me In the Electrical Schematic Drawing Control for Transformer is marked as (indoor) Selected Transformer Rating = 400 KVA Primary Side Contro! lL SFU 400A, 250MVA Protection 2 O/C and 1E/F Secondary Side = CB 600 A* 25MVA 8 O/C and 1E/F in built release *B00A, ACB is selected with OIC release set at 600 A Protection of Transformer Capacity of f ii kviasav— | Installation Tranetormers Primary side | Secondary side control and Protection Uptoand | Out door inchuaing | 630 kVA ‘Above 630 KVA | Indoor only but below 1000 KVA 1000 KVA and. | Indoor only above AB Switch, 1500/12004, LA. , D.0. fuse 25 MVA ACES drawout type with 20/0 +1 EF inbuilt releases and iow set EF protection using neutral C.T Oil SFUIAB SFUs 250 MVA, 4008 CBs with 2 O/C and One instantaneous EJF Inys with D.C. Trip 250 MVA 600A CBs | 1200/1600, 31 MV: prefereably VCBs | ACBs drawout type 2O/C and One | 3 O/C + 1 EJF inbul istantaneous E/F | releases and low Relays with D.C Trp, 250 MVA, 800A CBs | 1600/2500A 50 kA with 3 O/C + 1 E/F cil temprature alarm ‘and tip, Winding 20/0+1 BF temprature alarm and | Relays, REF Relay ip with OC trip. | (@aarie 3) RAKSON AND RAKBON