HR Roof Air Water ASTM 1680 1646
HR Roof Air Water ASTM 1680 1646
Rendered to:
Rendered to:
Project Summary: Architectural Testing, Inc. was contracted by All Weather Insulated Panels
to perform testing on a 120" by 96" Hi Rib insulated metal roof system. The test specimen was
tested for Air/Water performance in accordance with the referenced test standards. This report
includes comprehensive written and photographic documentation of testing performed and a
copy of "As-Tested" drawings.
Series/Model: HR
Typical Construction: Typical Construction: The mock-up consisted of three (3) panels
measuring 96" long by 40" wide with one (1) panel cut in two pieces approximately 20" in
width mounted at each edge of the assembly. Each of the six (6) ribs were secured to the
wood test buck with three (3) 1/4" by 6" long hex head self drilling screws with steel and
rubber washers located 4" from each edge of the assembly and centered. A 1-1/2" by 1-1/2"
SW-01 Saddle Washer was employed between each 6" hex head screw and roof panel. Each
of the three (3) panel seams was sealed with a 1/2" by 3/32" thick butyl tape at the rib peak
and Butyl sealant at the interior roof joint. Each seam was secured with four (4) #12 by 3/4"
long hex head self drilling screws with steel and rubber washers - two (2) of which were
evenly spaced between each 6" mounting screw. The perimeter of the mock-up was sealed
to the test buck with Acryl-R sealant.
Test Method:
ASTM E 1646, Standard Test Method for Water Penetration of Exterior Metal Roof Panel
Systems by Uniform Static Air Pressure Difference
ASTM E 1680, Standard Test Method for Rate of Air Leakage Through Exterior Metal
Roof Panel Systems
Test Results:
Air Leakage
1.57 psf 0.020 cfm/ft2
Air Leakage
6.24 psf 0.032 cfm/ft2
Air Leakage
20.0 psf 0.036 cfm/ft2
The "As-Tested" drawings, data sheets, a copy of this report, or other pertinent project
documentation will be retained by Architectural Testing, Inc. for a period of four years from the
original test date. At the end of this retention period, such materials shall be discarded without
notice and the service life of this report by Architectural Testing, Inc. will expire. Results
obtained are tested values and were secured by using the designated test methods. This report
does not constitute certification of this product nor an opinion or endorsement by this laboratory.
It is the exclusive property of the client so named herein and relates only to the specimen(s)
tested. This report may not be reproduced, except in full, without the written approval of
Architectural Testing, Inc.
TW:he
Attachments (pages): This report is complete only when all attachments listed are included.
Appendix-A: Photos (2)
Appendix-B: Drawings (2)
98062.01-301-44
Architectural Testing Page 3 of 3
Revision Log
This report produced from controlled document template ATI 00300, issued 11/07/07.
98062.01-301-44
Architectural Testing
APPENDIX A
Photos
APPENDIX B
Drawings