Computation of Process-Side Mass Flow Rate
small enough to allow arithmetical averaging of the and Heat load
temperatures alone.
(a) Computation of Mass Flow Rate
(5.5)
2 PnVnSn
n-1
(b) Computation of Heat Load
where n is an individual measurement
(c) Static Pressureor Differential Pressure. The read-
ings shall be arithmetically averaged.
The enthalpy of the process fluid at the entrance
5.3.2 Process Fluid Data Reduction and at the exit shall be determined by means, and
(a) Process Temperatures. Readingsof process fluid from data sources, mutually agreed uponby the par-
temperatures at a given station shall be arithmetically ties concerned prior to the test. For process fluids.
averaged. with no phase change,the above heat load equation
(b) Process Flow. Process flow measurements shall can be written
becalculated in accordance with ASME PTC 19.5,
FluidFlow Measurement Procedures, or its interim
supplement, ASMEFluid Meters, Part II.
(c) ProcessPressure.Processpressuremeasure- 5.4.3 Computation of Heat Balance Error. The per-
ments shall be calculated in accordance with ASME cent error in heat balance is calculated by
PTC 19.2.
I-I
to be calculated. The objectives of these calculations
are two-fold: (I) to determine the heat load of the Q, Q, , is the absolute value
heat exchanger under the test condition, and (2) to
check the validity of the set of test data obtained.To
If the percent error is within the acceptable limit
of 15 percent as stated in para. 3.16, the heat load
calculate the heat loads for both the air and process
Q to be used for data interpretation can be one of
sides, the air and process fluid mass flow rates are
the following:
first calculated. These flow rates are then used to (a) the air side heat load Q,
calculate the heat loads.
(b) the process side heat load Q,
(c) the average heat load (Q, + QJ2.
5.4.1 Air-Side Mass Flow Rate and Heat load
(a) Computation of Mass Flow Rate of Dry Air. For
computation of air mass flow rate,
(5.2) 'Theconstant 1.325 applies for U.S. CustomaryUnits of 5 and tR,
i.e., in. Hg and R.
'Values of Ha, and Ha2are determined from enthalpy data, using
'Thefactor 60 appliesto U.S. Customaryunitsof p. ,V. ,S.. thecorrespondingtestvalues of tl and t2.
24
Copyrighted material licensed to Stanford University by Thomson Scientific (www.techstreet.com), downloaded on Oct-05-2010 by Stanford University User. No further reproduction or distribution is permitted. Uncontrolled
AIR COOLED HEAT EXCHANGERS ASME PTC 30-1991
(-)
by Eq. (5.12).
In
5.6 COMPUTATION OF OVERALLHEAT
TRANSFER COEFFICIENT
ConstantProcess Fluid Temperature: T, = T2 = T vis calculated from
(t2 - t,) e =(A,) Q"
(EMTD")
(5.14)
LMTD = (5.ii)
25
Copyrighted material licensed to Stanford University by Thomson Scientific (www.techstreet.com), downloaded on Oct-05-2010 by Stanford University User. No further reproduction or distribution is permitted. Uncontrolled w
ASME PTC 30-1991 AIR COOLED HEAT EXCHANGERS
clearly identified, e.g., air-side, process-side, arith- is equal to the air pressure rise provided by the fan.
metic average, etc. Therefore, to measure the cooling system air pressure
The reference area maybe any convenient mu- loss, one can either measure thesecomponent losses
tually agreed upon heat transfer surface. There are separately or in combination, or one can deduce the
four commonly used reference areas. total losses from the fan drive system power con-
sumption and the measured airflow. The fan drive
system power consumption is comprised of the air
5.6.1 ‘Total Outside Heat Transfer Area Including
energy losses and the drive system mechanical and
Fins (A,)
electrical energy losses. Generally, in a performance
(3
test, it may not be necessary or desirable to measure
A, = [(N) (NfJ (LfJ - (D2ho- D 2 ~ o ) l each of these air pressure losses separately, and usu-
ally it is preferable and easier to measure only the
+ [(N) (LJ (IT) (DpJ (1 - NfnC)l (5.15)
cooling system power consumption for comparison
+ [(N) (IT) (Dpo)(L - Lm)l with design specifications and/or performance char-
acteristic data provided by the system supplier.
where
L, = the length of finned’ portion of tube 5.8 DETERMINATION OF PROCESS FLUID
Dtno= the outside diameter of fin PRESSURELOSSES
D, = the outside diameter of root
D,,, = the outside diameter of prime tube Thepressure loss between measuring stations is
L = the total length of tube simply the difference between the measurements
taken at these locations. Thetest measuring stations
(Note: Other symbols as defined in para. 2.2)
should be located in such away that they will provide
a pressure measurement at the required design sta-
5.6.2 Outside SurfaceBased on FinRoot Outside tions. If not, consideration must be given to the ef-
Diameter (A,) fects of the following factors:
(a) gravity
(This is a fictitious area) (b) fluid velocity
d (c) flow obstructions
A, =
0
IT N DRoL, (5.16) (d) fluid properties and flow rates
Figure 5.9 is aschematicrepresentation of the
process fluid piping foran ACHE. The measuring sta-
5.6.3 Prime Surface Based on Inside Tube Diameter tions (MS) and design stations (DS)have been delib-
(A,,,.) erately depicted in different vertical locations in order
that the following discussion and calculation proce-
A,, = .rrND,L (5.1 7) dures can encompassthis possibility.
Equation (5.19) shall be used to adjust the test
value of pressure loss across the measuring stations,
5.6.4 Prime Surface
Based on
Outside Tube to a deduced value of total pressure loss across the
Diameter (A,,,) design stations at the test conditions.
A, = .rrNDpoL (5.18)
Detailed procedures for solving the elements of Eq. The evaluation of K will depend on the type of
5.19 are presented in the following paragraphs. obstruction as described below.
Abrupt contraction andexpansion losses yield a
5.8.1 Gravity (Mg). Differences in elevationsand/orvalue of K as follows:
densities will have aneffect on process fluid pressure
measurements. These
effects
can
evaluated
be by K=0.5 X (1 - p') in contraction (5.25)
means of Eqs. (5.20) and (5.21) with reference to Fig.
5.9.
K= (1 - p2)2in expansion (5.26)
APgh-D = AEIDMpl - AE2Dd2 (5.20)
- inside
where B is the ratio of the smaller to the larger
pipe diameter.
AP,,-, = AE,,p,-AEB
5.8.3.3 PiDe and Cooler Tube Bend losses
5.8.3.4 Losses
Caused by Various Fittings
(5.22) (APO5-J. The valuesof the loss coefficient, K, for pipe
fittings, valves,etc., are dependent on the specific
where: geometry involved and cannot begeneralized.For
AP, = velocity pressure differential, Ibf/ft2 this reason it is best to plan the instrumentation so
that there areas few such lossesas possible between
measuringstations.Forthose components which
5.8.3 Flow Obstruction (ZAPoB).Obstruction losses must be evaluated, there are data availablefrom man-
between measuring stations mayinclude effects due ufacturers, such asRef. 131, and reference will have
to : to be made to these for the particular type of fitting
(a) pipe and bundle tube friction of interest.
(b) contractions and/orexpansions in the pipes
and bundle tubes
(c) pipe and bundle tube bends Summarizing,
(d) the presence of fittings such as bends, valves,
flow meters, tees, couplings, etc.
Copyrighted material licensed to Stanford University by Thomson Scientific (www.techstreet.com), downloaded on Oct-05-2010 by Stanford University User. No further reproduction or distribution is permitted. Uncontrolled wh
ASME PTC 30-1991 AIR COOLED HEAT EXCHANGERS
(.p.)
5.9 ADJUSTMENTS OF TEST DATA 2.7
CONDITIONS RPM*
X p2)* X (5.30)
+
+
(P1 P2)"
Since tests are rarely run at design conditions, the
recommended procedure is to adjust the ACHE per-
formance results determined under test conditions to NOTE: The cautions presented above applicable to the pressure
design conditions and compare these adjusted values drop evaluation are also applicableto the power adjustments.
with the design values. Adjusted driverinput horsepower may be obtained
When a procedurefor' acceptance testing is to be by introducing the driverand drive train efficiencies.
adopted, a discussion between the interested parties
is essential to establish agreement as to the method
by which data will be adjusted from test to design Fan Horsepower+
conditions. Presentedbelow are methods which may Driver Input Horsepower+ = (5.31)
qdrlvcr ?drive train
be usedto make adjustments required in some of the
more commonly encountered situations. Before us- (c) Air Density Determinations
ing these methods, the parties involved in the testing For determining thedensities required in the pres-
should assure their applicabilityto the test under con-. sure drop and horsepower adjustments, Eq. (5.3) may
sideration. Adjustments for some of the more com- be used.
plex casescanbemade using the relationships in
Appendix D. NOTE: This equationis used for the more typical applications and
neglectshumidityeffects. If widely variant humidity conditions
exist with respect to design, a more precise evaluation using psy-
chrometric data may be appropriate.
