Air System Sizing Summary for Cantine

Project Name: BATIMENT2 10/02/2022


Prepared by: ingenios 01:32

Air System Information


Air System Name: Cantine Number of zones: 1
Air System Type: Single Zone CAV Floor Area: 268,0 sqm
Location: Abidjan, Ivory Coast

Sizing Calculation Information


Calculation Months: Jan to Dec Calculation method: Transfer Function Method

Central Cooling Coil Sizing Data


Total coil load: 109,4 kW Load occurs at: Aug 1500
Total coil load: 109,4 kW OA DB / WB: 32,8/28,3
Sensible coil load: 53,0 kW Entering DB / WB: 26,6/22,6
Coil airflow: 3931 L/s Leaving DB / WB: 15,4/15,3
Sensible heat ratio: 0,484 Coil ADP: 14,8 C
Area per unit load: 2,5 sqm/kW Bypass Factor: 0,050
Load per unit area: 408,0 W/sqm Resulting RH: 66 %
Design supply temp: 15,0 C

Central Heating Coil Sizing Data


Max coil load: 3,3 kW Load occurs at: Des Htg
Coil airflow: 3931 L/s Ent DB / Lvg DB: 20,3/21,0
Load per unit area: 12,2 W/sqm

Supply Fan Sizing Data


Actual max airflow: 3931 L/s Fan motor BHP: 0,00 BHP
Standard airflow: 3922 L/s Fan motor kW: 0,00 kW
Actual max airflow per unit area: 14,67 L/(s-sqm) Fan static: 0,00 Pa

Outdoor Ventilation Air Data


Design airflow: 1416 L/s Airflow per person: 4,72 L/s/person
Airflow per unit floor area: 5,28 L/(s-sqm)

Space Sizing Data

Space Name Maximum Design Time of Peak Maximum Space Space


Cooling Airflow Load Heating Floor L/(s-sqm)
Sensible kW L/s Load kW Area
sqm
Cantine 37,9 3931 Aug 1700 1,2 268,0 14,67

Block Load 4.15 Page 1 of 3


System Design Load Summary for Cantine
Project Name: BATIMENT2 10/02/2022
Prepared by: ingenios 01:32

DESIGN COOLING DESIGN HEATING


Aug 1500 Design Heating Day
OA DB / WB 32,8 C / 28,3 C OA DB / WB 19,4 C / 13,3 C
Zone Loads based on TFM Details Sensible W Latent W Details Sensible W Latent W
Window and Skylight Solar Loads 12 sqm 2395 - 12 sqm - -
Wall Transmission 220 sqm 3062 - 220 sqm 569 -
Roof Transmission 283 sqm 10281 - 283 sqm 621 -
Window Transmission 12 sqm 109 - 12 sqm 21 -
Skylight Transmission 0 sqm 0 - 0 sqm 0 -
Door Loads 4 sqm 53 - 4 sqm 10 -
Floor Transmission 283 sqm 0 - 283 sqm 0 -
Partitions/Ceilings 0 sqm 0 - 0 sqm 0 -
Overhead Lighting 536 W 536 - 0W 0 -
Electric Equipment 0W 0 - 0W 0 -
People 300 20222 10551 0 0 0
Infiltration - 0 0 - 0 0
Miscellaneous - 0 0 - 0 0
Safety Factor 0% / 0% 0 0 0% 0 0
>>Total Zone Loads - 36658 10551 - 1220 0
Thermostat and Pulldown Adjustment - -83 0 - -336 0
Plenum Wall Load 0% 0 - 0 0 -
Plenum Roof Load 0% 0 - 0 0 -
Plenum Lighting Load 0% 0 - 0 0 -
Ventilation Load 1416 L/s 16394 45831 1416 L/s 2377 0
Supply Fan Load 3931 L/s 0 - 3931 L/s 0 -
>> Total System Loads - 52968 56382 - 3261 0
Central Cooling Coil - 52968 56382 - 0 0
Central Heating Coil - 0 - - 3261 -
>> Total Coil Loads - 52968 56382 - 3261 0
Key: Positive values are clg loads Positive values are htg loads
Negative values are htg loads Negative values are clg loads

Block Load 4.15 Page 2 of 3


System PsychrometricsforCantine
Project Name: BATIMENT2 10/02/2022
Prepared by: ingenios 01:32

Location: Abidjan, Ivory Coast


Altitude: 19,8 m
Data for: Aug DESIGN COOLING DAY, 1500
0,025
1. Outdoor Air
2. Mixed Air
3.CentralCoolingCoilOutlet
4. Supply Fan Outlet
5. Room Air 1

0,020

Specific Humidity ( kg/kg )


2 0,015

5
4
3
0,010

0,005

0,000
0 10 20 30
Temperature (C)

Block Load 4.15 Page 3 of 3