MCC2 Transformer Outgoing Feeder REF 611 Protection Curves
MCC2 Transformer Outgoing Feeder REF 611 Protection Curves
MCC2 Transformer Outgoing Feeder REF 611 Protection Curves
30 30
MV cable 3 SS_MVS_MCC2 - P
MV CABLE DAMAGE CURVE
3 - 1/C 300 mm²
10 10
LV CABLE 24 MCC2_MCC2LV - P
5 5
LV CABLE DAMAGE CURVE
Seconds
Seconds
6 - 1/C 240 mm² Copper XLPE
3 3
SS_MVS_MCC2_IED - P - 51
OC1
1 1
ABB MCC2_TX
REF 611 TRANSFORMER DAMAGE CURVE
.5 CT Ratio 100:5 0.63 MVA (Secondary) 2.5 %Z .5
IEC Very Inverse Delta-Wye Solid Grd
.3 Pickup = 0.43 (0.05 - 5 xCT Sec) .3
Time Dial = 0.86
3x = 5.81 s, 5x = 2.9 s, 8x = 1.66 s
.1 .1
Inrush
.03 .03
Multiplier = 8 xFLA (7274.613 Amps)
Duration = 6 Cycles
.01 .01
.5 1 3 5 10 30 50 100 300 500 1K 3K 5K 10K
SS_MVS-MCC2-CB
R
SS_MVS_MCC2_IED
MV cable 3 SS_MVS_MCC2
3-1/C 300
MCC2_TX_HV
MCC2_TX
0.63 MVA
MCC2_TX_LV
CABLE 24 MCC2_MCC2LV
6-1/C 240