5.9.1 Adjustment of Air-Side Bundle Pressure Drop
and Fan Performance. When the test is run at con-
ditions other than design air densities, velocities, or (d) Air Flow Determination
fanspeed, testmeasurementsmaybeadjusted to To adjust the test airflow to the conditionsof de-
their equivalent values at design conditions by use of sign fan horsepower and design air density, use
..(E)($)
the following equations. The user should recognize in.7 2/3
that accuracymaysuffer if adjustmentsaremade w+ = (5.32)
from conditions which vary significantly from design
conditions (see limitations in paras. 3.14 and 3.15).
(4Air-Side Bundle Pressure Drop
5.9.2 Adjustments of SinglePhaseProcess-Side
Fluid Pressure Drops
NOTE: For multi-phase
cases,
the
user
should
refer
to
Appendix D
or
To compare the measuredprocess-sidepressure
drop to the design value, adjustments may be nec-
essary to compensate for the following:
.Process fluids with properties or conditions other
than design
Because of the simplifying assumptions made in .Process flow rates other than design
the derivation,significantchanges in the Reynolds
Such adjustments may be made using
number, V, or RPM, between design and test condi-
tions will adversely affect accuracy. The 1.7 power
hasbeenestablishedasreasonable approximation
empirically, but may vary givendifferent system con-
figurations.
AP(z)i'a(2)($r,
(b) FanPowerAdjustments
Densities and viscosities should be evaluated at the from test conditions to design conditions, and finally
temperature.
recombine
mean component
coefficients
the to calculate
an adjusted overall heat transfer coefficient.
NOTES:
(1) This adjustment presumes that inlet and outlet pressureswere Agreementmust be reached prior to testing re-
measuredat their design locations within the system. If this is garding use of the adjustment procedure presented
not the case, adjustments must be made in accordance with below or analternate.
para. 5.8.
(2) Throughout Section 5, Re, of 2,300 is taken as a distinct sep-
aration between laminar and turbulent flow. Of course, a dis-
tinct separation does not exist. If Re, is found to be in the range STEP 7
of 2,000 to 70,000, the user may refer to Appendix D for a
more rigorous treatment. Determine the overall reference surface heat trans-
(3) If the Reynolds numbers for boththe design and test conditions
do notfall in the same regime, the simple ratios'above do not fer coefficient as indicated by the test result.
apply; in that situation, the user must refer to Appendix D.
(4) For thosecases in whichthe fluid inthe test is in a single phase U," = Q"/(A,X EMTD") (5.14)
throughout the system, temperature and velocity variations be-
tween design and test conditions will be the only parameters
affecting the pressure drop measurements. If the fluid is a liq- See para. 5.4 for development of Q" and para. 5.5
uid, the variations in temperature will usually cause only slight for development of EMTD".
variations in density and, in general, density may be neglected
in the above equations. The viscosity may or may not change
significantly, depending on the fluid and temperature ranges
involved. If the viscosity or friction factor varies by a factor of STEP 2
two or more from inlet to outlet, pressure drop must be eval-
uated on an incremental basis. The formulas presented above The testoverallreferencesurfaceheattransfer
presume pressure drop variations through the tubes are rep-
resentative of pressure drop variations through all components coefficient must be broken down into its component
between pressure measuring stations. If this is not believed t o parts. The following equation represents the normal
be the case, a more detailed evaluation of variations in pressure heat transfer resistanceswhich may be encountered.
drop through individual components of the heat exchanger may
be desirable.
29
Copyrighted material licensed to Stanford University by Thomson Scientific (www.techstreet.com), downloaded on Oct-05-2010 by Stanford University User. No further reproduction or distribution is permitted. Uncontrolled wh
ASME PTC 30-1991 AIR COOLED HEAT EXCHANGERS
The values of all the individualcomponents which determine fouling resistance during equipment test-
comprise the right side of this equation must bede- ing. Fouling resistances shall be agreed on as stated
termined. Some may be calculated directly by avail- in para. 3.2.
able correlations, some must be assumed and agreed Refer to Appendix E for additional discussion of
upon by the parties to the test as discussed below, fouling.
and the final factor (either the air-sideor process-side
film coefficient) will be determinedin Step 3 by solv-
Prime Wall:
ing the above equation.
.This resistance is calculated directly using the ap-
The decision as to whether the air-or process-side
plicable part of Eq. (5.35).
film coefficient is calculated directly should be made
on the basis of which can be determined more ac-
curately. In cases where it is uncertain which coeffi- Bond:
cient may be determined with greater confidence, it The value of the bond resistance, /lhb, will depend
may be agreed to calculate both and use the coeffi- upon the type of extended surface being used, the
cient showing the lower thermalresistance to solve tube and fin materials, the temperature level of ap-
for the other in Step 3. plication, and the manufacturing practice. In many
A discussion of how each component may be de- cases, the value of this component will be low in
termined follows. comparison with other terms, making it insignificant.
If this is thought not to be the case, it is suggested
that themanufacturer's design valuefor this term be
Inside (Process Fluid) Film: used in the calculation. However, mutual agreement
If the process fluid is a liquid in turbulent flow in on this matter must be reachedby the partiesto the
a plain tube (no internalenhancement), the value of test.
hp may be evaluated using the Sieder-Tate equation
(Ref. [41):
Fin Root Wall:
The value of this component will be smallin com-
parison with other terms, making it insignificant in
(7)"'
most cases. This resistanceis calculated by the basic
relationship shown in Eq. (5.35). Depending on the
(4)O'14 (5.36) details of fin construction, assessment of the outside
radius of the.fin root wall (rRo)may require consid-
erable judgment.
Inside Fouling:
Of the component resistances, fouling is the most (5.38)
difficult to determine. There is no practical way to
30
Copyrighted material licensed to Stanford University by Thomson Scientific (www.techstreet.com), downloaded on Oct-05-2010 by Stanford University User. No further reproduction or distribution is permitted. Uncontrolled wh
AIR COOLED HEAT EXCHANGERS ASME PTC 30-1991
NOTES:
(1) c
" .
is the mass flow rate evaluated with respect to the free
,
flow area.
TABLE 5.1
VALUES OF Ft, FOR EQ. (5.38)
(2) Equation (5.38) is applicablefor Re from 1000 to 20,000, where No. of Tube Tube Row
Row Deep Arrangement Factor, f,*
1 0.78
2 0.88
3 0.93
4 0.97
(3) F, is tube row arrangement factor; values are given in 5 0.98
Table 5.1. 6 1.oo
1.02 8
10 1.025
Once thefilm coefficient is evaluated, it may then GENERAL NOTES:
be used in the determinationof the fin efficiency+Of". (a) These factors are applicable for the normal staggered tube
Figures 5.10 through 5.13 may be used in this eval- arrangement.
(b) Values in this table are calculated from Fig. 11 of Ref. [6],
uation. Symbols in these figures are defined below: using V,, = 1000 feet per minute and using the value for 6
rows as a base, since Eq. (5.38) is based on 6 rows.
h = heat transfer coefficient
I = modified Bessel function of the first kind
K = modifiedBesselfunctionof thesecond
kind
k = thermal conductivity of fin material
n = a constant, orderof Bessel function
u = function of x defined by STEP 3
Solve for the component resistance not determined
by the correlationsby subtracting the sumof the eval-
uated component resistances from the overall heat
transfer resistance.
where i = f i ; c = a constant; p = a constant; a =
cross-sectional area of fin normal to x axis, and A = fin STEP 4
surface between origin and point x. The components on the right-handside of Eq.
w = fin height (5.35) mustbeadjusted to designconditions.The
x = distancealongaxisnormal to basicsur- only components which will ,be affected by these ad-
face justments are the inside film resistance and equiva-
y = half thickness of fin at point x lent convection and conduction resistance of the fins.
4 p = constants The adjustments may be made as follows:
b, e = conditions at base and edge, respectively
Inside (Process Fluid) Film:
For additional discussionof fin efficiencies andnu- The Sieder-Tate relationship may be used to ratio
merical relationships for calculation of the efficien- turbulent test and adjusted design coefficients
cies, the parties may refer to Ref. 171.
With the values of and h: established,the
+Of,
Fin and Air Film: heat load, process flow rate, inside film resistance,
Equation (5.40) may be used to yield an approxi- and EMTD are all unknown.
mate ratio of testandadjusteddesign film coeffi- The recommended procedure for determinationof
cients capability is:
(7) Assume a value of process fluid flow rate, W + .
(2) Computecorrespondingheatload from Eq.
