me
In the Electrical Schematic Drawing
Control for Transformer is marked as
(indoor)
Selected Transformer Rating
= 400 KVA
Primary Side
Contro! lL SFU 400A, 250MVA
Protection 2 O/C and 1E/F
Secondary Side
= CB 600 A* 25MVA
8 O/C and 1E/F in built release
*B00A, ACB is selected with
OIC release set at 600 A
Protection of Transformer
Capacity of f
ii kviasav— | Installation
Tranetormers
Primary side | Secondary side
control and
Protection
Uptoand | Out door
inchuaing |
630 kVA
‘Above 630 KVA | Indoor only
but below
1000 KVA
1000 KVA and. | Indoor only
above
AB Switch, 1500/12004,
LA. , D.0. fuse 25 MVA ACES
drawout type with
20/0 +1 EF
inbuilt releases and
iow set EF
protection using
neutral C.T
Oil SFUIAB SFUs
250 MVA, 4008 CBs
with 2 O/C and One
instantaneous EJF
Inys with D.C. Trip
250 MVA 600A CBs | 1200/1600, 31 MV:
prefereably VCBs | ACBs drawout type
2O/C and One | 3 O/C + 1 EJF inbul
istantaneous E/F | releases and low
Relays with D.C Trp,
250 MVA, 800A CBs | 1600/2500A 50 kA
with 3 O/C + 1 E/F
cil temprature alarm
‘and tip, Winding 20/0+1 BF
temprature alarm and | Relays, REF Relay
ip with OC trip. |
(@aarie 3)
RAKSON AND RAKBON