High Speed Tripping Relay TR

Description Features
Type TR high speed tripping relays are a range of voltage • High speed, positive action
operated, multi-contact, attracted-armature relays, complying • Robust design for long, reliable service life
with the appropriate requirements of IEC 60255. A wide • Supplied in Epsilon draw-out type case
range of models is available to meet the requirements of the • Can be supplied both in E2 and E4 casing
electrical power sector.
The relays are identified by the product designation 'TR'
followed by a series of numbers and letters which define
important relay features.

Low Burden, TR1 Series


Type TR1 relays are suitable for application for tripping and
auxiliary duties where immunity to capacitance discharge
is not required. These relays are not intended for use with
current operated series flag relays.

High Burden, TR2 Series


High burden relays have immunity to capacitance discharge
currents. They are also suitable for certain applications where
they are remote from the initiation signal.
A high burden also permits reliable operation of current
operated series repeat relays.

Figure 1: High Speed Tripping Relay - TR


Standard Relays
Type First Digit Second Digit Third Digit No. of Contacts Case Size
(Type of Burden) (Contact Reset) (Operating Coil
Cut-off)
TR112 Low (1) Self (1) Economy (2) 11 E4
TR121 Low Hand (2) Instantaneous (1) 11 or 22 E2 / E4 *
TR212 High (2) Self Economy 10 or 20 E4
TR221 High Hand Instantaneous 11 or 22 E2 / E4 *
TR231 High Electrical (3) Instantaneous 10 or 20 E2 / E4 *
TR241 High Hand & Electrical (4) Instantaneous 10 or 20 E2 / E4 *

10 Year
WARRANTY

www.erlphase.com
Rll

28
-VE

RESET
SOLENOD
-VE
26

Figure 2: Typical wiring diagram for TR231 relay with 10 contacts

- - - - -
Rl R2 -VE

Rll

Figure 2: Typical wiring diagram for TR221 relay with 22 contacts

www.erlphase.com
Technical Information Environment IEC 60068-2-1 & 2

TR1 and TR2 series relays


Temperature
Storage - 25 C to + 70 C
Rated Voltage, Vn 24V, 30V, 48V, 110V, 220V DC
Operating - 10 C to + 55 C
Operating Range 50% to 120% of Vn
Operating Time 10 ms at Vn
Humidity IEC 60068-2-3
Operating coils of self-reset and economy cut-off relays are
rated at 120% of rated voltage. All other operate and reset 56 days at 95% RH and 40 C
coils are short time rated, well in excess of the operating time
of their cut off contacts. Self-reset relays will reset at not less
than 5% rated voltage. Vibration IEC 60255-21-1
Relay meets the requirements vibration of class 1 for
Nominal Burdens (Watts) response and endurance.

Rated Voltage TR1-- TR2--


24V DC 43 43 Shock and IEC 60255-21-2

30V DC 43 43 Bump
48V DC 46 52 Relay meets the requirements with respect to shock &
bump testing for class 1 severity.
110V DC 47 127
220V DC 52 150
Rest Coil 50 50 Transient IEC 60255-5

Relays with economy circuits reduce to approximately 7W. Over Voltage


5KV 1.2/50µs 0.5 joules between all terminals and earth, or
Contact Standard Arrangement between any two terminals without damage or flashover.

No. of Arrangement
contacts Insulation IEC 60255-5
10 10M0B, 9M1B, 8M2B, 7M3B, 6M4B, 5M5B, 2KV rms for 1 minute between all terminals and earth.
4M6B 1KV rms for 1 minute across normally open contacts
11 11M0B, 10M1B, 9M2B, 8M3B, 7M4B, 6M5B,
5M6B, 4M7B
Operational / Mechanical Life
20 20M0B, 18M2B, 16M4B, 12M8B, 10M10B,
8M12B The relays will withstand in excess of 10,000 operations,
within the maximum contact loading specified, at a rate of
22 22M0B,20M2B, 18M4B, 16M6B, 14M8B 600 operations per hour.

Contact Rating
Make and carry continuously
1250VA AC or 1250W DC with limits of 660V and 5A

Make and carry for 3 seconds


7500VA AC or 7500W DC with limits of 660V and 30A
Break
1250VA AC or 100W DC (resistive) or 50W DC (inductive)
(L/R=0.04) with limits of 250V and 5A
Maximum rate of operation: 600 per hour
Indication
TR 1 and TR2 relays have a hand reset mechanical flag
indicator

www.erlphase.com
Cutout Details Ordering Information
• Relay type
• Contact arrangement
• Coil voltage
• Case size

Quality Certifications
ISO 9001 – 2008
CE Compliant to relevant EU Directives

Note:
1. All dimensions are in mm
2. All dimensions are measured equidistant from centre line
3. Maximum depth of equipment inside panel : 225mm

The policy of EASUN REYROLLE is one of continuous improvement and development. The company therefore reserves the right to
supply equipment which may differ slightly from that described and illustrated in the publication.

ERLPhase Power Technologies


Tel: 204-477-0591
Email: info@erlphase.com
The specifications and product information contained in this document are subject to change without notice.
In case of inconsistencies between documents, the version at www.erlphase.com will be considered correct. (D04253)

www.erlphase.com