(5.6) or (5.71, as appropriate.
(3) Adjust the test airflow rate to design fan power
and air density:
NOTE:The aboveequationisapplicable for Re from 1000 to
20,000,where
w+ = d ( $ )
1R.7
(2)2/3
(E)
(d) air inlet temperature and density
(e) fan power PERCENT WABILIN = x 100
The determination of this flow rate,asstated in
para. 5.1, is an iterative one, since the corresponding
32
Copyrighted material licensed to Stanford University by Thomson Scientific (www.techstreet.com), downloaded on Oct-05-2010 by Stanford University User. No further reproduction or distribution is permitted. Uncontrolled w
AIR COOLED HEAT EXCHANGERS ASME PTC 30-1991
R =
T, - T*
rn
T and t are not interchangeable
+=++A ‘1
T2
0.0 0.1 0.2 0.3 0.4 0.5 0.6 0.7 0.8 0.9
p - Thermal Effectiveness= -
-
‘2
-
T1
‘1
tl
33
Copyrighted material licensed to Stanford University by Thomson Scientific (www.techstreet.com), downloaded on Oct-05-2010 by Stanford University User. No further reproduction or distribution is permitted. Uncontrolled w
ASME PTC 30-1991 AIR COOLED HEAT EXCHANGERS
0.0 0.1 0.2 0.3 0.4 0.5 0.6 0.7 0.8 0.9 1.o
rz - r l
P - Thermal Effectiveness = -
T1 - tl
34
Copyrighted material licensed to Stanford University by Thomson Scientific (www.techstreet.com), downloaded on Oct-05-2010 by Stanford University User. No further reproduction or distribution is permitted. Uncontrolled wh
AIR COOLED HEAT EXCHANGERS ASME PTC 30-1991
‘1
0.0 0.1 0.2 0.3 0.4 0.5 0.6 0.7 0.8 0.9 1 .o
P -- Thermal Effectiveness = -
‘2 - f l
T1 - ‘1
35
Copyrighted material licensed to Stanford University by Thomson Scientific (www.techstreet.com), downloaded on Oct-05-2010 by Stanford University User. No further reproduction or distribution is permitted. Uncontrolled w
ASME PTC 30-1991 AIR COOLED HEAT EXCHANGERS
T, - T2
R =
m
T a n d r a r e not interchangeable
B
c
0
LL
0.0 0.1 0.2 0.3 0.4 0.5 0.6 0.7 0.8 0.9 10
P - Thermal Effectiveness = -
‘2 - ‘1
T1 - tl
36
Copyrighted material licensed to Stanford University by Thomson Scientific (www.techstreet.com), downloaded on Oct-05-2010 by Stanford University User. No further reproduction or distribution is permitted. Uncontrolled w
AIR COOLED HEAT EXCHANGERS ASME PTC 30-1991
1 .o
0.9
0.8
II
L
0
c
0
IL 0.6
.-L5
E
0
0 0.5
I
.u
0.4
0.3
0.0 0.1 0.2 0.3 0.4 0.5 0.6 0.7 , 0.8 0.9 1 .o
P - Thermal Effectiveness = -
-
-
‘2
T1
‘1
‘1
37
Copyrighted material licensed to Stanford University by Thomson Scientific (www.techstreet.com), downloaded on Oct-05-2010 by Stanford University User. No further reproduction or distribution is permitted. Uncontrolled wh
ASME PTC 30-1991 AIR COOLED HEAT EXCHANGERS
t^
0.0 0.1 0.2 0.3 0.4 0.5 0.6 0.7 0.8 0.9 1 .o
P - Thermal Effectiveness = -
‘2 - ‘1
T1 - ‘1
38
Copyrighted material licensed to Stanford University by Thomson Scientific (www.techstreet.com), downloaded on Oct-05-2010 by Stanford University User. No further reproduction or distribution is permitted. Uncontrolled w
AIR COOLED HEAT EXCHANGERS ASME PTC 30-1991
R= -
T1 - T2
‘2 - ‘1
T a n d t a r e not interchangeable
‘2 - ‘1
P - Thermal Effectiveness = -
TI - t l
39
Copyrighted material licensed to Stanford University by Thomson Scientific (www.techstreet.com), downloaded on Oct-05-2010 by Stanford University User. No further reproduction or distribution is permitted. Uncontrolled w
ASME PTC 30-1991 AIR COOLED HEAT EXCHANGERS
R= -
T1 - T2
‘2 - ‘1
r a n d t a r enor interchangeable
0.0 0.1 0.2 0.3 0.4 0.5 0.6 0.7 0.8 0.9 1 .o
-
P - Thermal Effectiveness = -
‘2
-
T1
‘1
‘1
40
Copyrighted material licensed to Stanford University by Thomson Scientific (www.techstreet.com), downloaded on Oct-05-2010 by Stanford University User. No further reproduction or distribution is permitted. Uncontrolled w
ASME PTC 30-1991
AE2BD
= measuring station
= design station
41
El
c3
FIG. 5.9
In
AIR COOLED HEAT EXCHANGERS
Copyrighted material licensed to Stanford University by Thomson Scientific (www.techstreet.com), downloaded on Oct-05-2010 by Stanford University User. No further reproduction or distribution is permitted. Uncontrolled wh
AIR COOLED HEAT EXCHANGERS
42
ASME PTC 30-1991
..
-r
c
N
Q
h
11
Copyrighted material licensed to Stanford University by Thomson Scientific (www.techstreet.com), downloaded on Oct-05-2010 by Stanford University User. No further reproduction or distribution is permitted. Uncontrolled w
I
0
c)
u
t
09 O’t OE 0’2 0 1 0
‘ 0
1‘0
Copyrighted material licensed to Stanford University by Thomson Scientific (www.techstreet.com), downloaded on Oct-05-2010 by Stanford University User. No further reproduction or distribution is permitted. Uncontrolled wh
AIR COOLED HEAT EXCHANGERS
44
8
ASME PTC 30-1991
8
1
I
Copyrighted material licensed to Stanford University by Thomson Scientific (www.techstreet.com), downloaded on Oct-05-2010 by Stanford University User. No further reproduction or distribution is permitted. Uncontrolled
s FOR HEAT FLOW
P
(D
EFFICIENCY OF ANNULARFINSWITH CONSTANT METAL AREA FIG. 5.13
s0 m w
rn
z
E; 5.0 4.0 3.0 2.0 1.o 0
Copyrighted material licensed to Stanford University by Thomson Scientific (www.techstreet.com), downloaded on Oct-05-2010 by Stanford University User. No further reproduction or distribution is permitted. Uncontrolled wh
AIR COOLED HEAT EXCHANGERS ASME PTC 30-1991
6.1 COMPOSITION OF REPORT It shall include astatement that the testwas con-
ducted in accordance with ASME PTC 30, including
The test report for a performance test
shall include
a list of exceptions, if any.
the following.
-
(c) List of Instrumentation This shall list all the 6.2.3 Air Densities
instrumentationused on the test, including manufac-
turer and model number. (a) Ambient air density - Ibm/ft3
(0" List of all participating personnel. (b) Inlet air density - Ibm/ft3
(e) Uncertainty Analysis Sample Calculation - A (c) Outlet air density - Ibm/ft3
sample calculation forone run should be included.It
should use the same run that was usedfor the results
sample calculation, per (a) above. 6.2.4 Air Flow
(2)Total inlet air flow - ACFM - ft3/min
6.1.1 0 Raw Data Distribution. At least one complete (b) Total outlet air flow - ACFM - ft3/min
set of .copies of the signed original log sheets shall (c) Total air flow - SCFM - ft3/min
be distributed to each party in the test. (d) Total air flow - Ibm/hr
O F
(g, Wind direction (h) Adjustedoverallheattransfercoefficient -
Btu/hr.ftZ*"F
6.2.2 Air-Side Temperatures (i) Adjusted process fluid flow rate - Ibm/hr
0) Adjusted heat load - Btukr
(4 Inlet dry-bulb temperature - O F (k) Capability - %
(b) Inlet wet-bulb temperature -
(c) Outlet dry-bulb temperature -
OF
OF
Copyrighted material licensed to Stanford University by Thomson Scientific (www.techstreet.com), downloaded on Oct-05-2010 by Stanford University User. No further reproduction or distribution is permitted. Uncontrolled w
i
A3 Plant operating personnel involved with the air A.9 Observe the exchanger in operation,keeping
cooled heat exchanger should be requested to report alert to hot air currentsfrom outside sources or dis-
on performance daily. Ask about maintenance pro- chargeairrecirculation. By agreement, eliminate
cedures,
on-stream
performance
characteristics, these to the maximum extent possible.
process upsets, mechanical problems, and any clues
concerning heat transfer performance. A.10 All test personnel should observethe maximum
safetyprecautions whiletaking data.Eachperson
A.4 A brief preliminarycheck of the operating proc- must stay within his assigned station to avoid inter-
ess flow andtemperatureconditionsandair-side ference or possiblydangerous disruption to other test
temperatures will help determineif the heat transfer personnel. Become acquainted with safety facilities,
and pressure drop are reasonably close to expecta- escape routes, and alarm systemsbefore undertaking
tions. Also, this may point to areas requiring spec,ial the test. Be alert to possible physical harm from hot
attention during the equipment inspection before for- process streams and discharge air. Insure that all re-
mal testing. quired safety and protective devices, suchas fan and
belt guards, are properly installed.
