vi, Check
Highest Capacity Motor = 100 HP
Transformer rating required for this motor with assisted start
Highest Capacity Motor x 100
me Transformer rating
40
In the Electrical Schematic Drawing
Transformer Rating Is marked as Transformer rating = 10x 100 = 250 KVA
required 40
+. The selected rating of 400 KVA is sufficient
Total Connected Load = (2x100) + 135 + 95 + 50 + 10 KW 7
= 480 HP + 10, KW
~ 490 KVA .
Diversity factor 21.5 (assumed) “2
Standard Ratings
Transformer 11KV/433V
dea
Total Connected Load
Maximum Demand
(MD) Diversity factor Se 63 KVA
123 Comers 100 KVA
aid a 160 KVA
==> =326,6KVA 7
ce tefen 200 KVA
250 KVA
Provide 20% spare Capacity for future
spare Capacity for future expansion, ean
Transformer rating =MD + MD x 20 = 326 + 826 x 20 400 KVA
required 100° 100 500 KVA ‘
=891.92 KVA 630 KvA_ovitece(r ne
; 750 KVA
= 400 KVA
100 KVA : 1000 KVA
(nearest standard rating of transformer) rE ve
1600 KVA
ootly hector 2 Beam ef Mateichowd
Boece Denso
RAKSON AND RAKSON