Architectural Testing

PERFORMANCE TEST REPORT

Rendered to:

ALL WEATHER INSULATED PANELS

PROJECT: HI RIB ROOF PANEL

This report contains in its entirety:


Cover Page: 1 page
Report Body: 3 pages
Drawings: 2 pages

Report No: 98062.01-301-44


Test Completion Date: 03/09/10
Report Date: 04/06/10

2524 E. Jensen Ave


Fresno, CA 93706
phone: 559-233-8705
fax: 559-233-8360
www.archtest.com
Architectural Testing

PERFORMANCE TEST REPORT

Rendered to:

ALL WEATHER INSULATED PANELS


929 Aldridge Road
Vacaville, California 95688
Report No: 98062.01-301-44
Test Completion Date: 03/09/10
Report Date: 04/06/10

Project Summary: Architectural Testing, Inc. was contracted by All Weather Insulated Panels
to perform testing on a 120" by 96" Hi Rib insulated metal roof system. The test specimen was
tested for Air/Water performance in accordance with the referenced test standards. This report
includes comprehensive written and photographic documentation of testing performed and a
copy of "As-Tested" drawings.

Test Specimen Description:

Series/Model: HR

Product Type: Insulated Metal Panel

Overall Size: 120" wide by 96" in length

Typical Construction: Typical Construction: The mock-up consisted of three (3) panels
measuring 96" long by 40" wide with one (1) panel cut in two pieces approximately 20" in
width mounted at each edge of the assembly. Each of the six (6) ribs were secured to the
wood test buck with three (3) 1/4" by 6" long hex head self drilling screws with steel and
rubber washers located 4" from each edge of the assembly and centered. A 1-1/2" by 1-1/2"
SW-01 Saddle Washer was employed between each 6" hex head screw and roof panel. Each
of the three (3) panel seams was sealed with a 1/2" by 3/32" thick butyl tape at the rib peak
and Butyl sealant at the interior roof joint. Each seam was secured with four (4) #12 by 3/4"
long hex head self drilling screws with steel and rubber washers - two (2) of which were
evenly spaced between each 6" mounting screw. The perimeter of the mock-up was sealed
to the test buck with Acryl-R sealant.

2524 E. Jensen Ave


Fresno, CA 93706
phone: 559-233-8705
fax: 559-233-8360
www.archtest.com
98062.01-301-44
Architectural Testing Page 3 of 3

Test Method:

ASTM E 1646, Standard Test Method for Water Penetration of Exterior Metal Roof Panel
Systems by Uniform Static Air Pressure Difference

ASTM E 1680, Standard Test Method for Rate of Air Leakage Through Exterior Metal
Roof Panel Systems

Note: ASTM E 1646 is a specialized adaptation of Test Method E 331.


Note 2: ASTM E 1680 is a specialized adaptation of Test Method E 283.

Test Results:

Test Method Title of Test Results

ASTM E 1680 Preload @ +15.0 psf

Air Leakage
1.57 psf 0.020 cfm/ft2

Air Leakage
6.24 psf 0.032 cfm/ft2

Air Leakage
20.0 psf 0.036 cfm/ft2

ASTM E 1646 Water Resistance*


12.0 psf No leakage

*Tested in the horizontal position (no roof slope)


98062.01-301-44
Architectural Testing Page 3 of 3

The "As-Tested" drawings, data sheets, a copy of this report, or other pertinent project
documentation will be retained by Architectural Testing, Inc. for a period of four years from the
original test date. At the end of this retention period, such materials shall be discarded without
notice and the service life of this report by Architectural Testing, Inc. will expire. Results
obtained are tested values and were secured by using the designated test methods. This report
does not constitute certification of this product nor an opinion or endorsement by this laboratory.
It is the exclusive property of the client so named herein and relates only to the specimen(s)
tested. This report may not be reproduced, except in full, without the written approval of
Architectural Testing, Inc.

For ARCHITECTURAL TESTING, INC.:

Tyler Westerling, P.E. Leaton Kirk


Project Engineer Director of Regional Operations

TW:he
Attachments (pages): This report is complete only when all attachments listed are included.
Appendix-A: Photos (2)
Appendix-B: Drawings (2)
98062.01-301-44
Architectural Testing Page 3 of 3

Revision Log

Rev. # Date Page(s) Revision(s)


0 04/06/10 N/A Original report issue

This report produced from controlled document template ATI 00300, issued 11/07/07.
98062.01-301-44
Architectural Testing

APPENDIX A

Photos

Photo #1 Air Infiltration Tare


98062.01-301-44
Architectural Testing

Photo #2 Water Infiltration Test with 1/2" of water pooling


98062.01-301-44
Architectural Testing

APPENDIX B

Drawings