A.5 The process fluid should be sampled and tested
to ensure that all of its physical and transport prop- A . l l Steady-state conditions aredesirable forthe
erties are within acceptable limits. most meaningful test results. If test personnel ob-
49
Copyrighted material licensed to Stanford University by Thomson Scientific (www.techstreet.com), downloaded on Oct-05-2010 by Stanford University User. No further reproduction or distribution is permitted. Uncontrolled w
ASME PTC 30-1991 AIR COOLED HEAT EXCHANGERS
serve transient test data, they should alert the test should be kept running in order to maintain the full
leader who should decideif testing should continue, unit air flow patterns. Potential uneven distribution
be stopped, or extended past the agreed-upon time. of flow of the process fluids mustbe considered, par-
ticularly if the process is a two-phase system. This
technique must also result in the inside-tube flow
A.12 Interchange of agreed-upon instrumentation regime being similarto the original design, i.e., lam-
during the test is a good technique to account for inar or turbulent, the same predicted mechanism of
individual instrument error, or to flag significant er- condensation, etc. Testing in the transition zone be-
rors. This is particularly applicable to the measure- tween laminar andturbulent flow will not be reliable.
ment of process fluid temperature and pressure at
the exchanger inlet and outlet.
A.14 Normally a performance test is run as soon as
possibleaftercleaning.However, if there is doubt
A.13 If process flow and heat load are inadequateto about the internal fouling resistance, it may be pos-
properly load all of the exchanger bays,'it may be sible to "shock" clean certain processes, while on
possible to divert theflow by valves to a fewer num- stream, using water, steam, or solvent injection. This
ber of bays so that the flow rate and the heat load should be arranged in advance of the test so that the
per bay are closer to the design point. If this tech- proper operations personnel are available if it appears
nique is agreedupon, the fans on inactive bays necessary to investigate the effect of such cleaning.
50
Copyrighted material licensed to Stanford University by Thomson Scientific (www.techstreet.com), downloaded on Oct-05-2010 by Stanford University User. No further reproduction or distribution is permitted. Uncontrolled w
AIR COOLED HEAT EXCHANGERS ASME PTC 30-1991
APPENDIX B EXAMPLE
(a) Fans
B.2 SPECIFICATIONS (7) Number per unit -2
The following specifications submitted by the suc- (2) Diameter, ft - 8
cessful vendor were accepted and made part of the (b) Gears
contract: (7) Number per unit - 2
(2) Type - right angle spiral bevel
B.2.1 General
(c) Drivers
(a) Type of unit - ACHE (7) Number per unit - 2
01)Service - water cooling (2) Type - electric motor
(c) Air flow mode - induced draft (3) Nominal size, HP - 15
51
Copyrighted material licensed to Stanford University by Thomson Scientific (www.techstreet.com), downloaded on Oct-05-2010 by Stanford University User. No further reproduction or distribution is permitted. Uncontrolled w
ASME PTC 3d1991 AIR COOLED HEAT EXCHANGERS
and the measured inlet air temperature shall be used. Exit DBT 134.0 133.5
The test values of air flow rate and/or exit air tem- Air density, Ibm/ft3: Ambient ' 0.071 05 0.07087
perature shall be adjusted so that Q: = Qp;this ad- Inlet 0.07092 0.07074
justment shall be based on the expected accuracies Exit 0.06622 0.06578
'of these two measurements. Uncorrected MTD, "F 43.23 36.60
(e) Testing and evaluation procedures shall be in MTD correction factor OF 0.99 0.99
accordance with the provisions of this Code. Corrected (effective) MTD, "F 42.80 36.24
(0 The test overall heat transfer rate shall be com- Overall heat transfer coefficient:
Btu/(hr-fP"F)
Service 104.91 119.1 5N""
puted from the test data, using Eq. (5.14). Drive-output power per fan, HP 10.20 11.40
For adjustment of the test data to design con-
NOTES:
ditions, Eq. (5.35) shall be used. (1) calculated
(h) For this example the air film is expected to be (2) based on external surface of prime tubes
the major resistance; therefore, the test value of //he
shall be established by deducting the summation of
the remaining resistances from the overall resistance. loads are equal. The capability will then be computed
(9 The process-side pressure drop predictedat de- from
signwatercirculationrate A f + shallbecomputed
from Test Capacity
Percent Capability = Design Capacity x 100
(F)
fore, air temperaturesfor EMTD" calculationwere not
0.6
LMTD" =
(141.2 - 92.2) - (160.0 - 133.5)
49.0
In -
26.5
= 36.605"F
B.6 PERFORMANCECALCULATIONS
Test heat load: Correction factor:
F = 0.99
= (540,692) (0.2421 (1 33.5 - 92.2)= 5,406,456 Btu/hr EMTD" = 36.605 X 0.99 = 36.24"F
53
Copyrighted material licensed to Stanford University by Thomson Scientific (www.techstreet.com), downloaded on Oct-05-2010 by Stanford University User. No further reproduction or distribution is permitted. Uncontrolled wh
ASME PTC 30-1991 AIR COOLED HEAT EXCHANGERS
Unadjusted test U:
Inside film resistance =
c =OZ,)(EMTD")
Q: - (1206)(36.24)
5'207t600 = 119.1
5 Btu/hrfP"F = 0.0007361 hrftz*"F/Btu
= 0.0010000 hr-ft'."F/Btu
[see para. B.3(c)]
(F)0'33
( &4°.'4
277,000
= 21,256 Whr
.I81
= (48)(~/4)(0.902/12)*(61 For the configurationused in this Example the pre-
ceding equation reduces to:
p; = 61.18 Ibm/ft3
Prime wall conduction resistance = 'Po '*
('PJ'P)
kPw
Ibm
p; = 0.455 X'2.42 = 1.1011 -
-In -
hr-ft 0.50 0.50
= l2 0'451 = 0.0000672 hr-ftZ-"F/Btu
64
ciP= 1.OO Btu/lbm "F
A, In (rRJrR>
Fin root wall conduction resistance =
(
21,256 X 0.07517 X 61.18 2 ~ l N k ,
hp =
0.07517 1.lo11
0.50
- I
n
0 58
= (0.1 181I) (9091.7) (1.41 33) (0.9925) -
~~
54
Copyrighted material licensed to Stanford University by Thomson Scientific (www.techstreet.com), downloaded on Oct-05-2010 by Stanford University User. No further reproduction or distribution is permitted. Uncontrolled w
AIR COOLED HEAT EXCHANGERS ASME PTC 30-1991
1
Summary of unadjusted test resistances:
.. ...........................0.0007361
inside film .... Trial EMTD =
(149.0 - 95.0) - (168.0 - 140.02)
inside fouling ..............................0.0010000 In -
54.0
outside fouling.. ...........................O.OOOOOOO 27.98
. . .............................0.0000672
prime wall . .
bond .... ... ............................. 0.0000100
. .
fin root wall.. ..............................0.0000529 X 0.99 = 39.18"F
air film .....................................0.0065266
Z R = 0.0083928
Adjusted inside film resistance:
c=IBR
0.8
E)1R"(
213
NOTE: The value of w" in this calculation is the test air flow rate
adjusted for heat balance.
Q' = t117.16) (1206) (39.18) = 5,535,960 Btulhr
Adjusted test air film resistance: Trial No. 2: assume W + = 290,000 Ibm/hr
= 5,510,000 Btulhr
55
Copyrighted material licensed to Stanford University by Thomson Scientific (www.techstreet.com), downloaded on Oct-05-2010 by Stanford University User. No further reproduction or distribution is permitted. Uncontrolled w
PTC ASME 30-1991 EXCHANGERS HEAT AIR COOLED
1
(149.0 - 95.0) -
(168.0 - 140.33)
Trial EMTD =
54.00 Adjusted ZR = 0.008531 3
In -
27.67
Adjusted R: = 0.0007361
Q' = (117.22) (1206) (38.98) = 5,510,498 Btu/hr
Adjusted XR = 0.008531
4 , By interpolation, W + = 290,022 Ibm/hr
-)
Trial No. 3: assume W + = 290,022 Ibm/hr
LIP' '(^^
t.8
Q+ = (290,022) (1.00) (19.0) = 5,510,513 Btu/hr Af,' = p w = 6.8( 285,000 = 7.16 psi
56
Copyrighted material licensed to Stanford University by Thomson Scientific (www.techstreet.com), downloaded on Oct-05-2010 by Stanford University User. No further reproduction or distribution is permitted. Uncontrolled w
AIR COOLED HEAT EXCHANGERS ASME PTC 30-1991
57
Copyrighted material licensed to Stanford University by Thomson Scientific (www.techstreet.com), downloaded on Oct-05-2010 by Stanford University User. No further reproduction or distribution is permitted. Uncontrolled wh
ASME PTC 30-1991 AIR COOLED HEAT EXCHANGERS
R, + R,' + R: + 0.0011301
i Q;
(C.3)
" = A, x EMTD"
1
(C.12)
(C.13)
R Z = u 1p -
0.001 8662 (C.4)
R', = E($) (C.6) inating all constants andall calculated parameters. All
design values are considered constants for the pur-
pose of the uncertainty analysis.
Q', = W' X c*,,~(T: -T:) (C.7) In reviewing the remaining parameters, it is .nec-
essary to ascertain if all of these parameters are, in
fact, independent. To do this, it is necessary to review
the calculations andcorrections, if any, that were
used in determining these values. In this case, the air
flow rate, wo, is found not to be an independent pa-
rameter. The air flow rate was determined by a ve-
locity traverse at the discharge of each of the fans;
however, by agreement, the mass flow rate of the air
wasbased on a heat balance calculation for use in
(7: - t:) - (7: - t') computing the test results. The equation for this com-
EMTD' = 0.99 X (C.10) putation was
0.8
58
Copyrighted material licensed to Stanford University by Thomson Scientific (www.techstreet.com), downloaded on Oct-05-2010 by Stanford University User. No further reproduction or distribution is permitted. Uncontrolled w
AIR COOLED HEAT EXCHANGERS ASME PTC 30-1991
(C.16)
rameters listed in TablesC.2 and C.3are the result
of propagating all the identifiable elemental error
sources. These values are provided for example pur-
poses only. The actual bias andprecision error values
In this case, there is a convenient mathematical are dependent on the particular ACHEtested, the
relationship between the result, AP;, and the inde- 'number and type of instruments, the calibration pro-
pendent parameters, AP," and W'. The absolute (di- cedures used, the length of the test, the constancy of
mensional) sensitivity factors, ej , are determined by the test conditions, andthe ambient conditions at the
partial differentiation of Eq. (C.16) by time of the test.
59
Copyrighted material licensed to Stanford University by Thomson Scientific (www.techstreet.com), downloaded on Oct-05-2010 by Stanford University User. No further reproduction or distribution is permitted. Uncontrolled wh
I-
4
I 9'PtSOGZ 8'60S68Z O'LOLLBZ 9'LC626Z S'LL 1662 6'EL018Z Z'OEPCBZ 9'2LS96Z L'ZZOOGZ (EL 'b3) .M
8OL&LLL ZBEO'LLL OSEO'9LL SOOP'8LL LPOE'LZL 686L'ELL P988'PLL 9LLZ'LLL ESZS'6LL (ZL :n
8OLOOO.O OLL000'0 60L0000 60L000'0 Z690000 LZL000.0 ZZL000'0 969000'0 60L000'0 (LC W !O
cr
6
8LELE'SP P829E'SP PLSEE'SP L86EE'SP S6LtS'SP E56ZL'EP 09LLS'SP EPO9L'Et OSLCE'SP (8-53) 3V
'8LL6LSS '9890099 'EEOSEPS 'SL8S9SS V
' f
X X89S 'S9Z60ES '088PE9S 'SLLS8ES
'LZPOLSS (L 'b3) ,"O
9PLS062 8'609681 ULOLLBZ S'LE6Z6Z S'LLL66Z 6'CLOL8Z Z'OCPCBZ 9ZLS961 L'ZZ006Z (ssaw) +M
189900'0 ZOL900'0 8LL900'0 909900'0 LZP9000 9L69000 6CE900'0 LS89000
1699000 (9 W !H
Z'660EOS Z'Z6696P 2'99800S
P'ZCOLOG L'ESESLS 6'09988P 6'09988t L'ESESLE E'ZLOZOS (S .b?) +M
9ZS9000 9ZS9000 0199000 EPPSOO'O 608900'0 292900'0 (t 'b3)
9ZS900'0 LLE9000 289900'0 :O
L9SL.611 L9SL.611 LS96'LLL Z8PF'OZL E8LOOZL ZOPE'SLL €286'911 PLOE'LZL L991'6LL (E W 3
Z98C2'9E Z98EZ'gE Z98EZ'9E EOZPt'9E 09PE0'9C Z98E2'9E
P9PPE'9E 8POE6'
SE 9E
Z98C2' (z W .a~w3
009LOZS 009LOZE
PZESSLS 9L96EZS OOL9PCS 00L690S I 0016909 009LOZS 0019PES (1 'b3) o
: 8
~ ~~
9SS90'0 10990'0 BLEW0 8LS90'0 8Lf900 8LS900 8LE900 8,390'0 8LS90'0 ZZ9900 (EU191Yd
ELZPZ'O LZtZ'O 1LZPZ'O 1LZPZ'O 1LZPZ'O 1LZPZ'O 1LZPZ'O 1LZPZ'O L LZPZ'O #do
9EL000'0 9EL0000 9CL000'0 9ELMx)'O SELM)O'O 9EL0000 9CLOoo'O 9EL0000
9EL000.0 . VN &I
091 09 1 091 091 09L 091 S'GSL 5.09 1 09 L 891 (J.)bl
... ... ... ... ... ... ... ...
%
... 902 L ,lI"V
0
OMP + SIP - LIP -
k 08P - 00P+ . oMP- SIP + L I P+ lSel . U6lSea slelelu8J8d )UepUedepUl
TABLE C.Ib ern
SENSITIVITY FACTORS FOR UNCERTAINTY ANALYSIS 0
0
Independent Parameters Design I Test I + dT: I -dT: 1 +dWBTt I -dWBTt 1 +dl; I - di; I +dHpo I -dHpo Prn
A..ftz 1206 I ... ... ... ... ... ... ... ... ... U
TY'V 168 160 160 160 160 160 160 160 160 160
7-2" F) 14p 141.2 141.2 141.2 141.2 141.2 141.2 141.2 141.2 141.2
Wllbrnlhr) 285000 '277000 277000 277000 277000
277000
277000 277000
277000
277000
%Cap.
(Eq. 14) 100.8907 102.6497 101.7386
101.7621 101.7844
101.7778 100.5392 101.7321
103.0533
dCap [Note (l)] 0.887597 -0.87142 0,015675 -0.02349 0.022291 -0.03004 - 1.22294 1.291174
dCapldX 1.775195 1.742840 0.031350 0.044582 0.060088
0.046999 - 2.44589 - 2.58234 s0
dCap/dx)avg 1,759017 0.0391 75 0.052335 - 2.51412
dCaoldT: dCapldWBT; dCaDldt: dCaoldHD"
NOTE:
(1) dCap = (%Cap- %Cap at Test Measured Conditions)
Copyrighted material licensed to Stanford University by Thomson Scientific (www.techstreet.com), downloaded on Oct-05-2010 by Stanford University User. No further reproduction or distribution is permitted. Uncontrolled wh
Copyrighted material licensed to Stanford University by Thomson Scientific (www.techstreet.com), downloaded on Oct-05-2010 by Stanford University User. No further reproduction or distribution is permitted. Uncontrolled wh
PTC ASME
TABLE C.2
ERROR ESTIMATEVALUES FOR CAPABILITY
Bias limit Precision
Index
Degrees of Freedom
Sensitivity
Factors
Parameter (Si 1 (Si 1 ($4 (e) (Note (111
G 59 0.05 0.006 4.61 14
c 0.10 0.013 58 6.3521
w 2.5 0.25 59 1.0229
58 0.63 c 0.25
WBT 58 0.25 0.50 0.0392
e 56 0.3 0.47 0.0523
hP” 0.2 ’ 0.08 7. 2.5141
B“ 0.01 0.01 2 3 1.7629
NOTE:
(1) Reported from Tables C.l a and C.l b.
C.5 PROPAGATETHEPRECISION AND BIAS Evaluating Eq. (C.18)with the values in Table C.2,
ERRORS
Siq : (4.61 X 140.006)l =
0.000766
C.5.1 Capability. The bias limit of the result, Bicap,
is computed using the equation Si, : (6.3521 X 0.013)’ =0.006819
Si, : (1.0299 x 0.25)’ =0.066293
Siq : (1.7590 X 0.63)’ =
1.228041
SiwBq: (0.0392X 0.50)’ = 0.000384
Si5 : (0.0523x 0.4712= 0.000604
Sihp. : (2.5141 x 0.08)’= 0.040452
Si, : (1.7629 X 0.012)’ = 0.000448
Evaluating Eq. (C.17) with the values in Table C.2,
ZSi’ = 1.343807
Bi, : (4.61 14X 0.05)’ = 0.053163
Si,,, = 1.1592
Bi, : (6.3521 x 0.10)’= 0.403492
Bi, : (1.0299 X 2.5)’ = 6.629338 Since not all the degrees of freedom given in Table
Biq : (1.7590X 0.25)’ = 0.193380 C.2 are greater than 30, the degrees of freedom for
BiWBq : (0.0392x 0.25)’ = 0.000096 the result,vcap,are computed according to the Welch-
Bi5 : (0.0523 X 0.3)’ = 0.000246 Satterthwaite formulas, as
Bi,, : (2.5141 X 0.2)’ = 0.252828
Si, : (1.7629X 0.01)’= 0.000311
ZBi’ = 7.532854
Si,,, = 2.745 vcap = #I9)
(C.
62
Copyrighted material licensed to Stanford University by Thomson Scientific (www.techstreet.com), downloaded on Oct-05-2010 by Stanford University User. No further reproduction or distribution is permitted. Uncontrolled w
AIR HEAT EXCHANGERS ASME PTC 30-1991
TABLE C.3
ERROR ESTIMATEVALUES FOR CAPABILITY
Bias Limit
Precision
Index
Degrees of Freedom
Sensitivity
Factors
Parameter (Bi ) (Si 1 (4 (e)
w 2.5 1.7 59 1
Ac 0.05 0.063 11 1.8
E= 0.02631
I-1 3
1.8058 69
vaP= -
0.02631 =
Evaluating Eq. (C.21) with the values in Table C.3,
Siu+ = 0.0238
v + =
-+-P
(1 x 0.01 7," +
(1.8X e)4 = 38
59 11
From Appendix B,
C.6 OVERALLUNCERTAINTYVALUES
AP; = 6.8 psi
The overall uncertainty in the result for a 95 per-
APp = 7.16 psi cent coverage, U ~ I , ~ ~by,
is defined
63
Copyrighted material licensed to Stanford University by Thomson Scientific (www.techstreet.com), downloaded on Oct-05-2010 by Stanford University User. No further reproduction or distribution is permitted. Uncontrolled wh
30-1991 ASME PTC AIR COOLED HEAT EXCHANGERS
TABLE C.4
TWO-TAILED STUDENT-t TABLE FOR THE 95 PERCENT CONFIDENCE LEVEL
Degrees of Degrees of
Freedom t Freedom t
1 12.706 16 2.120
2 4.303 17 2.1 10
3 3.182 18 2.101
4 2.776 19 2.093
5 2.571 20 2.086
6 2.447 21 2.080
7 2.365 22 2.074
8 2.306 23 2.069
9 2.262 24 2.064
10 2.228 25 2.060
11 2.201 26 2.056
12 2.1 79 27 2.052
2.160 13 28 2.048
14 2.145 29 2.045
15 2.1 31 30 or more use 2.0
GENERAL NOTE: Table gives values of t such that from -t to + t the area included is 95%.
and,
64
Copyrighted material licensed to Stanford University by Thomson Scientific (www.techstreet.com), downloaded on Oct-05-2010 by Stanford University User. No further reproduction or distribution is permitted. Uncontrolled wh
\
APPENDIX D
SPECIAL CONSIDERATIONS FOR COMPUTATION AND
ADJUSTMENT OF RESULTS
65
Copyrighted material licensed to Stanford University by Thomson Scientific (www.techstreet.com), downloaded on Oct-05-2010 by Stanford University User. No further reproduction or distribution is permitted. Uncontrolled w
AIR COOLED HEAT EXCHANGERS
Q
i
7 Q
a
II
ai
.
e
c
I
66
ASME PTC 30-1991
Copyrighted material licensed to Stanford University by Thomson Scientific (www.techstreet.com), downloaded on Oct-05-2010 by Stanford University User. No further reproduction or distribution is permitted. Uncontrolled wh
AIR COOLED HEAT EXCHANGERS ASME PTC 30-1991
The total tube-side pressure drop i s the sum of APf For fully developed turbulent flow (Re, > approx-
and Af,,,. Nozzle and header losses may need to be imately 7,000), there areseveral good correlations
separately considered. available. For general use, the Petukhov-Popov equa-
The properties used in these equations and those tion, Eq. (D.6), (Ref.[131), is regarded as the most
in the following paragraphs are usually evaluated at accurate but it is not in convenient form for ratioing
the arithmetic mean bulk temperature on the tube changes in velocity, for example,
side, except for P,,~, which is evaluated at the inside
wall temperature atthe point where the fluid reaches
its arithmetic mean bulk temperature.
(y ))(:
more convenient for adjustments of tube side con-
ditions:
0,0668(?)
3.65 +
1+0.04[ (Y)(y)(?)]
Forwater,Figs.D.2a and D.2b taken from Kern
(Ref. [141), are very easy to use.FiguresD.2aand
D.2b may be represented by the following dimen-
sional equation:
67
Copyrighted material licensed to Stanford University by Thomson Scientific (www.techstreet.com), downloaded on Oct-05-2010 by Stanford University User. No further reproduction or distribution is permitted. Uncontrolled wh
ASME PTC 30-1991 AIR COOLED HEAT EXCHANGERS
For transition flow (2100 < Re, < 7,000), no ac- vapor with no liquid presenthas a quality of 1.00,
curate predictions are possible because of the slow- and a totally condensed stream atits boiling point or
ness with which fully-developed velocity and thermal bubble point has a quality of zero.
profiles are achieved and because of the strong effect Estimates can be made of the frictional loss using
of the entrance flow geometry. An estimate can be the work of Martinelli andNelson(Ref. [IS]). The
made by linearly interpolating between the laminar frictional pressure drop through the tube for the con-
flow heat transfer coefficient,hi,L, obtained from Eq. densing flow entering as a saturated vapor(x, = 1.O),
(D.5) and the turbulent flow result, hi,, , obtained and exiting at a quality ofx, is found from
from Eq. (D.6) or (D.7), using the equation:
hi = FeL+ (hi,, -
- 2100
6&I( Rei49oo ) where TPF indicates two-phase flow and APp,v is the
pressuredropcalculated from Eq. (D.1) assuming
that theflow is all vapor and no condensation occurs.
for 2 100 < Re, e 7000 (D.9) The mean two-phase multipyingfactor, pv,,, is read
from Fig. D.3 as a function of the exit quality and the
reduced pressure of the vapor,
Any calculation in this range must beregarded as 1
highly uncertain.
P, = -P (D.11)
PC7
68
Copyrighted material licensed to Stanford University by Thomson Scientific (www.techstreet.com), downloaded on Oct-05-2010 by Stanford University User. No further reproduction or distribution is permitted. Uncontrolled w
AIR COOLED HEAT EXCHANGERS ASME PTC 30-1991
GENERAL NOTE: This chart applies only to a tube 0.62 inside diameter (e.g., 3/4 in. X 16 BWG).
For other diameters, refer to Fig. D.2b.
69
Copyrighted material licensed to Stanford University by Thomson Scientific (www.techstreet.com), downloaded on Oct-05-2010 by Stanford University User. No further reproduction or distribution is permitted. Uncontrolled wh
ASME PTC 30-1991 AIR COOLED HEAT EXCHANGERS
GENERAL NOTE: Multiply the value obtained from Fig. D.2a by the above factor.
r 7114
70
Copyrighted material licensed to Stanford University by Thomson Scientific (www.techstreet.com), downloaded on Oct-05-2010 by Stanford University User. No further reproduction or distribution is permitted. Uncontrolled wh
AIR COOLED HEAT EXCHANGERS ASME PTC 30-1991
where x, and x, are the inlet and exit qualities of the where Pr,,p = cp~t,pcL1*p
71
Copyrighted material licensed to Stanford University by Thomson Scientific (www.techstreet.com), downloaded on Oct-05-2010 by Stanford University User. No further reproduction or distribution is permitted. Uncontrolled wh
AIR COOLED HEAT EXCHANGERS
a
-
8
0
Q
II
72
-
-
a
9
8
0
Q
I1
ASME PTC 30-1991
Copyrighted material licensed to Stanford University by Thomson Scientific (www.techstreet.com), downloaded on Oct-05-2010 by Stanford University User. No further reproduction or distribution is permitted. Uncontrolled wh
AJR COOLED HEAT EXCHANGERS ASME PTC 30-1991
1 .oo
0.95
0.90
0.85
0.80
P
0.75
0.70
0.65
0.60,
0 0.5 1.0 1.5 2.0 2.5 3.0
~l,,,, radians
coefficient, and constant saturation temperature, is sure existing in the vapor space. In this case, it has
given by: been shown that the above-referenced equationsfor
condensing a saturated vapor adequately predict the
EMTD = LMTD = If , (D.17) heat transfer rate on the vapor side, if the saturation
temperature of the vapor is used as the process fluid
temperature in Eq. (D.17). It is necessary to include
in the heat load the sensible heat of cooling the va-
where T,,, is the saturation temperature of the con- por,even though its temperature is ignored in cal-
densing vapor. culating the EMTD.
If the surface is above the saturation temperature,
The EMTD under'these conditions is independent
the vapor will cool sensibly by the usual single phase
of flow arrangement. It should be noted that in fact
convectiveprocess until it reaches atemperature
the local condensing coefficients do vary with local
such that the wall does become wet. In principle, it
quality, but the effect on the overall coefficient i s
is only necessary to follow the cooling of the vapor
ordinarily small. Consideration of these effects is in
and the wall temperature until the wall reaches sat-
any case beyond the scope of this document.
uration temperature and then follow the procedure
given in the previous paragraph.
D.3.5 Superheated Vapors. A superheatedvapor However, such local vapor cooling calculations are
will condense directly from the superheated stateon tedious because the vapor temperature changes
a surfacethat is even slightly (perhaps 0.01 O F ) below along each tube and the airtemperature changes
the saturation temperature of the vapor at the pres- across each row of tubes as well as along each tube.
73
Copyrighted material licensed to Stanford University by Thomson Scientific (www.techstreet.com), downloaded on Oct-05-2010 by Stanford University User. No further reproduction or distribution is permitted. Uncontrolled w
AIR COOLED HEAT EXCHANGERS
74
ASME PTC 30-1991
Copyrighted material licensed to Stanford University by Thomson Scientific (www.techstreet.com), downloaded on Oct-05-2010 by Stanford University User. No further reproduction or distribution is permitted. Uncontrolled wh
AIR HEAT EXCHANGERS ASME PTC 30-1991
Reference [22] shows that the heat transfer flux for These calculations require vapor-liquid equilibrium
cooling a superheated vapormust be higher than the and enthalpy calculations that are usually computer-
condensing flux if the wall is to remain dry. Therefore, based andsupplied by the customer. Beforeany con-
if it i s assumed that the vapor is desuperheating in clusions can be drawn about the performance of the
the wet wall regime from the start (using the simple condenser, mutual agreement must be reached be-
procedure given in the first paragraph), the area cal- tween customer and vendor on the validity of these
culated to be required will either be correct (if the calculations.
wall is wet even at the vapor entrance)or conservative (b) Sensible heat transfer effects (i.e., cooling of
(if some portion of the wall is in fact dry). The term the vapor-gas mixture) are always present in multi-
correct means that the calculated area is as close to component condensation in both the vapor-gas and
that actually required as the validity of the correla- liquid phases. The cooling of the vapor-gas mixture
tions permits; conservative means that the calculated tends to be an important and often controlling part
area is larger than would be obtained by a detailed of the heat transfer process.
local calculation. (c) Mass transfer effectsare always present in mul-
ticomponent condensation. These processes areonly
poorly understood and must be treated in a fairly
0.3.6 Subcooling of Condensate. When subcooled arbitrary manner. The specific problem of a single
condensate is required, it is customary to design the condensable vapor with a noncondensable'gas can
condenser so that the bottom row or rows of tubes, be handled with some rigor as shown in Ref. [231.
disposed in one or more passes, run full of conden- (d) Physical properties change in bothphases, both
sate. The liquid phase heat transfercoefficient can be as a result of changing compositions and changing
calculated using the correlations given in para.D.2 temperatures.
and the heat transfer rateby using a corrected LMTD, Usually, careful analysis of multicomponent con-
the correction factors being given in para. 5.5 for the densation problems (which may include noncon-
appropriate pass arrangement. densable gases) requires zone-by-zone analysison a
The averageair temperature leavingthe subcooling computer. However, if the condensing temperature
section can be calculated by a heat balance. Without range is relatively small compared to the mean tem-
going to a zone-by-zone analysis (which requires a perature difference,or if only a smallamount of con-
computer program for all practical purposes), it is densate is formed, approximate calculations of
sufficient accuracy may be possible (Ref. 1241).
necessary to assume that the average air temperature
In these cases, the heattransferprocess on the
off of the subcooling rows is equivalent to a uniform
tube side may be considered to consist of two re-
inlet air temperature to the condensing rows. This is
sistances in series:
of course not the case, and it is usually somewhat
(7) Sensible heat transfer from the vapor-gas mix-
nonconservative to assume so. In analyzing the per-
ture to the condensate interface,with a typical vapor-
formance of an existing unit, this factor can be taken
phase heattransfer coefficient h,, calculated from the
into account qualitatively without agreatdeal of
correlations in para. D.2, and,
computation.
(2) Convection of the sensible heatfrom (11 above
and the latent heat released by condensation at the
interface through the condensate layer, with a con-
densing heat transfercoefficient hi,=.
A combined coefficient for these two processes on
D.4 MULTICOMPONENT CONDENSATION,
the condensing side, hi, may be calculated by Eq.
INCLUDING NONCONDENSABLE GASES
(D.18a)
There are several specialproblems associated with
the condensation of a multicomponent mixture or a 1
h, = 0 . 1 8a)
vapor containing a noncondensablegas. Among them z 1
are the following: -+-
hi,, hi,=
(a) It is necessary for accuratedesign to have a
condensing curve for the mixture;
condensing
a where
curve gives the temperature of the condensing mix-
ture and the fraction of the flow that has been con- Z= Q," (D.18b)
densed as a function of the amount of heat removed. Q,, + Qt + Qsr
75
Copyrighted material licensed to Stanford University by Thomson Scientific (www.techstreet.com), downloaded on Oct-05-2010 by Stanford University User. No further reproduction or distribution is permitted. Uncontrolled wh
ASME PTC 30-1991 AIR COOLED HEAT EXCHANGERS
Q,, is the heat duty required to cool thevapor-gas (c) Reduction in number of tubes in successive
mixture: passes in condensing(andsometimessubcooling)
service in order to maintain high vapor velocity and
condensing coefficients. Note however that uniform
distribution of the two phases among the tubes in
later passes can not be expected, and this can lead
to excessive subcooling in sometubesand incom-
Q, is the heat duty required forcondensation: plete condensation in others.
(0') Multiple servicesmaybe handled in a single
Q, = h W p , c o n d (D.18d) unit, usually with the sections in parallel on the air
flow (side-by-sidein the frame). Different tube sizes
and number of rows may be used in each section.
(e) A single row of tubes may be split between two
Q,, is the heat duty required for cooling the con- passes in order to obtain the same number of tubes
densate: in each pass, e.g., two passes in five rows of tubes.
(0 A row of tubes may contain asingle tube (or at
(0.18e) most a few tubes) servingas a vent condenser off of
an air removal point and having a different inlet and
outlet header connection.
Thermal analysisof types a, b, and c can be carried
-
Wp,, and W,,, are the average weight flow rates of out by a procedure similarto that suggested for sub-
vapor and condensatein the condensing process, and cooling sections above, and with the same caution
Wp,condis the amount of vapor actually condensed. upon assumingthe airinlet temperature to the upper
rows of tubes to be uniform.
Type d can be analyzed straightforwardly for each
section if the air flow and exit air temperature for
D.5 UNUSUAL PASS ARRANGEMENTS each section are measured.
Type e can be analyzedreasonablyclosely by
For avariety of reasons,unusualpassarrange-
straightforward methods, using the actual number of
ments of various kinds are often used in air cooled
tubes in each pass for tube-side calculations andig-
exchangers. The following examples may be cited:
noring the usually slight imbalance in the air tem-
(a) Reduction in number of tubes in successive
perature profile caused by the split pass or passes.
passes,used in cooling viscous liquids in order to
Type f poses no serious problems on the air side
increase thevelocity andmaintainturbulent flow
since only a fewtubes are involved. The analysis in-
conditions.
side the tube can be carried out by the methods of
(b) Using enhancement devices in one or more of
para. D.4 or Ref. 1231.
the last passes for the same purpose.
76
Copyrighted material licensed to Stanford University by Thomson Scientific (www.techstreet.com), downloaded on Oct-05-2010 by Stanford University User. No further reproduction or distribution is permitted. Uncontrolled w
AIR COOLED HEAT EXCHANGERS ASME PTC 30-1991
APPENDIX E - FOULING
E.l Theexchangerdesigner incorporatesaheat should preferably be performed in the clean condition
transfer fouling resistance to account for the accu- on both air-side and tube-side to minimize the effects
mulations of layers of resistive material on the heat of fouling dnce fouling cannot be reliably predicted.
transfer surfacesas the exchanger operates. Thefoul- The fouling resistances used to interpret the test re-
ing resistance is also known as fouling factor, dirt fac- sults shall be agreed upon by the parties to the test
tor, and dirt film. The fouling resistance occurs on prior to the start of the test, see para. 3.2(j).
both the air-side and the process-side heat transfer
surfaces. Unfortunately, the existing technology does
not provide a dependable analytical method for ac- E.3 The influence of fouling on the overall heat trans-
curate predictionof fouling. The purchaser normally fer coefficientwill vary according to the relativemag-
depends on experience in similar services to select nitudes of the fouling resistances and the clean heat
and specify the design fouling resistances. transferresistances.Forexample, aclosed-circuit
treated water cooler might have a low tube-side foul-
ing resistance of 0.0005 hr4tz*"F/Btu referencedto the
E.2 Fouling presentduring the test affects the air-side inside surface. Thismight be approximately5 percent
and process-side heat transfer coefficients and flow of the total heat transfer resistance. In comparison,
pressure drops. Fouling of the air-side surface may this resistance for a heavy oil cooler might be 0.003
occur from the deposition of air-borne materials such hr-ftz-OF/Btu which might be over 20 percent of the
as dust, organic material, seeds, and insects, or from total heat transfer resistance, making a clean condi-
corrosion. It is impossible to accurately predict the tion for testing relatively more important.
effect of such deposits and they must be removed
prior to testing. Fouling of the inside surface of the
tubes is dependent upon the fouling and corrosion E.4 For additional information on fouling the reader
characteristics of the fluid in the tubes.Testing may refer to Ref. [25].
77
Copyrighted material licensed to Stanford University by Thomson Scientific (www.techstreet.com), downloaded on Oct-05-2010 by Stanford University User. No further reproduction or distribution is permitted. Uncontrolled w
AIR COOLED HEAT EXCHANGERS ASME PTC 30-1991
79
Copyrighted material licensed to Stanford University by Thomson Scientific (www.techstreet.com), downloaded on Oct-05-2010 by Stanford University User. No further reproduction or distribution is permitted. Uncontrolled w
AIR COOLED HEAT EXCHANGERS ASME PTC 30-1991
APPENDIX C REFERENCES
[l I Field Testing of Air-Cooled Heat Exchangers, [141Kern, D. Q., Process Heat Transfer, McGraw-Hill
Chemical Engineering Progress, July 1960. Book Company, New York (1 950).
[2]Flow of Fluids Through Valves,Fittings, and Pipe [15]Martinelli, R. C., and Nelson, D. B., Trans. ASME
- Crane Co., Technical Paper No. 41 0,1978. 70,695, (1948).
[3]Fundamentals of Pipe Flow, R. P. Benedict, Wiley, [161 Nusselt,W., Zeits. VDI 60, 541, 569 (1916).
1980. Also cited in Refs. 161 and [91.
141 Sieder, E. N., and Tate, G. E., Ind. Eng.Chem., [17] Chaddock, J. B., Refrig.Eng. 65, No. 4, 36
28, 1429 (1936). (1 957).
151 Briggs, D. E., and Young, E. H., Convection Heat [181 Boyko, L. D., and Kruzhilin, G. N., Int. J. Heat
Transfer and Pressure Drop of Air Flowing Across Tri- Mass Trfr. 70, 361 (1967).
angular Pitch Banks o f Finned Tubes,AIChE, August [191Traviss, D. P., Baron, A. B., and Rohsenow, W.
1962. M., MIT Rept. No. DSR 72591-74 (1971).
161 Ward, D. J., and Young, E. H., Heat Transfer and [201Colburn, A. P., Trans. AlChE 30, 170 (1 934).
Pressure Drop of Air in Forced ConvectionAcross Tri-
angular Pitch Banks o f Finned Tubes, Chemical Engi- [21]Nilsson, S. N., Paper 2.32, Proc. Xlll Int. Cong.
neering Symposium Series No. 29, Vol. 55, 1959. Refrig., Washington, DC (1 9711.
[7]Gardner, K. A., Efficiency o f Extended Surface, [221Bell, K. J., Chem. Eng. Prog. 68, No. 7,81 (1 972).
ASME Transactions Paper 1945, Vol. 67. [23]Colburn, A. P., and Hougen, 0. A., Ind. Eng.
[8]Moody, L. F., Trans.ASME 66, 671 (1944). Chem. 26, 1 1 86, (1 934).
[9]Blasius, H., Forschg. Arb. Ing -Wes. No. 131, Ber- [24]Bell, K.J., and Ghaly, M.A., AlChE Symp. Series
lin (191 3).Cited in Schlicting, H., Boundary Layer 69, NO. 131, 72-79 (1 972).
Theory, 7th ed., McGraw-Hill Book Co., New York [251Kakac, S., Bergles, A.E., and Mayinger, G., Heat
(1 979). Exchangers: Thermal-Hydraulic Fundamentalsand De-
[lo]Shah, R. K., and London, A. L., Advances in Heat sign, McGraw-Hill, and Hemisphere Publishing Corp.
Transfer, Supplement 1: Laminar Flow Forced Convec- (1 1.981
tion in Ducts, Academic Press, New York (1978). 1261 Tubular Exchanger Manufacturers Association,
[ll] Hausen, H., VDlZ Beih.Verfahrenstech. 4. 91 Standards of TEMA, latest edition.
(1943).Cited in Ref. [12]. 1271 Cunter, A. Y., and Shipes, K. V., "Hot Air Recir-
[I21Jakob, M., Heat Transfer, J. W. Wiley and Sons, culation by Air Coolers,"AlChE Twelfth National
New York, Vol. 1 (1949). Heat Transfer Conference, AIChE-ASME, Tulsa,Okla-
homa, August 15-1 8, 1971.
[I31 Petukhov, B. S., and Popov, V. N., Teplofiz. Vy-
sok. Temperature 7, No. 1 (1963).Also discussed by [281 Collins, G. F., and Mathews, R. T., "Climatic
B. S. Petukhov in Advances In Heat Transfer, Vol. 6, Considerations in Design of Air Cooled Heat Exchan-
Hartnett, J. P., and Irvine, T. F., Jr. Eds., Academic gers,"Paper 59-A-255,December 4, 1959, Annual
Press, New York (1 970). Meeting ASME.
81
Copyrighted material licensed to Stanford University by Thomson Scientific (www.techstreet.com), downloaded on Oct-05-2010 by Stanford University User. No further reproduction or distribution is permitted. Uncontrolled w
ASME PTC 30-1991 AIR COOLED HEAT EXCHANGERS
[29] CoolingTower InstituteTechnical Subcommittee [34] Haldridge, E. S., and Reed, B. H., “Pressure Dis-
No. 2: “Recirculation,” CT
I Bulletin PFM-l%lO,1958. tribution on Buildings,” Department of Army, Con-
Also PFM-11OA, Appendix to PFM-110. tract No. DA-18-064CML77,August1956, Texas
Engineering Experiment Station, Texas A & M.
I301Schmidt, W., “Calculations of Distribution of
Smokeand
Waste
Gases in the Atmosphere,” [351 Haldridge, E. S., and Reed, B. H., “Pressure Dis-
-
Gesundheits Ing. Vol 49, 1926, pp. 425-426. tribution on Buildings-Report No. 2,” Department of
Army,Contract No. DA-18-064 CML77, August
[31] Sutton, 0. G.,“A Theory of Eddy Diffusion in 1956,
Texas
Engineering
Experiment
Station,
the Atmosphere,” Proc. Roy. Society (London) Ser. A
Texas A & M.
VOI. 135, 1932, pp. 143-165.
1361Kosten, C. J., Morgan, 1..I., Burns, J. M., and
[32] Bailey, A., and Vincent, N. D. G., “Wind Pressure Curlett, P. L., “Operating ExperienceandPerform-
on Building IncludingEffects on Adjacent Building,” anceTesting of the Worlds Largest AirCooled
Journal Institution of Civil Engineer, March 1943, Condenser,” April 27-29,1981,AmericanPower
pp. 243-275. Conference, Chicago, Illinois.
[331 Dryden, H. L., and Hill, C . C., “Wind Pressures
on Structures,” Scientific Papers of Bureau of Stan-
dards, Vol. 20, 1926, p. 697.
82
Copyrighted material licensed to Stanford University by Thomson Scientific (www.techstreet.com), downloaded on Oct-05-2010 by Stanford University User. No further reproduction or distribution is permitted. Uncontrolled w
COMPLETE LISTING OF ASME PERFORMANCE TEST CODES